You are on page 1of 8

Page 1 of 8

DIMENSIONING CTS FOR SMALL GENERATOR DIFFERENTIAL


PROTECTION

Rich Hunt Suhag Patel


Senior Member, IEEE Member, IEEE
GE Digital Energy GE Digital Energy
903 Haddon Hall Drive CA, USA
Apex, NC 27502, USA Suhag.patel@GE.com
Richard.hunt@GE.com

Abstract Protection of small generators that provide backup not equal, then a fault condition is declared in the zone of
or standby power for critical facilities is no different than that of protection. Differential protection can therefore be very
large generators. The challenge is that the CTs and CT sensitive, very selective, very dependable, and operate at high
secondary circuits for generator protection are not properly
speed. The challenge for differential protection is security,
designed for the installation. This paper discusses these issues,
and makes recommendations for proper design of CT circuits for because the function is dependent on the performance of the
small generator differential protection. CTs.
INeut ITerm
Index Termsprotective relays, generators, instrument tfmrs
52

I. INTRODUCTION
iNeut iTerm
Small generators are commonly installed to provide
backup or standby power for critical facilities such as
hospitals, data centers, communications centers, and the like. IDiff = iNeut + iTerm

These generators are typically diesel generators 1 to 3 MVA


in size, and are normally intended for use in applications for Fig. 1. Differential protection concept
facilities at the 4kV to 15kV level. For the generator stator differential protection of Figure
High-speed detection of internal electrical faults is 1, the differential current IDiff is simply the sum of the
typically provided by stator differential protection. terminal and neutral currents. During normal operations, or
Undesirable operation of the stator differential element due to during external fault events, IDiff should be 0. This is
unequal CT saturation during transformer energization or out- dependent on both CTs accurately replicating the primary
of-zone faults is well known. Protection engineers typically current, with a minimum of error. However, if during external
follow the guidelines outlined in ANSI C37.110 IEEE Guide fault events, one of the CTs has significant replication error,
of the Application of Current Transformers Used For or both CTs have different replication errors, IDiff will be
Protective Relaying Purposes to dimension CTs for stator greater than 0, as in Figure 2. The likelihood that CT errors
differential protection. The maximum accuracy class and will occur increases as currents increase.
turns ratio of the CT is typically limited by the physical Differential Current No CT Error With CT Error
dimensions of the switchgear and generator set. iNeut iTerm iTerm iTerm
However, beyond the recommendations in C37.110, the iNeut IDiff
iNeut
protection engineer must understand, and be able to model, IDiff = ITerm + I Neut IDiff = 0

the performance of the entire stator differential system,


including the differential relay, CTs, and CT secondary leads. Fig. 2 Differential current
This paper discusses methods to model the stator differential Percentage differential restraint protection relays, the
performance, based on the IEEE Power System Relaying type of relay most commonly applied for stator differential
Committee CT Saturation Calculator tool. The paper then protection, use the concept of a restraint current to provide
goes on to suggest methods to use this tool in dimensioning security against CT error. There are many different methods
CTs and CT secondary leads. in use to calculate the restraint current, including the sum of
the terminal and neutral current magnitudes, the average of
II. DIFFERENTIAL PROTECTION
these magnitudes, or the maximum of these magnitudes. The
Differential protection is nothing more than a practical differential element declares a trip when the differential
application of Kirchhoffs Current Law. The sum of the current IDiff is greater than some percentage of the restraint
currents entering a zone of protection should equal the sum of current IRest, as in Figure 3. Restraint current increases as the
the currents exiting the zone of protection. If these currents do overall magnitude of current flowing through the generator

978-1-61284-127-4/11/$26.00 2011 IEEE


Page 2 of 8

increases. The percentage differential therefore decreases relays became available, differential protection was not
sensitivity as current increases, to provide security against the routinely applied on small generators. This was due in part to
expected increase in CT replication error. This function cost, as differential protection required another set of CTs,
provides good security during AC saturation of CTs for high and required an additional set of relays. This was also due in
current magnitude external events. However, CTs may part to the limited benefits of differential protection for these
saturate for low-level external faults or local transformer machines. Many small generators are essentially disposable,
inrush due to the high DC time constant at the generator. as they wont be repaired for significant short circuits. The
Since these events occur at low levels of current, the level of major goal of high-speed differential protection is to limit
restraint current is very low, the differential element is very damage, and if a failed generator is to be replaced, there is
sensitive, and is at risk of operating for the CT error that can less incentive to limit damage.
occur. However, with microprocessor relays, stator differential
is commonly applied on generators of all sizes. This is
Differential
Current
because generator protection relays include stator differential
IDiff = ITerm + I Neut TRIP elements, so improved protection of the generator is gained
with no additional cost. However, additional effort is
Slope 2
necessary. When applying differential protection, there is still
Trip if IDiff > Slope 1 * IRest the requirement that good engineering be performed to design
or
Trip if IDiff > Slope 2 * IRest the protection and control system. This engineering includes
RESTRAIN
understanding how the stator differential element operates,
where the element may not operate as desired, selecting
significant CT error
appropriate CTs and CT secondary leads for the element, and
IRest = | ITerm | + | I Neut |
some CT error or calculating appropriate differential settings. Many stator
IRest = ( | ITerm | + | INeut | ) / 2 differential elements operate undesirably because good
or
IRest = max( | ITerm |, | I Neut | )
engineering practices have not been followed, especially
Slope 1
Restraint during the design of the CT circuits.
perfect CTs
Current
III. CT PERFORMANCE
To practice good engineering for differential protection, it
Fig. 3. Percentage differential characteristic
is necessary to understand the basics of CT performance. A
current transformer is simply a transformer designed for the
A. Stator Differential Protection
specific application of converting primary current to a
Generator faults require high-speed protection to clear secondary level for measurement purposes. The actual
the fault. Fault currents continue to flow even after the prime performance of a CT, and the equivalent model used for
mover is tripped and the field removed, both due to inertia, analysis purposes, are identical to that of any other
and to flux trapped within the machine. Tripping faster transformer, as shown in Fig. 4. The concern for the relay
obviously limits damage to the generator. This high-speed engineer is the actual current at the secondary terminals of the
protection is normally stator differential protection that CT. This current, ISEC, is the total secondary current as
operates with no intentional time delay. However, other forms transformed by the CT, ISEC Total, minus the current
of protection, including basic overcurrent short circuit necessary to supply the magnetizing branch IE.
protection, may be applied. If external resistance is used to RS XS
limit fault currents, high-speed protection may not be
ISEC Total ISEC
necessary. IPRI

Differential protection can protect against high IE


Xm Rm
magnitude faults in the generator zone of protection. VSEC Magnetizing
Current
VBURDEN ZB

However, due to the practical limits of sensitivity for setting


the protection, differential protection will not see faults within
the last 5% to 10% of the generator neutral. Also differential
protection may not be able to detect many phase-ground faults Fig. 4. CT equivalent circuit
if the generator uses high-impedance grounding to limit fault
currents. [1] A. CT Saturation
It is obvious on large generators, or on critical During normal load conditions, the flux requirement for a
generators, that differential protection is appropriate and CT is very small, and therefore the exciting current is very
required. However, on small generators, differential small, and the secondary current is almost a faithful
protection is not absolutely necessary. Before microprocessor reproduction of the primary current. Now consider what

978-1-61284-127-4/11/$26.00 2011 IEEE


Page 3 of 8

happens with the CT during a short circuit on the primary providing this initial current requirement, the DC component
circuit. The increase in primary current results in an increased is no longer required, and decays based on the X/R ratio of
secondary current. The increased secondary current results in the power system. The practical result is during short circuits
a higher voltage drop across the CT winding resistance and the primary current, and therefore the secondary current, may
connected burden of the CT, and results in a higher excitation be asymmetrical with respect to the current axis. This
voltage. This higher excitation voltage creates more flux. The asymmetrical current results in the peak current that will be
flux characteristic is still sinusoidal in shape, but may be high seen for a specific fault, and is known as the DC offset of the
enough to cause saturation of the transformer core. The fault current. [3] A typical offset fault current is shown in Fig.
hysteresis loop becomes negligible for this high level of 6.
excitation, as shown in Fig. 5. The resulting exciting current
needed to supply the flux is very high in magnitude, and may
t
approach the magnitude of the primary fault currents. I e TS

Remembering that the ISEC = ISEC Total - IE, then the


current output of the secondary winding is reduced
significantly by the higher exciting current. The core goes
into and out of saturation as the voltage varies over the power time
system cycle. As a result, the output of the CT is normal while
the core is unsaturated, and reduced when the core saturates.
mag
i

e Fig. 6. Asymmetrical fault current and DC time constant



saturation knee
This DC component is a problem for transformers, as the
pont DC component tends to create more flux in the core that adds
Time i
to the flux driven by the AC voltage. So essentially, the total
flux in the CT is dependent on the area under the curve in Fig.
6. Therefore, the longer the system time constant, the more
likely the CT is to saturate. The highest DC time constants on
the power system are found at generators, due to the reactance
Fig. 5. Flux and exciting current hysteresis during core saturation
of the generator. X/R ratios of between 25 and 90 (or 66ms to
As described, the excitation voltage induces flux in the CT 240ms at 60Hz) are typical. Therefore, CTs located at
core, and the flux is supplied by the excitation current. CT generators are at higher risk of saturating, even at low current
manufacturers supply the secondary excitation characteristic magnitudes, than CTs located elsewhere on the system.
to relate excitation voltage and excitation current for a
C. Basic Relations of CTs
specific model of CT. This characteristic is used to estimate
CT performance for protective relaying applications. This From the CT equivalent circuit of Figure 2, and the
characteristic, for example, can be used to determine the saturation factor and time to saturation, it is simple to derive
excitation voltage at which the CT will saturate. some basic relationships of the CT to X/R ratio, connected
This saturation voltage VX is the symmetrical voltage burden, and fault current. The voltage VSEC, which is the
across the secondary winding of the current transformer for secondary excitation voltage, is determined from the voltage
which the peak induction just exceeds the saturation flux drops across the CT secondary circuit:
density. It is found graphically by locating the intersection of VSEC  I SEC  RS  Z B 
the straight portions of the excitation curve on log-log axes. where RS = secondary winding resistance of the CT
[2] When the excitation voltage of the transformer exceeds ZB= total burden (including wiring leads) connected
this level, the transformer core is in saturation. The saturation to the CT secondary.
voltage is important for predicting CT performance during
fault conditions. For ANSI C-Class CTs, the leakage reactance ZS is
negligible, and may be ignored.
B. DC Offset
As described previously, the flux in the core can
In the highly inductive network of the power system, the approach 1+X/R during a fully offset fault. Therefore, a
current wave must be near maximum when the voltage wave second relation is that the CT will not saturate if the
is at zero. Therefore, when a short circuit occurs with the saturation voltage VX meets the following condition:
instantaneous voltage at zero, the current at the time of the
fault must be at a maximum. To supply this maximum current,
a countercurrent, the DC component, is produced. After 
V X  I SEC  Z S  1  X
R


978-1-61284-127-4/11/$26.00 2011 IEEE


Page 4 of 8

assuming a resistive burden. bus, and energizes the transformer, the generator relay trips
Based on this last equation, it is simple to see that on a stator differential operation. The stator differential
increasing fault currents, increasing connected burden, and operation doesnt happen every time, but does happen often.
increasing X/R ratio requires a higher saturation voltage to Fig. 7 illustrates the system arrangement, and provides
prevent CT saturation. In practice, it is rarely possible to some details from the event. The current waveforms from the
completely prevent CT saturation from occurring for all fault terminal and neutral side both show an inrush event. The
events. The best methods to reduce the likelihood of CT currents from both sides are correctly 180 opposite to each
saturation is to use a higher accuracy class CT (increasing the other, and appear to have the same magnitude. However, the
saturation voltage), a higher connected turns ratio (reducing stator differential element tripped on B-Phase approximately
the secondary current), and limiting the connected burden. 2.5 cycles after the generator connected to the bus and picked
up the transformer. This obviously requires further analysis.
IV. SMALL GENERATOR STATOR DIFFERENTIAL Fig. 8 looks at the B-Phase waveforms. (The terminal
PERFORMANCE side waveform is reflected 180 to allow for easy
There is no difference in stator differential relaying comparison). It is obvious that the neutral side CT starts to
between small generators (typically 3MVA and below) and saturate about 2.5 cycles after picking up the bus, and CTs
large generators. The same protective relays, using the same from both sides experience DC saturation after 3 cycles. This
stator differential algorithms can, and are, applied to 500kW, unequal CT performance resulted in the undesirable operation
480V generators, and 500MW, 13.8kV generators. The of the stator differential element.
difference is in the application of the complete protection Neutral CT Waveforms Terminal CT Waveforms
system, including the CTs and CT secondary circuits. Large
generators typically use C800 class CTs, with large turns
ratios such as 20,000:5. Small generators use switchgear CTs,
and common applications see the use of C20 class CTs and a
150:5 turns ratio. However, both large and small generators
4.16kV
drive the system time constant (X/R ratio) at the location of
C20 C20
the generator, resulting in a local X/R ratio of 25 to 90. This 300:5
52
300:5

5'
long DC time constant means CTs used for generator 1.875MW
#10 AWG

differential protection are likely to saturate for external faults


and transformer inrush events due to the DC component of 100' - #10 AWG

the system. Small generators, using low accuracy class CTs B-Phase Differential
Current

and a low connected turns ratio, are more susceptible to this Relay trips on
differential 2.5 cycles
kind of saturation. The best way to illustrate this phenomena after startup

is to look at a couple of examples of stator differential


performance for small generators.
A. Case 1: 1.875MW stator differential operation
This case involves a 1.875MW, 4160V diesel generator Fig. 7. 1.875MW stator differential operation
used as emergency power for a hospital facility. This
generator is one of set of generators tied to the same 4160 bus
that may start in parallel to serve hospital loads. Each
generator is connected to the bus through a circuit breaker as
part of a metal-clad switchgear lineup. The 4160 bus is
connected to a transformer used to connect to the hospital
distribution system.
This specific generator is the closest generator to the
4160 bus. The terminal side CTs are located in the
switchgear. The neutral side CTs are approximately 100 feet
from the switchgear breaker. The generator protection relay is
located in the switchgear breaker low voltage compartment.
CT secondary leads are #10 AWG copper wire. The CTs are
C20 class, 300:5 CTs. The CTs are identical models provided
by one manufacturer. Fig. 8. 1.875MW, B-Phase currents
A typical differential event starts when the generator is
brought up to speed. When the generator connects to the 4160 The performance of these CTs can be modeled using the
IEEE PSRC CT Saturation Calculator. [4] This tool is a

978-1-61284-127-4/11/$26.00 2011 IEEE


Page 5 of 8

spreadsheet tool that allows the modeling of a specific CT Neutral CT Waveforms Terminal CT Waveforms

application. Parameters include the system X/R ratio, the


connected burden, amount of DC offset, and remanence in the
CT. Using this tool, it possible to show the performance of
typical CTs for varying system conditions, including low
magnitude faults with high X/R ratios. 4.16kV

60 C20 C20
50 200:5 200:5
40 52
30
5'
20
10
#10 AWG
750kW
0
-10
-20
-30
125' - #10 AWG
-40
-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150
A-Phase Differential
60
50
40
30
20 Relay trips on
10 differential 1.5 cycles
0 after startup
-10
-20
-30
-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150

Fig. 9. 1.875MW, modeled CT performance


Fig. 11. 750kW, stator differential operation
The data from the CT Saturation Calculator can be used in
a spreadsheet to perform a simple differential calculation.
This calculation provides results (as in Fig. 10) very similar to
the results determined from the relay itself. Obviously, then,
this stator differential operated due to unequal performance of
the terminal side and neutral side CTs.

Fig. 12. 750kW, A-Phase waveforms

V. METHODS TO IMPROVE STATOR DIFFERENTIAL


Fig. 10. 1.875MW, modeled differential performance
PERFORMANCE

B. Case No. 2: 750kW stator differential operation It is clear that these two cases show stator differential
elements that dont achieve the main goal of a protection
This case involves a 750kW, 4160V generator used as
system: to be reliable. The challenge for differential
standby power for airport operations, as in Fig. 11. This
protection is to be secure, as unequal CT performance may
generator is also connected to a 4160V bus through metal
result in operation of the differential for out-of-zone faults, as
clad switchgears. CTs are C20 class, 200:5 CTs. The neutral
illustrated by these examples. It is necessary to understand
side CT secondary lead is approximately 125 feet of #10
how the performance of the stator differential can be
AWG copper wire. In this case, the stator differential element
improved to prevent these types of undesirable operations.
tripped approximately 1.5 cycles after the generator picked up
Essentially, microprocessor relays can use algorithm design to
the bus and transformer, and did this consistently for all starts.
try to detect and compensate for unequal CT performance.
In this case, the stator differential tripped on A-phase
Relay engineers can use good engineering judgment during
first. The A-phase current waveforms are shown in Fig. 12.
system design to minimize the likelihood of unequal CT
The difference in this case is that the neutral side CT saturates
performance. Both relay design and system design are critical
in the first third to half-cycle of the event. Modeling the CTs
for the security of differential protection.
using the CT Saturation Calculator verifies that the saturation
is to due to DC saturation, and that the stator differential A. Relay Solutions
operated due to this unequal CT performance. Before a protection engineer can apply good engineering

978-1-61284-127-4/11/$26.00 2011 IEEE


Page 6 of 8

judgment during system design, they must understand how the element. When CT saturation is suspected, the relay compares
relays they choose react to, and attempt to account for, the direction of the terminal side currents to the neutral side
unequal CT performance. currents. If the currents flow in opposite directions, (as
measured by the differential relay), then an external fault is
B. Second harmonic restraint
declared and the differential is blocked. If the currents flow in
The simplest solution applied by relay manufacturers, the same direction, as measured by the relay, then an internal
and the one most commonly applied, is to use second fault is declared, and differential tripping is permitted.
harmonic restraint of the differential element. The most likely
event to cause unequal CT performance is when the generator
energizes a local transformer before picking up load. The External Fault - Restrain Internal Fault - Trip

generator sees only the transformer inrush current. This


transformer inrush current can take seconds or minutes to
decay, increasing the possibility that CTs will saturate due to
the DC component of the current. The transformer inrush 90.00

current normally results in a very high level of second


harmonics. Second harmonic restraint will detect the high
level of second harmonic, and block the differential element.
There are two risks to using second harmonic restraint
for stator differential protection. The first risk is for an out-of-
zone fault. The differential CTs may saturate for this fault, but Fig. 14. Differential directional supervision
the CT performance may be good enough that the level of
The same direction is when the terminal and neutral
second harmonic is below the restraint threshold of the
currents are within 90 of each other. The internal and
differential element. This is a low risk event, as it takes some
external fault directions of Fig. 14 are dependent upon CT
time for the CT output to degrade, and other protection
polarity and connection to the relay terminals. For some
should clear the fault before the stator differential is likely to
models of relays, the trip and restraint directions may be
operate. During transformer inrush events, the differential
reversed. To ensure high-speed operation, the differential
current will probably be in the restraint zone by the time the
element is only supervised by the directional element when
second harmonic content drops below the restraint threshold.
CT saturation is suspected. DC saturation is suspected when
The bigger risk is improper restraint during a fault in the
there are high levels of DC present in either of the current
generator protection zone. The use of low accuracy class, low
waveforms. AC saturation is suspected when the restraint
turns ratio CTs means that the CTs are likely to saturate for
current exceeds a specific value; typically a breakpoint
high magnitude fault events. Consider an event where a
between the lower slope and upper slope, and the differential
6,000A phase-to-phase fault on the feeder cable between the
current is less than the lower slope. [5]
switchgear and the generator itself. Modeling the CTs using
For an external fault, or for an internal fault, the
the CT Saturation Calculator shows the terminal-side CTs
directional element provides excellent supervision. The phase
will saturate severely. The second harmonic content of the
angle of the current from a severely saturated CT rarely varies
current as seen by the relay can be calculated from this same
more than 90. Therefore, the directional element proves to
data. Plotting the ratio of the second harmonic current to the
be very secure. Fig. 15 shows the phase angle of the CT
fundamental current provides the plot of Fig. 13. This plot
current for the 6,000A fault of Figure 14. The blue line is the
also shows the two common restraint settings: 20% and 35%.
ideal current phase angle, and the black line is the phase angle
At these levels, second harmonic restraint will block tripping
calculated from the CT model.
of the differential element for 7 cycles or longer. While other 100

relaying will clear this fault, a slow clearing time defeats the 50

purpose of using differential protection. 0

-50
120%

100% -100

80% -150
60% -0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150

40%
Fig. 15. CT phase angle
20%

0%
-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150 The one challenge to the use of the directional element is
Fig. 13. Percentage of second harmonic during internal fault. the performance of the CT. There must be a minimum time of
saturation-free output of the CT to allow the DC and AC
C. Directional supervision saturation detection algorithms to operate. For relays with a
A different method developed by relay manufacturers is high sampling rate, and that perform protection calculation
to supervise the differential element with a directional passes at a high rate, this time may be as little as 2 3 ms of
saturation-free output. For relays operating at a lower

978-1-61284-127-4/11/$26.00 2011 IEEE


Page 7 of 8

sampling rate, and that perform protection calculation passes performance of the stator differential relay selected. It is also
at a lower rate, this time may be as much as 1 cycle. important to model CT performance for internal faults, to
ensure stator differential protection will operate dependably
D. Engineering Solutions
for these events. The CT Saturation Calculator is a valuable
For both the second harmonic restraint method and the tool in modeling CT performance. An extension of the CT
directional supervision method, the security and dependability Saturation Calculator is to use the output as part of another
of the differential element is still dependent on adequate CT spreadsheet tool that models the performance of the stator
performance. These two methods merely broaden the differential element for a specific relay.
definition of adequate CT performance to some degree. It is The final step in the engineering process, after design
still the responsibility of the protection engineer to ensure the and model, is to adjust the design based on the results of the
stator differential element will perform reliably. Therefore, model. If the CTs arent going to perform adequately, then
the protection engineer must ensure the selected CTs, and CT changes are required. These changes may mean increasing the
secondary leads, result in reliable performance of the relay. accuracy class of the CT, using a higher turns ratio on the CT,
The first step in the engineering process is to ensure the or matching the secondary burden on the CTs. Each one of
CTs meet the guidelines for generator differential protection these conditions must be modeled.
as described in ANSI C37.110, the IEEE Guide for the
Application of Current Transformers Used for Protective E. Example for Case #2
Relaying Purposes. The Guide makes the following For an example of modeling performance of CTs,
recommendations: consider the system of Fig. 11. It is reasonable to expect that
The CT primary current rating equal to 120% to 150% of a CT for generator protection take at least one cycle before
the continuous generator current rating shall be selected. DC saturation starts to occur. The system as installed uses
Full-winding ratio shall be utilized. C20, 200:5 CTs. The neutral side CTs use 125 feet of #10
CTs that have fully distributed secondary windings shall AWG for the CT secondary lead. Modeling CT performance
be used. in the CT Saturation Calculator gives the result of Fig. 16,
CTs with the highest practical secondary voltage where the CT clearly saturates in the first half-cycle.
capability shall be used. The 125 of #10 AWG results in a burden of 0.13375W,
CTs dedicated to the differential protection in order to which is a fairly reasonable burden. The 200:5 ratio is
minimize the burden shall be used. However, this may appropriate for the output of the generator full load current of
not be necessary if low burden digital generator 104A. Therefore, the first consideration should be to increase
protection relays are used for generator protection. the accuracy class of the CT at the generator neutral side. Fig.
For very high ratio CTs, 20,000/5, 4,000/5, or higher, 17 and Fig. 18 show the use of a C50 and C100 class CTs,
CTs with compensation windings to minimize the respectively. It is clear that even with a C100 CT, the CT will
proximity effect shall be specified. still saturate in the first cycle after an event occurs. It is
The differential CTs on both sides of a generator should difficult to find a 200:5 switchgear CT with an accuracy class
be of the same ratio, rating, connected burden, and greater than C100, so other measures must be taken.
preferably have the same manufacturer so that the 100
80
excitation characteristics are well matched. [2] 60
40
20
0

The last requirement is one that is consistently -20


-40

misinterpreted. The assumption is that adequate stator -60


-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150

differential performance is ensured if terminal side and Fig. 16. CT performance, C20, 200:5, #10 AWG
neutral side CTs of the same ratio, rating, and from the same 100
80

manufacturer. The requirements for highest practical 60


40

secondary voltage capability and same connected burden are 20


0

routinely overlooked or ignored. The two case studies in this -20


-40
-60
paper prove that it is not enough to simply match the terminal -0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150

side and neutral side CTs. Poor differential performance may Fig. 17. CT performance, C50, 200:5, #10 AWG
still result. The goal, as clearly described in the Guide, is to
100
match the excitation performance of the CT circuits to ensure 80
60

differential performance. 40
20

If the first step in the engineering process is to size CTs, 0


-20
-40
and design CT circuits, to meet the requirements of the Guide, -60
-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150
the second step is to model this design to see if the stator
differential will truly perform. The goal is, as much as Fig. 18. CT performance, C100, 200:5, #10 AWG
possible, to ensure that CT saturation for DC will not limit the The next solution to try is to decrease the burden on the

978-1-61284-127-4/11/$26.00 2011 IEEE


Page 8 of 8

neutral-side CTs by using a larger secondary wire. The not be possible to have reliable stator differential
simplest method is to simply run a parallel set of #10 AWG performance. Adding a time delay to the differential element
wire, to halve the connected burden. Fig. 19 shows the results is not appropriate. The differential element is intended to be
with the original C20 class CT. Further analysis shows that high-speed protection. Adding a time delay essentially defeats
even with parallel #10 AWG secondary leads, a C100 class the purpose of differential protection.
CT is still required before reasonable CT performance can be
expected. The results in Fig. 20 show the CT doesnt saturate VI. SUMMARY
until the second cycle after the event begins when using this This paper highlights the issues around stator differential
combination. protection for small generators. Stator differential protection
100
80
60
is used for high-speed detection of faults in the generator zone
40
20
of protection. Due to the dependence on the accuracy of CT
0
-20
replication, the challenge for differential protection is security
-40
-60 during external faults or when energizing a transformer.
-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150
Generators are at higher risk for CT saturation due to the high
Fig. 19. CT performance, C20, 200:5, Parallel #10 AWG
system X/R ratio at the generator, which leads to DC
100
80
saturation of the CTs. For small generators, this concern is
60
40 increased because these generators tend to use CTs with a low
20
0 accuracy class, low connected turns ratio, and relatively large
-20
-40
-60
burden. Every one of these factors increases the likelihood of
-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150
CT saturation. The selection of low accuracy class CTs and
Fig. 20. CT performance, C100, 200:5, Parallel #10 AWG large burden is normally based on economics, with little
Fig. 21 compares the terminal-side and neutral side CT consideration of the successful operation of the differential
waveforms using the C100, parallel #10 conductor element.
cominbation. The neutral side CT still saturates due to the DC This poor CT performance and the impact on stator
content. However, the relay should successfully declare DC differential relaying is a well-known phenomenon. Relay
saturation, and the directional element will successfully block manufacturers have taken steps in algorithm design to
tripping. improve the security of stator differential protection in
90 regards to DC saturation of the CTs. However, from an
80
engineering perspective, it is reasonable to expect at least one
70

60
cycle of saturation free time out of the CTs for low magnitude
50
fault events resulting in DC saturation. It is the responsibility
40

30
CT1 of the engineer designing the protection system to ensure
CT2
20 DIFF appropriate CTs are selected for the application, appropriate
DIR
10

0
CTSAT
OPERATE
CT secondary leads are used, and the stator differential will
-10
0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14
SAT AC
SAT DC
perform reliably.
-20

-30

-40 REFERENCES
-50

-60
[1] IEEE Recommended Practice for Protection and Coordination of
-70
Industrial and Commercial Power Systems, IEEE Std 242-2001, 2001.
[2] IEEE Guide for the Application of Current Transformers Used for
Fig. 21. CT performance with improved neutral side CTs
Protective Relaying Purposes, ANSI/ IEEE C37.110-1996, 1996.
During a high-magnitude internal fault, the CTs may [3] J. L. Blackburn, Protective Relaying Principles and Applications, 2nd
edition, Marcel Dekker, Inc., New York, NY, 1998.
saturate and AC saturation may be declared. However, the [4] IEEE PSRC CT Saturation Calculator, IEEE Power Engineering
directional element will correctly declare an internal fault, Society Protective Relaying Subcommittee, www.pes-psrc.org.
and permit tripping. [5] B. Kasztenny, D. Finney, Generator Protection and CT Saturation,
Texas A&M Protective Relay Conference, April 5, 2005.
This exercise is for a specific model of relay. For a stator [6] A. E. Fitzgerald, C. Kingsley, Jr., S. D. Umans, Electric Machinery, 4th
differential relay that uses second harmonic restraint, the edition, McGraw-Hill Book Company, New York, NY, 1983, pp. 4-24.
exercise is somewhat different. There the concern is the
dependability of protection during an internal fault. With poor
CTs, the stator differential should be secure for DC saturation
due to external events. However, with low accuracy class
CTs, and a high connected burden, the second harmonic
restraint may over-restrain for an internal fault.
For some configurations of generators and CTs, it may

978-1-61284-127-4/11/$26.00 2011 IEEE

You might also like