Note: If LP fuel gas available, switch supply gas from LPG fuel gas.
Manual Execution Acid Flare (FFG Ignition)
1 Open and close any drain valves in the FFG lines to ensure that
there is no water accumulation in these lines.
381-BAR-2213 (MTDF-PR-381-PID-1005)
381-BAR-1908 (MTDF-PR-381-PID-1005)
381-GAT-3013 (MTDF-PR-381-PID-1005)
381-GAT-3014 (MTDF-PR-381-PID-1005)
381-GAT-3015 (MTDF-PR-381-PID-1005)
381-GAT-3016 (MTDF-PR-381-PID-1005)
2 Turn On Local Control Panel 381-LCP-1002.
3 Turn the selector switch Auto/Manual to Manual position.
1. Manual indicator lamp (381-UI-1012) will be ON (Amber)
2. Pilot-off indicator lamp will be ON (green)
4 Open manual ball valve:
381-BAF-1314
381-BAF-1316
381-BAF-1317
381-BAF-1318
5 Close manual ball valve 381-BAF-1015
6 See pressure indicator (381-PI-1104) at 1/2 instrument air line
Range pressure 0-30 psig
7 See pressure indicator (381-PI-1105) at 1/2 instrument air line
Range pressure 0-30 psig
8 See pressure indicator (381-PI-1106) at 1/2 instrument air line
Range pressure 0-60 psig
9 See front door of local control panel (381-LCP-1002), to analyze
which line will be send fire ball/ignition
Pilot-off indicator lamp shall be ON condition (green)
10 Choose one pilot we want to ignite first by opening the 1 valve
(381-BAF-1306/7/8)
One of the 1 valve is opened while others are remained close.