Hubbell Industrial Controls, Inc.

SPECIFICATIONS
EUCLID MANUAL-MAGNETIC
DISCONNECT SWITCH 4245
AC AND DC 100 AMP TO 2700 AMP March 2008
Replaces January 2001

Features NEMA type 12 enclosures are standard.


NEMA Type 3R (weather resistant)
Prevents accidental application of
enclosures are also available. Both AC
power. and DC type switches range from 100
Provides positive manual control for to 2700 amperes, 8 hour open rating.
opening contacts.
Provides magnetic control for Application
remote opening of contacts. Crane specifications usually call for
Trip-free opening of power contacts. two disconnect switches, one mounted
Available in a wide range of ampere where the operator enters and leaves
ratings. the crane and the other installed
in the cab itself allowing for the
Contacts are silver-faced.
disconnecting in an emergency.
Utilized Euclid standard high quality
magnetic contactors. Euclid Type 4245 manual-magnetic
Totally front connected. disconnect switches combine the
Flange type operating handle has two features into one unit mounted
positive On and Off position. on the foot walk with a remote On-
Off pushbutton station permitting Specifications
Provides for Off position
control from the cab. With the manual Manual-Magnetic DC disconnect
padlocking. operating lever in the Off position, switches have two normally open main
Housed in NEMA Type 12 or 3R the power contacts cannot be made power contacts; the AC type has three
enclosures. to close electrically or forced closed normally open main power contacts.
JIC Door interlock. manually, thus providing reliable
power isolation. The power contacts are silver-faced for
Description Manual-magnetic disconnect switches
reliable operation.
The Manual-Magnetic Disconnect are used to disconnect AC or DC power
Switches are combination manually The disconnect switch operates as a
from crane motors or other motor remote mainline contactor with manual
and magnetically operated contactors drives under loaded conditions in the
enclosed in a NEMA Type wall- disconnect feature. For either the AC
case of emergency or as a general or DC type switch, the contactor coil
mounted or floor-mounted enclosure. disconnect switch. circuit is arranged for remote closing
The contactors for the disconnect and opening of the
switches are the same as the contactors main power contacts once the operating
used on Euclids crane and mill type handle has been placed in the On
magnetic controllers. Silver faced position.
NOTE: When applied to cranes
contacts are standard. or other intermittent service
applications, the continuous Three padlocks can be applied with the
All external connections to the ampere rating shall not be less manual operator in the Off position.
contactor panel are made on the than 50% of the total current This prevents accidental applications of
front of the panel. The incoming required by all motors, nor less power to the crane.
line terminals are located at the top than 75% of the current
and the load terminals are located required by any single motion. AVAILABLE OPTIONS
on the bottom of the contactor Overload relays
mounting panel. Control circuit wiring Power fuses
connections are made on the side of the Flange mounted pushbuttons and/ or
panel. indicating lights
Arc suppressors
Auxiliary contacts give a choice of two NEMA Type 4 or 4X enclosures
indicating light circuits.
Interface relay
Hubbell Industrial Controls, Inc. SPECIFICATIONS
EUCLID MANUAL-MAGNETIC
DISCONNECT SWITCH 4245
AC AND DC 100 AMP TO 2700 AMP March 2008
Replaces January 2001

APPROXIMATE DIMENSIONS FOR STD. DISCONNECTS


AC AND DC MANUAL-MAGNETIC H W D MH MW OH
3 100 AMP 35 29 15 36.25 23 37.75
4 150 AMP 35 29 15 36.25 23 37.75
5 300 AMP 50 33 15 51.25 27 52.75
5A 400 AMP 50 33 15 51.25 27 52.75
6 600 AMP 70 44 24 Floor Mounted
7 900 AMP 70 44 24 Floor Mounted
8 1350 AMP 70 44 24 Floor Mounted
77 1800 AMP 74 72 25 Floor Mounted
88 2700 AMP 74 72 25 Floor Mounted
Note: options may change height dimensions
DC Manual Magnetic Disconnect Switch AC Manual Magnetic Disconnect Switch
Typical circuit for 230/250 V DC Typical circuit for 240/480V AC, 3Ph

Hubbell Industrial Controls, Inc. Ph. 336-434-2800


4301 Cheyenne Dr. Fax 336-434-2803
Archdale, NC 27263 www.hubbell-icd.com