CHAPTER 1

HVAC SYSTEM ANALYSIS AND SELECTION


Selecting a System .......................................................................................................................... 1.1
HVAC Systems and Equipment ....................................................................................................... 1.3
Space Requirements ........................................................................................................................ 1.4
Air Distribution ............................................................................................................................... 1.5
Piping .............................................................................................................................................. 1.6
System Management ....................................................................................................................... 1.6

A N HVAC SYSTEM maintains desired environmental condi-


tions in a space. In almost every application, a myriad of
options are available to the design engineer to satisfy this basic goal.
Supporting a process, such as the operation of computer
equipment
Promoting a germ-free environment
In the selection and combination of these options, the design engi- Increasing sales
neer must consider all criteria defined here to achieve the functional Increasing net rental income
requirements associated with the goal. Increasing the salability of a property
HVAC systems are categorized by the method used to control
The owner can only make appropriate value judgments if the
heating, ventilation, and air conditioning in the conditioned area.
design engineer provides complete information on the advantages
This chapter addresses the procedures associated with selecting the
and disadvantages of each option. Just as the owner does not usually
appropriate system for a given application. It also describes and
know the relative advantages and disadvantages of different sys-
defines the design concepts and characteristics of basic HVAC sys-
tems, the design engineer rarely knows all the owners financial and
tems. Chapters 2 through 5 of this volume describe specific systems
functional goals. Hence, the owner must be involved in the selection
and their attributes, based on their heating and cooling medium and
of a system.
commonly used variations.
System Constraints
SELECTING A SYSTEM
Once the goal criteria and additional goal options are listed,
The design engineer is responsible for considering various sys- many constraints must be determined and documented. These con-
tems and recommending one or two that will satisfy the goal and straints may include
perform as desired. It is imperative that the design engineer and the
Performance limitations (i.e., temperature, humidity, and space
owner collaborate on identifying and rating the criteria associated
pressure)
with the design goal. Some criteria that may be considered are
Available capacity
Temperature, humidity, and space pressure requirements Available space
Capacity requirements Availability utility source
Redundancy Building architecture
Spatial requirements Construction budget
First cost Few projects allow detailed quantitative evaluation of all alter-
Operating cost natives. Common sense, historical data, and subjective experience
Maintenance cost can be used to narrow choices to one or two potential systems.
Reliability Heating and air conditioning loads often contribute to the con-
Flexibility straints, narrowing the choice to systems that will fit in the available
Life cycle analysis space and be compatible with the building architecture. Chapter 29
of the ASHRAE HandbookFundamentals describes methods used
Because these factors are interrelated, the owner and design to determine the size and characteristics of the heating and air con-
engineer must consider how these criteria affect each other. The rel- ditioning loads. By establishing the capacity requirement the size of
ative importance of factors, such as these, differs with different equipment can be determined, and the choice may be narrowed to
owners and often changes from one project to another for the same those systems that work well on projects within a size range.
owner. For example, typical concerns of owners include first cost Loads vary over time due to the time of day/night, changes in the
compared to operating cost, the extent and frequency of mainte- weather, occupancy, activities, and solar exposure. Each space with
nance and whether that maintenance requires entering the occupied a different use and/or exposure may require a different control zone
space, the expected frequency of failure of a system, the impact of to maintain space comfort. Some areas with special requirements
a failure, and the time required to correct the failure. Each of these may need individual systems. The extent of zoning, the degree of
concerns has a different priority, depending on the owners goals. control required in each zone, and the space required for individual
zones also narrow the system choices.
Additional Goals No matter how efficiently a particular system operates or how
In addition to the primary goal to provide the desired environ- economical it is to install, it can only be considered if it (1) main-
ment, the design engineer must be aware of and account for other tains the desired building space environment within an acceptable
goals the owner may require. These goals may include tolerance under all conditions and occupant activities and (2) phys-
ically fits into the building without being objectionable.
The preparation of this chapter is assigned to TC 9.1, Large Building Air- Cooling and humidity control are often the basis of sizing
Conditioning Systems. HVAC components and subsystems, but the system may also be

1.1
1.2 2000 ASHRAE Systems and Equipment Handbook (SI)

determined based on the ventilation criteria. For example, if large converts energy from fuel or electricity into a heating and/or cooling
quantities of outside air are required for ventilation or to replace air media. The secondary system delivers heating, ventilation, and/or
exhausted from the building, only systems that transport large air cooling to the occupied space. The two systems, to a great extent,
volumes need to be considered. are independent, so several secondary systems may work with a par-
Effective delivery of heat to an area may be an equally impor- ticular primary system. In some cases, however, only one secondary
tant factor in the selection. A distribution system that offers high system may be suitable for a particular primary system.
efficiency and comfort for cooling may be a poor choice for heating. Once subjective analysis has identified one or two HVAC sys-
This performance compromise may be small for one application in tems (sometimes only one choice may remain), detailed quantitative
one climate, but may be unacceptable in another that has more strin- evaluations must be made. All systems considered should provide
gent heating requirements. satisfactory performance to meet the owners essential goals. The
HVAC systems and the associated distribution systems often design engineer should provide the owner with specific data on each
occupy a significant amount of space. Major components may system to make an informed choice. The following chapters in the
also require special support from the structure. The size and appear- ASHRAE Handbooks should be consulted to help narrow the
ance of terminal devices (i.e., diffusers, fan-coil units, radiant pan- choices:
els, etc.) have an affect on the architectural design because they are
visible in the occupied space. Chapter 8, ASHRAE HandbookFundamentals covers physio-
Other architectural factors that limit the selection of some sys- logical principles, comfort, and health.
tems include Chapter 31, ASHRAE HandbookFundamentals covers methods
for estimating annual energy costs.
Acceptable noise levels in the occupied space Chapter 34, ASHRAE HandbookApplications covers methods
Space available to house equipment and its location relative to the for energy management.
occupied space
Chapter 35, ASHRAE HandbookApplications covers owning
Space available for horizontal and/or vertical distribution pipes
and operating cost.
and ducts
Acceptability of components visible in the occupied space. Chapter 37, ASHRAE HandbookApplications covers mechani-
cal maintenance.
Construction budget constraints can also influence the choice Chapter 46, ASHRAE HandbookApplications covers sound and
of HVAC systems. Based on historical data, some systems may be vibration control.
economically out of reach for an owners building program.
Selection Report
Narrowing the Choices
As the last step of selection, the design engineer should prepare
Chapters 2 through 5 cover building air distribution, in-room
a summary report that addresses the following:
terminal systems, central cooling and heating, and decentralized
cooling and heating. Each chapter briefly summarizes the positive The goal
and negative features of various systems. One or two systems that Criteria for selection
best satisfy the project goal can usually be identified by comparing Important factors
the criteria, other factors and constraints, and their relative impor- Other goals
tance. In making subjective choices, notes should be kept on all
systems considered and the reasons for eliminating those that are A brief outline of each of the final selections should be provided.
unacceptable. In addition, those HVAC systems deemed inappropriate should be
Each selection may require combining a primary system with a noted as having been considered but not applicable to meet the
secondary system (or distribution system). The primary system owners primary HVAC goal.

Table 1 Sample HVAC System Selection Matrix (0 to 10 Score)


Goal: Furnish and install an HVAC system that provides moderate space temperature
control with minimum humidity control at an operating budget of 220 kW/m2 per year
Categories System #1 System #2 System #3 Remarks
1. Criteria for Selection:
24C space temperature with 2C control during occupied cycle
20% relative humidity with 5% rh control during heating season.
First cost
Equipment life cycle
2. Important Factors:
First class office space stature
Individual tenant utility metering
3. Other Goals:
Engineered smoke control system
ASHRAE Standard 62 ventilation rates
Direct digital control building automation
4. System Constraints:
No equipment on the first floor
No exterior louvers below the perimeter windows
5. Other Constraints:
No perimeter finned tube radiation
TOTAL SCORE
HVAC System Analysis and Selection 1.3

The report should include an HVAC system selection matrix that for this shortcoming. Thus, a life cycle cost analysis is very impor-
identifies the one or two suggested HVAC system (primary and sec- tant when evaluating central versus decentralized systems.
ondary when applicable) selections, system constraints, and other Operating cost. A central system usually has the advantage of
constraints. In completing this matrix assessment, the engineer larger, more energy efficient primary equipment when compared to
should have the owners input to the analysis. This input can also be decentralized system equipment.
applied as weighted multipliers. Maintenance cost. The equipment room for a central system
Many grading methods are used to complete an analytical matrix provides the benefit of maintaining its HVAC equipment away from
analysis. Probably the simplest grading method is to rate each item the occupants in an appropriate service work environment. Access
Excellent/Very Good/Good/Fair/Poor. A numerical rating system to the building occupant workspace is not required, thus eliminating
such as 0 to 10, with 10 equal to Excellent and 0 equal to Poor, can disruption to the space environment, product, or process. Another
provide a quantitative result. The HVAC system with the highest advantage may be that because of its larger capacity, there is less
numerical value then becomes the recommended HVAC system to HVAC equipment to service.
accomplish the goal. Reliability. Central system equipment can be an attractive ben-
The system selection report should include a summary that pro- efit when considering its long service life.
vides an overview followed by a more detailed account of the
Flexibility. Redundancy can be a benefit when selecting standby
HVAC system analysis and system selection. This summary should
equipment that provides an alternative source of HVAC or backup.
highlight the key points and findings that led to the recommenda-
tion(s). The analysis should refer to the system selection matrix Among the largest central systems are those HVAC plants serv-
(such as in Table 1) and the reasons for scoring. ing groups of large buildings. These plants provide improved diver-
A more detailed analysis, beginning with the owners goal, sity and generally operate more efficiently with lower maintenance
should immediately following the summary. With each HVAC sys- costs than individual central plants. The economics of these larger
tem considered, the design engineer should note the criteria associ- central systems require extensive analysis. The utility analysis con-
ated with each selection. Issues such as close temperature and siders multiple fuels and may also include gas and steam turbine-
humidity control may eliminate some HVAC systems from being driven equipment. Multiple types of primary equipment using mul-
considered. System constraints and other constraints, noted with tiple fuels and types of HVAC generating equipment (i.e., centrifu-
each analysis, should continue to eliminate HVAC systems. Advan- gal and absorption chillers) may be installed in combination in one
tages and disadvantages of each system should be noted with the plant. Chapter 12, Chapter 13, and Chapter 14 provide design
scoring from the HVAC system selection matrix. This process details for central plants.
should reduce the HVAC selection to one or two optimum choices
to present to the owner. Examples of installations for other owners Decentralized System Features
should be included with this report to endorse the design engineers
final recommendation.This third party endorsement allows the Some of the criteria associated with this concept are as follows:
owner to inquire about the success of these other HVAC systems. Temperature, humidity, and space pressure requirements. A
decentralized system may be able to fulfill any or all of these design
HVAC SYSTEMS AND EQUIPMENT parameters.
HVAC systems may be central or decentralized. In addressing Capacity requirements. A decentralized system usually
the primary equipment location, the design engineer may locate this requires each piece of equipment to be sized for the maximum
equipment in a central plant (either inside or outside the building) capacity. Depending on the type and location of the equipment,
and distribute the air and/or water for HVAC needs from this plant. decentralized systems cannot take as much benefit of equipment
The other option is to decentralize the equipment, with the primary sizing diversity when compared to the central system diversity fac-
equipment located throughout the building, on the building, or adja- tor potential.
cent to the building. Redundancy. A decentralized system may not have the benefit
of backup or standby equipment. This limitation may need review.
Central System Features Space requirements. A decentralized system may or may not
Some of the criteria associated with this concept are as follows: have an equipment room. Due to the space restrictions imposed on
the design engineer or architect, equipment may be located on the
Temperature, humidity, and space pressure requirements. A roof and/or the ground adjacent to the building.
central system may be able to fulfill any or all of these design
First cost. A decentralized system probably has the best first cost
parameters.
benefit. This feature can be enhanced by phasing in the purchase of
Capacity requirements. A central system usually allows the
decentralized equipment on an as-needed basis (i.e., purchasing
design engineer to consider HVAC diversity factors that reduce the
equipment as the building is being leased/occupied).
installed equipment capacity. In turn, this offers some attractive first
cost and operating cost benefits. Operating cost. A decentralized system can emphasize this as a
Redundancy. A central system can accommodate standby benefit when strategically starting and stopping multiple pieces of
equipment of equal size or of a preferred size that decentralized con- equipment. When comparing energy consumption based on peak
figurations may have trouble accommodating. energy draw, decentralized equipment may not be as attractive when
Spatial requirements. The equipment room for a central system compared to larger, more energy efficient central equipment.
is normally located outside the conditioned areain a basement, Maintenance cost. A decentralized system can emphasize this
penthouse, service area, or adjacent to or remote from the building. as a benefit when equipment is conveniently located and the equip-
A disadvantage with this approach may be the additional cost to ment size and associated components (i.e., filters) are standardized.
furnish and install secondary equipment for the air and/or water When equipment is located on a roof, maintainability may be diffi-
distribution. A second consideration is the access and physical cult because it is difficult to access during bad weather.
constraints throughout the building to furnish and install this sec- Reliability. A decentralized system historically has reliable
ondary distribution network of ducts and/or pipes. equipment, although the estimated equipment service life may be
First cost. A central system may not be the least costly when less than that of centralized equipment.
compared to decentralized HVAC systems. Historically, central sys- Flexibility. A decentralized system may be very flexible because
tem equipment has a longer equipment service life to compensate it may be placed in numerous locations.
1.4 2000 ASHRAE Systems and Equipment Handbook (SI)

Primary Equipment Air Delivery Equipment


The type of central and decentralized equipment selected for Primary air delivery equipment for HVAC systems are classified
large buildings depends on a well-organized HVAC analysis and as packaged equipment, manufactured and custom manufactured
selection report. The choice of primary equipment and components equipment, or field fabricated equipment. Most ventilation equip-
depends on factors presented in the selection report with such fac- ment for large systems use centrifugal or axial fans; however, plug
tors as those presented in the section on Selecting a System. Primary or plenum fans are becoming more popular. Centrifugal fans are fre-
HVAC equipment includes heating equipment, air and water deliv- quently used in packaged and manufactured HVAC equipment.
ery equipment, and refrigeration equipment. Axial fans are more often part of a custom unit or a field-fabricated
Many HVAC designs recover internal heat from lights, people, unit. Both types of fans can be used as industrial process and high-
and equipment to reduce the size of the heating plant. In large build- pressure blowers. Chapter 18 describes fans, and Chapters 16
ings with core areas that require cooling while perimeter areas through 25 provide information about ventilation components.
require heating, one of several heat reclaim systems can heat the
perimeter to save energy. Chapter 8 describes some heat recovery Refrigeration Equipment
arrangements, Chapter 33 describes solar energy equipment, and The section on Refrigeration Equipment in Chapter 4 summa-
Chapter 44 introduces air-to-air energy recovery. In the ASHRAE rizes the primary refrigeration equipment for HVAC systems
HandbookApplications, Chapter 34 covers energy management designed to maintain desired environmental conditions in a space.
and Chapter 39 covers building energy monitoring.
The search for energy savings has extended to cogeneration or SPACE REQUIREMENTS
total energy systems, in which on-site power generation has been
In the initial phase of a buildings design, the engineer seldom
added to the HVAC project. The economics of this function is
has sufficient information to render the HVAC design. As noted in
determined by gas and electric rate differentials and by the ratio of
the section on Space Requirements in Chapter 4, the final design is
electric to heating demands for the project. In these systems, waste
usually a compromise between what the engineer recommends and
heat from generators can be transferred to the HVAC equipment
what the architect can accommodate. At other times, final design
(i.e., to drive the turbines of centrifugal compressors, to serve an
and space requirements may be dictated by the building owner who
absorption chiller, etc.). Chapter 7 covers cogeneration or total
may have a preference for a central or decentralized system. The
energy systems.
following paragraphs discuss some of these requirements.
Thermal storage is another energy savings concept, which pro-
vides the possibility of off-peak generation of air conditioning with Equipment Rooms
chilled water or ice. Thermal storage of hot water can be used in
heating. Many electric utilities impose severe charges for peak sum- The total mechanical and electrical space requirements range
mer power use or offer incentives for off-peak use. The storage between 4 and 9% of the gross building area with most buildings
capacity installed to level the summer load may also be available for falling within the 6 to 9% range. These ranges include space for
use in winter, thus making heat reclaim a viable option. Chapter 33 HVAC, electrical, plumbing, and fire protection equipment. These
of the ASHRAE HandbookApplications has more information on percentages also include vertical shaft space for mechanical and
thermal storage. electrical equipment.
Most facilities should be centrally located to (1) minimize long
With ice storage, colder supply air can be provided than that
duct, pipe, and conduit runs and sizes; (2) simplify shaft layouts;
available from a conventional air conditioning. This colder air
and (3) centralize maintenance and operation. A central location
allows the use of smaller fans and ducts, which reduces first cost and
also reduces pump and fan motor power, which reduces building
operating cost that can offset the energy cost required to make ice.
operating costs. But, for many reasons, not all the mechanical and
Similarly, the greater water temperature difference from hot water
electrical facilities can be centrally located in the building. In any
thermal storage allows smaller pumps and pipe to be used.
case, the equipment should be kept together whenever possible to
minimize space requirements, centralize maintenance and opera-
Heating Equipment tion, and simplify the electrical system.
Steam boilers or hot water boilers are the primary means of heat- Equipment rooms generally require clear ceiling height ranging
ing a space. These boilers are (1) used both for heating and process from 3 to 5 m, depending on equipment sizes and the complexity of
heating; (2) manufactured to produce high or low pressure; and (3) air and/or water distribution.
fired with coal, oil, electricity, gas, and sometimes, waste material. The main electrical transformer and switchgear rooms should be
Low-pressure boilers are rated for a working pressure of either 100 located as close to the incoming electrical service as practical. If
or 200 kPa for steam and 1100 kPa for water, with a temperature there is an emergency generator, it should be located considering (1)
limit of 120C. Package boilers, with all components and controls proximity to emergency electrical loads and sources of combustion
assembled as a unit, are available. Electrode or resistance-type elec- and cooling air and fuel, (2) ease of properly venting exhaust gases
tric boilers that generate either steam or hot water are also available. to the outdoors, and (3) provisions for noise control.
Chapter 27 has further information.
Where steam or hot water is supplied from a central plant, as on HVAC Facilities
university campuses and in downtown areas of large cities, the util- The heating equipment room houses the boiler(s) and may also
ity service entering the building must conform to the utilitys stan- house a boiler feed unit, chemical treatment equipment, pumps, heat
dards. The utility provider should be contacted at the system exchangers, pressure-reducing equipment, control air compressors,
analysis and selection phase of the project to determine availability, and miscellaneous equipment. The refrigeration equipment room
cost, and the specific requirements of the service. houses the chiller(s) and may also house chilled water and con-
When the primary heating equipment is selected, the fuels con- denser water pumps, heat exchangers, air-conditioning equipment,
sidered must ensure maximum efficiency. Chapter 26 discusses the control air compressors, and miscellaneous equipment. The design
design, selection, and operation of the burners for different types of of these rooms needs to consider (1) the size and weight of the
primary heating equipment. Chapter 18 of the ASHRAE Hand- equipment; (2) installation and replacement when locating and
bookFundamentals describes types of fuel, fuel properties, and arranging the room to accept this large equipment; and (3) applica-
proper combustion factors. ble regulations relative to combustion air and ventilation air criteria.
HVAC System Analysis and Selection 1.5

In addition, ASHRAE Standard 15, Safety Code for Mechanical vertical shafts are electric conduits/closets, telephone cabling/clos-
Refrigeration should be consulted for special equipment room ets, plumbing piping, fire protection piping, pneumatic tubes, and
requirements. conveyers.
Most air-conditioned buildings require a cooling tower or con- Vertical shafts should be clear of stairs and elevators on at least
denser unit. If the cooling tower or air-cooled or water-cooled con- two sides to permit access to ducts, pipes, and conduit that enter and
denser is located on the ground, it should be at least 30 m away from exit the shaft while allowing maximum headroom at the ceiling. In
the building (1) to reduce tower noise in the building, (2) to keep general, duct shafts having an aspect ratio of 2:1 to 4:1 are easier to
discharge air and moisture carry-over from fogging the buildings develop than large square shafts. The rectangular shape also makes
windows and discoloring the facade of the building, and (3) to keep it easier to go from the equipment in the fan rooms to the shafts.
discharge air and moisture carry-over from contaminating outdoor In multistory buildings a vertical distribution system with mini-
air being introduced into the building. Cooling towers should be mal horizontal branch ductwork is desirable because it is (1) usually
kept the same distance from parking lots to avoid staining car fin- less costly; (2) easier to balance; (3) creates less conflict with pipes,
ishes with water treatment chemicals. Chapter 35 and Chapter 36 beams, and lights; and (4) enables the architect to design lower
have further information on this equipment. floor-to-floor heights. These advantages also hold for vertical water
It is often economical to locate the heating plant and/or refriger- and steam pipe distribution systems.
ation plant at an intermediate floor or on the roof. The electrical ser- The number of shafts is a function of building size and shape. In
vice and structural costs are higher, but these may be offset by larger buildings, it is usually more economical in cost and space to
reduced costs for heating piping, condenser and chilled water pip- have several small shafts rather than one large shaft. Separate
ing, energy consumption, and a chimney through the building. Also, HVAC supply air, return air, and exhaust air duct shafts may be
the initial cost of equipment may be less because the operating pres- desired to reduce the number of duct crossovers. The same can be
sure is lower. said for steam supply and condensate return pipe shafts because the
Applicable regulations relative to both gas and fuel oil systems pipe must be pitched in the direction of flow. From 10% to 15%
must be followed. Gas fuel may be more desirable than fuel oil. Fuel additional shaft space should be allowed for future expansion and
oil storage has specific environmental and safety concerns. In addi- modifications. This additional space may also reduce the initial
tion, the cost of oil leak detection and prevention may be substantial. installation cost.
Oil pumping presents added design and operating problems.
Energy recovery systems can reduce the size of the heating Equipment Access
plant and/or refrigeration plant. Well-insulated buildings and elec- Properly designed mechanical and electrical equipment rooms
tric and gas utility rate structures may encourage the design engi- must allow for the movement of large, heavy equipment in, out, and
neer to consider several energy conservation concepts such as through the building. Equipment replacement and maintenance can
limiting demand, free cooling and thermal storage. be very costly if access is not planned properly.
Because systems vary greatly, it is difficult to estimate space
Fan Rooms requirements for refrigeration and boiler rooms without making
The fan rooms house the HVAC fan equipment and may include block layouts of the system selected. Block layouts allow the engi-
other miscellaneous equipment. The room must have space for re- neer to develop the most efficient arrangement of the equipment
moval of the fan shaft and coil. Installation, replacement, and main- with adequate access and serviceability. Block layouts can also be
tenance of this equipment should be considered when locating and used in preliminary discussions with the owner and architect. Only
arranging the room. then can the engineer obtain verification of the estimates and pro-
Fan rooms may be placed in a basement that has an airway for vide a workable and economical design.
intake of outdoor air. In this situation the placement of air intake
louver(s) is a concern because of debris from leaves and snow may AIR DISTRIBUTION
fill the area. Also, if parking areas are close to the building, the qual- Ductwork should deliver conditioned air to an area as directly,
ity of outdoor air may be compromised. quietly, and economically as possible. Structural features of the
Fan rooms on the second floor and above, have easier access for building generally require some compromise and often limit the
outdoor air, exhaust air, and equipment replacement. The number of depth of the space available for ducts. Chapter 9 discusses air dis-
fan rooms required depends largely on the total floor area and tribution design for small heating and cooling systems. Chapter 34
whether the HVAC system is centralized or decentralized. Buildings of the ASHRAE HandbookFundamentals discusses space air dis-
with large floor areas may have multiple decentralized fan rooms on tribution and duct design.
each floor or a large central fan unit serving the entire area. High- The designer must coordinate duct design with the structure as
rise buildings may also opt for decentralized fan rooms for each well as other mechanical, electrical, and communication systems. In
floor; or they may have a more central concept with one fan room commercially developed projects, a great effort is made to reduce
serving the lower 10 to 20 floors, one serving the middle floors of floor-to-floor dimensions. The resultant decrease in the available
the building, and one at the roof serving the top floors. interstitial space for ductwork is a major design challenge. In insti-
Life safety is a very important factor in fan room location. Chap- tutional buildings, higher floor-to-floor heights are required due to
ter 51 of the ASHRAE HandbookApplications discusses fire and the sophistication and complexity of the mechanical, electrical, and
smoke management. In addition, state and local codes have addi- communication distribution systems.
tional fire and smoke detection and damper criteria.
Air Terminal Units
Vertical Shafts In some instances, such as in low velocity, all-air systems, the
Vertical shafts provide space for air distribution and water and air may enter from the supply air ductwork directly into the condi-
steam (pipe) distribution. Air distribution includes HVAC supply tioned space through a grille or diffuser. In medium and high veloc-
air, return air, and exhaust air ductwork. If the shaft is used as a ity air systems, an intermediate device normally controls air
return air plenum, close coordination with the architect is necessary volume, reduces duct pressure, or both. Various devices are avail-
to insure that the shaft is airtight. Pipe distribution includes hot able, including (1) a fan-powered terminal unit, which uses an inte-
water, chilled water, condenser water, and steam supply and con- gral fan to accomplish the mixing rather than depending on the
densate return. Other mechanical and electrical distribution found in induction principle; (2) a variable air volume (VAV) terminal unit,
1.6 2000 ASHRAE Systems and Equipment Handbook (SI)

which varies the amount of air delivered to the space (this air may ASHRAE Standard 90.1 and Chapters 25 and 35 of the ASHRAE
be delivered to low-pressure ductwork and then to the space, or the HandbookFundamentals have information regarding insulation
terminal may contain an integral air diffuser); (3) an all-air induc- and the calculation methods.
tion terminal unit, which controls the volume of primary air,
induces return air, and distributes the mixture through low-velocity SYSTEM MANAGEMENT
ductwork to the space; and (4) an air-water induction terminal,
which includes a coil in the induced airstream. Chapter 17 has System management is an important factor in choosing the opti-
more information about air terminal units. mum HVAC system. It can be as simple as a time clock to start and
stop the equipment or as sophisticated as a computerized facility
Insulation management software system serving large centralized HVAC mul-
In new construction and renovation upgrade projects, HVAC tiple systems, decentralized HVAC systems, a large campus, etc.
supply air ductwork should be insulated in accordance with energy
code requirements. ASHRAE Standard 90.1, Section 9.4, and Automatic Controls
Chapter 34 of the ASHRAE HandbookFundamentals have more Basic HVAC system management is available in electric, pneu-
information about insulation and the calculation methods. matic, or electronic temperature control systems. Depending on the
application, the design engineer may recommend a simple and basic
Ceiling Plenums management strategy as a cost-effective solution to an owners heat-
Frequently, the space between the suspended ceiling and the ing, ventilation, and refrigeration needs. Chapter 45 of the ASHRAE
floor slab above it is used as a return air plenum to reduce the dis- HandbookApplications and Chapter 15 of the ASHRAE Hand-
tribution ductwork. Refer to existing regulations before using this bookFundamentals discuss automatic control in more detail.
approach in new construction or a renovation because most codes The next level of HVAC system management is direct digital
prohibit combustible material in a ceiling return air plenum. control either with or without pneumatic control damper and valve
Some ceiling plenum applications with lay-in panels do not work actuators. This automatic control enhancement may include energy
well where high-rise elevators or the stack effect of a high-rise monitoring and energy management software. The configuration
building create a negative pressure. If the plenum leaks to the low- may also be accessible by the building manager via telephone
pressure area, the tiles may lift and drop out when the outside door modem to a remote computer at an off-site location. Chapter 40 of
is opened and closed. the ASHRAE HandbookApplications covers building operating
Raised floors with a plenum space directly below are another dynamics.
way to provide horizontal air distribution and/or a return air plenum. Using computer technology and associated software the design
The return air temperature in a return air plenum directly below engineer and the building manager can provide complete facility
a roof deck is substantially higher during the air conditioning season management. This comprehensive building management system
than in a ducted return. This can be an advantage to the occupied may include HVAC system control, energy management, operation
space below because the heat gain to the space is reduced. Con- and maintenance management, fire alarm system control, and other
versely, return air plenums directly below a roof deck have substan- reporting and trending software. This system may also be integrated
tially lower return air temperatures during the heating season than a and accessible from the owners information technology computer
ducted return and may require supplemental heat in the plenum. network and the Internet.
PIPING System Management Interface
Piping should deliver refrigerant, hot water, chilled water, con-
Today, system management includes the purchasing of auto-
denser water, condensate drains, fuel oil, gas, steam, and condensate
matic controls that come prepackaged and prewired on the HVAC
to and from HVAC equipment as directly, quietly, and economically
equipment. In the analysis and selection of a system, the design
as possible. Structural features of the building generally require
engineer needs to include the merits of purchasing prepackaged
mechanical and electrical coordination to accommodate pipe pitch,
automation versus traditional building automation systems. Current
draining of low points in the system, and venting of high point in the
HVAC controls and their capabilities need to be compatible with
system. Chapter 35 of the ASHRAE HandbookFundamentals cov-
other new and existing automatic controls. Chapter 38 of the
ers pipe distribution and pipe design.
ASHRAE HandbookApplications discusses computer applica-
Pipe Systems tions and ASHRAE Standard 135 discusses interfacing building
automation systems.
HVAC piping systems can be divided into two parts; (1) the piping Other interfaces to be considered include the interface and com-
in the central plant equipment room and (2) the piping required to patibility of other mechanical and electric control and management
deliver refrigerant, hot water, chilled water, condenser water, conden- systems. Building systems, such as the fire alarm, medical gas sys-
sate drain, fuel oil, gas supply, steam supply, and condensate return to tems, and communication systems are just three of the management
and from HVAC and process equipment throughout the building. interfaces that an owner may want to work in unison with the
Chapters 10 through 14 discuss piping for various heating and cooling HVAC control system. Predictive and preventive maintenance us-
systems. Chapters 1 through 4 and 32 of the ASHRAE Handbook ing computerized maintenance management software (CMMS) also
Refrigeration discuss refrigerant piping practices. enhances the management and should be considered.
The major piping in the central plant equipment room includes
refrigerant, hot water, chilled water, condenser water, condensate
drains, fuel oil, gas supply, steam supply, and condensate return STANDARDS
connections. ASHRAE Standard 15-1994. Safety code for mechanical refrigeration.
ASHRAE/IESNA Standard 90.1-1999. Energy efficient design of new
Insulation buildings except low-rise residential buildings.
In new construction and renovation upgrade projects, HVAC ASHRAE Standard 135-1995. BACnetA data communication protocol
piping may or may not be insulated based on existing code criteria. for building automation and control networks.