Professional Documents
Culture Documents
Reverse-Power
PAC history
Leakage Suppression
Winding for Differential
CTs, Btow, 1925
PAC.SUMMER.2009
by Walter Schossig
Protection
71
History Biography
Walter Schossig
(VDE) was born
in Arnsdorf (now
Czech Republic) in
1941. He studied
electrical engi-
neering in Zittau
(Germany), and
Generator
joined a utility in
the formerEastern
Germany.After the
German reunion
Protection
the utility was
Special protection functions have been de- renamed as TEAG,
now E.ON Thuer-
veloped for bigger generators. inger Energie AG in
Erfurt. There he re-
PAC.SUMMER.2009
72
PAC history
50-scheme. Now the relay starts up even in case of inductive
reactive currents during unequal excitation.
5 Combined overcurrent and reverse-power
relay, AEG, 1903
On Ascension Day 1924 a disaster occurred in a steam
station in Erfurt (Germany) during the taking of a generator
out of service. The bolt of the trip valve was full of salt and
could not interrupt completely the steam supply. Now the
rotor was accelerated and the new installed generator was
destroyed completely.
In the 1920s AEG developed the RR2 power relays. See
Fig. 2. They consist of two induction driving elements with
a common Ferraris-disk. Springs hold them in the middle
position. The driving elements work in Aaron-circuit. An
arm moved according to the amount and direction of power.
It was more or less a wattmeter with a contact. The switching
capacity was poor and an auxiliary relays was necessary.
Reverse power protection was later used for protection of
steam turbines.
The turbine operates as a synchronous motor and it could
be damaged.
Circuit and view of a 2-pole reverse-power protection
CG90c (BBC) is shown in Fig. 3 and Fig. 10.
To avoid a tripping of the protection in case of turbine blade
1 Reverse-
salt deposits, the tripping signal is active only if the valve 2 is
closed (Fig.4).
current & direc- ZPA produced the reverse-power relay GSCT12 (Fig. 9)
tion-of-current in the early 1970s. For measuring a ferrodynamic relay SW
indication in Figure 8 was used. An advantage of this device was the
V&H, 1894 sensitivity for harmonics because it trips on the mean value
of the products of voltage and current. A torque was produced A definite time reverse power relay, type WCG, produced
only in case of equal fundamental or harmonic. by GEC in 1988 is shown in Fig. 11.
These relays could be used for earth-fault detection too. Differential Protection
The successor was the static relay GSCT12X in 1981. Effective short-circuit protection became possible with the
BBC produced a static PPX110/111 (Fig. 6) in the 1970s. introduction of differential protection. First developments
This relay was used for supervision and tripping of generators, and the usage for transformer and line protection have been
but it also could detect if a generator still receives energy in case covered in the last issues of this magazine. The most common
of a leak valve. Another usage was for huge changes of load basic connections in the 1930s are shown in Fig. 15.
which could cause an out-of-step of the generator. All these Unlike transformer differential the same transformers
conditions could be supervised and evaluated with a counter. (type, construction, ratio) could be used in star point,
PAC.SUMMER.2009
73
8 Reverse-power 9 Reverse-power
relays GSCT12-S1 relays GSCT-S1
wiring diagram, ZPA, 1976 ZPA, 1976
PAC.SUMMER.2009
74
PAC history
14 Simple differential protection, AEG, Interturn faults require the
1925
EM - Excitation Machine; FA - Field Surpression; RR - Reverse Relay; immediate switch-off of the
S - Oil-Breaker; Sp - connected to Voltage Transformer; St - Current Transformer;
UMZ - definite time.overcurrent relays; DR single phase differential
generator in order to prevent
further damage.
G
S
PAC.SUMMER.2009
75
18
is not considered). It is not possible to detect this fault by a
differential protection because the currents at the beginning
Differential Relays TG3, BBC, 1952
and at the end of the winding are equal.
B. Bauch (SSW) patented in 1925 (DRP 432837) the
circuit shown in Fig. 13. The generator to be protected (G) is
connected to the auxilliary inductor (S). This is an image
of the generator and consists of a transformer with a primary
winding in star connected to the neutral of the generator.
The neutral points are connected via the relays R. At the
beginning these relays have been simple overcurrent devices.
The inductor was equipped with a delta connection. In case
of a turn-to-turn fault the phase-voltage decreased. The star
point of the generator moves, the star point of the inductor
moves with the impact of the delta-winding into the triangle
of the voltages. Since a third harmonic current flows in the
connection of the neutrals , R. Bauch used the wattmetric
relay R in Fig. 13 with two coupled systems connected to the
sinusoidal voltages U12 and U23.
Siemens used a circuit for interturn short-circuit protection
19
in 1936. The RA2 (c) worked with a chain of reactors (b). See Generator differential protection,
Fig. 12. Details and characteristic of frequency (current limiting AEG, 1989
as a function of the frequency) is shown in Fig. 24, it was used The choice
to keep off the third harmonic. A combined differential- and
interturn short-circuit protection (5 and 6) for generators with of the
two parallel windings 1 is shown in Fig. 26. Interturn faults
cause equalizing currents between the neutral points, flowing characteristic
though the equalizing winding 4 to the relays 6.
In the 1950s SSW used the circuit shown in Fig. 25. The curve is
open delta winding was used for the interturn short-circuit
protection, connected to moving-coil relays with a rectifier performed by
and a filter network (for the 3rd harmonic). The secondary was
realized as a wye connection. Measuring devices and relays solder bridges.
have been connected to the supporting coil.
For generators with two windings instead of the coils the
"double phantom circuit" was used (Fig. 28).
Over-Voltage Protection
An increase of voltage was dangerous especially at hydro
generators since it may result in huge increases of speed.
20
In 1936 Siemens produced an increase-of-voltage-relay
21
High impedance Coarse and fine 22 Chain of
differential protec- differential protec- reactors for:
(RV5, Fig. 23). It worked properly for increases up to 200% of
tion, GEC, 1988 tion, Oerlikon, 1965 Interturn Short-Circuit
the nominal voltage. In 1984 Siemens produced a static relay
Protection RA2,
with two stages 7RE21-Z1 (Fig. 29).
Siemens, 1936
When the short-circuit currents in the high voltage
grids became bigger this caused especially problems in
effectively grounded systems due to high fault currents for
phase-to-ground faults. A limitation was possible with
isolation of different neutral points of transformers. This
became common at unit transformers. In case of opening the
circuit breaker between the unit and the grounded grid (e.g. in
case of load-shedding) dangerous over-voltages could occur.
The first nuclear power stations in Switzerland (Beznau I and
II which NOK put into operation in 1969 and 1971) have
been equipped with a star-point breaker developed by AEG (4
in Fig. 27).
The effective power of both power stations together was
700 MW. Generators operated as one unit (1 and 2); four
PAC.SUMMER.2009
76
24 26
PAC history
Circuit and characteristic of frequency, Combined differential and interturn
Siemens short-circuit protection
for generators with parallel windings, BBC, 1945
7
a b 5 6
2
120
100
Penetrability of current%
80 1
60
40 8
20 3
0
0 20 40 60 80 100 120 140 160 180 Hz 4
50 150
5 & 6 - A combined differential- and interturn short-circuit protection
a Supporting Reactance b Relays 1 - Generators with two parallel windings 4 - Equalizing winding 6 - Relays
S
G
G Generator S Open delta winding
PAC.SUMMER.2009