GENERAL SITE PREPARATION AND FOUNDATIONS CONCRETE CONCRETE MASONRY

1. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH 1. STRIP TOP SOIL TO THE RELATIVE LEVELS SHOWN ON THE 1. ALL WORKMANSHIP AND MATERIAL SHALL BE IN 1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN
ALL OTHER CONSULTANTS' DRAWINGS AND ARCHITECTS DRAWINGS. THE EXPOSED AREA SHALL THEN ACCORDANCE WITH AS 3600-2009. ALL FORMWORK SHALL ACCORDANCE WITH AS 3700-2011.
SPECIFICATIONS. ALL DISCREPANCIES SHALL BE BE PROOF ROLLED TO ENSURE THAT NO LOCAL SOFT BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH 2. ALL CONCRETE MASONRY BLOCKS SHALL HAVE A
REFERRED TO THE DESIGNER/ENGINEER BEFORE SPOTS EXIST. AS 3610-1995. CHARACTERISTIC UNCONFINED COMPRESSIVE STRENGTH
PROCEEDING WITH THE WORK. 2. CONTROLLED FILL UNDER BUILDINGS SHALL CONSIST OF 2. MINIMUM COVER TO REINFORCEMENT TO BE AS FOLLOWS OF 15MPa.
2. ALL DIMENSIONS RELEVANT TO SETTING OUT AND SAND (WITH LESS THAN 15% RETAINED ON THE 75 MICRON U.N.O. ON THE DRAWINGS. 3. MORTAR FOR BLOCKWORK SHALL BE OF CLASSIFICATION
OFF-SITE WORK SHALL BE VERIFIED BY THE CONTRACTOR SIEVE) PLACED AND COMPACTED FOR ITS ENTIRE DEPTH FOOTINGS 50mm M3 ABOVE GROUND & M4 BELOW GROUND.
BEFORE CONSTRUCTION IS COMMENCED. THE ENGINEER'S TO A DENSITY INDEX OF MORE THAN 65% ACCORDING TO EXTERNAL GROUND SLABS 40mm 4. MINIMUM 28 DAY COMPRESSIVE STRENGTH OF
DRAWINGS SHALL NOT BE SCALED. AS 1289. ALTERNATIVELY, FOR FILL UP TO 800mm DEEP, A INTERNAL GROUND SLABS COREFILLING GROUT SHALL BE 20MPa, AND A SLUMP OF
3. DURING CONSTRUCTION, THE CONTRACTOR SHALL BE BLOW COUNT OF 7 OR MORE MAY BE SATISFACTORY WHEN - TOP COVER 30mm 230-/+ 25mm. AGGREGATE SIZE SHALL BE 10mm. GROUT
RESPONSIBLE FOR MAINTAINING THE STRUCTURE IN A TESTED IN-SITU WITH A PENETROMETER IN ACCORDANCE - BOTTOM COVER TO MEMBRANE 40mm SHALL HAVE A CEMENT CONTENT OF NOT LESS THAN
STABLE CONDITION AND ENSURING NO PART SHALL BE WITH AS 1289. 3. CONCRETE GRADE SHALL BE AS FOLLOWS: 300kg/m3.
OVERSTRESSED UNDER CONSTRUCTION ACTIVITIES. 3. TEST CERTIFICATES OF ACTUAL DENSITIES TO BE FOOTINGS N20 5. MINIMUM GROUT COVER TO ANY REINFORCEMENT SHALL
4. WORKMANSHIP AND MATERIALS ARE TO BE IN PROVIDED BY THE CONTRACTOR. INTERNAL SLAB N25 BE 20mm.
ACCORDANCE WITH THE RELEVANT AND CURRENT 4. THE CONTRACTOR SHALL CHECK ALL FOOTING EXTERNAL SLAB N25 6. NO CHASES SHALL BE CUT INTO BLOCKWORK WITHOUT
AUSTRALIAN STANDARDS INCLUDING ALL AMENDMENTS EXCAVATIONS FOR ORGANIC MATERIAL AND RUBBISH. IF 4. REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY THE APPROVAL OF THE ENGINEER.
AND STATUTORY REQUIREMENTS, EXCEPT WHERE VARIED ANY OF THIS MATERIAL IS FOUND, IT SHALL BE REMOVED AND NOT NECESSARILY SHOWN IN TRUE PROJECTION. 7. ALL WALL INTERSECTIONS SHALL BE BONDED
BY THE CONTRACT DOCUMENTS. AND THE EXCAVATION BACKFILLED WITH CLEAN 5. ALL REINFORCEMENT SHALL BE SUPPORTED IN ITS CONSTRUCTION.
5. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS NOTED GRANULAR FILL. CORRECT POSITION SO AS NOT TO BE DISPLACED DURING 8. SHORE RETAINING WALLS UNTIL CORE FILLING HAS CURED
OTHERWISE. 5. IF DISTURBED, THE BOTTOM OF THE EXCAVATIONS SHALL CONCRETING, ON APPROVED BAR CHAIRS AT 1000mm AND UNTIL FULLY SUPPORTED BY FLOOR FRAMING OVER
6. DESIGN WIND LOADS ARE IN ACCORDANCE WITH BE COMPACTED TO A RELATIVE DRY DENSITY OF 100% AS MAXIMUM CENTRES BOTH WAYS. WHERE REQUIRED WHERE APPLICABLE.
AS/NZS 4055 - 2012 AS FOLLOWS: DETERMINED IN ACCORDANCE WITH AS 1289.5.4.1-2007 AND PROVIDE SUPPORT BARS N16 AT 1000mm MAXIMUM
REGION: C AS 1289.5.1.1-2003. CENTRES.
STRUCTURAL TIMBER
TERRAIN CATEGORY 2 6. THE FOOTINGS HAVE BEEN DESIGNED TO BE FOUNDED IN 6. REINFORCEMENT SYMBOLS:-
SHIELDING CLASS NS A STABLE MATERIAL WITH A SAFE ALLOWABLE BEARING SL HARD DRAWN STEEL WIRE REINFORCING FABRIC 1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN
TOPOGRAPHIC FACTOR T0 CAPACITY OF 100kPa. SLABS HAVE BEEN DESIGNED TO BE TO AS/NZS 4671-2001.
ACCORDANCE WITH AS1720.1-2010 AND ALL OTHER
WIND CLASSIFICATION C2 FOUNDED ON MATERIAL WITH A MINIMUM CBR OF 5% OR N HOT ROLLED DEFORMED BARS TO AS/NZS RELEVANT CODES OF PRACTICE.
INTL PRESSURE COEFFICIENT +0.7/-0.65 BETTER. SHOULD CONDITIONS OTHER THAN THOSE 4671-2001.
2. ABNORMALLY GREEN OR SPLIT TIMBER SHALL BE REJECTED.
7. DESIGN LIVE LOADINGS ARE IN ACCORDANCE WITH DESCRIBED ABOVE BE ENCOUNTERED, THEN THE MATTER R STRUCTURAL GRADE PLAIN ROUND BAR TO
3. TIMBER AT JOINTS SHALL BE FREE OF DEFECTS.
AS/NZS 1170.1-2002 AS FOLLOWS: IS TO BE REFERRED TO THE ENGINEER FOR POSSIBLE AS/NZS 4671-2001.
4. UNLESS NOTED OTHERWISE, STRUCTURAL TIMBER SHALL BE
BALCONY 2.0kPa RE-DESIGN. W REINFORCED WIRE TO AS/NZS 4671-2001.
MGP12 OF JOINT GROUP JD4 TIMBER OR BETTER.
FLOOR 1.5kPa 7. IF CONCRETE IS PLACED IN HOT AND/OR WINDY WEATHER
5. IT SHALL BE THE RESPONSIBILITY OF THE BUILDER TO
ROOF 0.25kPa SITE DETAILS (>28), AN ALIPHATIC FOG SPRAY IS RECOMMENDED TO
ENSURE THAT TIMBER IS PROTECTED FROM THE WEATHER
8. ALL ITEMS CALLED UP BY A TRADE NAME MAY BE REDUCE EVAPORATION.
AND STRENGTH IS NOT IMPAIRED IN ANY WAY.
SUBSTITUTED BY AN EQUIVALENT ITEM WITH SIMILAR CONFIRM THE FOLLOWING AND REFER ANY DISCREPANCIES TO 8. PIPES, CONDUITS AND OTHER CAST-IN ELEMENTS SHALL
6. THE TOLERANCE ON TIMBER ELEMENT DIMENSIONS SHALL
PROPERTIES, SUBJECT TO THE ENGINEER'S WRITTEN THE ENGINEER: BE POSITIONED TO ALLOW WET CONCRETE TO FLOW BE -0;+3mm.
APPROVAL. 1. REAL PROPERTY DESCRIPTION: AROUND ALL REINFORCEMENT. DO NOT TIE CONDUITS
7. ALL EXPOSED TIMBER SHALL BE OF DURABILITY CLASS 2 OR
LOT 01 ON RP1010. ALONGSIDE REINFORCEMENT. BETTER.
2. THE SITE HAS SOME FALL. 9. WELDING OR SITE BENDING OF REINFORCEMENT IS NOT 8. ALL BOLTS, SCREWS AND NAILS TO BE GALVANISED AND
3. THE SITE IS NOT SUBJECT TO EXISTING CONCENTRATED PERMITTED WITHOUT APPROVAL FROM THE INSTALLED IN ACCORDANCE WITH AS1720.1-2010.
OVERLAND FLOW. SUPERINTENDENT. 9. ALL NAIL AND SCREW PENETRATIONS NOMINATED ARE TO BE
4. NO TREES HAVE RECENTLY BEEN REMOVED FROM THIS 10. SLAB SURFACE AND EXPOSED SIDES SHALL BE CURED FOR INTO RECEIVING MEMBER.
SITE PRIOR TO CONSTRUCTION. A PERIOD OF AT LEAST 7 DAYS BY AN APPROVED METHOD 10. ALL PLYWOOD IS TO BE STAMPED PAA TESTED
5. THERE ARE NO EXISTING TREES ON THIS OR ADJOINING OF CURING. (MOIST CURING, SPRAYED MEMBRANE OR STRUCTURAL.
SITES LOCATED CLOSER TO THIS BUILDING THAN 1.5 TIMES IMPERMEABLE PLASTIC). 11. ALL BOLTS IN TIMBER TO TIMBER BOLTED STRUCTURAL
THEIR MATURE HEIGHT.
JOINTS SHALL BE PROVIDED WITH A WASHER AT EACH END
6. THE SITE HAS BEEN FILLED. THE FILL HAS BEEN PLACED IN
IN ACCORDANCE WITH AS1720.1-2010.
ACCORDANCE WITH ENGINEERING PRICIPLES AS
12. ALL BOLTS IN CONTACT WITH CCA PRESERVATIVE TREATED
CONFIRMED BY FIELD COMPACTION TESTING BY CARDNO
TIMBER SHALL BE COATED IN GREASE OR OTHERWISE
CONSTRUCTION SCIENCES.
INSULATED FROM THE PRESERVATIVE TREATED TIMBER
7. SITE CONDITIONS ARE CONTROLLED FILL OVERLYING
PRIOR TO ERECTION.
DENSE, NON-PLASTIC SILTY SAND OVERLYING HIGH PLASTIC
13. WHERE NO OTHER DETAILS ARE GIVEN, WORK SHALL
SANDY CLAY WITH AN ALLOWABLE BEARING CAPACITY OF
CONFORM TO AS1684.3-2010 FOR THE SPECIFIED WIND
MORE THAN 100kPa.
SPEED.
8. THERE ARE NO SEWER MAINS ADJACENT TO THE BUILDING.

ISSUED FOR
CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE NTS
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
PROJECT SPECIFIC NOTES S1
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU 0
WORKPLACE HEALTH AND SAFETY DESIGN REPORT FALLING OBJECTS TRAFFIC MANAGEMENT HAZARDOUS SUBSTANCES

THESE NOTES SHOULD BE READ AND UNDERSTOOD BY ALL 1. CONSTRUCTION, MAINTENANCE OR DEMOLITION 1. PARKING OF VEHICLES OR LOADING/UNLOADING OF 1. IF THIS BUILDING WAS CONSTRUCTED PRIOR TO 1990
INVOLVED IN THE PROJECT. WORK ON OR AROUND THIS BUILDING IS LIKELY TO VEHICLES ON THIS SITE/ROADWAY MAY CAUSE A IT MAY CONTAIN ASBESTOS IN EITHER CLADDING
INVOLVE PERSONS WORKING ABOVE GROUND TRAFFIC HAZARD. PARKING FOR WORKERS AND MATERIAL OR FIRE RETARDANT INSULATION
THIS INCLUDES (BUT IS NOT LIMITED TO): CLIENT, OWNER, LEVEL.WHERE THIS OCCURS, ONE OR MORE OF THE LOADING AREAS SHOULD BE PROVIDED AND MATERIAL. THE BUILDER SHOULD CHECK FOR THE
PRINCIPAL CONTRACTOR, SUB-CONTRACTORS, FOLLOWING MEASURES SHOULD BE TAKEN TO SUPERVISED BY TRAINED TRAFFIC MANAGEMENT PRESENCE OF ASBESTOS PRIOR TO ANY WORKS
TRADE-CONTRACTORS, CONSULTANTS, RENOVATORS, PREVENT INJURY FROM FALLING OBJECTS: PERSONNEL. COMMENCING AND IF PRESENT, TAKE APPROPRIATE
OPERATORS, MAINTENANCE WORKERS, DEMOLISHERS OR PREVENT OR RESTRICT ACCESS TO AREAS 2. CONSTRUCTION OF THIS BUILDING MAY REQUIRE ACTION.
GENERAL WORKERS. BELOW WHERE THE WORK IS BEING CARRIED LOADING AND UNLOADING OF MATERIALS ON THE 2. MANY MATERIALS USED IN THE CONSTRUCTION OF
OUT BY THE USE OF APPROPRIATE ROADWAY. DELIVERIES SHOULD BE WELL PLANNED THIS BUILDING CAN CAUSE HARM IF INHALED IN
GENERAL BARRICADES. TO AVOID CONGESTION OF LOADING AREAS. LOADING POWDERED FORM. PERSONS WORKING ON OR IN THE
PROVIDE TOE-BOARDS TO SCAFFOLDING OR AND UNLOADING SHOULD BE SUPERVISED BY BUILDING DURING CONSTRUCTION, MAINTENANCE OR
PROPER PERSONAL PROTECTIVE EQUIPMENT (PPE) SHOULD BE WORK PLATFORMS. TRAINED TRAFFIC MANAGEMENT PERSONNEL. DEMOLITION SHOULD ENSURE GOOD VENTILATION
PROVIDED, USED, WORN AND CURRENT AT ALL TIMES. PROVIDE MESH BARRICADES TO THE SIDE OF 3. PLANT OPERATING ON THIS SITE MAY CAUSE A RISK AND WEAR PERSONAL PROTECTIVE EQUIPMENT
SCAFFOLDING OR WORK PLATFORMS. OF COLLISION. A TRAFFIC MANAGEMENT PLAN INCLUDING PROTECTION AGAINST INHALATION WHILE
AN ADEQUATE FIRST AID KIT SHOULD BE PRESENT AND PROVIDE PROTECTIVE STRUCTURES, SHOULD BE ADOPTED AND SUPERVISED BY TRAINED USING POWDERED MATERIALS OR WHEN SANDING,
MAINTAINED ON SITE AT ALL TIMES. HOARDING AND GANTRIES BELOW THE WORK TRAFFIC MANAGEMENT PERSONNEL. DRILLING, CUTTING OR OTHERWISE DISTURBING OR
SLIPS, TRIPS AND FALLS AREA. 4. ANY TEMPORARY ROAD CLOSURES ARE TO COMPLY CREATING POWDERED MATERIAL.
ENSURE ALL PERSONS BELOW THE WORK WITH ALL LOCAL GOVERNMENT REQUIREMENTS. THE 3. TREATED TIMBER MAY BE USED IN THIS BUILDING.
1. CONSTRUCTION, CLEANING AND MAINTENANCE OF AREA HAVE SUITABLE PPE (HARD HATS, PRINCIPAL CONTRACTOR IS TO COMPLETE ALL DUST OR FUMES FROM THIS MATERIAL CAN BE
THIS BUILDING MAY REQUIRE PERSONS TO BE SAFETY FOOTWEAR, EYE PROTECTION ETC.) NECESSARY DOCUMENTATION FOR TRAFFIC HARMFUL. PERSONS WORKING ON OR IN THIS
SITUATED WHERE A FALL IN EXCESS OF 1.4m IS AND THAT IT IS USED CORRECTLY. MANAGEMENT, SIGNAGE, BARRICADES, TRAFFIC BUILDING DURING CONSTRUCTION, MAINTENANCE OR
POSSIBLE. WHERE THIS ACTIVITY CANNOT BE 2. DURING CONSTRUCTION, RENOVATION OR CONTROLLERS ETC. DEMOLITION SHOULD ENSURE GOOD VENTILATION
AVOIDED, SCAFFOLDING, LADDERS, FALL BARRIERS DEMOLITION OF THIS BUILDING, PARTS OF THE SERVICES AND WEAR APPROPRIATE PERSONAL PROTECTIVE
AND/OR PPE SHOULD BE USED IN ACCORDANCE WITH STRUCTURE WILL REMAIN STANDING PRIOR TO OR EQUIPMENT. DO NOT BURN TREATED TIMBER.
THE RELEVANT GUIDELINES, REGULATIONS OR AFTER SUPPORTING ELEMENTS ARE IN PLACE. 1. UNDERGROUND SERVICES MAY BE PRESENT AT THIS 4. MANY TYPES OF GLUE, SOLVENTS, SPRAY PACKS,
LEGISLATION. CARE SHOULD BE TAKEN TO PREVENT CONTRACTORS SHOULD ENSURE THAT TEMPORARY SITE. ALL SERVICES SHOULD BE LOCATED (USING PAINTS, VARNISHES AND SOME CLEANING MATERIALS
A FALL FROM ANY HEIGHT. BRACING OR OTHER REQUIRED SUPPORTS ARE IN DIAL BEFORE YOU DIG OR A SPECIALIST AND DISINFECTANTS HAVE DANGEROUS EMISSIONS.
2. THE SITE SHOULD BE KEPT TIDY AND FREE OF TRIP PLACE AT ALL TIMES TO PREVENT COLLAPSE. CONTRACTOR) AND CLEARLY MARKED PRIOR TO ANY AREAS WHERE THESE ARE USED SHOULD BE KEPT
HAZARDS AT ALL TIMES, INCLUDING DURING 3. DURING CONSTRUCTION, RENOVATION, WORKS COMMENCING. WELL VENTILATED. PERSONAL PROTECTIVE
CONSTRUCTION, MAINTENANCE AND EVERYDAY USE. MAINTENANCE OR DEMOLITION MECHANICAL LIFTING 2. OVERHEAD POWER LINES ARE PRESENT AT THIS SITE. EQUIPMENT MAY BE REQUIRED. THE
3. ADEQUATE LIGHTING SHOULD BE PROVIDED AT ALL OF MATERIALS MAY BE REQUIRED. WHERE SUCH WHERE THERE IS A RISK OF WORKERS OF PLANT MANUFACTURERS RECOMMENDATIONS FOR USE
TIMES DURING CONSTRUCTION AND MAINTENANCE LIFTING IS NECESSARY, ENSURE THAT APPROPRIATE COMING INTO CONTACT WITH POWER LINES THEY MUST BE CAREFULLY CONSIDERED AT ALL TIMES.
AND WHEN THE BUILDING IS BEING USED TO ENSURE LIFTING DEVICES ARE USED, THAT LOADS ARE SHOULD BE DISCONNECTED OR RELOCATED. WHERE 5. FIBREGLASS, ROCKWOOL, CERAMIC AND OTHER
SAFE WORKING CONDITIONS. APPROPRIATE AND ARE PROPERLY SECURED AND THIS IS NOT POSSIBLE, POWER LINES SHOULD BE MATERIAL USED FOR THERMAL OR SOUND
4. ACCESSWAYS AND PATHS SHOULD BE MONITORED AT THAT ACCESS TO AREAS BELOW THE LOAD IS CLEARLY MARKED WITH BRIGHT COLOURED MARKERS INSULATION MAY CONTAIN SYNTHETIC MINERAL FIBRE
ALL TIMES TO ENSURE SURFACES ARE KEPT FREE OF PREVENTED OR RESTRICTED. AND SIGNAGE SHOULD BE PROVIDED AT GROUND WHICH MAY BE HARMFUL IF INHALED OR IF IT COMES
ANY OBJECTS THAT MAY CAUSE A SLIP OR TRIP LEVEL. INTO CONTACT WITH THE SKIN, EYES OR OTHER
HAZARD. MAINTENANCE SHOULD BE CARRIED OUR 3. DURING RENOVATION AND MAINTENANCE WORK, ALL SENSITIVE PARTS OF THE BODY. APPROPRIATE
PUBLIC ACCESS
REGULARLY TO KEEP ALL SURFACES EVEN. EXISTING SERVICES WITHIN THE WORK AREA SHOULD PERSONAL PROTECTIVE EQUIPMENT SHOULD BE
BE LOCATED PRIOR TO WORK COMMENCING. IF WORN AT ALL TIMES WHEN INSTALLING, REMOVING
MANUAL TASKS 1. PUBLIC ACCESS TO CONSTRUCTION AND DEMOLITION
DISCONNECTION IS NOT POSSIBLE, SERVICES OR WORKING WITH SUCH MATERIALS.
SITES AND AREAS UNDER MAINTENANCE CAN CAUSE
SHOULD BE CLEARLY MARKED TO AVOID ANY RISK OF 6. THIS BUILDING CONTAINS TIMBER FLOORS WHICH
1. ANY ITEMS WITH A MASS GREATER THAN 25kg RISK TO WORKERS AND THE PUBLIC. WARNING SIGNS
CONTACT OR RUPTURE. HAVE AN APPLIED FINISH. AREAS WHERE FINISHES
SHOULD BE LIFTED BY TWO OR MORE WORKERS, OR AND BARRIERS SHOULD BE PROVIDED TO PREVENT
4. ANY TEMPORARY SERVICES ARE TO BE CLEARLY ARE APPLIED SHOULD BE KEPT WELL VENTILATED
WITH THE AID OF A MECHANICAL LIFTING DEVICE. UNAUTHORISED ACCESS. ELECTRICAL
MARKED AND HAVE ALL NECESSARY PROTECTIVE DURING SANDING AND APPLICATION AND FOR A
WHERE POSSIBLE, COMPONENTS SHOULD BE INSTALLATIONS, EXCAVATIONS, PLANT AND LOOSE
COVERINGS FOR THE PROPER PERFORMANCE OF PERIOD AFTER INSTALLATION. PERSONAL
STORED IN A WAY WHICH MINIMISES THE NEED FOR MATERIAL SHOULD BE SECURED WHEN NOT FULLY
THE WORK IN ACCORDANCE WITH THE PROTECTIVE EQUIPMENT MAY BE REQUIRED. THE
BENDING BEFORE LIFTING. SUPERVISED.
REQUIREMENTS OF THE RELEVANT AUTHORITIES. MANUFACTURERS RECOMMENDATIONS FOR USE
2. ALL PORTABLE TOOLS USED DURING CONSTRUCTION, MUST BE CAREFULLY CONSIDERED AT ALL TIMES.
MAINTENANCE AND DEMOLITION OF THIS BUILDING
SHOULD BE PROPERLY MAINTAINED IN ACCORDANCE
WITH THE MANUFACTURER'S SPECIFICATIONS. ISSUED FOR
CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE NTS
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
SAFE DESIGN NOTES S2
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU SHEET 1 OF 2 0
CONFINED SPACES OTHER HIGH RISK ACTIVITY GENERAL WORKPLACE HEALTH AND SAFETY REQUIREMENTS

1. CONSTRUCTION AND MAINTENANCE OF THIS 1. ALL ELECTRICAL WORK SHOULD BE CARRIED OUT IN 1. THE CLIENT/OWNER IS TO ENSURE THAT THE
BUILDING MAY REQUIRE EXCAVATION AND ACCORDANCE WITH: CODE OF PRACTICE: MANAGING PRINCIPAL CONTRACTOR COMPLIES WITH ALL
INSTALLATION OF ITEMS WITHIN EXCAVATIONS. ELECTRICAL RISKS AT THE WORKPLACE, AS/NZ 3012 REQUIREMENTS OF THE NATIONAL WH&S ACT 2011,
SPECIAL CARE MUST BE TAKEN WHEN WORKERS ARE AND ALL LICENSING REQUIREMENTS. WORKPLACE HEALTH AND SAFETY REGULATIONS 2011
REQUIRED TO ENTER A TRENCH MORE THAN 1.5m NEW ELECTRICAL INSTALLATION ON CONSTRUCTION AND CODES OF PRACTICE DURING THE
DEEP. AND DEMOLITION SITES MUST BE IN ACCORDANCE CONSTRUCTION OF THE BUILDING.
2. THE SOIL INVESTIGATION REPORT SHOULD BE READ WITH THE WIRING RULES OF AS/NZS 3000 AND 2. THE PRINCIPAL CONTRACTOR MEANS THE BUILDER
AND ASSESSED BEFORE ANY EXCAVATION WORK IS APPROPRIATE REQUIREMENTS OF AS/NZA 3012:2010. WHO HAS OBTAINED THE BUILDING PERMIT AND
COMMENCED. 2. ALL WORK USING PLANT SHOULD BE CARRIED OUT IN WHOSE LICENCE NUMBER IS BEING USED FOR THE
3. WHERE PRACTICAL, INSTALLATION SHOULD BE ACCORDANCE WITH: CODE OF PRACTICE: MANAGING CONTRACT.
CARRIED OUT USING METHODS WHICH DO NOT RISKS OF PLANT AT THE WORKPLACE. 3. THE CLIENT/OWNER SHOULD ENSURE THAT THE
REQUIRE WORKERS TO ENTER THE EXCAVATION. 3. ALL WORK SHOULD BE CARRIED OUT IN ACCORDANCE PRINCIPAL CONTRACT COMPLETES A CONSTRUCTION
WHERE THIS IS NOT PRACTICAL, ADEQUATE SUPPORT WITH: CODE OF PRACTICE: MANAGING NOISE AND WORKPLACE PLAN AS APPLICABLE UNDER THE WH&S
FOR THE EXCAVATED AREA SHOULD BE PROVIDED TO PREVENTING HEARING LOSS AT WORK. LEGISLATION.
PREVENT COLLAPSE. VEHICLES SHOULD BE 4. DUE TO THE HISTORY OF SERIOUS INCIDENTS, IT IS 4. THE CLIENT/OWNER SHOULD ENSURE THAT THE
RESTRICTED FROM ENTERING THE AREA NEAR THE RECOMMENDED THAT PARTICULAR CARE BE PRINCIPAL CONTRACTOR AND ALL TRADE
EXCAVATION. EXERCISED WHEN UNDERTAKING ANY WORK CONTRACTORS COMPLETE WORK METHOD
4. ENCLOSED SPACES WITHIN THIS BUILDING MAY INVOLVING STEEL CONSTRUCTION AND CONCRETE STATEMENTS (WMS) AS APPLICABLE UNDER THE
PRESENT A RISK TO PERSONS ENTERING FOR PLACEMENT. WH&S LEGISLATION BEFORE ANY WORK COMMENCES.
CONSTRUCTION, MAINTENANCE OR ANY OTHER 5. THE CLIENT/OWNER SHOULD ENSURE THAT
PURPOSE. WARNING SIGNS AND BARRIERS FIRE FIGHTING WORKERS HAVE A CURRENT GENERAL SAFETY
RESTRICTING ACCESS TO UNAUTHORISED PERSONS INDUCTION (WHITE OR BLUE) CARD.
SHOULD BE INSTALLED AND MAINTAINED 1. THE CLIENT/OWNER IS TO ENSURE THAT
6. THE CLIENT/OWNER SHOULD ENSURE THAT THE
THROUGHOUT THE LIFE OF THE BUILDING. WHERE APPROPRIATE FIRE FIGHTING EQUIPMENT IS
PRINCIPAL CONTRACTOR CONDUCTS THE
WORKERS ARE REQUIRED TO ENTER ENCLOSED PROVIDED ON SITE DURING CONSTRUCTION AND
NECESSARY SITE SPECIFIC INDUCTION AS REQUIRED
SPACES, AIR TESTING EQUIPMENT AND PERSONAL MAINTAINED FOR THE LIFE OF THE BUILDING.
BY WH&S LEGISLATION.
PROTECTIVE EQUIPMENT SHOULD BE PROVIDED. 2. ALL FIRE FIGHTING EQUIPMENT IS TO BE PROVIDED
7. THE CLIENT/OWNER/BUILDING SHOULD ENSURE THAT
5. SOME SMALL SPACES WITHIN THIS BUILDING REQUIRE AND MAINTAINED IN ACCORDANCE WITH THE
THE PRINCIPAL CONTRACTOR HAS THE APPROPRIATE
ACCESS FOR CONSTRUCTION AND MAINTENANCE RELEVANT AUSTRALIAN STANDARDS.
FIRST AID KITS AND THAT THEY ARE MAINTAINED AND
WORKERS. WARNING SIGNS AND BARRIERS KEPT ON SITE FOR THE DURATION OF THE
RESTRICTING ACCESS TO UNAUTHORISED PERSONS OPERATIONAL USE OF BUILDING CONSTRUCTION.
SHOULD BE INSTALLED AND MAINTAINED 8. THE CLIENT/OWNER SHOULD ENSURE THAT THE
THROUGHOUT THE LIFE OF THE BUILDING. WHERE 1. THIS BUILDING HAS BEEN DESIGNED AS A PRINCIPAL CONTRACTOR, TRADE CONTRACTORS AND
WORKERS ARE REQUIRED TO ENTER SMALL SPACES RESIDENTIAL BUILDING. IF IT, AT A LATER DATE, IS WORKERS MEET ALL OF THEIR WH&S OBLIGATIONS
THEY SHOULD BE SCHEDULED SO THAT ACCESS IS USED OR INTENDED TO BE USED AS A WORKPLACE, DURING CONSTRUCTION.
FOR SHORT PERIODS. MANUAL LIFTING AND OTHER THE PROVISIONS OF THE WORK HEALTH AND SAFETY 9. THE CLIENT/OWNER SHOULD ENSURE THAT THE
ACTIVITIES SHOULD BE RESTRICTED IN SMALL ACT 2011 OR SUBSEQUENT REPLACEMENT ACT PRINCIPAL CONTRACTOR AND TRADE CONTRACTORS
SPACES. SHOULD BE APPLIED TO THE NEW USE. ENSURE ONLY EXPERIENCED, QUALIFIED, LICENSED
PERSONS ARE EMPLOYED TO CARRY OUT THE WORK.
10. THE CLIENT/OWNER SHOULD ENSURE THAT THE
PRINCIPAL CONTRACTOR HAS PUT IN PLACE THE
WORKPLACE HEALTH AND SAFETY CONTROL
MEASURES IN ACCORDANCE WITH WHA&S
REGULATION FOR ALL HIGH RISK CONSTRUCTION
WORK INCLUDING BUT NOT LIMITED TO:
CONSTRUCTION SAFETY PLAN, WORK METHOD
STATEMENTS, ROOF EDGE PROTECTION, SCAFFOLDS
AND WORK PLATFORMS, WORK PLATFORMS ON
TRESTLE LADDERS, FALL ARREST PLATFORMS,
TRAVEL RESTRAINT SYSTEMS, FALL ARREST
HARNESS SYSTEMS, STAIR VOID PROTECTION,
BALCONY EDGE PROTECTION, INDUSTRIAL SAFETY ISSUED FOR
NETS AND EXCAVATION FALLS PROTECTION. CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE NTS
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
SAFE DESIGN NOTES S3
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU SHEET 2 OF 2 0
FOOTING SCHEDULE
SPECIAL REQUIREMENTS FOR CLASS M SITES CONCRETE MASONRY: HORIZONTAL BARS:
VERTICAL REINFORCEMENT: BOND BEAM - 400D (2 COURSE) BOND BEAM WITH 1-N16 IN
1. SURFACE DRAINAGE SHALL BE CONTROLLED 1/N12 BAR IN EACH CORNER, EITHER SIDE OF OPENINGS LESS THAN 2400 TOP AND BOTTOM COURSE TO PERIMETER OF BLOCKWORK MARK SIZE
FROM THE START OF THE SITE PREPARATION AND THEN AT 1200 MAXIMUM CENTRES. UNO. LAP 600 AS REQUIRED.
450 x 900 DEEP BORED PIER.
CONSTRUCTION. 2/N12 BARS EITHER SIDE OF OPENINGS 2400 BUT LESS THAN 3600. 1-N12 IN SILLS TYP. BP1 1-N12 CENTRAL.
2. WATER RUN-OFF SHALL BE COLLECTED AND 2/N16 BARS EITHER SIDE OF OPENINGS GREATER THAN 3600.
CHANNELED AWAY FROM THE BUILDING DURING ALL CORES CONTAINING REINFORCEMENT AND ENTIRE BOND BEAM TO 300W x 300D EDGE BEAM.
CONSTRUCTION. BE FULLY FILLED WITH 20MPa CONCRETE.
EB1 3-L12TM BOTTOM.
3. WATER SHALL NOT BE ALLOWED TO POND IN THE 300W x 300D EDGE BEAM.
TRENCHES. DENOTES N12 REINFORCING. EB2 3-L12TM BOTTOM.
4. THE BASE OF TRENCHES SHALL BE SLOPED AWAY DENOTES N16 REINFORCING.
FROM THE BUILDING. P1 100 SQ F14 HWD POST.
5. LAGGING SHALL BE USED AROUND ALL EB1
STORMWATER AND SEWER PIPE PENETRATIONS 3-N12 x 2000 OR 3-L12TM AT 300W x 400D STRIP FOOTING.
RE-ENTRANT CORNERS. 100 SF1 3-L12TM BOTTOM.
THROUGH EXTERNAL FOOTINGS. THE LAGGNG
SHALL BE A MINIMUM OF 20mm THICK ON CLASS M SL72. 40 COVER. 300W x 400D STRIP FOOTING.
SITES. SF2 3-L12TM BOTTOM.
6. JOINTS IN PLUMBING SHALL BE PROVIDED WITHIN SF1 EB1 EB2
300W x 400D STRIP FOOTING.
SF3

EB1
1m OF THE HOUSE UNDER CONSTRUCTION. JOINTS BP1 3-L12TM BOTTOM.
SHALL BE ARTICULATED TO ACCOMMODATE P1
GROUND MOVEMENTS WITHOUT LEAKAGE. 500W x 150D SLAB THICKENING.
ST1 3-L11TM BOTTOM.
7. TREES SHALL NOT BE PLANTED WITHIN 1 x THEIR CONTINUE EDGE BEAM
100

EB2
SF3
MATURE HEIGHT. THROUGH EXTRA

SF1
8. EXCAVATIONS NEAR THE EDGE OF THE FOOTING WIDTH TO PROVIDE
SL72. 30 COVER.
SYSTEM SHALL BE BACKFILLED IN SUCH A WAY AS CONTINUITY. ADD
TO PREVENT ACCESS OF WATER TO THE 1-N12 BOTTOM. SF3
FOUNDATION. FOR EXAMPLE, EXCAVATIONS EB2 S F1 MINIMUM HEIGHT OF SLAB FOR HABITABLE ROOMS
SHOULD BE BACKFILLED ABOVE OR ADJACENT TO BP1 SF2
SHALL BE 300mm.
THE FOOTING WITH MOIST CLAY COMPACTED BY P1 GROUND AROUND THE PERIMETER OF THE BUILDING
HAND-RODDING OR TAMPING. POROUS MATERIAL
EB2

SHALL SLOPE 50mm IN 1000mm MIN AWAY FROM THE

SF3
SUCH AS SAND, GRAVEL OR BUILDING RUBBLE

EB1
BUILDING.
SHOULD NOT BE USED. SF3 CUT AND PROVIDE FILL AROUND BUILDING AS
9. WHERE PIPES PASS UNDER THE FOOTING SYSTEM, REQUIRED TO MAINTAIN FALLS AND REQUIRED LEVELS.
THE TRENCH SHALL BE BACKFILLED FULL DEPTH ALL CONCRETE TO BE CAST IN ACCORDANCE WITH THE
SF1

SF1

SF1

SF1
WITH CLAY TO ACT AS A BARRIER TO THE 100 REQUIREMENTS OF AS3600 AND AS2870.
SF1
INGRESS OF WATER BENEATH THE FOOTING SL72. 40 COVER. GRADE (FALL) ALL WET AREAS TO FLOOR WASTE
SYSTEM. GULLIES AS REQUIRED.
10. CONCRETE IN BEAMS SHALL BE MECHANICALLY
EB1

BUILDING WORK SHALL BE PROTECTED FROM TERMITE


VIBRATED. ATTACK IN ACCORDANCE WITH AS 3660.1.
A TERMITE PROTECTION NOTICE ADVISING OF THE

ST1
TYPE OF PROTECTION USED BEING PRINTED ON
DURABLE MATERIAL AND CONFORMING WITH THE BCA
PART B 1.3(J)(ii) TO BE INSTALLED IN METER BOX AND
EB1 KITCHEN CUPBOARD PRIOR TO COUNCILS FINAL
INSPECTION (MIN 2 DURABLE NOTICES REQUIRED).

FOOTING AND SLAB PLAN


1:100
AS2870 EQUIVALENT CONSTRUCTION:
ARTICULATED MASONRY VENEER CONSTRUCTION
CLASS "M" SITE ISSUED FOR
REFER SOIL INVESTIGATION REPORT XXX.XX CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE 1:100
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
FOOTING AND SLAB PLAN S4
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU 0
STARTER BARS TO MATCH
SIZE AND GRADE OF WALL
450 LAP REINFORCEMENT TYP.
N10-600 TYP. 400 LAP. 400 LAP.

N10-600 TYP.

100

100

100

150
300

400

400

400

200
SF2
300

SF3

300
EB1 0.2mm POLYETHYLENE
SF1 300
300 300 EB2
MEMBRANE ON
COMPACTED SAND TYP.
300
TYPICAL SF2 DETAIL TYPICAL SF3 DETAIL 300
1:20 1:20

TYPICAL EB1 DETAIL TYPICAL SF1 DETAIL TYPICAL EB2 DETAIL


1:20 1:20 1:20

H.D. GALV. POST BRACKET. 400 LAP.


2-M12 BOLTS. 1-N16 COGGED
P1 OVER BOTTOM OF BRACKET.

100

100

100
N10-600 TYP.
60

75

1-N12. 500 LEGS. 1-N12. 500 LEGS.


50
100

450 LAP

3-N12 TIE BARS. TYPICAL STEP DOWN DETAIL 300


1:20
600 LAP. 150 COG.
300

FOOTING REINFORCEMENT LAP CORNER DETAILS


EB2 1:20
500 LAP
300

500 LAP
300

SF1
EB1 1
3
BP1

100
150
300 CRANK DOWN WHERE SF1
CONTINUES AS EB1/EB2.
450 500 ST1

TYPICAL EB1/SF1 DETAIL


TYPICAL BP1/EB2 DETAIL CONCRETE MASONRY CORNER DETAILS
1:20
1:20
1:20 TYPICAL ST1 DETAIL ISSUED FOR
1:20 CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE 1:20
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
FOOTING DETAILS S5
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU 0
ROOF BATTENS: MEMBER SCHEDULE
35 x 70 MGP12 ROOF BATTENS AT 600 CENTRES. 1/75mm No
14 TYPE 17 SCREW TO EACH TRUSS.
MARK SIZE
ROOF TRUSSES: FIX TIMBER FRAMES TO
TRUSSES AT 900 MAXIMUM CENTRES WITH PITCH AND CONCRETE MASONRY WALL L1 190 x 45 MGP12 LINTEL.
OVERHANG AS SPECIFIED BY THE ARCHITECT. NOTE WITH 1-M12 CHEMSET AT TOP
INTERNAL PRESSURE CO-EFFICIENT TO BE 0.7/-0.5. TRUSSES PLATE AND MID-HEIGHT TYP. P1 100 SQ F14 HWD POST.
TO BE SEASONED PINE MGP12 (H2) OR HWD F14 - J2. BB116s
TRUSS TO TRUSS CONNECTIONS TO BE AS DESIGNED AND
SPECIFIED BY THE TRUSS MANUFACTURER. RB1 130 x 65 HYNE BEAM 17C ROOF BEAM.

ROOF BRACING: RB2 195 x 65 HYNE BEAM 17C ROOF BEAM.


TYPE, POSITION AND TYPE OF FIXING TO BE AS SPECIFIED
BY THE TRUSS MANUFACTURER. RB3 RB2 RB3 295 x 85 HYNE BEAM 17C ROOF BEAM.

BB216s
P1
CEILINGS:
CEILINGS FIXED TO EX 42 x 35 PINE BATTENS IN 75 x 12mm PLATE OVER
RB3. 2-M12 TIE RODS.

BB116s

RB2
ACCORDANCE WITH MANUFACTURERS SPECIFICATION.

LBW
WALL FRAMING:
LOAD BEARING WALLS: LBW BB216s
COMMON STUDS: 70 x 35 MGP12 AT 450 CTS RB1 L1
TOP PLATES: 2/35 x 70 MGP12
P1
BOTTOM PLATES: 35 x 70 MGP12

BB116s
RB1

BB116s
NOGGINGS AT 1350 MAX HORIZ. CTS.
WIND DIRECTION B
M12 TIE RODS WITHIN 100mm OF ROOF TRUSSES TO
REQUIRED: 53kN
ACHIEVE DIRECT TIEDOWN.
ACHIEVED: 368kN
JAMB STUDS:
BB116s BB116s BB116s

OPENING: 900 = 2/70 x 35 MGP12

INTERNAL NON-LOAD BEARING WALLS:


COMMON STUDS: 70 x 35 MGP10 AT 450 CTS

BB116s
TOP PLATES: 35 x 70 MGP10

1.9:12.2
BOTTOM PLATES: 35 x 70 MGP10

1.6:10.2
LINTELS:
BB116s - 400D (2 COURSE) BLOCK LINTEL, 1-N16 IN
BRACING WALLS:
TOP AND BOTTOM COURSE WITH W8 STIRRUPS AT
STRUCTURAL BRACING WALL CONSTRUCTED TO 6.4kN/m
200 CENTRES
RATED BRACING CAPACITY. TOTAL BRACING CAPACITY BB116s BB116s BB116s BB116s BB216s - 400D (2 COURSE) BLOCK LINTEL, 2-N16 IN
OF BRACING WALLS IS GIVEN IN kN.
TOP & BOTTOM COURSE WITH W8 STIRRUPS AT 200
1.8:11.5 CENTRES.
TRUSS TO BRACING WALLS:
BUILDER TO ESTABLISH THE NUMBER OF CONNECTIONS
BETWEEN BRACING WALL AND ROOF FRAMING. No. OF WIND DIRECTION A

400

400
CONNECTIONS = BRACING WALL CAPACITY REQUIRED: 63kN
CONNECTION CAPACITY. ACHIEVED: 146kN

BB116s BB216s

BRACING PLAN
1:100
ISSUED FOR
CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE 1:100
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
BRACING PLAN S6
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU 0
CLEAT NAILED BETWEEN FIRST TWO CEILING CLEAT NAILED BETWEEN FIRST TWO CEILING 1/30 x 0.8mm G.I. LOOPED STRAP.
BATTENS WITH 3-2.8 DIAMETER NAILS. BATTENS WITH 3-2.8 DIAMETER NAILS. 4/2.8mm NAILS. 13kN CAPACITY.
17.5 17.5
75 x 12mm PLATE. 2-M12 BOLTS. BLOCKFAST LOOPED STRAP 17.5
INSTALLED IN ACCORDANCE
WITH MANUFACTURERS
SPECIFICATIONS.
2-M12 BOLTS
TO RB1.
3-M12 BOLTS
ALTERNATIVELY, 1/ 70x25 MGP12 ALTERNATIVELY, 1/ 70x25 MGP12 TO RB2 AND
PACKER EITHER SIDE OF WALL FIXED PACKER EITHER SIDE OF WALL FIXED RB3.
40kN CAPACITY. TO TRUSS WITH 3/2.8mm NAILS TO 18kN CAPACITY. TO TRUSS WITH 3/2.8mm NAILS TO
EACH TRUSS. EACH TRUSS.
P1

THREADED RODS WITH END COGGED,


EXTENDING DOWN THREE COURSES, BENT
TO SUIT. 25mm MAX FROM EACH TRUSS.
TRUSS TO ROOF BEAM DETAIL ROOF BEAM TO P1 DETAIL
TRUSS TIE DOWN DETAIL TRUSS TIE DOWN DETAIL 1:20 1:20
1:20 1:20

75 x 12mm PLATE. 2-M12 BOLTS.


40kN CAPACITY.
100mm MAX.
SOLID NOGGING.

100mm MAX.

J2 J3 J4 JD4 JD5 JD6


M12 BOLT 27 27 26 20 16 12
BOLT SIZE AS M16 BOLT 50 50 46 35 28 21
75 x 12mm PLATE. 2-M12 BOLTS.
PER TABLE.
40kN CAPACITY.
NOTE:
THE TOP PLATE SHALL BE FIXED TO THE LINTEL
THREADED RODS WITH END COGGED, WITHIN 100mm OF EACH RAFTER/TRUSS.
EXTENDING DOWN TWO COURSES, BENT
TO SUIT. 25mm MAX FROM EACH TRUSS.

TRUSS TO WALL DETAIL TRUSS TO WALL DETAIL


1:20 1:20
LINTEL TIE DOWN DETAIL ISSUED FOR
NTS CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE 1:20
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
ROOF FRAMING DETAILS S7
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU 0
2/30 x 0.8mm G.I STRAPS WITH NUMBER
TRIMMER: OF NAILS EACH END OF STRAPS AS PER
ONE BOLT: 90 x35mm F8 FRAMING TABLE, OR PROPRIETY NAILING PLATE
OR: 90 x 45mm F5 ANCHORS (LEGS WITH EQUAL CAPACITY. J2 J3 J4 JD4 JD5 JD6
TWO BOLTS: 120 x 35mm F8 NOT BENT) INTERNAL STRAPS NAILS
OR: 120 x 45mm F8 6/2.8mm NAILS BRACING
J2 J3 J4 JD4 JD5 JD6 4/2.8 4.3 3.1 2.2 3.3 3.0 2.1
WALL 1
EACH FACE. EXTERNAL WALL 6/2.8 6.5 4.6 3.3 4.9 4.0 3.1
SCREWS
SCREWS OR 1/No.14 TYPE 17 4/2.8 8.7 6.2 4.4 6.6 5.4 4.1
4.8 3.5 2.5 3.5 2.5 1.8 2
BOLTS AS PER
2/No.14 TYPE 17 9.7 6.9 4.9 6.9 4.9 3.6 6/2.8 13 9.3 6.6 9.8 8.1 6.1
TABLE.
3/No.14 TYPE 17 13 9.3 6.6 9.8 7.4 5.4 TOP PLATE
PROVIDE CLEARANCE NAILS, SCREWS OR BOLTS J2 J3 J4 JD4 JD5 JD6
BOLTS
WHERE ROOF IS TRUSSED. AS PER TABLE. BLOCKS TO
M10 6.4 4.1 2.6 4.3 3.0 2.0 NAILS
BE BOTH SIDES OF RAFTER
M12 7.6 4.9 3.1 5.1 3.6 2.5 OR BOTTOM CHORD. 4/3.05 5.0 3.6 2.5 3.6 3.0 2.2
2/M10 12 8.0 5.1 8.4 5.9 4.0 6/3.05 6.6 4.7 3.4 5.0 4.2 3.1
BLOCKING PIECES
2/M12 13 9.3 6.1 9.8 7.0 4.9 LARGE ENOUGH TO 4/3.33 5.6 4.0 2.8 4.0 3.3 2.5
BRACING WALL.
AVOID SPLITTING. 6/3.33 7.4 5.3 3.7 5.5 4.6 3.5
BOLTS
M10 6.4 4.1 2.6 4.3 3.0 2.0
M12 7.6 4.9 3.1 5.1 3.6 2.5
GAP BETWEEN 2/M10 13 8.0 5.1 8.4 5.9 4.0
NAILING PLATES OR FRAMING J2 J3 J4 JD4 JD5 JD6 TOP PLATE AND
SCREWS
ANCHOR (LEGS NOT BENT) TO EITHER NAILS TRUSS.
END OF NOGGING 6/2.8mm NAILS 2/No. 14 TYPE 17 9.7 6.9 4.9 6.9 4.9 3.6
4/3.05 5.0 3.6 2.5 3.6 3.0 2.2
EACH END FACE OR 2/No. 14 TYPE 17 BRACING WALL. 3/No. 14 TYPE 17 15 10 7.4 10 7.4 5.4
6/3.05 6.6 4.7 3.4 5.0 4.2 3.1
BATTEN SCREWS EITHER END. PLYWOOD SHALL BE NAILED TO FRAME USING 30 x 2.8
4/3.33 5.6 4.0 2.8 4.0 3.3 2.5 GALVANISED FLATHEAD NAILS OR EQUIVALENT.
90 x 35mm F8 6/3.33 7.4 5.3 3.7 5.5 4.6 3.5 HORIZONTAL BUTT JOINTS PERMITTED,
M12 RODS SHALL BE USED AT EACH END OF SHEATHED
OR 90 x 45mm F5 TRIMMER. PROVIDED NAIL FIXED TO NOGGING AT
BOLTS SECTION TOP PLATE TO BOTTOM PLATE/FLOOR FRAME.
SHEAR BLOCKS NAILED, 150 150mm CENTRES.
M10 6.4 4.1 2.6 4.3 3.0 2.0
BOLTED, OR SCREWED AS SHEATHED PANELS SHALL BE CONNECTED
M12 7.6 4.9 3.1 5.1 3.6 2.5
PER TABLE.
2/M10 13 8.0 5.1 8.4 5.9 4.0 TO SLAB WITH M12 CHEMSETS AT 1200mm
MAXIMUM CENTRES.
SCREWS

150
GAP 2/No. 14 TYPE 17 9.7 6.9 4.9 6.9 4.9 3.6
TO BRACING WALL. MINIMUM PLYWOOD THICKNESS (mm)
3/No. 14 TYPE 17 13 9.2 6.6 9.8 7.4 5.4
TRUSS.
STRESS STUD SPACING (mm)
GRADE
450 600

300
RAFTER OR TRUSS 2/3.05mm NAILS PER
BATTEN, 3.5mm HOLES F11 6 7
SHALL BE DRILLED IN F14 4 7
BATTEN TO ALLOW FOR FIXING OF BOTTOM PLATE TO FLOOR
TRUSS DEFLECTION J2 J3 J4 JD4 JD5 JD6 FRAME OR SLAB:
2.5 1.8 1.3 1.8 1.5 1.1 M12 ROD TOP TO BOTTOM PLATE M12 RODS AS SHOWN PLUS A 13 kN
EACH END OF SHEATHED SECTION. CAPACITY CONNECTION AT
MAXIMUM 1200mm CENTRES.

PROVIDE
150
CLEARANCE WHERE CEILING BATTENS FIXED
ROOF IS TRUSSED
WITH 1/3.05mm NAIL
EITHER SIDE OF WALL SINGLE SIDED PLYWOOD BRACING WALL: 6.4kN/m CAPACITY ISSUED FOR
NTS
BRACING WALL CONSTRUCTION
Project Job No. Scale
PO BOX 2572
ASCOT QLD 4007 PROPOSED DISPLAY HOME SAMPLE NTS
PHONE: 07 3102 2835
----
Title Drawing No. Revision
ABN 71 105 354 327
BRACING DETAILS S8
0 FOR CONSTRUCTION
Rev Description
MAC MAC
Designed Approved
21/03/13
Date
CORNELLENGINEERS.COM.AU 0