Professional Documents
Culture Documents
PAGE Contents-1
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
CONTENTS PAGE
CONTENTS PAGE
CONTENTS PAGE
LIST OF TABLES
LIST OF FIGURES
References A-25
1.1 Scope
The purpose of this Process Standard is to establish the methods and recommend the
practices to be used in specifying the relieving devices required for individual protection of
pressure vessels in process plants. Atmospheric and low pressure storage tanks are not
covered. The reader is referred to API Standard 2000 "Venting Atmospheric and Low
Pressure Storage Tanks".
1.2 Basis
A considerable part of the material included here has been obtained from :
a) API RP 520 "Sizing, Selection, and Installation of Pressure-Relieving Devices in
Refineries" Part I - Sizing and Selection, Sixth Ed., March 1993 (with Errata Sheet
issued in November 1994), and Part II - Installation, Fourth Ed., December 1994.
b) API RP 521 "Guide for Pressure-Relieving and Depressuring Systems" (Fourth Ed.,
March 1997).
c) 1995 ASME Boiler and Pressure Vessel Code, Sections I and VIII.
1.3 Limitations
These instructions should not over-rule national and local codes of jobsite or
customer's specifications.
The reader is referred to Process Standard 601, Section 3.0, "Codes and
Recommended Practices".
1.4 Definitions
Other non-reclosing pressure relief devices are explosion hatches and liquid
seals, normally employed below 15 psig.
C. Safety Valve
D. Relief Valve
A safety relief valve is a pressure relief valve which can be used in either
vapor or liquid service. For vapor service it is adjusted to give a "pop" action,
for liquid service it is adjusted for gradual opening.
PROCESS STD 602
PAGE 1.0-3
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
1.4 Definitions
This is a pressure relief valve in which the major relieving device is combined
with and is controlled by a self-actuated auxiliary pressure relief valve (pilot).
This pressure relief valve is a standard pressure relief valve (spring loaded)
fitted with an additional spring-diaphragm actuator to which a pneumatic
signal is fed from a pressure sensing pilot.
The arrangement connecting the actuator to the spindle is such that the valve
is still capable of operating as a standard safety valve in the event of pilot or
actuator failure. The pressure relief valve will then open at 105 % of the set
pressure as the valve spring set pressure is normally adjusted to 5 % higher
than the pilot set pressure.
1.4 Definitions
Notes :
K. Explosion Hatch
L. Liquid Seal
Liquid seals may be used for set pressures below 10-15 psig. Examples :
- seal leg of a flare
- liquid seals used in MEK units to protect the filters.
PROCESS STD 602
PAGE 1.0-5
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
1.4.2 Terms
A. Operating Pressure
It shall not exceed the maximum allowable working pressure and it is usually
kept at a suitable level below the setting of the pressure relieving devices to
prevent their frequent opening.
B. Design Pressure
1) The gauge pressure used in the design of a vessel for the purpose of
determining the minimum permissible thickness of the different parts of
the vessel.
Note that generally clients have their own rule which may be different
from above.
1.4 Definitions
1.4.2 Terms
The MAWP is the pressure which will be stamped on any ASME VIII
vessel.
PROCESS STD 602
PAGE 1.0-7
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
1.4 Definitions
D. Set Pressure
Set pressure is the inlet gauge pressure at which the pressure relief valve is
adjusted to open under service conditions.
E. Accumulation
F. Overpressure
Overpressure is the pressure increase over the set pressure of the relieving
device ; it is the same as "accumulation" when the relieving device is set at
the maximum allowable working pressure of the vessel, assuming no inlet
pipe loss to the relieving device.
G. Relieving Conditions
Relieving conditions of relief devices are the inlet gauge pressure and
temperature at a specific overpressure. The relieving pressure is equal to the
valve set pressure (or rupture disk burst pressure) plus the overpressure. The
temperature of the flowing fluid at relieving conditions may be higher or
lower than at the operating temperature.
H. Opening pressure
I. Closing pressure
Closing pressure is the value of decreasing inlet static pressure at which the
valve disk reestablishes contact with the seat or at which lift becomes zero.
PROCESS STD 602
PAGE 1.0-8
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
1.4 Definitions
J. Simmer
The leakage across the valve seat preceding the "pop" or true opening of the
valve. Simmering causes premature damage of the seat and occurs when the
valve is improperly adjusted or when the operating pressure is too close to
the set pressure.
Back pressure is the pressure that exists at the outlet of a pressure relief
device as a result of the pressure in the discharge system. It is the sum of the
superimposed and built-up back pressures.
This is the pressure at the relief device discharge before the device
opens. It is the result of pressure in the discharge system from other
sources. This type of pressure may be constant or variable ; it may
govern whether a conventional or a balanced pressure relief valve
should be used in a specific application.
L. Blowdown
Blowdown is the difference between the set pressure and the closing
pressure of a pressure relief valve, expressed as a percent of the set
pressure, or in pressure units.
M. Lift
Lift is the actual travel of the disk away from the closed position when the
valve is relieving.
PROCESS STD 602
PAGE 2.0-1
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
These are pressure relieving devices for gases or vapors which have been specifically
designed to give full opening with little over-pressure. The kinetic energy of relieving gas
or vapor creates a pop action which opens the disk rapidly, reaching the full lift before
maximum overpressure (see Fig. 5).
There are two basic types of safety valves : conventional and balanced valves.
A. If the bonnet is vented to the atmosphere, the back pressure acts with the
vessel pressure against spring force.
B. If the spring bonnet is vented to the valve discharge rather than to atmosphere,
the back pressure acts with the spring force.
If the superimposed back pressure were constant, (no matter what its value), it
could be taken into account in adjusting the spring loading so that the relief valve
would open at the required set pressure. In practice, however, the superimposed
back pressure is generally not constant and varies between a minimum, which
corresponds to the flow of purge gas alone in the flare system (no valve
discharging) and a maximum which corresponds to the design flow of the flare
system.
For a conventional valve of type B, spring set pressure is equal to design
pressure minus superimposed back pressure ; therefore the valve will open above
the vessel design pressure if the superimposed back pressure is higher than
expected, and will open below design pressure if the superimposed back pressure
is lower than expected.
In order to avoid opening of the valve at pressures too different from the required
set value (as a result of variable superimposed back pressure), the first step is to
only accept the use of conventional relieving valves when superimposed back
pressure varies over a range not exceeding 10% of set pressure (gauge).
However, this is not always sufficient because the flow performance after
opening must also be examined. When the valve is open, the built-up back
pressure tends to unbalance the equilibrium between spring force and vessel
pressure. For a conventional valve of type B, this may result in a reduction of
valve opening and rapid fall of capacity (see Fig. 2). Therefore conventional
valves, even when acceptable from the point of view of superimposed back
pressure, must be checked with regard to built-up back pressure. The designer
must check that the difference between the maximum value of back pressure and
the minimum value of superimposed back pressure does not exceed 10% of set
pressure (gauge).
PROCESS STD 602
PAGE 2.0-2
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Balanced safety relief valves are those in which the back pressure has little
influence on the performance characteristics.
Piston type and Bellows type are available, the latter being more widely used (See
Fig. 3).
A. Bellows Type
The effective bellows cross sectional area is equal to nozzle seat area ; disk
areas extending beyond the bellows and beyond the seat area are equal and
forces developed over those areas cancel each other.
Area under the bellows is kept under a constant pressure by venting the
bellows to a source of constant pressure, which is often atmosphere, unless
fluid which would be vented in case of bellows failure is dangerous ; in that
case, vent should be discharged to a safe location, provided that its pressure
is constant.
Bellows valves have limited allowable set and outlet pressures (refer to
Table 5).
If the maximum set or back pressure allowed for a single orifice appears too
low, use a combination of smaller valves having an aggregate area equal to
the valve in question. Use of smaller valves will permit higher set or back
pressures.
B. Piston Type
In the piston type, of which several variations are manufactured, the piston
guide is vented so that the back pressure on opposing faces of the valve disk
cancels itself, and the top face of the piston, which has the same area as the
nozzle seat area, is kept at atmospheric pressure by venting the bonnet.
Since gases may leak past the piston to the bonnet, the bonnet of piston-type
valves must be vented in a safe manner.
Note that the vent on the valve bonnet should not be piped back into the flare
header as its performance will then be the same as a conventional valve
(Clients may request this for environmental reasons such as preventing
hydrocarbon releases to atmosphere due to ruptured bellows).
PROCESS STD 602
PAGE 2.0-3
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
For back pressures higher than this limit, valve size becomes progressively larger
for the same flow, even if critical flow conditions are maintained. For back
pressures higher than 50% of set pressure, the valve manufacturer must always
be consulted for valve sizing. In general, although there would be an incentive in
increasing back pressure with balanced type valves in order to reduce size and
cost of relief headers, values exceeding 30-35% of set pressure (gauge) should
not be used without checking with an instrument specialist.
Compared with the pilot operated valves, the main advantages are the following :
. As an external energy is used, the valve operation is not affected by the nature of the
process fluid (duty service, corrosive fluid ).
. The system is very reliable as the valve is not totally dependent on the pilot. In case of
pilot or actuator failure, the valve will operate as a standard safety valve which opens
typically at 105 % of the pilot set pressure.
It has to be noticed that local codes and regulatory requirements are to be reviewed to
ensure that pilot-assisted pressure relief valves are acceptable devices for overpressure
protection.
PROCESS STD 602
PAGE 2.0-5
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
2.5.1 Installation
Rupture disk devices are used either alone or in conjunction with a pressure relief
valve. The application of rupture disks alone is limited by the fact that when the
disk ruptures the entire contents of the system may be lost. They may, however,
be installed in parallel with a pressure relief valve to provide additional capacity ;
in this case, the relief valve is set at a lower pressure to limit rupture disk bursting
to major disasters.
Rupture disks are pressure differential devices and the relieving capacity is
therefore affected by the sizes and lengths of the inlet and outlet pipework.
The hatch consists of a hinged metal cover placed over an opening. It is used for vessels
operating near atmospheric pressure and when risk of explosion exists (e.g., asphalt
oxidizers, air borne dusts, etc.).
Explosion hatches are not recommended for use at higher pressures, since the weight of
the hatch will be excessive and this may prevent quick opening.
In the first case, the vessel is designed to withstand full vacuum. In the second case, the
designer can choose between specifying the vessel for full vacuum or providing a vacuum
relief device (valve or liquid seal) which permits the entrance of air, inert gas, or fuel gas,
etc., to prevent vacuum conditions.
Pressure relief valves may leak when the operating pressure is above 90 % of the valve set
pressure.
It is possible to enhance the tightness of a spring loaded pressure relief valve for max operating
pressure up to 92 % of set pressure (above 92 % consider pilot operated pressure relief valves),
either with :
- an "O ring" seat seal ; the compatibility of this seal with the product has to be carefully
investigated,
- a stellited pressure relief valve.
2.10 Breaking Pin Devices and Spring-Loaded Non-Reclosing Pressure Relief Devices
(Rupture Pin Devices)
Refer to 1.4.1 J for a basic description of these devices and to Figure 16.
A rupture pin valve may be used instead of a rupture disk, considering the following advantages :
- the rupture pin valve is not subject to premature failure due to fatigue, nor to set pressure
variations with operating temperature changes,
- a lower tolerance for rupture pin valves at low set pressures (below 50 psig),
- a rupture pin valve can be quickly reset without breaking flanges.
Nevertheless a rupture disk should remain the first choice in services where the disk seldom
ruptures, because of its lower cost and demonstrated performance.
PROCESS STD 602
PAGE 2.0-8
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
2.10 Breaking Pin Devices and Spring-Loaded Non-Reclosing Pressure Relief Devices
(Rupture Pin Devices) (contd)
In ASME Code section VIII (UG-134) the same rules apply to the set pressure of a pressure
relief valve or of a spring-loaded non-reclosing device, the burst pressure of a rupture disk
device, or the breaking pressure of a breaking pin device. However, the recommended approach
is to specify a lower "set pressure" for all pressure relief devices having a set pressure tolerance
above the standard pressure relief valve tolerance (shown in 3.2.3.G). Refer also to 3.2.4 for
recommended approach on rupture disks.
Additional specific requirements of ASME Code for these devices are the following :
Breaking pin devices shall be used only in combination with a pressure relief valve, between the
valve and the vessel.
The space between a breaking pin device and a pressure relief valve shall be provided with a
pressure gauge, a try cock, a free vent, or suitable telltale indicator.
Tolerances
The rated pressure at which the pin will break at the coincident operating temperature
(specified by the user) shall be guaranteed by the manufacturer with the following
tolerances :
30 150 5 psi
151 275 10 psi
276 375 15 psi
Pressure Setting
The rated breaking pressure of the breaking pin plus the tolerance shall not exceed 105 % of the
M.A.W.P. (or design pressure) of the vessel.
Such a device may not be used in combination with any other pressure relief device.
Tolerance
Reported below are the recommendations of the ASME Code regarding safety. This code is
generally known and accepted in many countries. For other national codes refer to Paragraph
3.4.
The two sections of the ASME Boiler and Pressure Vessel Code of interest are :
Generally, all unfired pressure vessels, including filters and shell and tube heat exchangers, fall
under the jurisdiction of Section VIII, while Section I covers fired and electric boilers and
organic fluid vapor generators (i.e. Dowtherm vapor generators).
In the case of unfired pressure vessels classified as unfired steam boilers (e.g. waste heat
boilers), the vessels can be designed according to Section I or VIII, depending on process
conditions and local safety regulations, but their safety devices will follow Section I.
Unfired pressure vessels in which steam is generated shall be classed as unfired steam boilers
with the following exceptions :
The process engineer should check with the Heat Transfer Engineering Group and/or
Technology Department as to whether the particular steam generators shall be classed as
unfired steam boilers or process heat exchangers, depending upon process conditions and local
safety law. The classification will dictate which section shall be chosen to properly specify
relieving devices.
Other types of equipment requiring protection include compressors, pumps, piping and air
coolers. For such non-code equipment it is customary to base safety-relief valve specification
and sizing on the same rules used for code equipment.
3.1. Boilers, Economizers, Superheaters, Reheaters, Organic Fluid Vapor Generators (ASME,
Section I)
A. Each boiler shall have at least one safety valve or safety relief valve.
Rupture disks are not accepted, except on organic fluid vapor generators between
safety valve and vapor if certain conditions are satisfied (Part PVG of Section I,
paragraph 12.3).
PROCESS STD 602
PAGE 3.0-2
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
3.1. Boilers, Economizers, Superheaters, Reheaters, Organic Fluid Vapor Generators (ASME,
Section I)
For a boiler with combined bare tube and extended water-heating surface
exceeding 500 sq ft, two or more safety valves or safety relief valves are
required only if the design steam generating capacity of the boiler exceeds
4000 lb/hr (Paragraph PG-67).
C. Any economizer which may be shut off from the boiler, thereby permitting
the economizer to become a fired pressure vessel, shall have one or more
safety relief valves.
D. Forced-flow steam generators with no fixed steam and water line may be
protected by means of safety valves and power-actuated pressure-relieving
valves (See PG-67.4).
F. Every reheater shall have one or more safety valves and at least one valve
shall be located at reheater outlet.
When auxiliary firing and waste heat recovery are used, the effect of such heat
shall be taken into account.
PROCESS STD 602
PAGE 3.0-3
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
3.1. Boilers, Economizers, Superheaters, Reheaters, Organic Fluid Vapor Generators (ASME,
Section I)
A. Organic fluid vapor generators shall be designed for at least 40 psi (280 kPa)
above the normal operating pressure.
B. One or more safety valves on the boiler shall be set at or below the
M.A.W.P.
If additional valves are used, the highest pressure setting shall not exceed the
M.A.W.P. by more than 3 percent.
C. When multiple safety valves are installed, the difference between the highest
and the lowest set pressures should not be greater than 10 percent of the
highest set pressure (on high-temperature water boilers this 10 percent range
may be exceeded, as stated in ASME I PG-67.3).
D. The safety valves shall be capable of discharging all the steam that can be
generated by the boiler without allowing the pressure to rise more than 6
percent above the highest set pressure and in no case to more than 6 percent
above the M.A.W.P.
E. The popping point tolerance plus or minus shall not exceed the following :
2 psi (14 kPa) for pressures up to and including 70 psig (483 kPa g)
3% for pressures over 70 psig up to and including 300 psig
(2100 kPa g)
10 psi (69 kPa) for pressures over 300 psig (2100 kPa g) up to and
including 1000 psig (6900 kPa g)
1% for pressures over 1000 psig (6900 kPa g)
For electric boilers see also ASME, Sect. I, Part PEB. For organic fluid vapor
generators see also ASME, Sect. I, Part PVG.
No valve of any description shall be placed between the required safety valves or
safety relief valves and the boiler, nor on the discharge pipe between the safety
valve or safety relief valve and the atmosphere.
PROCESS STD 602
PAGE 3.0-4
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Pressure vessels having an inside diameter not exceeding six inches, without limitation in
temperature and pressure, or vessels with an internal or external operating pressure not
exceeding 15 psig, with no limitation in size, do not fall under the jurisdiction of ASME,
Section VIII (U-1).
All pressure vessels within the scope of ASME Code, Section VIII, irrespective of size
and pressure, shall be provided with protective devices (pressure relief valves or non-
reclosing pressure relief devices may be used as protective devices). Heat exchangers
and similar vessels shall be protected with a relieving device of sufficient capacity to avoid
overpressure in case of an internal failure (UG-133 (d) of ASME, Section VIII).
Vessels connected together by a system of adequate piping not containing isolating valves
may be considered as one unit and protected by one relieving device (e.g., tower with its
reflux drum).
No rule is set by code ; the number of relieving devices is only a function of total
capacity. Unfired steam boilers, if designed under the provisions of Section VIII,
shall be protected as required by Section I of ASME Code.
Code does not specify capacity, which is left to the designer to specify according
to various hazardous conditions (see paragraph 4.0). Unfired steam boilers, if
designed under the provisions of Section VIII, are to be protected according to
Section I of ASME Code.
B. For all other vessels, except unfired steam boilers, when a single relieving
device is installed, it shall be set to blow at a pressure not higher than the
M.A.W.P.
C. If more than one relieving device is installed, only one device needs be set to
open at a pressure not exceeding the M.A.W.P. The additional valves may
be set to open at a higher pressure, but not to exceed 105 percent of
M.A.W.P.
PROCESS STD 602
PAGE 3.0-5
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
D. In case of a vessel with operating pressure at the top lower than operating
pressure at the bottom because of pressure drops and/or liquid heads, while
the mechanical design (wall thickness) of each section of the vessel is based
on its design pressure, the set pressure of the relieving device must be based
on the design pressure at the point where the relieving device is connected,
which is generally the top. If a relieving device placed at the top were set at
the design pressure of the bottom, the bottom section would be exposed to
pressures greater than design, when the device relieves.
E. In the case of vessels filled with liquid, such as crude desalters, with relief
valve connected to the top of the desalter through a vertical pipe, the set
pressure is the design pressure of the vessel at the top minus the liquid head
of the connecting pipe.
F. In the case of multiple relieving valves, one of which is installed for fire
exposure only, this particular valve may be set at a pressure not exceeding
110 percent of M.A.W.P.. Refer to Fig. 6.
G. Tolerance
ASME, Section VIII (UG-126) specifies that set pressure tolerance of a
safety valve shall not exceed + 2 psi for pressures up to and including 70
psig, and + 3 % for pressures above 70 psig.
0 - 200 None
201 - 600 1%
601 - 800 2%
801 - 1000 3%
above 1000 5%
PROCESS STD 602
PAGE 3.0-6
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
The following guidelines are based upon ASME code and general recommended
design practices.
The manufacturer shall guarantee that the disk will burst within 5% (plus or
minus) of the stamped bursting pressure above 40 psig (Some manufacturers
may guarantee plus or minus 2%), and within 2% (plus or minus) up to and
including 40 psig (UG-127) at the coincident disk temperature specified by
the user. This tolerance is comparable to the pressure relief valve tolerance
of 3 % on set pressure.
B. Manufacturing range
It is the pressure range agreed with the rupture disk manufacturer, and
associated to the specified burst pressure. The stamped or rated burst
pressure derived from destructive tests performed from each rupture disk lot,
must fall within the manufacturing range.
C. Pressure cycling
Rupture disks are liable to fail prematurely due to metal fatigue if pressure
cycling can occur on the upstream process side. The disk manufacturer
should be advised of pressure/temperature cycling situations on the process
side.
The stamped burst pressure shall not exceed the vessel MAWP.
The values of the maximum accumulated pressure follow the same rules
given for pressure relief valve. Refer to Fig. 6 for these values of maximum
allowable accumulated pressure.
The burst pressure and design pressure (use MAWP if available) are
determined from the following considerations :
Note that some National Codes (French for instance) require to consider all
tolerances guaranteed by the manufacturer for the maximum burst pressure.
PROCESS STD 602
PAGE 3.0-8
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
In any case the design pressure of a vessel protected by a rupture disk shall
be reviewed with the following data :
When a rupture disk is installed upstream of the pressure relief valve and the
devices are close coupled, the maximum burst pressure and set pressure
should be the same nominal value. Whenever possible the combination of the
rupture disk and the pressure relief valve should be specified and purchased
as one set.
E. Relieving temperature
If the rupture disk is located at an appreciable distance from the vessel then
the local temperature may be considerably lower than the vessel
temperature. This could result in the rupture disk being specified and supplied
by the Manufacturer with an effective set pressure which is significantly
higher than the nominal value, and could subsequently result in overpressure
of the vessel.
According to ASME Code (UG-125) all pressure vessels, other than unfired
steam boilers (which are to be protected in accordance with Section I), shall be so
protected by pressure relieving devices that the pressure is prevented from rising
above the design pressure (or M.A.W.P.) more than the following values :
When specifying a vacuum relief valve and the vacuum design pressure of a
vessel, attention has to be paid to the fact that the vacuum design pressure shall
never be exceeded (in terms of negative pressure), even during the operation of
the vacuum relief valve.
Please note that most clients require full vacuum design whenever there is a
vacuum operating pressure.
PROCESS STD 602
PAGE 3.0-10
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
If a partial vacuum design is used, it shall accommodate for the minimum pressure
encountered when the vacuum relief valve is operating. The pressure conditions
are then staged as follows :
The margins between these conditions should be carefully reviewed with the
vacuum relief valve supplier.
Guidelines for specifying pressure accumulation based upon ASME code and general
recommended design practice are summarized in Table 2 in the appendix A of this
standard.
Regulations imposed by other national codes will be reported under this paragraph as
required.
The total capacity of the pressure relieving device(s) shall be adequate to prevent
the pressure rising to more than 10 % more than the design pressure. There is no
special concession on this figure for cases where the pressure rise is due to
exposure to external heat or fire. (This makes sense as the design of vessels to
B.S. 5500 is based on smaller safety factors than ASME VIII Div. 1).
The pressure setting of a relief valve shall not be greater than the design pressure
of the vessel, except that where the capacity is achieved by more than one
relieving device, one only need be set at or below the design pressure and the
others may be set at a pressure not more than 5% above design pressure.
PROCESS STD 602
PAGE 3.0-11
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Refer to :
J.O. nb 1498 Appareils pression
Arrt of September 4, 1967 Rgles damnagement et dexploitation des
units de traitement de ptrole brut, de ses drivs et rsidus,
Arrt of November 9, 1972 Rgles damnagement et dexploitation des
dpts dhydrocarbures liqufis,
and to CODAP, Section S.
All specific requirements listed hereabove for the British Standard ( 3.4.2) also
apply to the French Code. In addition the French Code is more stringent for steam
or condensate vessels, particularly on the number of pressure relief valve required.
PROCESS STD 602
PAGE 4.0-1
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Any circumstance that reasonably constitutes a hazard under the prevailing conditions for a
system should be considered in the design.
The relief requirements are classified as due to either "fire" or "operational failures".
The simultaneous occurrence of two or more conditions that could result in overpressure will not
be postulated if the causes are unrelated. The simultaneous occurrence of two or more unrelated
contingencies is unlikely and classified as a "double hazard or risk" ; therefore, it is rarely used as
a basis for determining the maximum relieving load. For example, in a plant where a single boiler
is used for both process steam and electric power generation, a boiler failure ( a single
contingency) could cause simultaneous loss of electric power and steam. If instead, electric
power is supplied from an external source, simultaneous loss of steam and electric power should
not be considered because it would be caused by two unrelated events. In case of two vessels
connected through a line having an isolating valve always open during normal operation, the
simultaneous occurrence of this valve blocked and fire should not be considered as a double risk,
since the situation of valve blockage may be extended in time (for instance, during maintenance)
and during this time the occurrence of a fire is a distinct possibility ; therefore, a relieving valve
for fire protection will be installed on each vessel.
Where very large quantities of hazardous materials are involved (flammable or toxic) such as for
storage or transportation, then a hazard analysis should be carried out. This type of analysis
deals with all possible failure cases, both single and multiple. For on plot equipment the total
number of multiple failure cases to be considered would become very large and this approach
then becomes very costly and time consuming. Some client codes however require the possibility
of multiple failure to be considered.
Having established which equipment items require protection, and the design temperatures and
pressures of these, it is next necessary to determine all of the applicable causes of overpressure
for each equipment item and the resulting individual relieving rates. Most standards refer to API
RP 521 Sections 2 and 3 (including Table 2) for guidance. This shall be done for all possible
operating cases including start-up, shutdown, turndown, feedstock variations and variations (as
detailed in the basis of design) in process conditions. Include for example aging of catalysts and
adsorbents and fouling of heat exchange surfaces where these considerations are relevant.
The possibility of autorefrigeration occurring when LPG or LNG is depressurized must also be
taken into account (See process Standard 603).
Good engineering judgment, rather than blind adherence to the proposals shown hereafter should
be followed in each case. This is not intended to be a complete list and a detailed study of all the
Standards and Codes specified by the project should be carried out before starting the design of
the relieving systems.
PROCESS STD 602
PAGE 4.0-2
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
4.1 Fire
Atmospheric and low-pressure storage tanks are not covered by this standard. The reader
is referred to API Standard 2000 "Venting Atmospheric and Low Pressure Storage
Tanks".
Flammable fluids may escape from a vessel or a pipe (from leaking joints or from
operational mishaps). They may be carried some distance from the source of the
leakage, by the natural slope of the ground, by air currents, or by a jetting stream (if
coming from a pressure source), and may accidentally become ignited. Therefore,
any pressure vessel (including heat exchangers, filters, or air coolers) may be
exposed to a fire at some time in its life, even though the content of the vessel itself
is not flammable. The heat absorbed by radiation or by direct contact from hot
gases and/or flames will cause the contained liquid to evaporate, if the critical
pressure of the fluid is in excess of the relieving pressure. When pressure relief
conditions are above critical point, the rate of vapor discharge depends on the rate
at which the fluid will expand as a result of the heat input.
For liquid-full vessels (such as treaters), at the start of a fire the opening of the
pressure relief valve is due to the thermal expansion of the liquid. Afterwards, the
liquid will vaporize.
As long as the vapor quantity generated under these conditions is below the flow
capacity of the safety relief valve, the valve, when opened, will discharge until the
pressure in the vessel has dropped to the valve reseating pressure and the valve
closes.
Intermittent valve operations, (called chattering), will continue in this range of heat
input. At higher rates of heat input the valve will start to operate constantly in an
open position and pressure in the vessel will build up to maximum accumulation.
A vessel or group of vessels must be protected from fire exposure by using one of
the following pressure relief devices :
Additional protection should be provided (however, not substituted for the pressure
relieving device) with the purpose of improving emergency control ; for instance :
PROCESS STD 602
PAGE 4.0-3
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
4.1 Fire
This additional protection is important, because the vessel can fail because of
excessive metal temperature, even though the pressure is controlled by the relief
valves. The risk is greater for a vessel containing only gas because the heat
absorption due to evaporation of liquid is missing. This additional protection is
recommended by ASME, Sect. VIII, Division 1, Appendix T and in API RP 521
( 3.15.4.1). Another method for limiting heat input from fire is earth-covered
storage or location of pressure storage underground.
Where equipment can contain liquids having high boiling points then the relieving
temperature in the case of fire may be considerably higher than normal operating
and hence design temperatures. For heavy materials in big vessels, it may be
interesting to :
For vessels containing liquids, the total heat absorbed is computed by using the
following formula (see Figure 7) :
Q = 21,000 F A 0.82
where :
Note : NFPA Code 30 does not allow for an insulation environment factor lower
than 0.3. In the UK there is also a lower limit of 0.3 for some types of storage
containing liquefied flammable gases (IP Code).
4.1 Fire
Mineral type insulation (calcium silicate, mineral wool, diatomaceous earth, perlite)
when covered with stainless steel, or galvanized steel or aluminized steel sheets
shall be considered to meet the fire resistant insulation requirements. Insulation
such as polyurethane, iso-cianurate, fiber glass and metal sheets made in
aluminum do not meet the requirements.
Conductance Thickness
Btu/hr. ft2 .F inches
4 1
2 2
1 4
For each item the area effective in generating vapor is the area wetted by liquid.
The total wetted surface A shall be at least :
The term "grade" usually refers to ground grade, but may be at any level at
which a sizable fire could be sustained (platforms, roofs, etc.).
B. for spheres and spheroids, the wetted surface included within the elevation of
the maximum horizontal diameter or within 25 ft., whichever is greater.
4.1 Fire
The wetted surface is calculated on the basis of the internal liquid contents.
The liquid contents under variable level conditions should ordinarily be taken at
the average inventory, i.e. :
Shell side :
Tube side :
The wetted surface will be based on the high liquid level in the bottom,
bottom head, plus wetted surface corresponding to four inches of liquid for
any tray within a height of 25 ft. from grade.
The wetted surface will be calculated up to the high liquid level but at least
50 percent of the total vessel surface, heads included.
4.1 Fire
Usually 50 percent of the surface, since they usually work half full and in any
case a certain time is necessary to raise a large volume of liquid to its boiling
point, but at least up to 25 ft. from grade (refer also to B for spheres and
spheroids).
4.1 Fire
API RP 521 Section 3.15.2 suggests using the following formula for
vessels containing vapor and exposed to open fires :
P1
T1 = Tn
Pn
4.1 Fire
The rate of vapor release through the relief device may be calculated
as follows :
W = Q
L
No credit is normally taken for the sensible heat capacity of the fluid in
the vessel, all heat input being considered as latent heat. Thus no time
limit is placed on the duration of the fire.
PROCESS STD 602
PAGE 4.0-10
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
4.1 Fire
4.1 Fire
For fluids that reach or exceed their critical point before their vapor
pressure reaches the set pressure of the relief valve, a fictitious latent
heat is used to calculate the flow of fluid. API RP 521 3.15.3.1
suggests that a minimum value of 50 Btu/lb is sometimes acceptable as
an approximation.
Noting that the apparent latent heat of hydrocarbons near the critical
point is approximately 74 Btu/lb for methane and 42 Btu/lb for octane,
the suggestion made by API may be explained by means of the
following theoretical approach (not of API source) :
A. Foreword
The gas escapes from the vessel for the following reasons :
a) thermal expansion of gas ;
b) vaporization of liquid which causes an equal
number of gas moles to escape ;
c) thermal expansion of liquid which causes less
volume to be available to the gas phase.
PROCESS STD 602
PAGE 4.0-12
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
4.1 Fire
A. Foreword (cont'd)
4) When all the gas has escaped and liquid has not yet
reached its critical temperature, the relief valve
discharges liquid at very low density, while its
temperature increases.
Step 1. Gas flows through the relief valve until all gas has
escaped.
W = QB
C
PROCESS STD 602
PAGE 4.0-13
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
4.1 Fire
where :
Notes : (1) S.G. and C values are at saturation pressures, while they
should be at constant pressure, but the two errors should
tend to cancel each other.
PROCESS STD 602
PAGE 4.0-14
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
4.1 Fire
Notes :
2 2
D D
1 2
B=
2 (T - T ) D D
2 1 1 2
4.1 Fire
where :
M = molecular weight
N = number of lb-mols
P = pressure, psia
V = vessel volume, ft3
R = gas constant (10.73)
T = temperature, R
Z = compressibility factor.
w = PVM T = w T (2)
ZRT2 T
q = TCw (3)
where :
t = q/Q (4)
where :
4.1 Fire
W = w = Q (5)
t CT
API RP 521 requires that possible hazards due to wrongly closed outlets be
considered, for example vessels on the discharge side of a pump when shut-off
pressure of the pump is above M.A.W.P. of the vessel.
The main sources of overpressure are pumps, compressors, high pressure supply
headers and process heat.
To determine the capacity of the relieving device the maximum in-flow of the
liquid to the vessel under consideration or the maximum vapor generation therein
should be considered at the specific relieving conditions, i.e. set pressure plus
overpressure. There can be a considerable reduction in required valve capacity
when the basis is considered for mechanical equipment. Nevertheless, if the
characteristic curves are not known when the valve is specified, the normal flow
should be considered.
If not all outlets are blocked, then API RP 521 3.10.4 allows that credit for flow
out through the remaining outlets be taken unless automatic control action will
tend to close them. This credit should be calculated at relieving conditions, which
can considerably reduce the required relief loads. However, before any credit is
taken, a detailed risk analysis must be made in order to justify that the assumption
made is valid. Note that the possibility that operators will completely block in the
system during abnormal operation is not considered to be multiple jeopardy.
A special case of closed outlet is that affecting a process system where a single
pressure relief device is used to protect several equipment components. A typical
example is that of a hydrotreater - reactor recycle - gas loop. It is not necessary
to design the entire system for the highest pressure occurring during normal
operation (i.e. at feed pump discharge). Follow the procedure set forth in the
Foster Wheeler Hydrotreater Manual. Alternately, the procedure in API RP 521,
Appendix B may be checked (some Clients may require it), but it may give either
more, or less, conservative design pressures than the FW method.
PROCESS STD 602
PAGE 4.0-18
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
In the case of non-flashing liquids some Clients make an exception where the
system to be protected has a sufficiently large liquid ullage space (free vapor
space). This is usually quoted as the time required to fill the ullage space from
either normal or maximum liquid level to full. These specifications will depend on
the Client but are generally from between 10 and 30 minutes. It is essential that
the operators be provided with reliable alarms and instrumentation to monitor the
liquid levels concerned and be provided with reliable valves, shut-down systems
etc. to stop the flow of liquid into the system.
The valve shall be considered fully opened and where applicable the methodology
of 4.2.11.1 should be followed.
Failure of a check-valve to close can have the same effect as inadvertent valve
opening. If the downstream pressure is significantly higher than the design
pressure of equipment upstream, consideration should be given to the provision of
a secondary device to minimize the potential for a reversal of flow (refer to API
RP 521, paragraph 2.3.4).
Critical flow, flashing from liquid to vapor, entrance of volatile liquid into a hot
fluid or vice versa, are to be considered.
The main effects of cooling water failure are loss of process or utility cooling or
condensing duty. Loss of seal or lube oil cooling and jacket water for rotating
equipment should also be considered.
For distillation columns with no air condenser and no pump-around, normally the
gross overhead is to be discharged by the relief device less any net overhead
vapor product flow through the control valve at relieving conditions.
For very large relieving capacities, consider the possible reduction of vaporization
due to the increase of pressure from normal to design. This possible reduction of
vaporization is discussed in 4.2.4.
PROCESS STD 602
PAGE 4.0-19
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
If an air condenser is provided upstream of the water condenser, the relieved load
is the total vapor entering the water condenser minus any overhead net vapor
product.
For towers with pumparound or sidestream reflux circuits, e.g. crude distillation
towers and cat cracking fractionators, water coolers also will be inoperative.
The vapor rate therefore equals the total steam and vapor input to the tower plus
the vapor generated in the system, minus any vapors condensed in exchangers
cooled by some medium other than cooling water.
Failure of reflux or top product, which may be due to pump shutdown or control
valve closure, causes condenser flooding (or accumulation of non-condensable in
condenser in case of top vapor product failure), which is equivalent to the total
loss of coolant. Refer also to 4.2.10 for considerations on the reflux drum
overfilling case.
A heat balance around the tower should be made, but the gross overhead is
generally considered adequate, except in quench towers, where the quench liquid
failure requires the relieving of the total vapor entering the tower.
Where credit is taken for LMTD reduction due to the elevation of pressure and
temperature above normal at relieving conditions then account should be taken of
the reduction in latent heat which also occurs. This reduction in latent heat will
tend to increase relief flow rates.
Controller action must be considered also since the particular configuration of the
various process controllers which are regulating the operation of a distillation
column can have a marked effect on the behavior of the column if overhead
failure should occur. If the flow of reboiler heating medium is under differential
pressure control, top temperature control or top or bottom composition control
then the reboiler steam or hot oil control valve will be driven fully open on reflux
failure. This is because the separating power of the column will be lost and the
controller will attempt to rectify this. The flow rate of heating medium to the
reboiler will then be the maximum flow which can occur through the fully open
control valve. Each case should be reviewed in detail with regard to the particular
control scheme employed.
It is possible that higher than normal volatility material may reach the column
during upset conditions in upstream equipment, like :
Note that the reflux drum design pressure should be specified above the column
design pressure, to account for the max liquid static head in the overhead system
in case of any operational failure resulting in liquid build-up and potential
condenser flooding. A differential pressure of 7-8 psi (0.5 bar) corresponding for
instance to 25 feet of liquid SG = 0.7 is generally adequate.
When the system is protected by one pressure relief valve (PSV) on the top of
the column (or overhead line), the reflux drum pressure will not exceed its design
value even if the condenser gets flooded when the PSV starts opening (no liquid
relief through PSV).
When the system is protected by two PSVs with one on the reflux drum for fire
protection only, it is with the above recommendation not necessary to consider
liquid relief (through the PSV) due to reflux drum overfilling.
It has been stated in the past that it is only necessary to consider the possibility of
the control valve moving to the fully open position if the valve failure mode is
open. This is incorrect since failure of the process controller, the valve positioner
or operator error can all result in the valve moving fully open. The effect of the
control valve moving fully open must therefore be considered irrespective of the
valve actuator failure mode.
The following points should be reviewed where the relieving flow is being
determined as the flow through a fully open control valve.
PROCESS STD 602
PAGE 4.0-23
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Note the potential transient liquid relief due to HP vapor into liquid full
vessel. The filling of the downstream vessel has to be carefully
evaluated considering the liquid flow out of the vessel (see f
hereafter). Note also the API RP 521 3.20.2 : "Where valves or
other devices are sized to relieve vapors caused by vapor entry or
generation of vapor in a normally all-liquid system (see 3.10,
3.12, 3.13, and 3.19), care should be taken to locate the device
so that it actually relieves vapor and is not required to relieve the
volumetric equivalent of the vapor as liquid." with API 3.10.3
dealing with inlet control device failure.
e) By-passes :
Size the downstream relief valve(s) for the flow which is obtained
with both the control valve and the by-pass fully open. Specify
the by-pass valve as an HCV having the same Cv (or lower Cv) as the
main control valve. Note that globe valves can have a Cv many
times larger than the installed control valve. Note also that globe
valves belong to the bulk piping material, and it is therefore almost
impossible to get the information about the Cv of the by-pass
globe valve (and to be sure of it).
Omit or remove the by-pass and fit a hand wheel to the control
valve.
PROCESS STD 602
PAGE 4.0-25
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
e) By-passes : (cont'd)
For any equipment located between the fully open control valve and
the LP vessel fitted with the relief device, the pressure should be
checked considering :
the accumulated pressure in the LP vessel,
the friction losses at relieving flowrate in the LP system.
This pressure should not exceed accumulated pressure of the
equipment.
3. Controller Failure
4.2.12 Abnormal Process Heat Input (Refer to API RP 521, Section 3.11)
a) The wide open capacity of control valves admitting fuel, hot oil or steam shall
be considered, even if limit stops are provided on the valve.
c) In shell and tube heat exchangers, heat input should be calculated on the basis
of clean, rather than fouled conditions. Calculate the overall heat transfer
coefficient hc from
l/hc = l/hd - fh - fc
d) A calculation margin of 20% above the heat exchanger design duty should be
employed for abnormal process heat input where the exchanger contains fluids
such as water, light hydrocarbons, hydrocarbon vapors, steam. This has been
advised by Heat Exchanger department and is made up of a 15% correlation
margin and a 5% design margin (note these margins do not include the process
design margin). For fluids such as crude oil and residues a margin of 30%
above the heat exchanger design duty should be employed.
No general rule can be given for determining the relieving requirements in case of
internal explosion. When protection is required, rupture disks should be used, since
they react faster than safety valves. It should be noted that the peak pressure
reached during a vented explosion is usually higher, sometimes much higher than
the pressure at which the vent device activates. The design pressure should be
determined accordingly.
In API RP 521 3.12 it is mentioned that for design of explosion relief systems,
simplified rules-of-thumb (as shown in previous editions of API RP 521 up to
Edition 3) should not be used as these can lead to inadequate designs.
Refer to NFPA 68, Guide for Venting Deflagrations, and to NFPA 69,
Expansion Prevention Systems, for guidance on this subject.
a) Defining the design basis upset conditions for the reaction system.
b) Characterizing the systems through bench scale tests simulating the design
basis upset conditions.
c) Using vent sizing formula which account for two phase gas/liquid vent flow.
The design basis upset conditions are process specific, but generally include one
or more of the following : external fire, loss of mixing, loss of cooling, mischarge
or reagents.
Refer to API RP 521 3.13 for further general information on chemical reaction,
and to the DIERS documentation.
PROCESS STD 602
PAGE 4.0-28
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
The use of pilot-assisted pressure relief valves (refer to 1.4.1 G and to 2.4)
should also be considered here with the following principles :
- the main valve spring set pressure (usually 105 % pilot set pressure) shall not
exceed the reactor MAWP,
- the pilot is generally pressure sensing, but alternate pilot can sense
temperature, flow, liquid level or other parameter necessitating valve opening.
Examples : Solar radiation on a blocked pipeline, liquid blocked in on the cold side
of an exchanger with flow in the hot side, piping or vessels blocked and heated by
heat tracing, coils or fire. Sections of piping containing more than 500 liters of
LPG or toxic material which could be normally blocked in.
The following factors should be taken into account when deciding whether to fit
thermal expansion relief :
Relieving capacity :
For the amount of fluid to be discharged, see Par. 4.3.2.1 under Shell and
Tube Heat Exchangers. Generally a 3/4 in. x 1 in. safety-relief valve is
adequate, unless long pipelines or large vessels are involved.
The thermal relief valve should discharge to atmosphere, drain, or into a closed
circuit if the fluid is dangerous. It should not discharge into the same line outside
of the block valves. When thermal relief valves discharge into a closed system,
the effects of back pressure should be considered.
Typically, a "caution" sign is placed at the block valves of all exchangers not
equipped with a permanently open bypass.
The wording typically is as follows :
CAUTION
Cause Rupture
DO NOT CLOSE
Electric power failure will shut down electrically driven equipment such as pumps,
compressors, air coolers, solenoid valves, etc. Note that in turn, a pump failure
can cause loss of cooling water, reflux, fuel, pumparound, etc. A compressor
failure may cause loss of instrument air, inert gas, refrigeration, etc.
In addition, air cooled condensers may flood. In this case no credit shall be given
for natural convection.
The analysis of (a) and (c) is usually relatively straightforward. Partial power
failure (b) may be analyzed as failure of any single transformer bus bar. In order
to do this it is necessary to examine the one line wiring diagram or its equivalent.
The one line wiring diagram is usually not available early in the project so the
basis upon which the relief valve sizing has been carried out and the assumptions
made in the calculations for partial power failure should be made clear to all
interested parties (Project Dept., Electrical Dept., Client, HAZOP Team etc.) and
recorded in writing. Alternatively take the simultaneous failure of electrically
driven equipment which yields the largest relief load.
Note that in the case of power failure a fired heater may still contribute to the
relief load because of the heat retained in the fire bricks. This heat can be
estimated to range from about 10 % of normal duty for large forced draught fired
heaters to 70 % of normal duty for small natural draught heaters.
The relief load for air failure should be based on the failure of the single most
critical component of the air supply system. See paragraph 4.2.19 below for credit
taken for spare equipment.
In order to reduce the risk of instrument air failure the main air compressor is
generally spared by another compressor which automatically starts on low
pressure in the air receiver. This spare compressor may be either turbine-driven
or motor-driven using electricity from a different source. An air receiver is also
usually provided, sized to give 5 to 10 minutes before the instrument air pressure
drops to 50 percent of normal.
In determining the relief loads the Process Engineer must consider the action of
control valves on air failure. This action can be either fail open, fail closed or fail
locked (at the last controlled position). For this last case, since there is no way of
determining what the valve position is, the position causing the largest relieving
load must be assumed.
PROCESS STD 602
PAGE 4.0-32
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Each case should be individually analyzed. Note that in a plant where a single
boiler or source of steam is used for both process drivers and electric power
generation, a failure of a steam source can cause simultaneous loss of electric
power. In this case, if an alternate source of electricity is not available, consider
the possible loss of cooling tower fans, cooling tower pumps and reflux pumps.
Credit may be taken for parallel equipment powered by a different energy source
(e.g. turbine-driven pumps) only when it is normally operating. Automatic starting
of spare equipment is not sufficiently reliable to eliminate the need for relieving
capacity. Manual start of auxiliaries must be carefully analyzed for time and
operator requirements before it can be used to reduce relief requirements.
In series fractionation (that is, where the bottoms from the first column feed into
the second column, and the bottoms from the second feed into the third), the loss
of heat input to a column can overpressure the following column. Loss of heat
results in some of the light ends mixing with the bottoms and being transferred to
the next column as feed. Under this circumstance, the overhead load of the
second column may consist of its normal vapor load plus the light ends from the
first column. If the second column does not have the condensing capacity for the
additional vapor load, excessive pressure could occur.
There may also be flows from depressuring operations (especially during fire) and
flows from operational flaring of surplus vapor (especially during start-up and
shut-down).
Paragraphs 4.1 and 4.2 give the necessary instructions for protection of pressure
vessels.
PROCESS STD 602
PAGE 4.0-33
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
The liquid in the cold side of a heat exchanger may be accidentally blocked in and
continue to absorb heat from the fluid flowing in the hot side.
t t
Q
WL = BQ
1 bp
c Wv = t t x
1 av
L
where :
WL or Wv = liquid or vapor to be relieved, lb/hr (or kg/hr)
When a relieving device is installed, its set pressure shall not exceed to
the M.A.W.P. or the design pressure of the low pressure side.
Consider for each of the above mentioned relief device, the installation
of 2 rupture disks in series, with an excess flow valve or a PAH in-
between, to avoid relief due to spurious rupture.
A further analysis can be done using dynamic modeling, to review the
LP side design pressure and select the adequate overpressure
protection system, i.e. relief device type, number and location : an
example of such analysis is described in the publication "Prevent
overpressure failures on heat exchangers" by J.R. Cassata, Z.J. Feng,
S. Dasgupta and R. Samways, in Hydrocarbon Processing Nov. 1998.
d) Flowrate
A tube rupture is considered to be a sharp break in one tube. The high
pressure fluid flows through both openings, which is equal to twice the
cross-sectional area of the single tube.
In some cases Clients would not consider the possibility of complete
guillotine fracture of heat exchanger tubes greater than 1" or 1.25"
occurring. This is because of the very large relief flows which would
result if larger tube sizes are considered. Check procedures,
documentation and with the Client for the Project concerned. If a very
high standard of mechanical design is employed, some Clients relax
this requirement and employ a smaller break cross sectional area than
that which results from a guillotine fracture.
PROCESS STD 602
PAGE 4.0-37
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
d) Flowrate (contd)
In determining the flow rate, allowance should be made for any liquid that
will flash to vapor either as the result of the pressure reduction or, in the case
of certain volatile fluids being heated, because of the combined effects of
pressure reduction and vaporization as the fluid is intimately contacted by the
hotter material on the low-pressure side.
The following equations can be used to calculate the flow from the high to
the low pressure side (equations based on a discharge coefficient of 0.7,
Cp/Cv = 1.33 and area of tube break equal to twice the cross sectional area
of one tube) :
M
Vapors WG = KG d2 P 1 (1)
zT
Liquids WL = KL d2 (P P ) (2)
L 1 2
P1 P 2
Equivalent to VL = KL d2 (2)
L
4.3.2 Shell and Tube and Double Pipe Heat Exchanger (cont'd)
d) Flowrate (cont'd)
The liquid equations (2) or (2) will be used in the following cases :
the liquid flow stays liquid as it flows through the tube break :
P 2 > PVL
P VL (*) : vapor pressure of the liquid
then :
i) if the upstream pressure P1 is significantly above the liquid vapor pressure
(P 1 > PVL), use PVL instead of P2 and calculate WL or VL based on P1 - PVL.
ii) If the liquid is at boiling conditions on the high pressure side (or close to these
conditions), the liquid flow WL or VL can still be calculated using (2) or (2),
but based on :
d) Flowrate (cont'd)
x 1 x
M = 1 / +
G L
If the calculated discharge exceeds the normal total flow in the high pressure
side, the latter flow should be used, except when sufficient volume on the HP
side may supply the calculated flowrate above the normal flowrate.
PROCESS STD 602
PAGE 4.0-40
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
d) Flowrate (cont'd)
When calculating the flow out of the low-pressure side, credit can be
taken for the fluid-handling capacity of both the inlet and outlet lines
unless the inlet contains check valves or control valves which would tend
to be closed by the effects of tube breakage.
Valves on low pressure side provided only for isolation may be assumed
fully open, control valves in a position equivalent to the minimum normal
flow unless the valve could automatically close due to the emergency
situation.
In some cases the flowrate to be relieved out of the low-pressure side is
greater than the flow through the tube break -calculated using (1), (2) or
(2')- because of the additional vaporization due to the mixing of a volatile
fluid with a hot fluid.
4.3.3.1 Fire
If the client requests the use of API RP 521 ( 3.15.7.1) then this should be done
and the client informed of the extra cost. Note that with lump-sum jobs this should
be settled with the client at the time the job is bid.
FW Recommended Methods
Assume that all cooling capacity within the fire zone is lost but that the
air cooler does not absorb heat from the fire. Relief loads will then be
excess vapor due to the lost cooling capacity plus vapor generated by
the fire from liquid in associated equipment within the fire zone. For a
tower with an air cooled condenser this would be the total of the
normal gross overhead minus vapor product plus any vapor generated
by fire exposure under the tower bottom, reboiler and reflux drum.
In an air cooler used for gas cooling the tubes may soften and rupture
on fire exposure, even if depressuring is provided, since heating of the
tubes may occur much faster than the time needed for depressuring.
Note that liquid filled air cooled exchangers that may be blocked in
must be protected by a pressure safety valve. This requirement is in
accordance with ASME Section VIII, Division 1 or 2, UG-125, which
requires that all pressure vessels within the scope of this Division shall
be provided with a protective device in accordance with UG-125
through UG-136.
API Methods
API RP 521, 3.15.7.1 does not recommend the methods below, but
explains :
It is possible to lose all the fans of an air cooler, the reflux and product
pumps, at the same time. The condenser may be flooded and therefore
no credit should be taken for the effect of natural convection on the air
condenser.
If a condenser can be blocked in, check the vapor pressure of the fluid
at ambient temperature for the possibility of creating a vacuum inside
the exchanger. If the vapor pressure is below atmospheric pressure
the exchanger should be designed for vacuum conditions or a vacuum
relief valve provided.
4.3.4 Pumps
The relief valve set pressure should be equal to the maximum allowable pressure
of the pump casing, discharge piping or downstream equipment, whichever is
lowest, and shall be reviewed with the mechanical specialist. In case of motor-
driven reciprocating or rotary pumps, the set pressure of the relief valve is
generally set at 10% or 25 psi, whichever is greater, above the operating
discharge pressure in order not to overload the electric motor.
Piping and equipment downstream from a centrifugal pump are normally designed
for the maximum pump shut-off pressure (see paragraph 4.2.1), therefore a relief
valve is generally not required.
There are, however, cases where a relieving device is necessary in order to avoid
excessive design pressure of downstream equipment, for instance when two
centrifugal pumps are in series.
The head/capacity curve of the selected pump shall be consulted to ensure that
the pressure relief valve capacity shall be at least equal to the flow on the
head/capacity curve corresponding to the set pressure of the relief valve plus
overpressure.
For all types of pumps, consideration should be given to possible speed change
with consequent change of the characteristic curve.
4.3.5 Compressors
Interstage and discharge pressure relief valves shall be provided for the same
reasons given for positive displacement pumps.
Pressure relief valve capacity and set pressure should be provided by compressor
vendor.
Like centrifugal pumps, for this type of compressor a relieving device is not
normally required. However, when the characteristic curve is steep, it may be
convenient to install a relief valve to avoid excessive design pressure of discharge
equipment.
In the case of multi-stage centrifugal compressors, a relief valve is necessary
between stages to protect the interstage equipment (cooler, K.O. drum) and
upstream stage, in the event that the antisurge control valve of the downstream
compressor stage fails open, causing a back flow of gas from high pressure to
lower pressure. In selecting interstage design pressure consideration should be
given to the effect of possible speed change.
Generally, any necessary relief valve for centrifugal compressors should be
specified in accordance with compressor manufacturer's instructions.
PROCESS STD 602
PAGE 4.0-46
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
4.3.6 Turbines
Condensing Turbines
Non-Condensing Turbines
Non-condensing turbines exhausting into a steam main (API Standard 611) do not
require installation of a safety valve to protect the turbine casing ; a sentinel valve
(which warns the operator with a sound alarm in case of overpressure) supplied
by the turbine manufacturer is considered acceptable. It is also advisable,
however, to specify the exhaust steam block valve as "car seal open".
Although not mandatory, large non-condensing turbines with high back pressure
generally have a safety valve on the outlet, set for 10% accumulation and a
relieving pressure at least 10% higher than normal exhaust pressure, but never
greater than the design pressure of the turbine casing. Turbine outlet pressure
relief valves are specified by vendor (flow and set pressure) based on the design
pressure of the discharge side of the turbine. Also, for large, non-condensing
turbines, the exhaust steam block valve must be specified "car seal open".
In the case of turbine drivers note that an additional margin on shut off head may
be required to account for the possibility of the turbine being operated at speeds
higher than normal.
4.4.2 Autorefrigeration
Flashing of a saturated liquid will result in cooling of the fluid. This becomes
particularly apparent when flashing low boiling fluids such as liquefied petroleum
gases or liquefied natural gases.
It may be necessary to specify a lower equipment and/or line design temperature
in addition to the usual upper design temperature. Selection of material of
construction must be made accordingly.
Careful installation, avoiding water in LPG's avoiding mixing LPG's with other
products containing water, injection of methanol and steam tracing are possible
solutions to the potential plugging problem.
PROCESS STD 602
PAGE 5.0-1
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Sizing pressure relief valves is the responsibility of the Instrument Specialist who will do
the sizing on the basis of the process specifications transmitted by the Process Engineer.
Calculation method (to be mainly used for inlet/outlet lines sizing) can be found in
Appendix "B".
Unless the relieving capacity of the combination of the rupture disk device and the
pressure relief valve is established by certification tests carried out according to ASME
VIII, it is necessary to (refer to ASME VIII, UG-127 (a.3.b.2)) :
- derate the capacity of the combination to 90 % of the rated relieving capacity of the
valve alone.
- ensure that the opening provided through the rupture disk, after burst, is sufficient to
permit a flow equal to the capacity of the valve, and there is no chance of
interference with proper functioning of the valve ; and this area shall be at least the
area of the inlet of the valve.
The required relieving capacity, W, for explosion hatches (and for rupture disks in case of
explosion) is :
W = 3,600 W
e
'
where :
The time to attain maximum pressure for mixtures of gases and air at one atmosphere and
150F is 0.01 seconds for hydrogen, 0.045 seconds for ethane, 0.056 for propane, 0.06 for
hexane and naphtha, 0.017 for acetylene, 0.06 for benzene, 0.10 for toluene.
PROCESS STD 602
PAGE 5.0-2
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
The required open area, A, to discharge the relieving capacity W, using a discharge
coefficient of 0.8 is :
W zT
A =
245P1 M
where :
A = discharge area, sq. in.
W = required relieving capacity, lb/hr
P1 = relieving pressure, psia
T = initial temperature, R (F + 460)
z = compressibility factor, at P1 and T
M = mixture molecular weight
5.4.1 Explosion
Codes may allow CSO (car seal open) or LO (locked open) block valves at the inlet
and/or outlet side of a relieving device for maintenance. Section VIII of ASME Code
permits such block valves, whereas for power boilers, ASME Code Section I does not
allow any valve at the inlet nor at the outlet side of a pressure relief valve (refer to 3.1.5
of this standard).
Such block valves, when permitted, shall be full bore and shall be sized following the
criteria shown hereafter for inlet piping and discharge piping. For 3" and smaller valve, the
full bore requirement should be noted on the EFD since most piping block valves of this
size are reduced port.
English, French, German and Swedish codes allow block valves if adequate spare capacity
is provided, and if the block valves are so interlocked that the required relieving capacity is
always available.
Italian code allows the installation of CSO block valves on inlet and/or outlet, subject to
certain conditions.
An English manufacturer (Castel) supplies key operated systems for both open relief
systems (to atmosphere) and closed relief systems (to flare or blowdown drum).
Three way valves (change-over or selector valves) may be used in place of interlocked
block valves : they shall be of the full open port type and are typically one or two line sizes
larger than the pressure relieving valve inlet/outlet. Note that the Safety Selector Valve
manufactured by Keystone Anderson, Greenwood & Co has a "Y" shape which is
particularly adequate for the low pressure drop requirements detailed hereafter.
6.2 Piping
Preferably the relief devices should be mounted in the vapor section of the vessel
protected. It is, however, allowable to install them on piping connected to the
vessel (ASME Code, Section VIII).
The total pressure drop between the vessel and the relief valve, including the
pressure drop due to entrance, contraction, fittings, etc... should be kept below 3%
of the pressure relief valve set pressure (in gauge units). The pressure loss should
be calculated using the rated capacity of the pressure relief valve (API 520, Part
II, 2.2.2). This pressure drop limitation is related to the pressure relief valve
blowdown characteristic (6-7 %), and is imposed to prevent valve chattering. This
may be a critical factor for set pressure below 50 psig.
Some clients may require that it be calculated on the basis of the actual capacity
of the relief valve : rated capacity is generally 10 % less than actual. The 10 %
margin is required by ASME Code, section VIII.
PROCESS STD 602
PAGE 6.0-2
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
6.2 Piping
According to API RP 520 Part II, 2.2.2, an engineering analysis of the valve
performance at higher inlet losses may permit increasing the allowable pressure
loss above 3 %. In this case, the blowdown of the pressure relief valve needs to
be increased accordingly, and the valve capacity shall not be reduced (by the
higher pressure drop) below that required.
The cross sectional area of the inlet piping, when multiple relief valves are
manifolded, shall be at least equal to the sum of the cross sectional area of all the
relief valve inlets tied to the manifold.
For a single pressure relief valve, the inlet line size and associated fittings must be
at least equal to the pressure relief valve inlet size.
Alternate arrangements in case of pressure drop problems are :
- pilot-operated valve with remote sensing point ( 6.4),
- for multiple valves, individual inlet lines which will give less pressure drop than
a manifolded configuration.
When car seal open valves are provided at the inlet of a pressure relief valve, a
bleed valve should be installed between the CSO valve and the pressure relief
valve.
Where fouling of relief valve inlets due to coke, catalysts, etc., is anticipated,
provision should be made for continuous injection of steam or other purging fluid
into the inlet riser between the vessel and the relief valve. A purge velocity of 5
ft/sec. in the inlet riser is normally satisfactory.
Occasionally for a very corrosive service when a vessel is equipped with a mist
eliminator the relieving device should be connected below the mist eliminator to
avoid the possibility of blockage due to disintegration of the mist eliminator. This
should also be done when a problem of plugging of the wire mesh pad may occur
or when depressurizing may cause the wire mesh to lift. Connection of the
relieving device below the mist eliminator need not be done in cases where the
possibility of blockage may be considered to be remote.
The discharge lines and associated fittings from individual pressure relief valves
should not be smaller than the pressure relief valve outlet size.
Silencers or any form of restriction should never be installed at discharge of
pressure relief valves.
The rated capacity of the pressure relief valve shall be used to size the discharge
line from the pressure relief valve to the relief header (API RP 520, Part II,
Fourth Ed., 3.3).
PROCESS STD 602
PAGE 6.0-3
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
6.2 Piping
Velocity and back pressure considerations determine the size of the discharge
lines.
Liquid relief valves and valves normally in vapor service but which might vent
liquid under certain conditions are always discharged to a closed system.
Vapor relief valves relieving to the atmosphere, are generally discharged at a
point 10ft. above the highest structure within the unit area and at a distance of at
least 50 feet from a furnace.
For other details see Section 603.
Steam tracing of discharge piping, and sometimes of the inlet piping, is required
when the discharging fluid solidifies either at ambient temperature or due to
refrigeration caused by fluid expansion or evaporation.
Quenching steam may be piped into atmospheric discharge of safety relief
valves to minimize the hazard of ignition
Inlet line
The operating and design conditions of the relief valve inlet line should be the
same as that of the equipment it protects.
In addition, the highest relieving temperature from any contingency shall be added
as a note to the line list (or to the Engineering Flow Sheet), except where this
relieving temperature is less than the design temperature. This relieving
temperature will then be used to stress the relief valve inlet pipework, including
the main process line if the relief valve is not directly located on the equipment.
The extent of the main process line to be stressed at this higher temperature
needs careful consideration, and depends on the relief case in question.
PROCESS STD 602
PAGE 6.0-4
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
6.2 Piping
Discharge line :
If there is only a fire case contingency for the relief valve, then the inlet line
design temperature should also be taken for the outlet line.
The fire case temperature shall be noted for the inlet line. This will be used for
stress purpose.
Remote sensing for a pilot-operated pressure relief valve (i.e. sensing directly on
protected equipment instead of integral pressure sensing) can be useful when there is
excessive inlet pipe pressure loss or when the main valve must be located at a pressure
source different from the pilot sensing point because of service limitations of the main
valve (Refer to API RP 520, Part II, Section 2.2.3).
PROCESS STD 602
PAGE 6.0-5
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Refer to paragraph 2.4.4 of this standard and to API RP 520 - Part II - Section 2.6.
A rupture disk device may be installed on the outlet side of a pressure relief valve,
provided (ASME Code Section VIII-1, UG-127 (a.3.c)) :
1) The valve is so designed that it will not fail to open at its proper pressure
setting regardless of any back pressure that can accumulate between the
valve disk and the rupture disk. The space between the valve disk and the
rupture disk shall be vented or drained to prevent accumulation of pressure
due to a small amount of leakage from the valve.
3) The stamped bursting pressure of the rupture disk at the coincident disk
temperature plus any pressure in the outlet piping shall not exceed the design
pressure of the outlet portion of the pressure relief valve and any pipe or
fitting between the valve and the rupture disk device. However, in no case
shall the stamped bursting pressure of the rupture disk at the coincident
operating temperature plus any pressure in the outlet piping exceed the
maximum allowable working pressure of the vessel or the set pressure of the
pressure relief valve.
4) The opening provided through the rupture disk device after breakage is
sufficient to permit a flow equal to the rated capacity of the attached
pressure relief valve without exceeding the allowable overpressure.
5) Any piping beyond the rupture disk cannot be obstructed by the rupture disk
or fragment.
6) The contents of the vessel are clean fluids, free from gumming or clogging
matter, so that accumulation in the space between the valve inlet and the
rupture disk (or in any other outlet that may be provided) will not clog the
outlet.
7) The bonnet of the safety relief valve shall be vented to prevent accumulation
of pressure.
Note : the installation of a rupture disk at the outlet of a pressure relief valve is not
allowed by the French Code.
PROCESS STD 602
PAGE 7.0-1
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
In order to be able to design flare network and flare stack, or to fill the effluent summary
(reliefs to atmosphere) a complete set of information should be filled for any emergency
case causing the pressure relieving device to discharge. Cases to be investigated are listed
at the bottom of the process specification.
NOTES
No. Subject
The following items differ from the pressure relief valve data sheet.
(1) Burst pressure, corresponds to the set pressure (in gauge units for P above
atmospheric, in absolute units for P below atmospheric) of pressure relief
valves.
(2) Allowable burst tolerance, covers the allowable range around the specified
burst pressure.
(5) Size (optional data). The size is shown as a nominal pipe size.
(6) Type (optional data). Client or service may require a specific type, such as
conventional domed, or reverse buckling.
(7) Design pressure (optional data). Specify if different from max burst
pressure.
PROCESS STD 602
PAGE 7.0-5
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-1
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
References:
1. Physical Constants of Hydrocarbons C1 to C10 . ASTM Special Publication No.
109A, Philadelphia, Pa., 1963
2. International Critical Tables, , McGraw-Hill Book Co., Inc., New York.
3. Engineering Data Book. Gas Processors Suppliers Association, 1977.
PROCESS STD 602
PAGE A-2
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
STEAM
Operating Overpressure 6 6 10 16 20
Fire - - 21 21
GAS OR VAPOR
Operating Overpressure - - 10 16 20
Fire - - 21 21
(2) Pressure relief valve for piping protection only (no equipment protection).
"(f) Occasional variations above design conditions shall remain within one
of the following limits for pressure design :
(1) .
Set Pressure
(Pounds per
square inch Temperature (degrees Fahrenheit)
Gauge) 300 400 500 600 700 800 900 1000 1100 1200
15 1.00 0.98 0.93 0.88 0.84 0.80 0.77 0.74 0.72 0.70
20 1.00 0.98 0.93 0.88 0.84 0.80 0.77 0.74 0.72 0.70
40 1.00 0.99 0.93 0.88 0.84 0.81 0.77 0.74 0.72 0.70
60 1.00 0.99 0.93 0.88 0.84 0.81 0.77 0.75 0.72 0.70
80 1.00 0.99 0.93 0.88 0.84 0.81 0.77 0.75 0.72 0.70
100 1.00 0.99 0.94 0.89 0.84 0.81 0.77 0.75 0.72 0.70
120 1.00 0.99 0.94 0.89 0.84 0.81 0.78 0.75 0.72 0.70
140 1.00 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.70
160 1.00 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.70
180 1.00 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.70
200 1.00 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.70
220 1.00 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.70
240 --------- 1.00 0.95 0.90 0.85 0.81 0.78 0.75 0.72 0.70
260 --------- 1.00 0.95 0.90 0.85 0.81 0.78 0.75 0.72 0.70
280 --------- 1.00 0.96 0.90 0.85 0.81 0.78 0.75 0.72 0.70
300 --------- 1.00 0.96 0.90 0.85 0.81 0.78 0.75 0.72 0.70
350 --------- 1.00 0.96 0.90 0.86 0.82 0.78 0.75 0.72 0.70
400 --------- 1.00 0.96 0.91 0.86 0.82 0.78 0.75 0.72 0.70
500 --------- 1.00 0.96 0.92 0.86 0.82 0.78 0.75 0.73 0.70
600 --------- 1.00 0.97 0.92 0.87 0.82 0.79 0.75 0.73 0.70
800 --------- --------- 1.00 0.95 0.88 0.83 0.79 0.76 0.73 0.70
1000 --------- --------- 1.00 0.96 0.89 0.84 0.78 0.76 0.73 0.71
1250 --------- --------- 1.00 0.97 0.91 0.85 0.80 0.77 0.74 0.71
1500 --------- --------- --------- 1.00 0.93 0.86 0.81 0.77 0.74 0.71
1750 --------- --------- --------- 1.00 0.94 0.86 0.81 0.77 0.73 0.70
2000 --------- --------- --------- 1.00 0.95 0.86 0.80 0.76 0.72 0.69
2500 --------- --------- --------- 1.00 0.95 0.85 0.78 0.73 0.69 0.65
3000 --------- --------- --------- --------- 1.00 0.82 0.74 0.69 0.65 0.62
TABLE 4 - VISCOSITY CORRECTION FACTOR Kv (Ref.1)
Referenced in Appendix B
Reynolds Number Viscosity Correction Reynolds Number Viscosity Correction
Factor, Kv Factor, Kv
35 0.30 300 0.82
40 0.35 400 0.85
50 0.40 600 0.87
Set P limit
psig (2)
Effective Inlet x Conventional Outlet P limit Remarks
Area (1) Outlet Size Valves psig (2) (3)
Orifice sq.in (sq.cm) in &
Balanced
Bellows V. Conventional Balanced
Valves Bellows V.
D 0.110 (0.71) 1x2 1235 285 Balanced valve
1x2 3080 600 500 with D orifice may be not
1x3 5135 740 500 available
E 0.196 (1.26) 1x2 1235 285 230 Balanced valve with E
1x2 3080 600 500 orifice may be not available
1x3 5135 740 500
F 0.307 (1.98) 1x2 1235 285 230
1x3 5000 740 500
G 0.503 (3.24) 1x3 1845 740 470 Size may be : 1 x 2
2x3 3705 740 470
H 0.785 (5.06) 1x3 285 285 230
2x3 2750 740 415
J 1.287 (8.30) 2x3 285 285 230
3x4 2700 600 230
K 1.823 (11.86) 3x4 1235 285 200
4x6 2220 600 200
L 2.853 (18.41) 3x4 285 285 100
4x6 1500 285 170
M 3.6 (23.2) 4x6 1100 285 160
N 4.34 (28.0) 4x6 1000 285 160
P 6.38 (41.16) 4x6 1000 285 150
Q 11.05 (71.23) 6x8 600 115 115
R 16.0 (103.23) 6x8 100 60 60
8 x 10 300 100 100
T 26.0 (167.75) 8 x 10 300 100 100
PROCESS STD 602
PAGE A-5
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Notes on Table 5
(1) These effective areas are valid only when used with the sizing equations of API RP
520, Part I (i.e. sizing equations shown in this FW standard).
(2) API STD 526 details Set Pressure Limit and Outlet Pressure Limit for various
temperature ranges and materials of Body/Bonnet and Spring :
and for different inlet flange class (150 # , 300 #...up to 2500 # ) and outlet flange
class (150 # , 300 # ).
The data shown here correspond to the highest class available for each valve size.
Notes on Figure 6
2. The set pressure and all other values related to it may be moved downward (below
MAWP) if the operating pressure permits. Overpressure may then be higher than
accumulation.
3. This figure conforms with the requirements of ASME Code, Section VIII, shown in API
RP 521. The British and French codes do not allow any accumulated pressure above 110
% of MAWP (Refer to par. 3.4 of this standard).
7. A Multiple valve installation requires the combined capacity of two or more pressure
relief valves to alleviate a given overpressure contingency : First valve + Additional
valve(s).
A Supplemental valve provides relieving capacity for fire exposure. It is used only in
addition to valves sized for process (non fire) contingencies.
PROCESS STD 602
PAGE A-11
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-12
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-13
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Note on Figure 8
Different hydrocarbon liquids have different latent heats of vaporization even though
hydrocarbons as a group behave similarly to one another. The latent heat of vaporization of
a pure single-component liquid decreases as the temperature at vaporization increases and
the latent heat becomes zero at the critical temperature and pressure for that liquid.
Figure 8 shows the vapor pressures and latent heats of the pure single-component paraffin-
hydrocarbon liquids. This chart is directly applicable to such liquids and applies as an
approximation to paraffin hydrocarbon mixtures composed of two components whose
molecular weights vary no more than propane to butane and butane to pentane.
The chart may also be applicable to isomer hydrocarbons, aromatic or cyclic compounds, or
paraffin hydrocarbon mixtures of components that have slightly divergent molecular weights.
The equilibrium temperature should be calculated. Using the relationship for the calculated
temperature versus vapor pressure, the latent heat can then be obtained from Figure 8. The
molecular-weight relationship as shown by the chart is not to be used in such cases ; the
molecular weight of the vapor should be determined from the vapor-liquid equilibrium
calculation.
For cases that involve mixtures of components that have a wide boiling range or widely
divergent molecular weights, a rigorous series of equilibrium calculations may be required
to estimate vapor generation rates, as discussed in API RP 521 Section 3.15.3.2.
Note that if the unit has been simulated, the time-dependant relief (composition, T, flow)
discussed in API RP 521 3.15.3.2 should be evaluated using the simulator.
PROCESS STD 602
PAGE A-14
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-15
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-16
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCEDURE 4D
A DESK CALCULATION METHOD FOR ESTIMATING THE DENSITY OF PURE ORGANIC GASES
Method
Figures 4D-1 through 4D IV are given as a procedure which produces rapid, reasonably accurate estimates of
gas phase densities. I procedure 4D, the compressibility factor , Z, is obtained as a function of the reduced
temperature, the reduced pressure and the reduced compressibility factor.
Z = (Tr,Pr,Zc)
Plots of compressibility factors based on a critical compressibility factor , Zc of 0.27 are given in figure 4D-1
and 4D-2. Figure 4D-III or 4d-IV provides a correction to the compressibility factor for compounds whose Zc
differs from 0.27 . The equation for the compressibility factor Z is then:
Z = Z|Zc-0.27 + Di (Zc-0.27)
Where:
M
=
ZRT
Where
M = Molecular weight
= pressure, pascals
R = gas constant = 8314.0 (Pa) (m3 ) per (kmol) (K)
T = temperature, kelvins
Z = compressibility factor
= density of the gas (or vapor) at temperature T, kilogram per cubic metre
Procedure
Step 1: Obtain the critical properties and molecular weight from appropriate sources
Step2: Calculate the reduced temperature and reduced pressure.
Step 3: Depending on the magnitude of the reducxed pressure, estimate the compressibility factor at Zc
= 0.27 from the appropriate figure.
Step 4: Depending on whether Zc is greater than or less than 0.27, estimate the deviation term Di, from
the appropriate figure.
Step 5: Using equation (4D-2), calculate the compressibility factor, Z.
Step 6: Calculate the density of the gas ( or vapor) using Equation (4D-3)
With the exception of mercaptans and carboxylic acids, the figures given in procedure 43D are
applicable to all families of organic compounds. The deviation charts, however are restricted to a
PROCESS STD 602
PAGE A-17
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
reduced temperature greater than or equal to 0.90 . The deviations can be ignored (without any
significant loss in accuracy) when the reduced temperature is less than 0.90. Procedure 4D gave an
average devation of 5% for 63 data pointsa covering 33 representative compounds. Although procedure
4D has been hudged to produce rapid, reasonably good estimates of gas ( or vapor), phase densities, use
of procedure 4E is recommended wherever possible.
Literature Source
Figures 4D-I through 4D-IV have been adapted from Lyderson, A.L., R.A.Greenkorn, O.A. Hougen,
Univ Wisconsin Eng Exp. Station Rept. 4 (Oct 1955). Also in Hougen, O.A., K.M. Watson, R.A.Ragatz,
Chemical Process Principles charts, 3rd ed., 1964
PROCESS STD 602
PAGE A-18
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-19
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Note: This chart is typical and suitable for use only when the make of the valve, or actual critical flow
pressure point for the vapor or gas is unknown; otherwise, the valve manufacturer should be consulted
for specific data. This correction factor should be used only in the sizing of a conventional (non-
balanced) pressure relief valves that have their spring setting adjusted to compensate for the
superimposed back pressure. It should not be used to size balanced-type valves.
PROCESS STD 602
PAGE A-20
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-21
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-22
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-23
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-24
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-25
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
PROCESS STD 602
PAGE A-26
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
1) API RP 520 Sizing, Selection and Installation of Pressure Relieving Devices in Refineries
Part I : Sizing and Selection, 6T h . Ed., 1993
2) API RP 521 Guide for Pressure-Relieving and Depressuring Systems, 4th Ed., March 1997
3) API STD 526 Flanged Steel Pressure Relief Valves, 4Th. Ed., June 1995
PROCESS STD 602
PAGE B-1
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Note that steady state flow and Newtonian fluids are assumed in these formulas.
For a gas or vapor flowing in non-critical conditions through a nozzle from the
upstream pressure P1 to the downstream pressure P2 the rate of flow is given by
the following formulas, in English units :
MP1 ( P1 P2 )
W = 735 F2 KA (1)
ZT
k+1
2/ k
W = 735 KAP1 M k P 2
P2 k (2)
ZT k 1 P1 P1
where :
K= discharge coefficient.
Z= gas compressibility
k 1
F2 = k r 2 k 1 r k
k 1 1 r
P2
r= = ratio of back pressure to upstream pressure
P1
PROCESS STD 602
PAGE B-2
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
The critical flow pressure P cf, in absolute units, may be estimated by the
following equation for ideal gases :
k
P 2 k 1
cf = (3)
P
1
k + 1
The critical flow pressure ratio for hydrocarbon gases usually encountered is
given in Table 1. The listed values range from 0.53 to 0.59.
kPcf
Vcf = 68 (4)
Dcf
where :
Substituting the values of Pcf from equation (3) in formula (1), the theoretical gas
discharge formula for critical flow is obtained :
M
W = CKAP1
ZT
where :
Z = gas compressibility
and
( )
n +1 0.5
C = 520 n n2+1 n 1
where n is the isentropic expansion coefficient of the actual gas or vapor. The
ratio k of specific heats may be used instead.
PROCESS STD 602
PAGE B-3
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
The effective discharge area of a pressure relief valve (refer to Table 5) will be
one of the following two areas, whichever is controlling, depending on valve
design :
2) the curtain area which is the product of the circumference of the minimum
passage through the valve seat and the valve lift.
The discharge area for safety and safety relief valves in gas or vapor
service can be determined by use of the following formula (API RP 520,
4.3.2.1 and 4.3.4.1) :
A= W ZT
CKd P1 K b M
Note that the same formula may be used for conventional or balanced
pressure relief valve, with different Kb.
3.2 Steam
Safety and safety relief valves in steam service are sized by use of the
following formula (API RP 520, 4.4.1) :
A = W
51.5P1 Kd KN Ksh
W = flowrate, lb/hr.
PROCESS STD 602
PAGE B-4
FOSTER WHEELER SAFETY REVISION 3
PROCESS PLANTS DIVISION RELIEVING DEVICES DATE December 1999
Kd = coefficient of discharge.
API RP 520 suggests using Kd = 0.975.
n +1
( )
0.5
C = 520 n 2 n 1
see Figure 15
n +1
735 F2
Kb = 1 r
C
When using Figure 11 for sizing balanced-bellows valves, consult the valve
manufacturer for Kb in case of :
- set pressure lower than 50 psig
- subcritical flow back pressure
3.3 Liquids
Safety relief valves in liquid service may be sized by the use of the
following formula (API RP 520, 4.6), a conversion from a basic liquid
flow formula :
gpm G
A=
38 .0 K d K p K w K v 1.25 P Pb
where :
When a relief valve is sized for viscous liquid service, it is suggested that it
be sized first as for non viscous type application (Kv = 1) in order to obtain
a preliminary required discharge area, A. From manufacturer's standard
orifice sizes, the next larger orifice size should be used in determining the
Reynold's number, R, from either of the following relationships :
gpm (2,800 G)
R=
A1 / 2
or
12 ,700 gpm
R=
U A1 / 2
where :
The API RP 520 method consists in determining the valve's size by adding
up the areas calculated for the liquid and flashed vapors separately (refer
to 4.4.1).
The effect of any auto-refrigeration that may arise from the flashing of
liquid should also be investigated. Materials of construction must be
adequate for the outlet temperatures involved ; in addition, the installation
must preclude the possibility of flow blockage occurring from hydrate or
possibly solid formation.