Professional Documents
Culture Documents
2. Conductor Selecting
2.1 Summary
The Badrah transmission line is to transport power from the Badrah power plant with a capacity of
24.7[MW] x4 to new S/S and this design is to review and select it in the following aspects:
Select a conductor by allowable current and then, review voltage drop, specific load, stability etc.
for the selected conductor and select a power line in terms of transmission carrying capacity.
Given economic feasibility, consider working tension, economical span and sag related to the
height of the steel tower.
Select a line showing excellent fatigue limit stress against the vibration of the conductor due to
wind.
-9-
33kV Bhadra T/L
Badrah related transmission lines are expected to be transmission lines of low power factor
and so are considered to be determined by section 3 stability.
Allowable current
If the temperature rises to more than a certain limit, mechanical strength and many other
functions are degraded for conductor and hence, the allowable current of the conductor of Badrah
T/L is lower than that of the conductor under normal conditions because it is under unfavorable
conditions of high ambience temperature at room temperature so the proper power capacity shall
be transported under the conditions to meet the conductor. Allowable current is highly dependent
on quality of material, structure, surface condition of the conductor , ambient temperature,
amount of solar radiation, wind speed, rain or snow, altitude etc. but the important thing is that it
shall not exceed the maximum allowable temperature of the conductor. Because when the
temperature rises, it is difficult to maintain appropriate ground clearance due to reduction in
mechanical properties and sag increase on the aluminum conductor.
C. Transmission capacity
1) Transmission capacity by allowable current
Transmission capacity is calculated by the following equation
P=(EaEs/XL)
Ea : Sending end voltage
Es : Receiving end voltage
XL : Reactance on the line
: Angle of Power factor
This review applied allowable capacity of current requested by the client for transmission capacity
Transmission capacity
P= 3 V I [MVA ]cos
= 3 33 [ KV ] 500 [ A ]1
Tne conductor depending on the thermal capacity was reviewed and as a result, candidate the
= 28.57 [MVA]
conductor of Table 1 was selected
[Table2-1] Comparison of power lines depending on thermal capacity
Kind of conducor ACSR/AW ACSR/AW ACSR/AW
240 240 240
Description (HAWK) (Flicker) (Pelican)
P= P= P=
Carrying capacity 3 33 504 0.8=23
3[MW
33 514
] 3 33
0.8=23.5 [MW509
] 0.8=23.2[MW ]
- 10 -
33kV Bhadra T/L
Allowable temperature
90 90 90
(continuous)
Voltage drop
Voltage drop is expressed as the difference in algebraical expression (Vs-Vr) between sending end
voltage Vs and receiving end voltage Vr and this value is calculated according to Impedance and
admittance of line, power factor and volume of the load in the transmission line. And the
percentage of this voltage drop and receiving end voltage is referred to as voltage drop rate.
VsVr
100 [ ]
Vr
Generally, the standard of the maximum value of voltage drop rate in the transmission line is
defined as 5% ,but this line is 10% which was required by client
Stability margin
The stability in the power system refers to the ability for the system to continue safe operation
- 11 -
33kV Bhadra T/L
under the given operating conditions and stability margin is defined as follows and 20 to 30% is
generally applied.
80 22.85 60
70 20 55
60 17.14 47
50 14.28 37
- 12 -
33kV Bhadra T/L
Vibration of line
Vibration characteristics
If the breeze is blowing from the side to an overhead power line, swirl is generated behind the line,
causing mechanical alternating force in the line in the vertical direction. Usually, the frequency of the
vibration is 5~30 and loop length of the wave is about 3~10m and although amplitude is small, if this
vibration is generated and lasts for a long time, the conductor is worn out and fatigue due to repeated
stress and conductors are cutted off inside the clamp, causing transmission accidents. Generally a
steel wire is highly vibration resistant but AL is less vibration resistant and easy to be cutted off. In
particular, the river crossing section is a place easy to get stressed due to micro vibration because the
difference in altitude is a little big so it is necessary to use conductors with good mechanical strength.
Measures for vibration
When designing long span places such as river crossing, channel crossing especially, sections of more
than 500m, fatigue caused by vibration should be considered and narrow base towers was used in
most of tower and the maximum span is around 200m so it is considered that no special vibration
measures are not necessary and HAWK with the biggest cross-section area of a steel wire among 240
conductors was selected to reduce the influence caused by vibration on conductor and as
measures against micro vibration, 1 STOCK BRIDGE DAMPER of 100m~250m, 2 STOCK BRIDGE
DAMPERs of 250m~600m2 and 3 STOCK BRIDGE DAMPERs of more than 600m are to be attached to
both ends of span.
- 13 -
33kV Bhadra T/L
5 0.52
[1.01+0.0372 ( 21.8 0.9651 0.5 2.05 10 ) ]0.02956 (9055)
QCF2: High wind speed area
0.6
0.0119 ( 21.8 0.9651 0.5 2.05 105 ) 0.02956 ( 9055 ) [W /m]
QCN: No wind speed area
- 14 -
33kV Bhadra T/L
5 9 2
0.02424+7.477 10 T e 4.407 10 HT e [ W /m ]
23.4583 0.9922
: Time angle
AM :11 :0015 :00
PM :2: 30
ZL: Latitude
ZC: Azimuth of the sun
C+ tan1 ( )
18069
- 15 -
33kV Bhadra T/L
-180<<0 0 180
1.002
- 16 -
33kV Bhadra T/L
1.037
3) AC resistance
Rac
1+ 2 +Rdc
0.1489[/ km]
- 17 -