History log:
All values and parameters are available from PCtools LiteEdit and InteliMonitor.
4.1.3 Sd Override
Created new setpoint Sd Override (group: Engine Protect) for disable all configured protections, except
Overspeed and Emergency Stop. New setpoint can be set:
ENABLED - all configured protections except Overspeed and Emergency Stop are inactive. They are just
displayed on alarm list and recorded to historry, but they have no influence to running engine. The setting
ENABLEDis indicated in tha alarm list by warning SdOverride Act. It is recorded in history too.
DISABLED - all configured protections are active.
Setting of setpoint Starting POil for AIN1 configured as binary input means:
Starting POil = 0 - the engine is considered as running if pressure switch is open (AIN1 = log.0).
Starting POil = 1 - the engine is considered as running if pressure switch is closed (AIN1 = log.1).
I/O-R-Button
Setpoint group Basic Settings Related fw 1.0.2
Range [units] None/SpeedUp
Default value SpeedUp
Step
Description
Increase of engine speed request - short press changes the speed of 1 RPM, long press change the speed
according to set Speed ramp (setpoint in group Engine Param2). This button has exactly same functionality
as existing LBI Speed Up.
Sd Override
Setpoint group Engine Protect Related fw 1.0.2
Range [units] ENABLED / DISABLED
Default value DISABLED
Step
Description
The setting ENABLED disables all engine protections. They are just displayed on alarm list and recorded to
historry, but they have no influence to running engine. The setting ENABLEDis indicated in tha alarm list as
warning SdOverride Act and recorded to history as record SdOverride Act.
Day hrs
Value group Statistics Related FW 1.0.2
Resolution [units] 0.1 hour
Description
Counts the number of engine running hours. It is reseted by LBIClear DayStat together with statistics value
DayCons.
Regulator Request 2 0 *
Regulator Reg Gain 10 % *
LoadLimit LoadRequest 1 90 *
LoadLimit LoadRequest 2 80 *
LoadLimit LoadDnLimit 0 *
LoadLimit Load Gain 10 % *
LoadLimit LoadLimitAout *
Engine Values RPM * * *
Statistics NextServTime * * *
Statistics E-Stop *
Statistics ShutDown *
Statistics DayCons * * *
Statistics TripCons * * *
Statistics Total 1 *
Statistics Total 2 *
Analog CU Ubat * * *
Analog CU D+ * * *
Analog CU Oil Press * * *
Date/Time Date *
ID Info Engine state * * *
ID Info SW version * * *
ID Info Application * *
ID Info SW branch * *
ID Info PasswordDecode * *