You are on page 1of 10

ASAE S248.

3 MAR1976 (R2005)
Construction and Rating of Equipment for Drying Farm Crops

American Society of Agricultural Engineers

ASAE is a professional and technical organization, of members worldwide, who are


dedicated to advancement of engineering applicable to agricultural, food, and biological
systems. ASAE Standards are consensus documents developed and adopted by the
American Society of Agricultural Engineers to meet standardization needs within the scope
of the Society; principally agricultural field equipment, farmstead equipment, structures, soil
and water resource management, turf and landscape equipment, forest engineering, food
and process engineering, electric power applications, plant and animal environment, and
waste management.

NOTE: ASAE Standards, Engineering Practices, and Data are informational and advisory
only. Their use by anyone engaged in industry or trade is entirely voluntary. The ASAE
assumes no responsibility for results attributable to the application of these ASAE
Standards, Engineering Practices, and Data. Conformity does not ensure compliance with
applicable ordinances, laws and regulations. Prospective users are responsible for
protecting themselves against liability for infringement of patents.

This standard may be designated ANSI/ASAE. If so, this standard is an American National
Standard. Approval of an American National Standard requires verification by ANSI that the
requirements for due process, consensus, and other criteria for approval have been met by
the standards developer.
Consensus is established when, in the judgment of the ANSI Board of Standards Review,
substantial agreement has been reached by directly and materially affected interests.
Substantial agreement means much more than a simple majority, but not necessarily
unanimity. Consensus requires that all views and objections be considered, and that a
concerted effort be made toward their resolution.

CAUTION NOTICE: In the case that this standard is an ANSI/ASAE standard, this American
National Standard may be revised or withdrawn at any time. The procedures of the
American National Standards Institute require that action be taken periodically to reaffirm,
revise, or withdraw this standard. Purchasers of American National Standards may receive
current information on all standards by calling or writing the American National Standards
Institute.

Copyright American Society of Agricultural Engineers. All rights reserved.

ASAE-The Society for engineering in agricultural, food, and biological systems


2950 Niles Rd., St. Joseph, MI 49085-9659, USA ph. 269-429-0300, fax 269-429-3852,
hq@asae.org
ASAE S248.3 MAR1976 (R2005)

Construction and Rating of Equipment for Drying Farm


Crops

Developed and approved by the Crop Dryer Manufacturers Council of the 4.1.1 Combustible materials shall not be used in the construction of
Farm and Industrial Equipment Institute July 1962; subsequently dryers where that material will be subjected to sustained temperatures in
approved by the ASAE Electric Power and Processing Steering excess of 74 C (165 F).
Committee August 1962; adopted by ASAE as a Tentative Standard 4.1.2 Dryers designed for outdoor use shall be so constructed or
December 1962; revised editorially April 1964; revised and reclassified as anchored that they will safely withstand wind pressures or snow loads to
a full Standard December 1964; revised February 1971, March 1976; which they may be normally subjected.
reconfirmed December 1980, December 1981, December 1982;
reconfirmed by the Food and Process Engineering Institute Standards 4.1.3 Dryers shall be equipped with appropriate safety shields, guards,
Committee December 1987, December 1988, December 1989, and screens. Intake openings for drying air shall be equipped with not
December 1990, December 1991; reaffirmed December 1992, December greater than 13 mm (0.5 in.) screen openings which shall be readily
1993, December 1994, December 1995; reaffirmed January 2001, accessible for cleaning.
December 2001, February 2005; revised editorially February 2005. 4.1.4 Dryers of the direct-fired type shall have combustion-air intake
openings so located that foreign material is not likely to enter the
combustion chamber. Where that is not practical, such openings shall be
1 Purpose provided with a screen. Where foreign material is likely to enter the
1.1 This Standard is intended to promote uniformity and consistency in primary air to the burner, this intake should be screened. Such screens
the terms used to describe, rate and evaluate crop dryers, dryer shall be readily accessible for cleaning.
components, and crop dryer operation. 4.1.5 All dryers designed to recirculate a portion of the exhaust air shall
1.2 This Standard is intended to promote efficiency and safety in the employ an approved means of removing combustible material from the
design, construction, and use of heated-air crop dryers. air in the recirculation duct. In a direct-fired dryer using fuel oil or solid
fuels, a target plate or other effective means shall be used to minimize
1.3 This Standard gives minimum requirements. Where local codes are the possibility of burning materials entering the drying chamber.
more stringent, they should be followed.
4.1.6 Interior surfaces of all dryers shall be designed to facilitate
cleaning.
2 Scope 4.1.7 Access doors or openings shall be provided to permit inspection,
2.1 This Standard refers to equipment in which heated air or artificially cleaning, maintenance, and the effective use of extinguishers or hose
generated radiation is used to reduce the moisture content of grain, hay, streams in all parts of the dryer and connecting spouts or conveyors. All
and other farm crops. These units, hereinafter referred to as dryers, access doors which permit personnel entry shall be provided with
include the batch type units, continuous-flow type units, heated-air units hardware which will permit manual opening without tools from either side
and supplemental-heat units and fans. of access doors, except for access openings in spray dryers and cyclone-
type dryers where the use of inside hardware will interfere with the proper
2.2 Within the scope of this Standard a dryer shall be understood to operation of the dryer.
include the grain-holding compartment in which the product is confined
while being dried, together with its source of heat or radiation, fuel 4.1.8 All wiring shall comply with National Fire Protection Association
supply, fuel transmission system, burner, vaporizer, heat exchanger, air Standard NFPA No. 70, National Electrical Code (American National
moving device (AMD), control system, power source, materials handling Standard, C-1, National Electrical Code). Electric motors shall be
system, and AMD tube or other discharge ducts which are integral parts installed so that adequate ventilation is provided, in accordance with
of the basic dryer. NFPA No. 70, National Electrical Code.
4.1.9 Clearance requirements and means of venting furnaces shall be in
accordance with standard practice.
3 Compliance definitions NOTE: For provisions on clearances in venting, refer to: National
3.1 Compliance definitions. The accepted definitions of shall, Board of Fire Underwriters, National Building Code; National Fire
should, and approved, as included in this Standard, are: Protection Association, NFPA No. 90-A, Installation of Air Conditioning
and Ventilating Systems of Other Than Residence Type; NFPA No.
3.1.1 Shall is intended to indicate requirements.
211, Chimneys, Flues and Vents; Underwriters Laboratories, Inc. UL-
3.1.2 Should is intended to indicate recommendations, or that which is 731, Oil Fired Heaters, and UL-795, Commercial Industrial Gas
advised but not required. Heating Equipment.
3.1.3 Approved or approval refers to listing by a nationally 4.1.10 Provisions for expansion or contraction shall be provided if
recognized testing laboratory or agency. necessary to prevent damage.
4.1.11 Outside surface temperatures of dryer housing should be
maintained at less than 93 C (200 F) where adjacent to combustible
4 General construction material. Where insulating material is used, it shall be so installed that it
4.1 General. Dryers and related equipment shall be built with regard to will not absorb moisture.
the hazard inherent in the equipment operating at elevated temperatures,
4.2 Noise level. Consideration should be given to design factors
the hazard occasioned by overheating the product, the hazard of open
influencing noise emissions and every effort should be made to keep
flames, the hazard in incomplete combustion of direct-fired devices, the
noise levels at a minimum.
hazard to the operator from mechanical equipment and high
temperatures, and with regard to the promotion of safety and reliable
operation over the expected life of the equipment.

ASAE STANDARDS 2005 ASAE S248.3 MAR1976 R2005 561


4.2.1 Each manufacturer shall have available the sound power level 5.2.6.1.1.7 The pilot shall be proved before gas is admitted to the main
rating in decibels and shall make available octave sound power levels on burner.
request. 5.2.6.1.1.8 Flame response timing shall not exceed 90 seconds.
4.2.2 The sound power level rating shall be obtained from octave sound 5.2.6.1.2 Standing pilot. Pilot supervision is mandatory.
power levels measured in accordance with Air Moving and Conditioning
Association Standard AMCA 300-67, Test Code for Sound Rating Air 5.2.6.2 Direct spark ignition
Moving Devices. 5.2.6.2.1 If direct spark ignition is employed, it shall be suitably
4.3 Pollutant emission level. Consideration should be given to design interlocked to insure a pre-purge of at least 15 seconds or 4 complete air
factors influencing particulate emissions and every effort should be made changes of the plenum chamber and duct, prior to an ignition attempt.
to keep particulate emission levels at a minimum. Each manufacturer 5.2.6.2.2 The high voltage ignition spark shall ignite the main flame
shall have available the particulate emission level rating as soon as within 4 seconds after the gas reaches the main burner(s) parts.
reliable test standards are developed. 5.2.6.2.3 The trial for ignition of the main flame shall not exceed 90
seconds.
5 Heat-producing devices 5.2.6.2.4 Flame failure response timing shall not exceed 90 seconds.
5.1 General clearance requirements and means of venting furnaces 5.2.6.2.5 The ignition transformer shall not be energized until
shall be in accordance with standard practice. combustion air supply and circulating air flow is proved. Air flow sensing
NOTE: For provisions on clearances in venting, refer to: The National devices such as pressure switches, sail switches, and differential
Board of Fire Underwriters, National Building Code; National Fire switches shall be of the approved type.
Protection Association NFPA No. 90-A, Installation of Air Conditioning 5.2.6.2.6 Main flame supervision shall be located so as to prove ignition
and Ventilating Systems of Other Than Residence Type; NFPA No. across the entire face of the burner.
211, Chimneys, Flues and Vents; Underwriters Laboratories, Inc., UL-
5.2.7 The gas or vapor handling components shall have a working
731, Oil Fired Heaters, and UL-795, Commercial Industrial Gas
pressure rating in accordance with the following:
Heating Equipment.
5.2.7.1 For natural gas and liquid propane gas, twice the maximum
5.2 Gas-fired devices
available safety monitored supply pressure.
5.2.1 Gas burners shall be designed so that the normal function of the
5.2.7.2 For liquid propane systems, at least 1.72 MPa (250 psi) from
automatic gas-control valves cannot be manually bypassed.
point of supply connection to and including the pressure regulator
5.2.2 Gas burners and associated mixing equipment shall be suitable for downstream of the vaporizer.
the service intended as follows:
5.2.7.3 All components downstream from the vaporizer shall be
5.2.2.1 For heat content of the gas used. designed to withstand the maximum vapor temperature that is
5.2.2.2 For the operating pressures listed on nameplate. encountered with the system.
5.2.2.3 Capable of maintaining flame stability throughout the turn-down 5.3 Electrically heated devices. All types of heating devices that use
range. electrical energy for heat shall comply with the following requirements:
5.2.2.4 Designed with the required safety interlocks. 5.3.1 Induction or dielectric heating systems which employ
5.2.3 Approved methods of ignition shall be employed. high-frequency electrical energy may be used for dryers.
5.2.4 Electrical operation of the valves shall be of common 5.3.2 Infrared heating systems may be used for dryers.
characteristics of cycle, frequency and voltage. 5.3.2.1 Infrared lamps shall not be used where combustible dust may be
5.2.5 Gas-fired infrared generators may be used. Adequate clearances present or where accumulation of combustible dust may form on surfaces
shall be provided to assure safe surface temperatures for the product of the lamps.
being dried. 5.3.2.2 Infrared lamps of suitable focal length shall be used to assure
5.2.6 Methods of ignition of gas-fired devices safe surface temperatures for the product being dried. Instruction
concerning replacement of lamps should include necessary warning and
5.2.6.1 Pilots be a part of the permanent label.
5.2.6.1.1 Continuous and interruptible gas pilots 5.3.3 Resistance-type heating systems may be used for dryers.
5.2.6.1.1.1 If a continuous or interruptible pilot is employed, it shall be 5.3.4 All internal wiring of electrically heated devices shall conform to the
suitably interlocked to insure a pre-purge of at least 15 seconds or 4 requirements contained in NFPA No. 70, National Electrical Code.
complete air changes of the plenum chamber and duct prior to an ignition
attempt of the pilot. 5.4 LP-gas vaporizers and vaporizer-burners for direct-fired
application. The vaporizer section of vaporizer-burners used for dryers
5.2.6.1.1.2 Trial for ignition shall not exceed 90 seconds. shall be constructed as follows:
5.2.6.1.1.3 The construction of all safety pilots shall be such that in the 5.4.1 Vaporizer-burners shall have a minimum design pressure of 1.72
event of breakage or failure of the flame sensing device they shall fail MPa (250 psi) with a factor of safety of 5.
safe.
5.4.2 The vaporizer section shall be protected by a hydrostatic relief
5.2.6.1.1.4 The input to the pilot(s) shall not exceed 21.10 MJ/h (20 000 valve, located where it shall not be subjected to temperatures in excess
BTU/h) or 3 percent of the maximum input to the main burner as fired, of 60 C (140 F), and with a pressure setting such as to protect the
whichever is greater. components involved but not lower than 1.72 MPa (250 psi). The relief
5.2.6.1.1.5 Pilot burners not automatically lighted shall be fixed in place valve discharge shall be directed upward and away from the component
so that they can be safety lighted manually. parts of the vaporizer burners. Fusible plugs shall not be used.
5.2.6.1.1.6 Main flame supervision is mandatory where any part of the 5.4.3 A means shall be provided for manually turning off the gas to main
main burner is more than 0.91 m (3 ft) from the point of supervision of the burner and pilot.
pilot along the path of flame travel or run. Main flame supervision shall 5.4.4 Vaporizing-burners shall be provided with an automatic safety
also be required if the main flame cannot be observed from the point of device to shut off the flow of gas to the main burner and pilot in the event
manual start up. The main flame supervision is necessary with any pilot is extinguished. See Prevention of Fire and Dust Explosions in Grain
burner that can supply gas through a channel or part that is not
immediately adjacent to a proved pilot.

562 ASAE S248.3 MAR1976 R2005 ASAE STANDARDS 2005


Elevators and Bulk Grain Handling Facilities, NFPA No. 61B, for ignition 6.1.3.2.1 Fittings used with liquid LP-Gas, or with vapor LP-Gas at
and combustion controls applicable to vaporizing-burners associated with operating pressures over 0.86 MPa (125 psi) shall be suitable for a
grain dryers. working pressure of 1.72 MPa (250 psi).
5.4.5 Pressure regulating and control equipment shall be so protected as 6.1.3.2.2 Fittings for use with vapor LP-Gas at pressures not exceeding
not to be subject to temperatures above 60 C (140 F), unless it is 0.86 MPa (125 psi) shall be suitable for a working pressure of 0.86 MPa
designed and recommended for use by the manufacturer for a higher (125 psi).
temperature. 6.1.3.2.3 Soldering or brazing filler material shall have a melting point
5.4.6 Pressure regulating and control equipment located downstream of exceeding 538 C (1000 F).
the vaporizing section shall be designed to withstand the maximum 6.1.4 Installation of piping, tubing, and fittings
discharge temperature of the hot vapor.
6.1.4.1 LP-Gas normally is transferred into containers as a liquid, but
5.4.7 The vaporizer section of vaporizer-burners shall not be provided may also be conveyed as a liquid or vapor under container or lower
with fusible plugs. regulated pressure. Piping shall comply with the following:
5.4.8 Dryers utilizing vaporizing burners shall be equipped with 6.1.4.1.1 Vapor LP-Gas piping with operating pressures in excess of
automatic devices both upstream and downstream of the vaporizing 0.86 MPa (125 psi) and liquid LP-Gas piping shall be suitable for a
section. These devices shall be installed and connected to shut off in the working pressure of at least 1.72 MPa (250 psi).
event of excessive temperature, flame failure and if applicable,
insufficient air flow. 6.1.4.1.2 Vapor LP-Gas piping subject to pressures of not more than
0.86 MPa (125 psi) shall be suitable for a working pressure of at least
5.4.9 Vaporizing-burners shall not raise the fuel pressure above the 0.86 MPa (125 psi).
design pressure of the vaporizing section.
6.1.4.2 Pipe joints may be threaded, flanged, welded or brazed using
5.4.10 The vaporizing-burner or the appliance in which it is installed shall pipe and fittings complying with 6.1.1 and 6.1.3. Threaded joints,
be permanently and legibly marked with the maximum burner input J/h including joints threaded and back welded, shall comply with the
(BTU/h) and the name or symbol of the manufacturer. following:
6.1.4.2.1 For LP-Gas vapor at pressures in excess of 0.86 MPa (125 psi)
6 LP gas systems or LP-Gas liquid, Schedule 80 or heavier pipe or nipples shall be used.
6.1 Piping, tubing and fittings 6.1.4.2.2 For LP-Gas vapor at pressures of 0.86 MPa (125 psi) or less,
Schedule 40 or heavier pipe shall be used.
6.1.1 Pipe. Pipe shall be wrought iron or steel (black or galvanized),
brass or copper and shall comply with 6.1.1.1 through 6.1.1.4. 6.1.4.2.3 Welded joints shall be made with suitable types of welding
fittings or flanges for the service in which they are to be used and shall
6.1.1.1 Wrought iron pipe. ANSI B36.10, Wrought-Steel and Wrought- be at least Schedule 40 pipe.
Iron Pipe.
6.1.4.3 Tubing joints may be flared, soldered or brazed using tubing and
6.1.1.2 Steel pipe. ASTM A53, Specification for Welded and Seamless fittings, and solder or brazing material complying with 6.1.2 and 6.1.3.
Steel Pipe.
6.1.4.4 Piping in systems shall be run as directly as is practicable from
6.1.1.3 Brass pipe. ASTM B43, Specification for Seamless Red Brass one point to another, and with as few restrictions, such as ells and
Pipe, Standard Sizes. bends, as conditions will permit, giving consideration to provisions of 6.2.
6.1.1.4 Copper pipe. ASTM B42, Specification for Seamless Copper 6.1.4.5 Provision shall be made in piping including interconnecting of
Pipe, Standard Sizes. permanently installed containers, to compensate for expansion,
6.1.2 Tubing. Tubing shall be steel, brass or copper and shall comply contraction, jarring and vibration, and settling. Where necessary, flexible
with 6.1.2.1 through 6.1.2.3. connectors complying with 6.2 should be used.
6.1.2.1 Steel tubing. ASTM A539, Specification for Electric-Resistance- 6.2 Hose, hose connections and flexible connectors
Welded Coiled Steel Tubing for Gas and Fuel Oil Lines. 6.2.1 Hose, hose connections and flexible connectors shall be fabricated
6.1.2.2 Brass tubing. ASTM B135, Specification for Seamless Brass of materials resistant to the action of LP-Gas both as liquid and vapor. If
Tube. wire braid is used for reinforcement it shall be of corrosion resistant
6.1.2.3 Copper tubing material such as stainless steel.
6.1.2.3.1 Type K or L: ASTM B88, Specification for Seamless Copper 6.2.2 The correctness of design, construction and performance of hose
Water Tube. shall be determined by Underwriters Laboratories, Inc., their nationally
recognized testing laboratory or approval of authority having jurisdiction.
6.1.2.3.2 ASTM B280, Specification for Seamless Copper Tube for Air
Conditioning and Refrigerator Field Service. 6.2.3 Hose, hose connections, and flexible connectors used for
conveying LP-Gas liquid or vapor at pressures of 0.0345 MPa (5 psi)
6.1.3 Pipe and tubing fittings. Fittings shall be steel, brass, copper, shall comply with 6.2.3.1 and 6.2.3.2.
malleable iron or ductible (nodular) iron, and shall comply with 6.1.3.1
and 6.1.3.2. 6.2.3.1 Hose shall be designed for a minimum bursting pressure of
120.66 MPa (1750 psi) [2.41 MPa (350 psi) working pressure] and shall
6.1.3.1 Pipe joints in wrought iron, steel, brass or copper pipe may be be identified LP-Gas or LPG at not greater than 3 m (10 ft) intervals.
screwed, welded or brazed.
6.2.3.2 Hose assemblies after the application of connections shall be
6.1.3.1.1 Fitting used with liquid LP-Gas, or with vapor LP-Gas at capable of withstanding a test pressure of not less than 4.83 MPa (700
operating pressures over 0.86 MPa (125 psi) shall be suitable for working psi).
pressure of 1.72 MPa (250 psi).
6.2.4 Flexible connections used in piping systems shall comply with
6.1.3.1.2 Fittings used with vapor LP-Gas at pressures not exceeding 6.2.1, 6.2.2, and 6.2.3 for the service in which they are used and shall be
0.86 MPa (125 psi) shall be suitable for a working pressure of 0.86 MPa installed in accordance with manufacturers instructions. Flexible
(125 psi). connectors in lengths up to 914 mm (36 in.) may be used for liquid or
6.1.3.1.3 Soldering or brazing filler material shall have a melting point vapor piping, or portable or stationary tanks to compensate for
exceeding 538 C (1000 F). expansion, contraction, jarring and vibration, and settling. This is not to
6.1.3.2 Tubing joints in steel, brass or copper tubing shall be made with be construed to mean that flexible connectors shall be used if provisions
approved gas tubing fittings and may be flared, soldered or brazed. were incorporated in the design to compensate for these effects.

ASAE STANDARDS 2005 ASAE S248.3 MAR1976 R2005 563


6.2.5 Hose and hose connections subjected to regulated pressures not a device which proves air flow. Drum or rotary dryers which do not
greater than 0.345 MPa (5 psi) shall be designed for a bursting pressure employ air flow are exempt from this requirement.
of not less than 0.86 MPa (125 psi). 7.2.6 A maximum temperature thermostat shall be located between the
6.2.6 A shut-off valve shall be provided in the piping immediately heat producing device and the dryer or shall be located in the heat
upstream of the inlet connection of the hose. When more than one such producing device.
appliance shut off is located near another precautions shall be taken to 7.3 Minimum fire safety controls for heat producing devices
prevent operation of the wrong valve.
7.3.1 The circuitry shall be so designed that there will not be an
6.3 Relief valves automatic restart after an unsafe shutdown.
6.3.1 A hydrostatic relief valve shall be installed in each section of piping 7.3.2 All safety devices and safeguarding sequences shall be automatic
(including hose) in which liquid LP-Gas can be isolated between shut-off in operation following initial ignition of the pilot and main flame for
valves so as to relieve to a safe atmosphere the pressure which could devices burning liquid or gaseous fuel. Trial for ignition of main flame or
develop from the trapped liquid. The start-to-discharge pressure setting flame failure shall not exceed 90 seconds.
of such relief valves shall not be in excess of 3.45 MPa (500 psi).
7.3.3 The fuel supply to gas pilots shall be automatically shut off in the
6.3.2 Shut-off valves shall not be located between a safety relief device event the pilot is extinguished.
and the container, unless the arrangement is such that the relief device
capacity flow will be achieved through additional relief devices which 7.3.4 Circuitry for safety shut-off valves, combustion safeguards,
remain operative. pressure switches, maximum-temperature thermostats, electrical
interlocks, and other controls, shall be arranged to provide fail-safe
6.3.3 Relief shall be away from component parts of the equipment and operation.
operating personnel, and shall not terminate in or beneath any part of the
equipment if below 1.8 m (6 ft). 7.3.5 All electric power for the operation of the dryer and its controls
shall be supplied by the same source, or shall be interlocked to
6.3.4 Safety relief valves shall be so designed that the possibility of accomplish the same as a single circuit or feeder.
tampering will be minimized. Externally set or adjusted valves shall be
provided with an approved means of sealing the adjustment. 7.3.6 Pre-ventilation of the combustion chamber and dryer shall be
accomplished by a control installed on the heating device, for direct-fired
6.3.5 Fail safe automatic safety shut-off valve dryers employing gaseous fuels, which will prevent ignition and flow of
6.3.5.1 Two automatic safety shut-off valves shall be installed in series fuel before the fan has provided 4 air changes of the plenum chamber.
and wired in parallel if one fail-safe type is not used. 7.4 Manual controls for heat producing devices. In addition to the
6.3.5.2 On vaporizer-burners the fail-safe valve shall be installed up- automatic controls required, each installation using either gaseous or
stream of the vaporizer section. liquid fuels shall have a quick-acting, manually operable valve in the fuel
6.4 Testing. All piping, tubing and hose shall be tested after assembly supply line ahead of all dryer fuel equipment and outside any enclosures.
and proved free from leaks at not less than normal operating pressure. 7.5 Electrical control enclosures
7.5.1 Exposed control. All controls directly exposed to the elements
shall be of weather-resistant construction.
7 Control equipment 7.5.2 Housing of electrical controls
7.1 General. Control equipment shall be of such construction and design
7.5.2.1 All electrical controls not inherently of the weather-proof type
and so arranged that required conditions of safety for the operation of the
shall be enclosed in weather-resistant construction.
heat-producing device, the dryer, and the ventilating equipment used will
be maintained. 7.5.2.2 The control box shall provide for separation of the electrical
controls from all gas controls. Gas valves, strainers, reliefs, etc., shall not
7.2 Minimum fire-safety controls for dryers
be located in the electrical control box.
7.2.1 Automatic recycling-type control systems shall not be used.
Control systems shall be of the type that requires manual resetting after
shut-down for an unsafe condition. 8 Holding capacity of batch dryers
7.2.2 Dryers in which the dried product moves automatically from the 8.1 The holding capacity of a batch dryer shall be defined as the
dryer to the storage building shall have an approved maximum volumetric capacity of the structure containing the product to be dried
temperature thermostat located in the exhaust air stream, or other when the structure is filled to the normal operating level. It may be
approved device, which will prevent the transfer of fire from the dryer to expressed in m3 (bushels), based on 28.4 bushels/m3.
the storage building.
7.2.3 Dryers in which the dried product moves manually from the dryer
into a storage building should have one or more approved maximum 9 Basis for stating drying capacity of batch and
temperature thermostats located in the exhaust air stream, or other continuous-flow grain dryers
approved devices, which will prevent the transfer of fire from the dryer to 9.1 Drying capacity shall be stated as the number of wet bushels of grain
the storage building. The operation of these controls shall shut off all heat dried per hour, wet basis, using clean, yellow corn as the standard grain
being supplied to the dryer and should stop the movement of air through and shall include the following:
the dryer, interrupt the flow of the product into and away from the dryer; 9.1.1 Moisture reduction from 25.5 percent to 15.5 percent, or 20.5
and sound an audible alarm. percent to 15.5 percent.
7.2.4 Dryers of combustible construction or containing combustible trays 9.1.2 The drying air temperature used in rating the dryer shall be stated.
shall have a thermostat set to prevent the combustible material from Based on a 10 C (50 F) ambient, the rating temperature shall not
reaching sustained temperatures in excess of 74 C (165 F). Such exceed that at which the dryer will operate continuously without damage
controls shall shut off all heat being supplied to the dryer; shall permit the to grain or machine.
continued movement of unheated air through the dryer and shall sound
an audible alarm. 9.1.3 Inclusion of time to cool to 15.6 C (60 F) [i.e. within 5.6 C (10 F)
of ambient temperature].
7.2.5 A control device of suitable design shall be provided which will cut
off all heat being supplied to the dryer should the movement of air 9.1.4 Loading and unloading time shall not be included in the rating for
through the dryer be stopped. For AMD driven directly by electric motors, batch dryers. This shall be so stated in all published data.
this may be an electrical device at the motor, and in all other instances 9.1.5 Ratings of other grains shall be on a similar basis.

564 ASAE S248.3 MAR1976 R2005 ASAE STANDARDS 2005


10 Burner ratings 12.3 Motor loading
10.1 Direct fired LP and natural gas 12.3.1 The maximum load imposed on motors shall be such that the
temperature in the windings shall not exceed that permitted in NEMA
10.1.1 Maximum inlet gas pressure shall be stated on the nameplate.
standards. The motor horsepower loading shall not exceed the motor
10.1.2 The burner rating shall be indicated on the nameplate and in horsepower rating on nameplate multiplied by service factor.
descriptive material in joules (BTU) per hr input at rated manifold gas
12.3.2 For air-over applications, the motor nameplate shall clearly state
pressure with a specified orifice.
that air-over motor must be installed in air streams.
10.2 Convertible units (LP to natural)
12.4 Motor controls. Motor controls shall meet the requirements of
10.2.1 Natural gasLP vapor burner. On burners designed to burn NFPA No. 70, National Electrical Code.
either natural gas or LP vapor, the changing of the orifice shall constitute
12.4.1 Each motor shall be protected against running overcurrent
the only conversion necessary to switch from one gas supply to the
(overload) by one of the following means:
other.
12.4.1.1 A separate over-current (overload) device, such as
10.2.2 Natural gasliquid LP burners. Dryers utilizing liquid burners
dual-element fuses, adjustable or non-adjustable circuit breakers,
shall be designed so that the burner and fuel train assembly can be
thermal relays or thermal-trip motor switches which are responsive to
dismounted and a natural gas burner and fuel manifold be mounted
motor current shall be used. This device shall be rated or selected to trip
without major alterations to the remainder of the dryer.
at not more than 115 percent of the maximum-load current of the motor.
12.4.1.2 A thermal protector, integral with the motor, approved for use
11 Testing and rating of air moving devices (AMD) with the motor which it protects on the basis of service factor and
11.1 All air moving devices (AMD) used for crop drying or aeration shall prevention of dangerous over-heating of the motor due to overload or
be tested and rated in accordance with Air Moving and Conditioning failure to start shall be used. If the motor-current-interrupting device is
Association, Inc., Bulletin 210, Standard Test Code for Air Moving separate from the motor and its control circuit is operated by a protective
Devices. device integral with the motor, it shall be so arranged that the opening of
the control circuit will result in interruption of current to the motor.
11.2 Testing AMDs only. Only AMDs as equipped for production shall
be used in tests. AMDs intended for use as individual or separate units 12.4.2 Where devices other than dual element fuses are used for motor-
shall be tested and rated with all screens, guards, mounting structure, running overload protection, the minimum allowable number and location
etc., in place as equipped for operation. of over-current units, such as trip coils, relays, or thermal cutouts, shall
be as follows:
11.3 Testing AMDs for heated air units. AMDs intended for use in
heated air units shall be tested and rated with all screens, guards, fan 12.4.2.1 One in either ungrounded conductor to all single-phase motors.
tube extension, burner, plumbing, controls, and all other equipment which 12.4.2.2 One in each of the ungrounded conductors to all three-phase
comes in contact with the air stream, in place as used in operation. All motors.
optional equipment shall also be in normal operating arrangement. 12.4.3 Magnetic starter size shall be selected on the basis of maximum
11.4 Rating curves and charts on AMDs and heated-air units horsepower or ampere rating of the motor.
11.4.1 All rating curves shall show cfm air flow, static pressure, brake 12.4.4 Enclosures
horsepower, total and basic efficiency per AMCA Standard Test Bulletin 12.4.4.1 Controls located outdoors shall be in National Electrical
No. 210-67, and shall specify which regular and optional equipment was Manufacturers Association, Standard III or IV enclosures on NEMA
installed. I enclosures if mounted in a weatherproof housing or shelter.
11.4.2 All published performance charts shall show cfm air flow and 12.4.4.2 Controls attached to units and mounted in weatherproof
brake horsepower of each static pressure point shown. housing may be NEMA O open starters.
11.4.3 Ratings expressed on compliance certificates shall be as noted in 12.5 Electric wiring
Section 13.
12.5.1 Internal wiring. All conducting non-current-carrying material and
11.5 Log sheets. Log sheets are to be used in such form as to suit the enclosures attached to or part of the unit shall be electrically bonded
testing procedure, as long as they are in keeping with the code together and connected to the proper grounding conductor of the electric
requirements. supply system.
11.6 Test supervision. All AMDs and heated-air unit tests should be 12.5.2 Electric supply wiring and protective devices should comply with
supervised and certified by a registered engineer or recognized test NFPA Standard No. 70, National Electrical Code.
authority.
12.5.2.1 Wire, service entrance, and fusing shall be sized according to
maximum operating current of unit.
12 Electric motor ratings and applications 12.5.2.2 Voltage drop between motor and power meter should be limited
12.1 Motor types to 3 percent.
12.1.1 Single-phase motors shall be capacitor-start induction-run, 12.5.2.3 All units shall be grounded directly to service neutral through
capacitor-start capacitor-run, or repulsion-start induction-run on belted power cable: Single-phase, 120-v and 240-v, with 3-wire connections;
applications only. and three-phase with 4-wire connections.
12.1.2 Three-phase motors shall be squirrel cage induction motors. 12.6 Electronic generators on engine or tractor-driven units
12.2 Motor enclosures. The following motor enclosures, as approved 12.6.1 Generators shall be equipped with copper grounding wire or strip
by the National Electrical Manufacturers Association Standard, NEMA solidly bonded to generator frame and attached to copper ground rod by
MG 1, Motors and Generators, may be used: approved clamp or other fastener, with a suitable label or tag stating that
ground rod must be driven into ground when unit is operating. Grounding
12.2.1 Drip-proof, equipped with rodent screens. shall be in accordance with NFPA No. 70, National Electrical Code.
12.2.2 Totally enclosed non-ventilated. 12.6.2 When pre-wired electric outlets are provided on the generator,
12.2.3 Totally enclosed, fan-cooled. they shall be of the 3-wire, polarized type with ground connections.
12.2.4 Totally enclosed, air-over. 12.7 Motor nameplates
12.2.5 Dustproof or explosion-proof. 12.7.1 A nameplate shall be provided for each electric motor showing

ASAE STANDARDS 2005 ASAE S248.3 MAR1976 R2005 565


the following minimum data for the maximum loading to which the motor included on compliance certificates for all fans used with unheated air for
is subjected in the particular application: drying or aeration:
MAX RATE HP.......................................@ RPM....................................... MODEL...........................................
PHASE..........................CYCLES..........................VOLTS.......................... AMD RATING.......................................................CFM @ 1 IN. OR 2 IN.
AMPS ...................................@ FULL LOAD S. F. ................................... WC PRESSURE AT DISCHARGE
MOTOR RATINGS FOR AIRSTREAM RATED SPEED..................RPM
APPLICATION ONLY* ........................................................................... AMD BRAKE HP MAX: HP FROM 0 IN. TO................................IN. WC
..................................................................................................................... TOTAL ELECTRICAL POWER REQUIREMENT .......................KW MAX
....................AMP MAX AT....................VOLTS MAX
*Where applicable fill in type of application (airstream onlyintermittent duty).

13.5 Motor nameplates. Nameplate data as specified in paragraph 12.7


13 Compliance certificates shall appear for each motor used on drying and aeration equipment. This
13.1 Compliance certificates shall be applied only by the original data may be included with the compliance certification data, or may be
equipment manufacturer. When a certificate of compliance is displayed attached separately to each motor in a location clearly visible to the
on a crop dryer or AMD, information specified in paragraphs 13.2 through operator.
13.5 shall be included. Data may be in the form of decals, metal plates, 13.6 Instructions. Manufacturers whose equipment bears a compliance
or other suitable materials. Size, color, etc., shall be established by the certificate shall provide printed instructions for installation and operation
manufacturer. Arrangement of data shall be as shown in paragraphs of units.
13.2, 13.3, and 13.4.
13.2 Data for batch and continuous-flow dryers. The following 14 Installation recommendations
minimum data shall be included with compliance certificates for batch or
14.1 Fuel supplies and electrical connections, up to the point of
continuous-flow dryers as applicable:
connection with the dryer where applicable shall comply with the
MODEL...............................................TYPE............................................... following standards of the National Fire Protection Association:
GRAIN HOLDING CAPACITY....................CU FT....................BUSHELS NFPA NO. 31, Standard for the Installation of Oil Burning Equipment.
TYPE OF FUEL .......................................................................................... NFPA No. 54, Standard for the Installation of Gas Appliances and Gas
BURNER RATING...............................................................BTU/HR MAX, Piping.
NFPA No. 58, Standard for the Storage and Handling of Liquified
OR..........................................................................GAS FUEL/HR MAX
Petroleum Gases.
OR: .............................................GAS FUEL/HR AT 200 F TEMP RISE NFPA No. 70, National Electrical Code.
FAN RATING ..........................................CFM AT 2 IN. WC PRESSURE 14.2 The fuel line from the natural gas meter to the fuel train inlet of the
IN PLENUM dryer shall be sized and installed to meet American National Standard,
RATED FAN SPEED ..........................................................................RPM Z83.1, Installation of Gas Piping and Gas Equipment on Industrial
BRAKE HORSEPOWER REQUIREMENTS AT RATED Premises and Certain Other Premises.
SPEED:
MAX AMD ONLY...........................................................................HP Appendix A
MAX CONVEYOR SYSTEM .........................................................HP A.1 Definitions are intended to relate only to this Standard and its
application:
TOTAL MAX ..................................................................................HP Air-moving device (AMD): A revolving, wheel-type, mechanical
TOTAL ELECTRICAL POWER device used to move air for drying or aeration. For the purposes of
this Standard, an AMD shall include the wheel or blade assembly,
REQUIREMENTS ............................................................KW MAX mounting structure and casing, but may or may not include a power
.............................AMP MAX AT .............................VOLTS source.
Aeration: The purposeful movement of air at a low rate through a
13.3 Data for heated-air units and supplemental-heat units. The product to maintain or improve product quality. Air flow rates usually
following minimum data shall be included with compliance certificates for do not exceed 0.08 cubic meters per minute per cubic meter of
heated-air units as applicable. Where burners and AMD units are product (0.1 cubic feet per minute per bushel of product) through a dry
furnished separately, individual certificates shall be applied to each and product and 0.80 cubic meters per minute per cubic meter of product
shall include only the appropriate data. (1 cubic foot per minute per bushel of product) through a wet product.
Ambient temperature: The temperature of the surrounding air.
MODEL...........................................
Approved: The use of approved or approved-type refers to listing
TYPE OF FUEL .......................................................................................... by a recognized testing agency or laboratory.
BURNER RATING.........................................BTU/HR MAX FUEL INPUT Available heat: In drying a harvested crop, the quantity of heat in air
OR: ...........................................................................GAS FUEL/HR MAX that can be utilized in evaporating water from the product.
AMD RATING......................................................CFM AT 1 IN. OR 2 IN. Batch: A quantity of a harvested crop put into a bin or container on
WC PRESSURE AT DISCHARGE a repetitive basis specifically for treatment, such as drying.
RATED FAN SPEED.............RPM Blending: The process of mixing two or more different products
AMD BRAKE HP MAX: HP FROM 0 IN. WC TO ........................IN. WC together, such as grains and supplements, to obtain desired food
ratios, or the process of mixing different quantities of the same
TOTAL ELECTRICAL POWER REQUIREMENT .......................KW MAX product with different moisture contents to obtain a final mass with a
....................................AMP MAX AT....................................VOLTS MAX uniform moisture content.
13.4 Data for drying and aeration AMDs. The following data shall be Bushel:

566 ASAE S248.3 MAR1976 R2005 ASAE STANDARDS 2005


One bushel by volume equals to 1.25 cubic feet. Dryer, counter-flow: A type of continuous-flow dryer wherein the
One dry bushel is that weight of grain defined by government product being dried moves in one direction and the drying air moves
grain standards as a standard unit for trading at a specific mois- in the opposite direction.
ture (e.g. 56 pounds at 15.5 percent w. b. for No. 2 corn). Dryer, cross-flow: A type of dryer wherein the flow of air is trans-
A wet bushel is the weight of wet grain which when dried will give verse to the direction of flow of the product being dried.
one dried bushel as specified in paragraph above (e.g. 63.5 lb of Dryer, direct-fired: Type of dryer in which the products of combustion
25.5 percent w. b. corn). come into direct contact with the product being dried.
Casing: The outer enclosure surrounding the entire heat exchanger Dryer, fluidized or spouted bed: A dryer where the product is in
and confining the air being heated. suspension, or is moved through the dryer by the drying and/or the
Combustible material: Combustible refers to a material or structure cooling air.
which can burn. Combustible is a relative term. Many materials which Dryer, indirect-fired: Type of dryer in which the products of combus-
will burn under one set of conditions will not burn under other. For tion do not come in contact with the products being dried.
example, structural steel is not combustible, but fine steel wool is Dryer, in-storage: A dryer in which the drying bin or compartment is
combustible. The term combustible is not related to any specific igni- also used to store the product after it is dried.
tion temperature.
Dryer, self-contained: Any dryer manufactured as a package unit
Conduction: Transmission through or by means of a conductor, consisting of the drying and cooling chamber, necessary heat or
distinguished in the case of heat from convection and radiation. radiation source, all AMDs and duct work, along with the necessary
Control: Any component of a dryer, or dryer heat source, so designed controls and product handling equipment. These dryers may be either
to affect or limit any normal or abnormal condition of the drying fixed or portable.
operation. Dryer, tunnel: A type of dryer wherein the product being dried is
Convection: Transference of heat or electricity by moving masses of conveyed through a tunnel-like chamber. It may be continuous or
matter, as by currents in gases and liquids caused by differences in batch-type.
density, or by electrically charged particles across a spark gap. Drying: The removal of moisture from a product, usually to some
Cooling stage: The time required to move a cooling zone entirely predetermined moisture content.
through a product mass. Drying air: The air being passed through the product which is being
Cooling zone: That portion of the product mass in storage where the dried.
product temperature of the crop is falling during aeration. Drying air temperature: The temperature of the air entering the
Cubic meters per minute (CFM): Volumetric measure of quantity of product being dried.
flow. (CFM is the most common customary measure.) Drying front: The divisional layer between the dried and undried
Curing: A form of conditioning as opposed to simple drying in which products in drying systems.
a chemical change occurs, such as in tobacco, sweet potatoes, etc., Drying time maximum permissible: The maximum elapsed time that
to prepare the crop for storage or use. may be used to complete the drying of any portion of the product
Cycling burner: Type of operation wherein application of maximum without undesirable change in quality.
heat is periodic such as cycling between high fire and low fire, cycling Drying zone: The band or layer of product in which most of the drying
between high fire and a constant pilot; and cycling from high fire to is occurring at any instant.
off, then restarted to high fire by constant or intermittent ignition.
Electrical induction: Act or process by which an electric conductor
Dehydration: The rapid removal of moisture, usually to a very low becomes electrified when near a charged body.
level.
Equilibrium moisture content: The moisture content of a product
Depth factor (Df): When drying with air, a depth which would contain when it is in equilibrium with the surrounding atmosphere.
enough product that, if all the theoretical heat available for drying
could be used, it would all dry to equilibrium in a period of time equal Equilibrium relative humidity: The relative humidity of air
to the time required for the fully exposed product to dry half-way to surrounding a product in equilibrium with a given moisture content.
equilibrium. The air and product are at the same temperature.
Dryer: A unit which provides the conditions for removing moisture Fail-safe control: A control designed so that a malfunction of any of
from a product. its components will stop the operation of the device or equipment
controlled by it.
Dryer, batch: Any dryer wherein the product to be dried is placed in
the dryer, the complete drying or drying and cooling operation Fuel train: The fuel train, mounted on the grain dryer structure and
performed, and then removed for storage or further processing. connected to the gas burner, includes all piping components of fuel
Usually it is self-contained comprising a drying compartment, either flow control and safety shut-off valves.
horizontal or vertical, to contain the product being dried while heated Heat exchanger: A device used to transfer heat from one fluid stream
air is forced or drawn through it from a central portion usually called to another without intermixing.
a plenum chamber. Cooling is usually carried out in the same manner. Heating-air drying: Use of forced ventilation with the addition of heat
Integral conveying equipment provides for loading and unloading the for removing moisture.
dryer. Also included are the AMD, burner, and control system. Batch
Heated-air unit: Basic heated-air-producing unit including AMD,
dryers are usually portable, but may be stationary.
burner system, and electrical system. It is usually coupled to drying
Dryer, circulating: A batch dryer equipped to circulate or mix the structure by means of a flexible duct. It may have transport chassis
product during the drying and cooling period. and wheels for portability.
Dryer, concurrent flow: A type of continuous flow dryer wherein the Insulating fitting: A type of fitting designed to prevent galvanic
product being dried moves in the same direction as drying air. Some- current flow when used between two dissimilar metals.
times referred to as parallel flow.
Joule (BTU): A measure of quantity of heat. One joule will raise the
Dryer, continuous-flow: Any dryer wherein the product to be dried is temperature of one gram of water one degree Celsius. (One BTU will
in continuous movement through the dryer and air movement is raise the temperature of one pound of water one degree Fahrenheit.)
continuous, in contrast to batch operation.
Line pressure: The pressure of the fuel in the supply line to the dryer.

ASAE STANDARDS 2005 ASAE S248.3 MAR1976 R2005 567


LP-gas: A mixture of gaseous petroleum products normally stored quantity of water vapor which the same volume of air could hold at the
and transported as a liquid under pressure. The principal constituents same temperature.
are propane and butane. Static pressure: A measure of air pressure usually expressed in
Modulate (as applied to crop drying in reference to regulation of pascals [inches of water column (WC)].
fuel in continuous flow): Automatically governing the rate of fuel Steady state: Condition when the operation or process reaches equi-
flow by a control which is temperature-sensitive in order to maintain a librium.
constant temperature at the location of the sensing device.
Suction system: Method of air movement in which the air is moved
Moisture content (dry basis): For products, expressed as through the product with the air duct or ducts at a pressure lower than
percentage, by weight, of water in the product divided by dry matter. atmospheric. It is also called an exhaust system of air movement.
weight of water in product Supervision: Continuous monitoring to react automatically to flame
Moisture content, percent=(100) failure so as to shut off gas flow to the unit.
weight of dry matter
Supplemental heat: Any heat added to that already present in the
Moisture content (wet basis): For agricultural producers, usually atmosphere to obtain a limited temperature rise, usually less than
expressed as percentage, by weight, of water in the product, wet 11 C (20 F), to accomplish drying within the maximum permissible
basis. drying time to prevent spoilage.
Temperature rise: As applied to crop drying, the term refers to the
weight of water in product difference between ambient temperature and the temperature of the
Moisture content, percent=(100)
weight of dry matter+water drying air resulting from the addition of heat by the dryer burner.
Tempering: Equilization of moisture or temperature throughout the
Natural gas: A gaseous hydrocarbon, odorless and flammable, found
product. Bringing a product to a desired moisture content or tempera-
in its natural state in particular geologic formation as a product of
ture for processing.
decomposition of organic matter. The composition is chiefly of the
methane series with varying amounts of other components such as Time of drying: The elapsed time from the start of the drying process
carbon dioxide, hydrogen, and helium often being present. to the instant the drying front arrives at any point or place in the
product.
Orifice: The opening through which gas is admitted to the burner.
Time of one-half response: Time required to dry fully exposed prod-
Pascal (psipounds per square inch or inches of water column):
ucts halfway to equilibrium.
A measure of pressure or stress. Assumed to be gage pressure
unless followed by the term absolute. Turning: The process of moving a product through the air within a bin
or storage structure, or from one bin or storage structure to another.
Pilot-continuous: The pilot remains lit during the time power is
supplied to the burner. Valve, excess-flow: A check valve which permits flow of fluid in
either direction but which limits excessive flow in one direction. If the
Pilot-interruptible: The pilot is lit during the time combustion is being
designated flow rate is exceeded, the valve automatically closes.
established. When combustion is established the pilot is deenergized.
Valve, pressure-relief: A valve designated as a safety device to
Pilot-standing: The pilot is manually lit and remains lit until manually
open, and remain open, to discharge a fluid whenever the fluid pres-
shut off.
sure reaches the start-to-discharge setting of the valve. When the fluid
Plenum: An air chamber maintained under pressure (positive or pressure drops below this setting, the relief valve automatically closes.
negative) usually connected to one or more distributing ducts in a
Valve, quick-acting: A manually operated valve specially designed to
drying or aeration system. The term is also used to designate the air
accomplish rapid shut-off to fuel flow to dryer.
chamber under the perforated floor in a grain bin and the pressure
chamber between grain columns in some types of batch or continuous Valve, solenoid: A valve which is opened or closed by a solenoid
dryers. (electromagnet). In the normally closed type, for example, the valve is
opened by the solenoid but closed by a return spring and held closed
Pressure regulator: A mechanical device which reduces the fluid
by the fluid pressure upstream from the valve.
(liquid or gas) pressure to a relatively constant delivery pressure while
the inlet pressure may vary and while the volume of gas may also Vapor pressure (fuel): Commonly taken to mean saturated vapor
vary. pressure which is the vapor pressure of a vapor in contact with its
liquid form. An example is the pressure in an LP-gas storage tank.
Pressure system: Method of air movement in which air is forced
The term is also used for the pressure of the vaporized fuel being fed
through the product with the air duct or ducts at a pressure above
to the burner orifice.
atmospheric pressure. It is called a pushing or forcing system of air
movement. Vaporizer: In an LP-gas system, the vaporizer is a heat exchanger
wherein heat is supplied to change the liquid fuel to vapor, ready for
Pre-ventilation: As applied to crop dryers, the term refers to clearing
combustion. The vaporizer may be integral with the burner so that part
or purging the plenum chamber or duct of any volatile gases prior to
of the heat of combustion is used for vaporization.
ignition of the burner. It is usually accomplished by a device which
insures that the fan must operate for a certain period of time before Vaporizer-burner: An integral vaporizer-burner unit, dependent upon
ignition will be permitted. the heat generated by the burner as the source of heat to vaporize the
liquid fuel.
Radiation: The process by which energy is emitted from molecules
and atoms owing to the internal changes. Also the combined Velocity of air flow for conditioning:
processes of emission, transmission, and absorption of radiant Apparent velocity in meters per minute (feet per minute): The
energy. rate of air flow determined by dividing the quantity of air flow in cfm
Recirculation: As applied to crop dryers, the term refers to the return by the cross-sectional area.
of a portion of the exhaust air to the air intake of the dryer, or to the Average velocity: The rate of air travel through product void
return of underdried grain to the dryer or container from which it was space. It is determined by dividing the apparent velocity by the
removed. product void space expressed as a decimal. The average velocity is
Relative humidity: A measure of the moisture content of air always greater than the apparent velocity.
expressed as a percentage. It is the ratio of the weight of water vapor Traverse time: The in-product travel time of air from entrance to
in a given volume of air at a given temperature to the maximum any point, usually expressed in seconds.

568 ASAE S248.3 MAR1976 R2005 ASAE STANDARDS 2005


Ventilation: Air movement through space. ASTM A53, Specification for Welded and Seamless Steel Pipe
Ventilation front: The locus of all points of equal traverse time in ASTM A539, Specification for Electric Resistance-Welded Coiled Steel
the product being conditioned. Tubing for Gas and Fuel Oil Lines
Void space: The space between particles in a bulk of stored crop, ASTM B42, Specification for Seamless Copper Pipe, Standard Size
usually expressed as percent of total volume. ASTM B43, Specification for Seamless Red Brass Pipe, Standard Sizes
Weatherproof: So constructed or protected that exposure to the ASTM B88, Specification for Seamless Copper Water Tube
weather will not interfere with safe operation. ASTM B135, Specification for Seamless Brass Tube
A.2 A partial list of testing laboratories of agencies follows: ASTM B280, Specifications for Seamless Copper Tube for Air Condi-
tioning and Refrigerator Field Service
A.2.1 All testing laboratories approved by Air Moving and Conditioning
NBFU, National Building Code
Association, Inc., 205 West Touhy Avenue, Park Ridge, Illinois
60068. NEMA MG1, Motors and Generators
NFPA No. 31, Standard for Installation of Oil Burning Equipment
A.2.2 Canadian Standards Association, 235 Montreal Road, Ottawa 7,
NFPA No. 54, Standard for Installation of Gas Appliances and Gas
Ontario, Canada.
Piping
A.2.3 Factory Mutual Engineering Corporation, 1151 Boston-Providence NFPA No. 58, Storage and Handling of Liquified Petroleum Gases
Turnpike, Norwood, Massachusetts 02062.
NFPA No. 61B, Prevention of Fire and Dust Explosions in Grain Eleva-
A.2.4 Underwriters Laboratories, Inc., 207 E. Ohio St., Chicago, Illinois tors and Bulk Grain Handling Facilities
60611. NFPA No. 70, National Electrical Code
Cited Standards: NFPA No. 90A, Installation of Air Conditioning and Ventilating Systems of
Other than Residence Type
AMCA 210.67, Standard Test Code for Air Moving Devices NFPA No. 211, Chimneys, Flues and Vents
AMCA 300-67, Test Code for Sound Rating Air Moving Devices UL 731, Oil Fired Heaters
ANSI B36.10, Wrought-Steel and Wrought-Iron Pipe UL 795, Commercial Industrial Gas Heating Equipment
ANSI Z83.1, Installation of Gas Piping and Gas Equipment on Industrial
Premises and Certain Other Premises

ASAE STANDARDS 2005 ASAE S248.3 MAR1976 R2005 569

You might also like