Instruction for Speed Demand Change from CAN to Bin Up/Down

First-Step Confirm the genset had two free digital Input.

Please check whether there is connection From DI 50 to DI 55 and


ensure that DI is not in used?
Second Step After confirm the genset had two free digital Input.

Example for reference DI 50 or DI 51 is not in used.

Enter the Deif utility software 3.39.0


New level, please change to basic
to master

After changing to master

Password is 2002
After Enter the Password

Front page of Deif Utility software


Download and upload from the Deif
controller

Able to read and write from the Device


To configure DI 50 or DI 51 for decrease
in speed or increase speed.

To configure DI 50 or DI 51.

M-Logic
Example Logic 37 and Logic 38 is not used.

Example we using Logic 37 to configure DI 50 for speed increase.

Inputs
Selected the Input- Dig. Input No.50 DI50

1) Set the Dig. Input No. 50


2) Set the speed increase

Dig. Input No.50

And double click


output

EIC commands

EIC command EIC speed increase


EIC Speed increase
Dig Input No.50 Inputs

EIC speed increase EIC command

Setting DI51 to Speed decrease with Logic 38.


Dig. Input No.51
EIC speed decrease

Dig input
Set out a third Line in M-logic that not used to a TRUE Logic

Set the output EIC binary Speed in-De Enable: EIC commands

EIC binary Speed In-De


Enable

Example Logic 32 is Not used set to TRUE Logic

True Logic