STATEMENT:
Hence , the rest of the energy must be stored in and supplied by the
battery bank and it is
If the voltage of the battery bank is 108 V , then its charge capacity =
142,222 / 108 = 1316.87
These four diodes waste some photovoltaic power which depends on the
currents. At 108 V , the load current is = 1000 W /108 = 9.26 A
Both the diodes will dissipate power which is = 9.26 x 0.7 = 6.5 W
Total energy dissipated in four diodes = 1092 + 1181 = 2273 Whr (this
energy must also supplied by PV) and
Hence, the energy delivered at the input of the MPPT from the array =
184495 /0.9 = 204,994.44 Whr
Finally, we need account for the wiring and cabling losses and therefore
the oput of the array = 204994.44 + (204994.44x5/100) = 215244.16 whr
If the array is set to collect the maximum energy over one year , then the
tit angle should be fixed at
The radiation data for delhi at a tilt angle of 25 gives a value of 2131.2
kWhr/m2 annually. This amount to an average of 2131 / 365 = 5.84
kWhr/m2/day.
= (0.5/100) x 40 x 150 = 30 W
1. Pmax = 150 W
2. Imax = 4.80 A
3. Vmax = 34 V
4. Isc = 5.0 A
5. Voc = 42.8 V