Professional Documents
Culture Documents
Fans
Fire Safety
in Ventilation Systems
2 | Fire safety
DS 428.4
Code for technical measures for
fire protection in ventilation systems
Systemair has a complete range of components for fire protection of ventilation systems. This brochure will provide a list of
the most commonly used components, including fire- and smoke dampers, smoke dampers, smoke evacuation dampers and
a fire control system for monitoring and exercising of the dampers. It also shows various system solutions that provide an
overview of the different possible combinations, all of which are in accordance with the fire protection standard DS 428.4.
DS 428.4 A2: Non-combustible material Roof curbs: Must be insulated with 50 mm insu-
Foreword S1: Very limited smoke development lation A2-s1,d0, through the roof, minimum 100
The standard contains a number of requirements D0: No burning droplets mm under and 100 mm above the roof.
that dictate how to achieve a responsible fire RV: Smoke fan intended for a smoke extraction
technical safety and operation of ventilation sys- system System solutions:
tems. Ho: Horizontal The duct system must be such designed, that
Ve: Vertical the risk of smoke and fire spreading to other fire
Introduction io: Fire from the inside and outside. cells, fire sections or similar building units is not
The standard contains a number of requirements increased.
to ensure a responsible fire technical construc- Fire-, flame-, smoke- and smoke evacuation
tion of ventilation systems, so that the risk for dampers Damper-secured system:
start, developing and spreading of a fire due to BRS: Fire- and smoke damper class EI60 (ve ho Securing a ventilation system against spreading
the ventilation system is minimized. io)S, 70 C fire thermostat, spring-return actu- of smoke must be based on the creation of rea-
ator. Shall prevent fire and smoke being spread sonable security against that smoke and
Scope between fire sections. combustion products can enter the duct system.
The purpose of this standard is to ensure that
mechanical ventilation systems shall be FRS: Flame- and smoke damper class E60 (ve Smoke-ventilated systems:
designed, executed and maintained in such a ho io)S, 70 C fire thermostat, spring-return Securing a ventilation system against spreading
manner that the potential for start, developing actuator. Shall prevent smoke being spread of smoke must be based on the creation of rea-
and spreading of a fire due to the system is between fire sections. sonable security against that smoke and com-
minimized. The standard contains requirements bustion products, which have entered the duct
regarding design, construction, testing, and RS: Smoke damper class E30 (ve ho io)S, system, can not be spread through the duct sys-
operation of mechanical ventilation systems. spring-return actuator. Shall prevent smoke tem to other fire cells, fire sections or similar
being spread between fire cells. building units.
The standard applies to mechanical and hybrid
ventilation systems permanently installed in RES: Smoke evacuation damper class E30 (ve ho A smoke-ventilated system must be such
buildings. Installations for natural ventilation io)S, spring-return actuator. Must ensure the designed, that smoke in the system is dis-
must be performed according to this standard to discharge of smoke during a fire situation. charged to the outside with reasonable safety.
the extent that they can be assimilated with A smoke-ventilated system cannot be combined
mechanical ventilation. Dampers shall be tested according to EN 1366 with fire-, flame- and/or smoke damper, which
and classified according to EN 13501-3, appen- prevents the discharge of smoke that has
Installations for industrial or semi-industrial pro- dix classes ho ve io. Monitoring must be entered the system. With the exception of the
cesses and storage should at least follow the installed through the control system, which outermost fire cell or similar building units, from
requirements in the standard, but there may be checks the function of the sensors and damper where spreading of smoke to other fire cells, or
additional requirements from authorities. actuators. similar building units are impossible. In a smoke-
ventilated system, the smoke must run via a
Definitions Flexible connections: Must comply with class duct, by-passing parts of the system with large
Fire section: Separation with building material A2-s1,d0, melting point of at least 850 C, max flow resistance, or components in which the risk
class (R) EI60 A2-s1, d0 (formerly BS60) length of 300 mm for fan connections in of clogging of the smoke particles from a fire is
Fire cell: Separation with building material class unexploitable attic. great. This includes filters, heat recovery compo-
(R) EI60 (formerly BD60) nents, heating- and cooling coils, etc.
R: Carrying capacity
E: Integrity
I: Isolation
S: Tightness for smoke
Fire safety | 3
Fire Safety
Regarding fire safety of ventilation systems, the most Buildings and especially inventory
important is: To save lives and valuable inventory, and to contain an amount of combustible
ensure good working conditions for the rescue team. A material. A correct fire safety of ven-
fire occurrence must be limited before it develops into a tilation systems can prevent heat and
disaster. Foremost to save lives, but also significant values smoke from spreading through the
may be lost. The requirements for personal safety and the ventilation system. Should for exam-
emergency response capacity are very closely linked to ple a too early destabilization of the
the risk of fire spreading and stability of the building. building occur, a collapse can cause a
Strategically, this means that in case of a fire, persons disaster risk of a significant size. Fire
must be able to exit the building by themselves or with safety in ventilation plants is thus
help from the rescue team. necessary in modern buildings.
4 | Fire Safety
Type PK-I-R EI60S DV9-T The damper blade consists of calci- of 72C (tolerance of 1.5C) in 30
Type PK-I-R EI90S DV9-T um-silicate board (asbestos-free), fit- to 60 seconds, activates the actuator
Approved according to EN 1366-2 ted in a protecting frame of galva- and closes the damper blade within
Classified according to EN 13501-3 nized steel. The damper blade has a 60 seconds.
Additional class EI60 (ve ho io)S, fire passive sealing (a ring of rubber,
100-630 which prevents penetration of smoke) Accessories: 2 sets of cover plates
Additional class EI90 (ve ho io)S, and a fire active sealing (an expand- made from calcium-silicate boards
710-1000 ing fire paste, which prevents pene- must be used at installation in light-
Fire class according to DS 428.4, tration of smoke and heat transfer weight walls (gypsum walls) and
EI60 (ve ho io)S during a fire). The damper has male heavy structures (bricks/concrete), if
For mounting in circular ducts connection. The damper will be deliv- no casting is made around the damp-
(100-1000) ered as type DV9-T with spring-return er. The cover plates must be fastened
For mounting both horizontal and actuator (24 V), currentless closed. on both sides of the wall/covered and
vertical, independent of position of 230 V is available. tightened against smoke with fire
the damper shaft sealing. Fire- and smoke dampers
Ready to install in all types of walls The actuator will close the damper must always be installed in the sec-
and ceilings blade at thermal or electrical signal. tion separation. Installation manual
Equipped with 24 V spring-return The damper has a fire thermostat and installation certificate PK-I-R
actuator, currentless closed. which, when having reached or EI60/90S, see www.systemair.com/
exceeded the ambient temperature dk/Danmark/Produktkatalog/
Fire- and smoke dampers shall pre-
vent fire and smoke being spread
between fire sections or similar fire
performance units through the duct PK-I-R EI60S d L L1 L2 kg
system. PK-I-R EI60S 100 100 450 - - 3,6
PK-I-R EI60S 125 125 450 - - 4,0
PK-I-R EI60S 160 160 450 - - 4,8
122
PK-I-R E60S (RS) / EK-I-R E60S 160 (RES) 160 350 - - 3,6
PK-I-R E60S (RS) / EK-I-R E60S 200 (RES) 200 350 - - 3,9
PK-I-R E60S (RS) / EK-I-R E60S 250 (RES) 250 350 7 - 4,5
45 45 PK-I-R E60S (RS) / EK-I-R E60S 315 (RES) 315 350 40 - 5,3
L1 350 L2 d+88 PK-I-R E60S (RS) / EK-I-R E60S 400 (RES) 400 350 82 - 6,8
PK-I-R E60S (RS) / EK-I-R E60S 500 (RES) 500 350 132 12 10,7
PK-I-R E60S (RS) / EK-I-R E60S 630 (RES) 630 350 197 77 16,0
6 | Fire Safety
Type PK-I-S EI90S DV9-T A fire- and smoke damper shall pre- which, when having reached or
Approved according to EN 1366-2 vent fire and smoke being spread exceeded the ambient temperature
Classified according to EN 13501-3 between fire sections or similar fire of 72C (tolerance of 1.5C) in 30 to
Additional class EI 90 (ve ho io)S performance units through the duct 60 seconds, activates the actuator
Fire class according to DS 428:4, system. The damper blade consists of and closes the damper blade within
EI 90 (ve ho io)S calcium-silicate board (asbestos-free), 60 seconds.
For mounting in square ducts fitted in a protecting frame of galva-
(100x100 - 1000x1600) nized steel. The damper blade has a Accessories: 2 sets of cover plates
For mounting both horizontal and fire passive sealing (a rubber sealing, made from calcium-silicate boards
vertical which prevents penetration of smoke) must be used at installation in light-
Ready for installation in all types of and a fire active sealing (an expand- weight walls (gypsum walls) and
walls and ceilings ing fire paste, which prevents pene- heavy structures (bricks/concrete), if
Equipped with 24 V spring-return tration of smoke and heat transfer no casting is made around the damp-
actuator, currentless closed. during a fire). er. The cover plates must be fastened
on both sides of the wall/covered and
The damper will be delivered as type tightened against smoke with fire
DV9-T with spring-return actuator (24 sealing. Fire- and smoke dampers
V), currentless closed. 230 V is must always be installed in the sec-
available. tion separation. Installation manual
and installation certificate PK-I-S
The actuator will close the damper EI90S, see www.systemair.com/dk/
blade at thermal or electrical signal. Danmark/Produktkatalog/
The damper has a fire thermostat
8 6 7 2 1 8
122
H+80
H
L
255 145 L+80
W=400 L+130
A: Fire- and smoke dampers in small sizes. See table A below.
8 7 2 2 1 7
120
H+80
H
255 145 L
W1 W2
W=400 L+80
L+140
B: Fire- and smoke dampers in large sizes. See table B on page 6.
1. Damper blade, 2. Frame, 3. Inspection cover,
4. Damper actuator, 5. Fire thermostat
Note: Dampers with dimensions 150 mm have flange dimensions of 30 mm.
Fire control system BR-A2 R eset of the alarms above. Mounting bracket included
Systemairs fire control system has Manual exercise of fire- and smoke Terminals and cable clamp for con-
been prepared in accordance with DS dampers, smoke dampers, smoke nection of damper and bus cable.
428.4 for easy and simple installation evacuation dampers, and possibly,
(bus system); it is configurable and smoke extract fan Power supply BR-A2, SF
therefore extremely flexible. The fire Timer-setting for weekly exercise The section controller can supply
control system contains all the neces- A control panel can be connected to the first 5 dampers
sary functions such as monitoring, max. 16 section controllers Hereafter use a power supply for
testing and verifying the operation of Event log for the latest 84 exercises every 8 dampers
fire- and smoke dampers, smoke and service receipts are saved auto- Max. 100 m cable to the farthest
dampers, smoke evacuation dampers, matically. damper
and communicating with the unit and Max. total bus length 1200 m.
possibly, the smoke extract fan. Section controller BR-A2, SK
Max. 62 damper units can be Smoke detector for duct type RDK-2
Key features: controlled and monitored (UG-3-O)
Disables the dampers and discon- When using more than 62 dampers Smoke detector for measuring/
nects the fan/unit in case of a fire an extra section controller must be detection of smoke in the duct sys-
Weekly tests of dampers and possi- connected as a slave tem
bly, the smoke extract fan, to Smoke detector (max. 10 pcs.) Air velocity between 0.2 and 20
ensure that they are operational BTB temperature sensor with reset m/s.
Manual testing is possible on the control panel, 40 C (default)
Ensures that the dampers are open Detailed error message on each Temperature sensor type BTB (TT-
during normal operation, and venti- damper 522)
lation is functioning as planned Stop of the fan/unit The temperature sensor detects a
When smoke-/fire is detected, you External fire detection system or set temperature due to fire and
can choose to have all dampers signal device transmit the signal to the section
closed and shut down the ventila- Start and control of smoke fan controller.
tion in the entire building or only in Service signal
the current fire section DPT Differential pressure transmitter Differential pressure transmitter
Detailed error message on each for monitoring and control of fan type DPT
damper IP 54 box enclosed Differential pressure transmitter incl.
24 V supply and control via the bus Main power supply 230 V AC connector and measure hose,
system for each damper. Power supply 24 V DC for detects the pressure in the duct and
5 dampers transmits the signal to the section
The fire control system consists of The section controller can work controller
the following components: without any control panel. Monitors the exhaust fan operation
Control of smoke fan operation by
Control panel BR-A2, BP Damper module BR-A2, SM weekly exercising
Display for monitoring and setting of One damper module used by each Pressure control of the smoke fan in
the necessary parameters fire- and smoke damper, smoke a fire situation.
Alarm readout for fire- and service damper or smoke evacuation
alarms and alarm log damper
Fire Safety | 9
Wiring plan
BR-A2, SK, Section controller
TIME ec
230 V AC
KBR/F-EC
230 V AC
BR-A2, SF
230 V AC BR-A2, SM Damper module, max. 8 pcs.
Power supply
AXC(B)
400 V AC 230 V AC
DVV
400 V AC
BR-A2, SF
BR-A2, SM Damper module Power supply
RDK-2
230 V AC
BTB
PDS network cable Cat 6 AWG 23 (24)
1 x 230 V AC
Damper-secured system
Excerpts from DS 428.4
Ventilation room
Fire cell
Explanation of symbols
AKHI
Fire section separation
ULHI RDK-2
Fire cell separation DPT
Unexplorable
Ventilation duct R attic
P
RS Smoke damper
Iso Insulation
RV Smoke fan
activated by the shared detector of Air intake- and exhaust dampers must Weekly exercise of smoke dampers
the current fire section. also be closed. You can also choose to and ensuring that the dampers are
stop the supply- and exhaust fans. open during normal operation. It is
At fire detection, you can choose to Then all smoke dampers and fire- and possible to do manual testing of
let supply- and exhaust fans continue smoke dampers must close. dampers.
to run, and only close the smoke
dampers and fire- and smoke damp-
ers that are operating the fire affect-
ed section. Ventilation room
Fire cell
AKHI Unexplorable
attic
ULHI P
DPT
RS LDC
RS
R
RDK-2
RS BRS
RS BRS
R
RDK-2
RS BRS
BRS
RS
R
RDK-2
Example 2
3 residential fire sections, 6 residential fire cells: 6 pcs. BRS fire- and smoke dampers, 6 pcs. RS smoke dampers. Fire control system consisting of: 1 pcs.
BR-A2, BP control panel, 1 pcs. BR-A2, SK section controller, 1 pcs. BR-A2 SF power supply, 12 pcs. BR-A2, SM Damper modules, 3 pcs. RDK-2 Smoke detec-
tor for duct, 1 pcs. DPT pressure transmitter. Alternatively, 3 pcs. BR-A2, SK section controls (no BR-A2 SF power supply, but BRS in all branches of the
shaft). All ventilation ducts in the ventilation room and unexplorable attic must be insulated with thermal insulation class A2-s1, d0. The drawing is indicati-
ve, and it is the design engineers responsibility to ensure that the design is in accordance with the law.
12 | Fire Safety
Smoke-ventilated system
Excerpts from DS 428.4
Ventilation room
Fire cell
Iso Insulation
RV Smoke fan
Example 3, elderly housing, usage category 6
Fire thermostat or temperature sensor BTB
Residential ventilation with heat recovery unit and smoke fan (50/30 Pa). Level 1: 1 pcs. smoke fan RV,
P Pressure transmitter DPT 2 pcs. FLXB flexible connections, 2 pcs. smoke damper, 3 pcs. smoke evacuation dampers. Fire control
system consisting of: 1 pcs. BR-A2, BP control panel, 1 pcs. BR-A2, SK section controller, 1 pcs. DPT pres-
R Smoke detector, duct mounting RDK-2 sure transmitter, 1 pcs. BTB temperature sensor, 5 pcs. cooking hoods H-106-E. All ventilation ducts in
the ventilation room must be insulated with thermal insulation class A2-s1, d0. Ducts in unused attic
ABA+AVA Auto. fire alarm- and warning system
must be insulated with fire insulation class EI 30/E 60 A2-s1, d0. The drawing is indicative, and it is the
design engineers responsibility to ensure that the design is in accordance with the law.
Fire Safety | 13
damper that is closed at normal located within this. Ducts in an unex- should be fire insulated corresponding
operation with voltage (currentless ploitable attic, which only serves one to the diameter of the branch, but a
open). A smoke-ventilated system is fire section and are located within minimum of 0.2 m. For an extraction
generally performed as a duct class EI this, must be insulated with minimum system, reasonable safety for the dis-
30/E60 A2-s1,d0, which also includes 50 mm insulation class A2-s1,d0. charge of smoke to the outside can
ducts in installation shafts and unex- Branches from a fire insulated duct be achieved by: Smoke-ventilated
ploitable attics. An exception to this is system with smoke fan in operation,
ducts in the ventilation room, ducts in where all residential fire cells is per-
the open air (outdoor) and ducts that formed with a minimum of 50 Pa
Ventilation room
only serve one fire section and are smoke resistance.
Fire cell
ULHI AKHI
RES
RES RV
DPT
RS BTB
RES p Unexplorable
attic
RS
TSK/PER
30 Pa
LDC
50 Pa 50 Pa
Cooker hood EFF/RFP
30 Pa
LDC
50 Pa 50 Pa
30 Pa
LDC
50 Pa
50 Pa
Example 4
Residential ventilation with heat recovery unit and smoke fan: 1 pcs. smoke fan RV, 2 pcs. FLXB flexible connections, 2 pcs. smoke damper, 3 pcs. smoke evacua-
tion damper. Fire control system consisting of: 1 pcs. BR-A2, BP control panel, 1 pcs. BR-A2, SK section controller, 5 pcs. BR-A2, SM damper modules, 1 pcs. DPT
pressure transmitter, 1 pcs. BTB temperature sensor, 3 pcs. cooker hoods H-106-E. All ventilation ducts in the ventilation room must be insulated with thermal
insulation class A2-s1, d0. All ducts in shaft and unexplorable attic must be insulated with fire insulation class EI30/E60 A2-s1, d0. The drawing is indicative, and
it is the design engineers responsibility to ensure that the design is in accordance with the law.
14 | Fire Safety
Smoke-ventilated system
Excerpts from DS 428.4
For supply air systems, where the fan or coupled with the smoke fan in and possible flexible connections
extract system in the operated fire the extract system. All residential fire must everywhere be performed as
sections or similar fire units are units are performed with a minimum material class A2-s1, d0 with a melt-
designed as smoke-ventilated sys- of 30 Pa smoke resistance. A smoke ing point of at least 850 C. The
tem, can reasonable safety for the resistance including connected ducts smoke fan can be the extract fan for
discharge of smoke to the outside be the normal operation or a separate
achieved by: Converted system, fan exclusively for smoke extraction.
where the supply air system is The connection point for the smoke
designed as a smoke-ventilated duct fan must be at or above the upper
system, supplemented with a smoke channel system branching to the
AKHI
(Alternatively, roof fan type DVG-V/F-EC)
FLXB
LDC P Cebocon10
RV
KBR/F-EC
ULA
50 Pa LDC
50 Pa EFF/RFP
Cooker hood
50 Pa LDC
50 Pa
50 Pa LDC
50 Pa
Example 5
Residential ventilation with the smoke fan as daily, normal fan (50 Pa): 1 pcs. RV smoke fan KBR/F-EC (400 C), 2 pcs. FLXB flexible connections, 1 pcs. CEBOCON
10 pressure control, 3 pcs. cooker hoods H-106-E (50 Pa), 1 pcs. AKHI roof cowl. Alternatively, roof fan type DVG-V/F-EC can be used. All ducts in shaft and unu-
sed attic must be insulated with fire insulation class EI30/E60 A2-s1, d0. The drawing is indicative, and it is the design engineers responsibility to ensure that the
design is in accordance with the law.
Fire Safety | 15
operating area, so that smoke will not The temperature at the smoke fan is ture, the maximum air volume in the
be sucked down into a duct system set as a mixing temperature, consist- fire room is used. For remaining rooms,
with branches. A smoke fan must be ing of 945 C from the fire room, and use diversity factor 0.2 for the differ-
able to withstand the occurring tem- 20 C from the remaining rooms (the ence in air volume between minimum
perature for 60 min. after the fire has mixing temperature must be at least and maximum air volume without
started, valid from a normal-tempera- 100 C). The fire room is usually incalculation of other diversity factors.
ture operating fan with a minimum of determined as the fire cell with the The air volume depends on the build-
1 hours operation and at an ambient largest air volume - for systems with ings density and is typically smaller
temperature of 20 C without cooling variable air volume, uses the maxi- than the air volume. The volume must
from wind or rain. Functional require- mum air volume rate. For calculation be sufficient to ensure the systems
ment is documented by manufacturer. of the maximum flue gas tempera- required smoke resistance, however
pressure limited to a maximum of 100
Pa negative pressures at the upper
AKHI Exhaust over roof ridge
Discharge duct
Explanation of symbols
Ventilation duct
KVKE-EC
RS Smoke damper
ULA
RES Smoke evacuation damper
100 Pa LDC
100 Pa
EFF/RFP BRS Fire- and smoke damper
Cooker hood
x xx Pa Smoke resistance indicated in Pa
Iso Insulation
RV Smoke fan
ULA
100 Pa LDC Fire thermostat or temperature sensor BTB
100 Pa
P Pressure transmitter DTP, Cebocon5
Example 6
Residential ventilation with the extract fan as daily, normal fan (100 Pa). Separate fire insulated ducts in shaft: 1 pcs. KVKE-EC box fan, 2 pcs. FLXB flexible
connections, 1 pcs. CEBOCON 5 pressure control (100 Pa), 2 pcs. cooker hoods H-106-E (100 Pa), 1 pcs. AKHI roof cowl. All ducts in shaft and unused attic must
be insulated with fire insulation class EI30/E60 A2-s1, d0. The drawing is indicative, and it is the design engineers responsibility to ensure that the design is in
accordance with the law.
Systemair A/S Denmark
Brandsikring_uk_04_2013-V1
Ved Mileplen 7
DK-8361 Hasselager
Tel. +45 87 38 75 00
mail@systemair.dk
www.systemair.dk