Electrical Service and Equipment for Irrigation
NOTE: ASAE Standards, Engineering Practices, and Data are informational and advisory
only. Their use by anyone engaged in industry or trade is entirely voluntary. The ASAE
assumes no responsibility for results attributable to the application of these ASAE
Standards, Engineering Practices, and Data. Conformity does not ensure compliance with
applicable ordinances, laws and regulations. Prospective users are responsible for
protecting themselves against liability for infringement of patents.
This standard may be designated ANSI/ASAE. If so, this standard is an American National
Standard. Approval of an American National Standard requires verification by ANSI that the
requirements for due process, consensus, and other criteria for approval have been met by
the standards developer.
Consensus is established when, in the judgment of the ANSI Board of Standards Review,
substantial agreement has been reached by directly and materially affected interests.
Substantial agreement means much more than a simple majority, but not necessarily
unanimity. Consensus requires that all views and objections be considered, and that a
concerted effort be made toward their resolution.
CAUTION NOTICE: In the case that this standard is an ANSI/ASAE standard, this American
National Standard may be revised or withdrawn at any time. The procedures of the
American National Standards Institute require that action be taken periodically to reaffirm,
revise, or withdraw this standard. Purchasers of American National Standards may receive
current information on all standards by calling or writing the American National Standards
Institute.
Proposed by the Nebraska Inter-Industry Electrical Council and The Canadian Electrical Code, for voltages greater than 150 V. Location of
Irrigation Association; reviewed by the ASAE Soil and Water Division enclosures, motors, and irrigation piping is important in maintaining
Standards Committee; approved by the Electric Power and Processing proper access.
Division Standards Committee; adopted by ASAE as a Tentative 3.4 Support. Electrical installations shall be designed and constructed to
Standard December 1978; reconfirmed December 1979, December provide adequate support and protection for equipment and services.
1980, December 1981, December 1982, December 1983, December
1984; reclassified as a full Standard and revised December 1985; revised 3.5 Before purchasing and installing electrical equipment, determine the
editorially July 1989; reconfirmed December 1990; revised December type of electrical service which will be supplied. Figures 17 show the
1992; approved as an American National Standard February 1993; proper equipment to go with each specified service. Canadian Electrical
reaffirmed by ASAE December 1997; reaffirmed by ANSI November Code does not permit service as shown in figures 3, 4, and 7.
1998, February 2003; reaffirmed by ASAE February 2003.
4 Circuit disconnecting means
1 Purpose and scope 4.1 Circuit disconnecting means shall be a fused safety switch, not a
circuit breaker.
1.1 The purpose of this Standard is to provide a common document for
use by all those involved in electrical irrigation systems; such as 4.1.1 ANSI/NFPA 70 and Canadian Electrical Code permit circuit
electricians, power suppliers, well drillers, irrigation dealers and breakers. Because of infrequent operation, breakers may be adversely
manufacturers, extension specialists and irrigators. affected by dust and moisture. Therefore, a fused switch is required for
more positive fault protection.
1.2 This Standard applies to three-phase, 240 V, or 480 V service, the
most commonly used irrigation service voltages for irrigation pump 4.2 Disconnecting means shall be four-wire, three-pole, solid neutral,
motors, irrigation machines, and auxiliary equipment. This Standard is in horsepower rated and rated as service equipment.
accordance with ANSI/NFPA 70, and the 14th edition of Canadian 4.2.1 Three fuses shall be used when service has all ungrounded phase
Electrical Code, Part I-1990, where applicable (see C22.1-1990). All conductors (see figures 1, 2, 4, and 6). Two fuses shall be used when
materials shall conform to Article 100 of ANSI/NFPA 70, and in Canada service has a grounded phase (see figures 3, 4, and 7).
shall conform to Section 2-024 of Canadian Electrical Code.
2 Normative references
The following standards contain provisions which, through reference in
this text, constitute provisions of this Standard. At the time of publication,
the editions indicated were valid. All standards are subject to revision,
and parties to agreements based on this Standard are encouraged to
investigate the possibility of applying the most recent editions of the
standards indicated below. Standards organizations maintain registers of
currently valid standards.
ANSI/ASAE S318.10 DEC92, Safety for Agricultural Equipment
ANSI/ASAE S362.2 DEC92, Wiring and Equipment for Electrically Driven
or Controlled Irrigation Machines
ANSI/ASAE S493 DEC92, Guarding for Agricultural Equipment
ANSI/NEMA ICS 6-1983, Enclosures for Industrial Control and Systems
ANSI/NEMA MG 1-1978, Motors and Generators
ANSI/NEMA 250-1985, Enclosures for Electrical Equipment
ANSI/NFPA 70-1990, National Electrical Code
CSA C22.1-1990, Canadian Electrical Code
NEMA ICS 2-449-1978, AC Automatic Combination Irrigation Pump
Controllers
Figure 3 Recommended equipment and grounding for a corner-grounded, Figure 5 Recommended equipment and grounding for open-delta, center-
delta transformer secondary connections tapped transformer secondary connections
Class
for
Motor rated not motor
over 40 C or starting Dual-
not less than All other inrush element Non- aTHW (75 C)
1.15 S.F. motors Switch or and fuse Switch or time Switch or bTHWN (75 C)
Ampere (max. fuse (max. fuse fuseholder code (time fuseholder delay fuseholder NEMA cTHHN (90 C)
Kilowatts Horsepower rating 125%) 115%) size letter delay) size fuse size size dXHBH (90 C) In.
*Equipment in general use is made primarily for connection to copper wire. Wire size shown does not compensate for voltage drop (from table 310-16 ANSI/NFPA 70).
Rigid metal, intermediate grade, and electrical metallic conduit are not approved for direct burial unless corrosive protection is provided. Galvanized rigid metal conduit
and rigid nonmetallic conduit are recommended for direct burial.
Minimum
Dual-element fuse for Branch circuit protection size of Minimum
motor overload protection (short-circuit protection only) Minimum copper size of
(These fuses also provide (These fuses do not give size of wire* trade
Size of motor branch circuit protection.) motor overload protection.) starter AWG or MCM conduit
Class
for
Motor rated motor
not over 40 C starting Dual-
or not less than All other inrush element Non- aTHW (75 C)
1.15 S.F. motors Switch or and fuse Switch or time Switch or bTHWN (75 C)
Ampere (max. fuse (max. fuse fuseholder code (time fuseholder delay fuseholder NEMA cTHHN (90 C)
Kilowatts Horsepower rating 125%) 115%) size letter delay) size fuse size size dXHBH (90 C) In.
1 15 30 25 30
3.7 5 7.6 9 8 30 2 15 30 20 30 0 14 a,b,c,d 1/2
34 15 30 15 30
1 20 30 35 60
5.6 7 1/2 11 12 12 30 2 20 30 30 30 1 14 a,b,c,d 1/2
3 20 30 25 30
4 20 30 20 30
1 20 30 45 60
7.5 10 14 17 1/2 15 30 2 20 30 35 60 1 12 a,b,c,d 1/2
3 20 30 30 30
4 20 30 25 30
1 30 30 70 100
11.2 15 21 25 20 30 2 30 30 60 60 2 10 a,b,c,d 1/2
3 30 30 45 60
4 30 30 35 60
1 40 60 90 100
14.9 20 27 30 30 60 2 40 60 70 100 2 8 a,d 3/4
3 40 60 60 60 8 b,c 1/2
4 40 60 45 60
1 50 60 110 200
18.7 25 34 40 35 60 2 50 60 90 100 2 8 a,d 3/4
3 50 60 70 100 8 b,c 1/2
4 50 60 60 60
1 60 60 125 200 6 a 1
22.4 30 40 50 45 60 2 60 60 100 100 3 6 b 3/4
3 60 60 80 100 8 c 1/2
4 60 60 60 60 8 d 3/4
Minimum
Dual-element fuse for Branch circuit protection size of Minimum
motor overload protection (short circuit protection only) Minimum copper size of
(These fuses also provide (These fuses do not give size of wire* trade
Size of motor branch circuit protection.) motor overload protection.) starter AWG or MCM conduit
Class
for
Motor rated motor
not over 40 C starting Dual-
or not less than All other inrush element Non- aTHW (75 C)
1.15 S.F. motors Switch or and fuse Switch or time Switch or bTHWN (75 C)
Ampere (max. fuse (max. fuse fuseholder code (time fuseholder delay fuseholder NEMA cTHHN (90 C)
Kilowatts Horsepower rating 125%) 115%) size letter delay) size fuse size size dXHBH (90 C) In.
1 400 400
149.2 200 240 300 250 400 2 400 400 600 600 5 350 a,b 2 1/2
3 400 400 500 600 300 c,d 2
4 400 400 400 400
*Equipment in general use is made primarily for connection to copper wire. Wire size shown does not compensate for voltage drop (from table 310-16 ANSI/NFPA 70).
Rigid metal, intermediate grade, and electrical metallic conduit are not approved for direct burial unless corrosive protection is provided. Galvanized rigid metal conduit
and rigid nonmetallic conduit are recommended for direct burial.
15.6.1 Protective structures. Structures may be closed or have open of the sun and from inclement weather. When possible, controls should
sides and function only as a shade. Structures should be removable to be mounted on a north wall with at least 25 mm (1 in.) of air space
facilitate service and repair of motor and well. between the control and the outside covering of the structure.
15.6.1.1 Size. Structures shall be large enough to allow servicing of the
motor and equipment from all sides. Clearances are specified in 3.3.
16 Main disconnecting means
15.6.1.2 Base. For a closed structure the base should be the same size
as the structure, constructed of concrete, and drained to the outside. For 16.1 Installation of a disconnecting means ahead of the main pump
a shade only, the base does not need to be the size of the shade. panel is recommended for safety and convenience. Many accessories
such as irrigation machines and fertilizer injectors are often added to
15.6.1.3 Ventilation. Cross ventilation of closed structures shall be todays irrigation systems. These accessories shall be connected to the
provided by doors or louvers. All doors shall have positive catches to service side of the pump motor disconnect and shall be provided with a
hold the door open. disconnecting means and overcurrent protection. These accessory
15.6.1.4 Control mounting. Controls should be protected from the heat disconnects can be installed and serviced simply if a main disconnecting
7.5 10 4 5 5 2 4 5
11.2 15 5 5 7.5 4 4 5
14.9 20 5 7.5 10 5 5 7.5
18.7 25 7.5 7.5 10 5 7.5 10
22.4 30 7.5 10 15 7.5 7.5 10
29.8 40 10 15 20 7.5 10 10
37.3 50 15 20 25 10 10 15
44.8 60 20 20 25 10 15 20
56.0 75 25 25 30 10 15 20
76.6 100 30 30 35 20 25 30
93.3 125 35 35 40 20 30 30
111.9 150 40 40 50 25 35 45
149.2 200 50 50 70 40 50 70
186.5 250 60 60 80 50 50 80
Figure 10 Recommended equipment and grounding for service to a phase
*For other voltages or motor speeds consult capacitor manufacturers literature. converter supplying an irrigation machine from 240 V single-phase
Check size of overload heaters when capacitors are installed (see 5.4.1). transformer secondary connections