Professional Documents
Culture Documents
The major components of an Electrical Submersible Pump (ESP) system are shown in (Figure 1).
Figure 1
The systems surface equipment includes transformers, a switchboard, junction box and surface
power cables. Power passes through a cable running from the transformer to the switchboard and
junction box, then to the wellhead
The ESP downhole assembly is located in the well at the bottom of the tubing. The motor, seal,
intake and pump assembly, along with the power cable, goes in the well as the tubing is run. The
well power cable is spliced to a motor cable that is connected to the outside of the downhole
assembly. Power from the surface facilities connects to the ESP at the junction box. The ESP itself
is a centrifugal pump located at the top of the downhole assembly (Figure 2: ESP systempump
diagram. Courtesy of Schlumberger).
Figure 2
Below the pump is an intake that allows fluid to enter the pump. Below the intake is a gas
separator and a protector or seal, which equalizes internal and external pressures and protects
the motor from well fluids. At the bottom is a motor that drives the pump. The assembly is
positioned in the well above the perforations; this allows fluid entering the intake to flow past the
motor and cool it.
Transformer
The first component of the ESP system is the transformer system, which is used to step-up or
step-down the voltage from the primary line to the motor of the submersible pump. The system is
usually arranged in banks of three single-phase transformers, a three-phase standard transformer,
or a three-phase autotransformer. Because a range of operating voltages may be used for
submersible pump motors, the transformer must be compatible with the selection of the motor
voltage.
For example, a primary voltage of 12,500 volts (V) may need to be stepped down to 2,400V by a
transformer. On the other hand, the primary voltage delivered to a well may be 440V, so a
transformer would be needed to step up that voltage to 880V. In general, the manufacturers of
electrical submersible pumps also build and sell the necessary transformers. An example of
transformer specifications, adapted from one page of a manufacturers catalog, is given in Table 1.
Switchboard
The electrical cable from the transformer goes to the switchboard (Figure 1: Switchboard for ESP
system. Courtesy Weatherford International Ltd).
Figure 1
Switchboards sold by the ESP manufacturer are available in a range of sizes and models to
accommodate the electrical submersible pump system (Table 2)
The switchboard controls the pump motor and provides overload and underload protection.
Protection against overload (a condition where excessive amperage flows through the motor) is
needed to keep the motor windings from burning. Protection during underload (a condition where
the pump is not displacing its design volumes) is needed because low fluid flow rates will prevent
adequate cooling of the motor.
In addition to these functions, the switchboard may be used to record amperage on a continuous
basis, using a 24-hour chart. This chart is a good diagnostic tool for measuring pump
performance. The switchboard can also be used as an adjustable time-automatic restart control. In
this case, a pump that shuts down because the well is pumped off would depend on a switchboard
control to begin pumping again after a fixed time period. This protection is needed because the
pump should not be restarted until the previously pumped fluid has stopped backflowing through
the pump. Such backflow causes the motor impeller to reverse circulate. Placing a standing valve
in the tubing will normally eliminate this problem.
The switchboard may include additional features such as signal lights and automatic remote
control. Switchboards are available in ranges from 240 to 4800V.
Junction Box
The next component of the ESP system is the junction box, which connects the power cable from
the switchboard to the power cable from the well. As such, it should provide an explosion-free vent
to the atmosphere for any gas that might migrate up the power cable from the wellbore. The
junction box should be located at least 15 feet from the wellhead, and should be securely locked
at all times to protect against vandalism.
Figure 2
A special wellhead is used to pack off the power cable so that it can enter the wellbore without
leaks . Cable is available in round and flat styles (Figure 3: Round ESP cable; Figure 4: Flat ESP
cable). The conductors are available in different sizes and are usually made of copper or
aluminum.
Figure 3
Figure 4
The proper selection of the cable and the conductors depends on:
The expected amperage that will flow through the cable to the motor
The calculated voltage drop in the line from the surface to the pump.
The space that exists between the tubing collar and the casing (even though the cable is
banded to the tubing at selected points, there must be enough space to install and pull the
pump without damaging the cable or hanging it in the well).
The equipment operating environment - such as the operating pressure and temperature at
pump depth.
CABLE AMPERAGE
The first consideration in selecting cables is amperage. The limits on amperage for cables
containing copper conductors are as follows:
1 115
2 95
4 70
6 55
Note that the cable with the smaller number has the larger diameter. Thus, a Number 1 cable can
carry a maximum of 115 amps.
VOLTAGE DROP
The second selection consideration is the voltage drop that will occur between the wellhead and
the pump. Normally, the maximum voltage drop for an electrical cable is about 30V per 1000 feet.
(Figure 5) is a graph of amperage versus voltage drop per thousand feet of cable length for
various conductors.
Figure 5
For example, if a 60-amp current is flowing through a 1000-foot cable, then the voltage drop in a
No.1 copper conductor will be about 16 V. In a No.4 copper conductor, it will be about 31V; while a
No. 6 copper conductor produces a voltage drop of about 45V. Clearly, the larger conductor with
the lower voltage drop is more desirable, especially in deep wells. A counter-argument to this is
that the larger cable costs more, and might not fit within accepted tolerances between the tubing
collars and the casing. These factors must be anticipated and balanced when designing a system.
As the shaft of the pump moves in response to the force of the motor, the impeller turns, causing a
rotating motion in the fluid. The diffuser changes the direction and velocity of flow and directs fluid
from the impeller of one stage to the impeller of the next stage. The type of stage determines the
volume of fluid to be produced. The number of stages contained in a pump determines the total
pressure, or head, generated. The horsepower required by the motor is determined by both the
volume displaced and the head generated. Pumps are manufactured in a range of capacities to
satisfy almost all well conditions.
A pumps impellers are designed to operate efficiently over a specific capacity range (Figure 2:
Optimal ESP operating range). Operating the pump below its design capacity causes the impeller
to downthrust against the diffuser, resulting in wear on the bearings and washers. Conversely, if
the pump operates above its design capacity, the impeller upthrusts against the upper part of the
diffuser, causing similar wear. Ideally, the impeller should float freely, and will do so throughout its
recommended operating range. This recommended operating range will allow the pump to run at
highest efficiency.
Figure 2
Pump length and diameter are constrained by manufacturing and wellbore conditions. Assembly
and handling difficulties usually limit the length of a single pump section to about 20 to 25 feet.
However, it is possible to join pump sections together, adding successive stages to develop the
required head. Pump diameters are limited by the size of casing in which they are to be run. Table
3 lists the suggested pump diameters for various casing sizes; for example, a 3 3/8-inch OD pump
will fit within 4 1/2-inch OD casing. If the casing diameter is 8 5/8 inches or greater, then larger
pumps could be used.
17 lb/ft
15.5 lb/ft
24 lb/ft
20 lb/ft
The number of stages that can be added to a pump are limited by three variables:
Horsepower rating of the shaft that turns the pump
Pressure rating of the pump housing
Capacity of the thrust bearing
The pump manufacturer takes each of these variables into account when a customer specifies the
capacity range for a pump.
These curves are published by pump manufacturers for each of their individual pump typesthe
ones shown in (Figure 1), for example, are for a 100 stage, Schlumberger-Reda D1350 pump .
They are obtained by running a pump in water at a constant speed, while varying its throughput by
throttling the discharge side of the pump. During the test, the pressure difference across the pump,
the brake horsepower, and the pump efficiency are measured at different pump throughput rates.
The resulting pressure increase is then converted to its equivalent head. With this data,
performance curves are drawn showing head, pump efficiency, and brake horsepower for a
specified number of pump stages, as a function of pump throughput rate.
Although these curves are generated using fresh water (with a specific gravity of 1.0), the same
values of head are usually used when selecting a pump for a fluid with a different specific gravity
provided the viscosity of the fluid is similar to the viscosity of water. Brake horsepower, on the
other hand, does require a specific gravity correction.
Pump performance curves are normally published for either a single pump stage or, as was done
in Figure 1, for 100 pump stages.
Pump Horsepower Requirements
Using the pump performance curve shown in (Figure 1) above, we may determine the horsepower
requirements for a pump under a given set of operating conditionsfor example, a flow rate of
1250 B/D and a required pump pressure of 1725 psi.
First, we note the following values corresponding to a capacity of 1250 B/D:
Head generated for 100 stages = 2280 ft, or 22.8 ft per stage
Brake horsepower required = 32.5 hp, or 0.325 hp per stage
Pump efficiency = 64 percent.
(1)
The total head is equal to the required pump pressure divided by the pressure gradient of fresh
water (the fluid upon which the pump curve is based), or 0.433 psi/ft. Therefore,
To calculate the required brake horsepower (hp), we multiply the horsepower per stage by the
number of stages and by the specific gravity of the fluid being pumped (in this case, the fluid is
fresh water, and so the specific gravity is 1.0):
hp = (hp per stage) x (stages) x (specific gravity) (2)
= (0.325) x (l75) x (1.0) = 56.9 hp
In summary, this procedure requires specifying the pump operating conditions (required capacity,
in B/D, and the required fluid head). The required capacity of the pump is based on an estimate of
the wells inflow performance. The performance curves are actual test curves. If we assume that
very little gas will be pumped, we do not need to apply a pump efficiency factor. We should select
the pump to provide the desired capacity based on continuous operation.
In evaluating the capabilities of various pumps, we may have a number of options from which to
choose. It is important to study the performance curves supplied by the manufacturer to select a
pump that, at the required capacity, will operate in its optimal capacity range at the highest pump
efficiency. Remember that pump capacity depends on the design of the impeller and not on the
number of stages. With the selected performance curve and pump capacity, look up or calculate
the head/stage and horsepower/stage. Once we know the required head, we can calculate the
total number of stages needed and the horsepower required for the motor.
Because there is no backpressure on the annulus, the TDH, expressed in feet, can be estimated
using the following equation:
TDH = head due to tubing backpressure + frictional losses + net lift (3)
The net lift, with no packer in the hole, is simply the depth to the pump, minus the height of the
fluid level above the pump:
Net Lift = 8500 - 700 = 7800 ft
When all values are substituted, the total dynamic head is:
TDH = 191.3 + 195 + 7800 = 8186.3 ft
This is the value of TDH to use when selecting a pump.
Motor Selection
Once we determine a pumps required capacity and TDH, the next step in the design is to review
performance curves from different manufacturers. The goal is to (1) select the pump that best
meets the capacity needs, (2) calculate the number of stages required, and (3) specify the
required motor horsepower.
To illustrate, assume the same well conditions that were given in the Total Dynamic Head
calculation above, and use the resulting TDH value of 8186 feet. Assume also that after reviewing
the performance curves, the pump from (Figure 1) was selected . This pump has an OD of 4
inches and will easily fit within the 7-inch casing.
The performance curves for this pump show that at a throughput rate of 1400 B/D and a TDH of
8186 ft:
head = 2100 ft / l00 stages
hp = 34 hp/100 stages
The number of stages and motor horsepower required are as follows:
stages = 8186 ft divided by 21 ft/stage = approximately 390 stages
hp = (hp / stage) x (stages) x (spec. grav.) = (0.34) (390) (0.904) = approximately 120 hp
If the bottomhole temperature is higher than 180 F, the horsepower required should be increased
by as much as 20%. In the example well, high temperature is not a limiting factor, so we can go
with 120 hp in our design.
Next, we need to select a 120 hp motor that will fit into a 7-inch OD casing. In this case, we can go
to our manufacturers catalog and see a listing of 120 HP Series 456 motors with the
specifications shown in Table 1.
HP Volts Amps
120 1000 77
120 1170 66
120 1350 57
120 2300 34
The Series 456 has an OD of 4.56 inches, which easily fits inside the 7-inch casing. Each of the
120 HP motors listed above has a different required voltage; note that the higher voltage motors
require lower current.
Now we must select one motor for the application. In general, the choice of motor voltage is a
function of line voltage losses, capital costs, and the electric power cost.
The required surface voltage is the voltage required by the motor, plus voltage losses between the
motor and the surface, including losses in the cable, other system components, and the
transformer. The cable losses are the most significant. As an upper limit, cable losses should be
less than 30V/1000 ft.
If, for example, we select the 1000V, 77-amp motor from Table 1, we can then go to (Figure 2)
(Amperage per voltage drop per 1000 feet of cable, various conductors).
Figure 2
We note that an ideal conductor is the No. 2 copper conductor, which at this amperage has a
voltage drop of 25V per l000 feet of cable.
Another option would be the 2300V, 34-amp motor. This would allow us to use a smaller No. 6
copper conductor and have the same voltage drop along the cable. Because the No. 6 copper
conductor is smaller than the No. 2, going with this higher-voltage option would result in a lower
capital cost for the cable. However, a higher voltage switchboard will be more expensive than a
lower voltage switchboard.
We could also consider using a larger conductor cable (for instance the No. 2 copper cable) with
the 2300V motor. The voltage loss in the cable will drop from 25V to 11V per 1000 ft. The larger
conductor cable will require a higher capital cost, but lower operating costs. Within limits, then, a
larger, more expensive cable will allow for lower line losses and thus lower operating costs.
In summary, motor selection requires an economic analysis of voltage and cable alternatives;
however, the following recommendations should serve as a guide:
For low horsepower motors and shallow depths, use a 440V system.
For less than 70 hp at intermediate depths, use an 830V system.
For 70 to 200 hp in deep wells, use a 1500V system.
For motors of 200 volts and greater, use a1500V or 2400V system. The choice of voltages will
depend on economics.
All other considerations equal, it is more difficult to size pumps for wells that pump gas, because it
becomes necessary to estimate the pressure-volume effects that occur between the pump intake
and discharge pressures. This is illustrated in (Figure 3) (Effect of gas compression on ESP
throughput) .
Note that the initial pump stages perform a substantial amount of gas compression. Between an
intake pressure of 500 psi and a discharge pressure of 1215 psi, the fluid volume is reduced
almost by half.
Figure 3
Handling gas effects in the ESP design generally involves the following steps:
1. Estimate the pump intake pressure from inflow data
2. Estimate the pump discharge pressure from multiphase flow correlations
3. Divide the range of pressure between the inlet and discharge valves into discrete increments
and then calculate the pressure-volume changes that occur between increments
4. Calculate the average volume throughput and average fluid gradient, from the pump intake to
discharge points, and, with this data, select a pump and then specify the number of stages
required using the pumps performance curves.
The appropriate calculations are typically incorporated into company and manufacturer ESP
design software. You should check on the individual program that you are using to ensure that gas
effects are taken into account where appropriate.
ESP SYSTEM OPERATION
One disadvantage of ESP systems is that the tubing string normally has to be pulled in order to
replace the pump or other subsurface equipment (unlike, for example, a free hydraulic pump, a
rod pump or a wireline-retrievable gas lift valve). This requires a workover rig, which adds to the
cost of well maintenance and repair.
Replacement of downhole equipment may become necessary because of failures at the motor,
pump or cable (Table 1), or because the pump needs to be re-sized due to changes in the wells
inflow performance.
Twisted shaft caused by starting a pump while the fluids are still moving
downward in the pump after shut-down
Cable Mechanical damage caused during running or pulling operations
Deterioration caused by the downhole environment
If the wells inflow has been increasing, the cost of bringing in a workover rig is relatively easy to
justify, because the newly installed pump will pay for itself with the higher production rate. But if
the inflow is decreasing, the expense is harder to bear, and the temptation might be to just cycle
the pump daily instead of replacing it.
The problem with cycling an ESP is that large current surges occur when starting up a high
voltage, high horsepower induction motor that is separated from its starter at the surface by five or
ten thousand feet of cable. These surges are often five to eight times the normal operating current
(in Figure 1, a normal 32-amp current surged to 141 amps at start-upNeely, 1982). This type of
starting is referred to as across-the-line starting. Starting and stopping the motor also causes
amperage and voltage spikes that can damage or burn out the motor. Normally, only a limited
number of stops and starts are possible, so most operators are reluctant to stop and start a
submersible pump unless it is absolutely necessary.
Figure 1