Process Industry Practices


Architectural

PIP ARC01016
Building Data Sheet
PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES

In an effort to minimize the cost of process industry facilities, this Practice has
been prepared from the technical requirements in the existing standards of major
industrial users, contractors, or standards organizations. By harmonizing these
technical requirements into a single set of Practices, administrative, application, and
engineering costs to both the purchaser and the manufacturer should be reduced. While
this Practice is expected to incorporate the majority of requirements of most users,
individual applications may involve requirements that will be appended to and take
precedence over this Practice. Determinations concerning fitness for purpose and
particular matters or application of the Practice to particular project or engineering
situations should not be made solely on information contained in these materials. The
use of trade names from time to time should not be viewed as an expression of
preference but rather recognized as normal usage in the trade. Other brands having the
same specifications are equally correct and may be substituted for those named. All
Practices or guidelines are intended to be consistent with applicable laws and
regulations including OSHA requirements. To the extent these Practices or guidelines
should conflict with OSHA or other applicable laws or regulations, such laws or
regulations must be followed. Consult an appropriate professional before applying or
acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time by the responsible Function Team and
will be reviewed every 5 years. This Practice will be revised, reaffirmed, or withdrawn.
Information on whether this Practice has been revised may be found at www.pip.org.

Process Industry Practices (PIP), Construction Industry Institute, The


University of Texas at Austin, 3925 West Braker Lane (R4500), Austin,
Texas 78759. PIP member companies and subscribers may copy this Practice
for their internal use. Changes, overlays, addenda, or modifications of any
kind are not permitted within any PIP Practice without the express written
authorization of PIP.

PIP will not consider requests for interpretations (inquiries) for this Practice.
PRINTING HISTORY
June 2002 Issued
August 2002 Editorial Revision

Not printed with State funds


ASSOC. PIP:
DATA SHEET ARC01016
ARC01015
PAGE 1 OF 10
Building Data Sheet August 2002

Owners Name: Name of Building:


Project Title: Ref. No:
Project Number: ____________________ Date:
Project Site Location:

1. General
This Practice is intended to be used in conjunction with PIP ARC01015 - Architectural and Building Utilities Design
Criteria, PIP CVC01017 - Plant Site Data Sheets, and PIP STC01018 - Blast Resistant Building Design Criteria.
These data sheets contain architectural, HVAC, electrical, fire protection, plumbing, and communication information
that may be conveyed from the owner to the project design team or from the project design team leaders to the team
design members. This data may be provided by the owner or developed by the project design team and approved by
the owner.
Building Code: As Specified on PIP CVC01017.
Elevation:
Finished Grade: __________ ft (__________ m)
Floor Elevation (Ground Floor): __________ ft (__________ m)
Floor Elevation (___ Floor): __________ ft (__________ m)
Floor Elevation (___ Floor): __________ ft (__________ m)
Special Requirements:
Description Yes No
Blast Resistant Construction See PIP STC01018 for design criteria.
Windows Permitted
Floor Drains Permitted
Furniture/Furnishings
Landscaping
Interior Design
Parking at Building # of cars ____ # of bikes ____
Signage/Graphics
Bridge Crane __________ tons ( ) capacity
Existing Colors or
Textures to Be Matched
Existing Siding/Roofing Profiles
to Be Matched
Designed for Future Expansion
Visual Access to Control Room
Number of Men ________________
Number of Women _____________
Number of Men per Shift ________________
Number of Women per Shift _____________
Number of Shifts ________________
General Comments:
Cashier
Air Lock

Auditorium

Battery Room
Room Types
(Description)

Break Room(s)

Carpentry Area

Communications
Communications
Change Room(s)

Computer Room(s)
2. Architectural

Equipment Room(s)
Ambulance Van Bay

Chemical Laboratory

Coffee/Vending Room(s)

Communication Closet(s)
Requirements
Room
Number of Rooms

Size of Rooms

Notes (See Section 8)


2.1 Room Size and Room Finish Schedule

Exposed Concrete
Hardened Concrete Finish
ARC01015
ASSOC. PIP:

Sealer on Concrete
Ceramic Tile
Vinyl Composition Tile
Floors

Access Flooring System


Seamless Monolithic
Chemical Resistant
Carpet
Vinyl Cover Base
Ceramic
Bases

Carpet
Wood
Chalk/Marker Boards
Bulletin Boards
Boards

Painted
Acoustical Wall Panel
DATA SHEET

Concrete Block (CMU)


Building Data Sheet

Gypsum Board
Plaster
Ceramic Tile - Ft High
Exposed Concrete
Walls

Operable Steel Partition


Vinyl Wall Covering
Fabric
Wood Paneling
Exposed Concrete
Metal Liner Panels
Plaster
Acoustical Tile
Gypsum Board
August 2002
ARC01016

PAGE 2 OF 10

Painted
Ceilings

Metal Liner Panels


Exposed Construction
Room(s)
Room(s)
Room Types

Fire Truck Bay


(Description)

Dining Room(s)
Control Room(s)

Generator Room
Covered Parking
Copy/Fax Room(s)
Computer Room(s)

Emergency Shower
Conference Room(s)

Electrical Repair Area

Fire Suppression Equip.


Elevator and Equip. Room
Requirements
Room

Communications Entrance

Electrical/Telephone/Radio
Number of Rooms

Size of Rooms

Notes (See Section 8)


Exposed Concrete
Hardened Concrete Finish
ARC01015
ASSOC. PIP:

Sealer on Concrete
Ceramic Tile
Vinyl Composition Tile
Floors

Access Flooring System


Seamless Monolithic
Chemical Resistant
Carpet
Vinyl Cover Base
Ceramic Tile
Bases

Carpet
Wood
Chalk/Marker Boards
Bulletin Boards
Boards

Painted
Acoustical Wall Panel
DATA SHEET

Building Data Sheet

Concrete Block (CMU)


Gypsum Board
Plaster
Ceramic Tile - Ft High
Exposed Concrete
Walls

Operable Steel Partition


Vinyl Wall Covering
Fabric
Wood Paneling
Exposed Concrete
Metal Liner Panels
Plaster
Acoustical Tile
August 2002
ARC01016

PAGE 3 OF 10

Gypsum Board
Painted
Ceilings

Metal Liner Panels


Exposed Construction
Lounge

Office(s)
I/O Room

Kitchen(s)
Laboratory
Room Types

Medical Room
(Description)

Janitors Room
Health Services

Maintenance Pit

Men's Restroom
Lobby/Reception
Ladies Restroom

Mechanical Room(s)

Men's Locker/Shower
Ladies Locker/Shower
Instrument Repair Area

Library/Reading Area(s)

MCC/Switch Gear Room


Requirements
Room

Instrumentation I/O Room


Number of Rooms
Size of Rooms

Notes (See Section 8)


Exposed Concrete
Hardened Concrete Finish
ARC01015
ASSOC. PIP:

Sealer on Concrete
Ceramic Tile
Vinyl Composition Tile
Floors

Access Flooring System


Seamless Monolithic
Chemical Resistant
Carpet
Vinyl Cover Base
Ceramic Tile
Bases

Carpet
Wood
Chalk/Marker Boards
Bulletin Boards
Boards

Painted
Acoustical Wall Panel
DATA SHEET

Concrete Block (CMU)


Building Data Sheet

Gypsum Board
Plaster
Ceramic Tile - Ft High
Exposed Concrete
Walls

Operable Steel Partition


Vinyl Wall Covering
Fabric
Wood Paneling
Exposed Concrete
Metal Liner Panels
Plaster
Acoustical Tile
August 2002
ARC01016

Gypsum Board
PAGE 4 OF 10

Painted
Ceilings

Metal Liner Panels


Exposed Construction
Shop(s)
Radio Area

Testing Area
Prayer Room

Reproduction
Room Types

Security Office
(Description)

Refueling Area
Receiving Area

Travel Services
Recovery Room

Storage Room(s)

Training Room(s)
Sandblasting Area
Record/File Room(s)

Unloading Area (Open)


Open Landscaped Area

Safety Equipment Room

Unloading Area (Covered)


Requirements
Room
Number of Rooms

Size of Rooms

Notes (See Section 8)


Exposed Concrete
Hardened Concrete Finish
ARC01015
ASSOC. PIP:

Sealer on Concrete
Ceramic Tile
Vinyl Composition Tile
Floors

Access Flooring System


Seamless Monolithic
Chemical Resistant
Carpet
Vinyl Cover Base
Ceramic Tile
Bases

Carpet
Wood
Chalk/Marker Boards
Bulletin Boards
Boards

Painted
Acoustical Wall Panel
DATA SHEET

Concrete Block (CMU)


Building Data Sheet

Gypsum Board
Plaster
Ceramic Tile - Ft High
Exposed Concrete
Walls

Operable Steel Partition


Vinyl Wall Covering
Fabric
Wood Paneling
Exposed Concrete
Metal Liner Panels
Plaster
Acoustical Tile
August 2002

Gypsum Board
ARC01016

PAGE 5 OF 10

Painted
Ceilings

Metal Liner Panels


Exposed Construction
.
Others:
X-Ray Room
Welding Pipe
Vending Area

Waiting Room
Room Types
(Description)

VIP Waiting Room


Vehicle Maintenance

Fitting Machine Shop


Requirements
Room
Number of Rooms

Size of Rooms

Notes (See Section 8)


Exposed Concrete
Hardened Concrete Finish
ARC01015
ASSOC. PIP:

Sealer on Concrete
Ceramic Tile
Vinyl Composition Tile
Floors

Access Flooring System


Seamless Monolithic
Chemical Resistant
Carpet
Vinyl Cover Base
Ceramic Tile
Bases

Carpet
Wood
Chalk/Marker Boards
Bulletin Boards
Boards

Painted
Acoustical Wall Panel
DATA SHEET

Concrete Block (CMU)


Building Data Sheet

Gypsum Board
Plaster
Ceramic Tile - Ft High
Exposed Concrete
Walls

Operable Steel Partition


Vinyl Wall Covering
Fabric
Wood Paneling
Exposed Concrete
Metal Liner Panels
Plaster
Acoustical Tile
Gypsum Board
August 2002
ARC01016

PAGE 6 OF 10

Painted
Ceilings

Metal Liner Panels


Exposed Construction
ASSOC. PIP:
DATA SHEET ARC01016
ARC01015
PAGE 7 OF 10
Building Data Sheet August 2002

2.2 Materials and Construction:


Primary Structure Exterior Walls
Steel Frame Concrete Masonry Units (CMU)
Reinforced Concrete Frame Brick Veneer
Pre-Engineered System Tilt-up/Precast Concrete
Load-Bearing Reinf. Masonry (CMU) Cast-in-place Concrete
Load-Bearing Precast Concrete Walls Metal Panels
Load-Bearing Cast-in-Place Walls Light Gage Steel Framing
Blast Resistant Wood Sheathing
Other ________________________ Stucco
Store Front System
Painted
Insulated
Other ________________
Elevated Levels Doors
Single-Ply Membrane INT. EXT.
Built-up Standard Steel
Uninsulated Metal Panel Pressed Steel Frame
Insulated Metal Panel Wood
Fiberglass/Plastic Aluminum and Glass
Bare Concrete Fiberglass
Sealed/Coated Concrete Painted
Other _______________________ Galvanized
Laminated
Roll-up
Canopy
Other ________________
Roof Systems Windows
Single-Ply Membrane Steel Frame
Built-up Asphalt Roof Aluminum Frame
Uninsulated Metal Panel Safety Glass (Type: _______________)
Insulated Metal Panel Insulating Glass
Fiberglass/Plastic Fixed
Bare Concrete Operable
Sealed/Coated Concrete Tinted Glass
Other ________________ Other ________________
Other ________________
Roof Structures Louvers
Metal Form Deck Operable
Composite Metal Deck/Concrete Slab Fixed
Wood Formed Concrete Slab Birdscreen
Metal Deck Only Steel
Precast Concrete Aluminum
Composite (Type: ________________) Blast Resistant
Standing Seam Roof System Other ________________
Other ________________
ASSOC. PIP:
DATA SHEET ARC01016
ARC01015
PAGE 8 OF 10
Building Data Sheet August 2002

3. Heating, Ventilation, and Air Conditioning (HVAC)


(Refer to PIP CVC01017 for outside design temperatures.)
Heating: No Electric Steam Hot Water Gas Other ___________
Ventilation: No Blow Through Draw Through Gravity
Air Conditioning: No
Cooling Medium: Chilled Water DX _________________
System: Packaged Split _________________
Condenser: Water Cooled Air Cooled
Corrosion Resistant Coil Coating: Air Handler Condenser
Stand by Capacity ________ %
Air Distribution System: Multi Zone Single Zone Other ______________
Thermostat Control: Pneumatic Electronic
Motor: Standard Explosion Proof
Wall Louvers: Yes No Dust Filter: Yes No
Air Intake Stack: Yes No Sand Filter: Yes No
Chemical Filter: Yes No
Equipment Heat Loads:
Electrical Equipment: Btu/hr (kW) Btu/hr (kW)
DCS Equipment: Btu/hr (kW) Btu/hr (kW)
Thermostat Setting Temperatures and % Relative Humidities and Pressures (Deviation or Addendum from
PIP ARC01015):
______________ Room __________ deg F (C) _________ % RH _________ inches of water (Pa)
______________ Room __________ deg F (C) _________ % RH _________ inches of water (Pa)
______________ Room __________ deg F (C) _________ % RH _________ inches of water (Pa)
___________________ __________ deg F (C) _________ % RH _________ inches of water (Pa)
___________________ __________ deg F (C) _________ % RH _________ inches of water (Pa)
___________________ __________ deg F (C) _________ % RH _________ inches of water (Pa)
Special Ventilation System Requirements:
For Whole Building: Yes No
Partial Area ____________________________________________________
Fresh Air Makeup Controlled: Yes No
Air Intake Shutdown Capability: Automatic Manual
Building Pressurization: No Pressure: _________________ inches of water (Pa)
Building Purging: Yes No Gas Detection Alarm: Yes No
4. Electrical
Power Source for Building ____________________________
Interior Electrical Light: Incandescent Lamp Fluorescent Lamp Others __________________
Special Grounding __________________________________
Interior Wiring __________________________________
Exterior Wiring __________________________________
Exterior Lighting: Yes No
Other Requirements _________________________________
5. Communication
Communication Standards Bodies:
USA TIA/EIA, BICSI, NFPA, IEEE Yes No
Other
Communication Requirements:
Telephone Yes No
Closed Circuit TV Yes No
Other
ASSOC. PIP:
DATA SHEET ARC01016
ARC01015
PAGE 9 OF 10
Building Data Sheet August 2002

6. Building Fire Protection and Safety


Description Yes No Description Yes No
Fire Detection/Alarm: Fire Suppression:
Smoke Detector Hose Cabinets
Heat Detector Sprinkler System
Fire Alarm Box Clean Agent Fire-Extinguishing
Audible/Visual Alarm System
Fire Alarm Panel Portable Fire Extinguisher
Sprinkler System 17-lb (7.7-kg) ABC (Ammonium
Pressure Switch Phosphate) Extinguisher
Fixed Fire Suppression 15-lb (6.9-kg) CO2 Extinguisher
Discharge 100-lb (45.3-kg) CO2 Wheeled
Extinguisher
Fixed Fire Suppression Building Hydrant (Standpipes):
Discharge Class I Class II Class III
Automatic Sprinkler Miscellaneous:
Actuation Emergency Lighting
Sprinkler Flow Switch
Safety:
Gas Detection System
Breathing Air System
Combustible Gas
Detectors
Toxic Gas Sensors
Oxygen Analysis
7. Plumbing
7.1 Plumbing Codes
State Plumbing Code (year: _______)
Local/County/Municipal Plumbing Code (year: _______)
(Or Adopted Plumbing Code ________, year: _______, date: _______)
(In the absence of any locally adopted plumbing code, building plumbing system will be designed in accordance
with) the latest edition of the International Plumbing Code (IPC).
7.2 Plumbing Systems
Description Yes No Description Yes No
Domestic Water Fire Water
Cold Water Natural Gas
Hot Water Sanitary Sewer
Storm Drain Instrument Air
Cooling Tower Steam
Supply Condensate Return
Return Oily Water Sewer
7.3 Plumbing Fixtures and Specialties
Description Yes No Description Yes No
Water Closet Emergency Shower
Urinal Emergency Eye Wash
Lavatory Electrical Water Cooler
Kitchen Sink Hose Bib
Service Sink Shower Stall
Lab Sink Dishwasher
Floor Drain Rough-in (for Ice Maker)
ASSOC. PIP:
DATA SHEET ARC01016
ARC01015
PAGE 10 OF 10
Building Data Sheet August 2002

(Section 7.3, continued)

Garbage Disposal Vacuum Pump


Water Heater Backflow Preventor
Grease Interceptors Pressure Regulator
Oil Interceptor Drinking Fountain
8.0 Notes