S/E GIS Giria Appr.: EM HP GIS PE ENS MEN/ Dr. Niederkorn Sheet: 1
8DN9 230kV Date: 18.01.2016 E50115-B0162-R102
GRAPHICS
GENERAL DEFINITION
DEFINITION OF LOADS ORIENTATION OF FORCES
LC1 Dead load AND MOMENTS
LC2 Load by thermal expansion X
LC3 Static conductor tension Mx
LC4 Windload X-direction Fx
LC5 Windload Y-direction
LC6 Short-circuit forces
Fy
LC7 Switching forces
Fz
LC8 Earthquake load X-direction
My Y
Directions: X, Y, Z
LC9 Earthquake load Y-direction Mz Forces: Fx,Fy,Fz
Moments: Mx,My,Mz
LC10 Earthquake load Z-direction Z
LOADCASES
If not otherwise specified, the following load combinations shall be used:
The loads shall be combined in the direction that produces the most severe mechanical stresses
at each foundation point.
NOTES
1. All loads are working loads without safety factors. For design loads safety factors shall be regarded.
2. All foundation loads are given as action loads and refer to top of foundation.
3. Loadtype LC2, LC4, LC5, LC7, LC8, LC9 and LC10 shall be considered with the same values
in opposite direction too.
4. Foundation loads for the circuit breaker (Loadpoints 101-104, 201-204) shall be considered
to act with an eccentricity of 175 mm above fastening level (Z-direction).
EARTHQUAKE LOAD
Earthquake Data see Dwg.-No.: (4) E50115-B0162-R104
Acceleration at center of gravity: horizontal 2.625 g vertical 1.837 g
WIND LOAD
Max. wind pressure: 950 N/m corresponding to wind velocity 140 km/h
SWITCHGEAR OVERVIEW
Isometric
NUMBERING OF LOADPOINTS
Node Numbering In Z-direction
201 203
202 204
101 103
102 104
Z X
Y
1000.00 [mm]
PDVSA Author: EM HP GIS PE ENS MEN/ Alzner P-014982 Page: 3/5
S/E GIS Giria Appr.: EM HP GIS PE ENS MEN/ Dr. Niederkorn Sheet: 1
8DN9 230kV Date: 18.01.2016 E50115-B0162-R102
RESUL T S