INTRODUCTION 1
NOMENCLATURE 1
STANDARD 3
OPTIONS 3
ACCESSORIES 3
CONTROLLER 4
SELECTION PROCEDURE 5
MODELS LAYOUT 12
PETRAs Ducted Split Units (DSP Low optional controls and accessories are available to
Capacity) are designed specifically for easy meet different design requirements.
NOTA
maintenance and installation in small and
medium sized air conditioning systems. DSP Low Capacity units consist of two sections: For more technical details, please refer to the
These air-cooled condensing units may be the evaporator section (RAC unit, CMD unit or nearest PETRA sales office or to the PETRA
connected to a wide range of PETRA's indoor CM unit) and the condenser section (DSP unit) factory .
units, making them ideal for use in residential of matching size. This series is available in a
and commercial applications such as homes, capacity range of 15 to 60 @ 50 Hz nominal
stores, shops, villas, restaurants, commercial MBH.
complexes, offices, laboratories, etc. DSP Low
Capacity units can be used for cooling or
heating with the optional heat pump. Additional
NOMENCLATURE
48
95F
472 L/s
944 L/s
944 L/s
1
DSP
FEATURES AND BENEFITS
Outdoor Unit (DSP Type)
Casing Fans Coils
It is a heavy gauge galvanized steel casing with All units are provided with direct driven Coils are designed to function with optimum
weatherproof, polyester powder electrostatic forward curved centrifugal fans of the double performance in all design conditions. Coils are
paint, oven-baked to ensure maximum gloss inlet type that are designed for maximum manufactured from seamless copper tubes
and hardness. efficiency and uniform air distribution. The mechanically expanded into aluminum fins. All
fans are statically and dynamically balanced to coils are air pressure tested at 450 Psi, under
Compressor
ensure quiet operation and optimal water to avoid leakage. They also undergo dry
It is a low noise, hermetically sealed, high performance. chemical cleaning after manufacturing for
efficiency with internal thermal motor optimum system cleanness.
protection. (Suitable for cooling and heat pump Motors
application) Permanent split capacitor three-speed electrical Fans
motors, with internal thermal protection. Double Width, Double Inlet (DWDI)
Coils centrifugal forward curved fans are used, with
Coils are designed to function with optimum Filters
All models are provided with a nominal 0.5 a V-belt drive and a variable pitch pulley. The
performance in all design conditions. Coils are fans are statically and dynamically balanced to
manufactured from seamless copper tubes inch thick aluminum mesh media flat filter.
ensure quiet operation and optimal
mechanically expanded into aluminum fins. All Drain Pan
performance.
coils are air pressure tested at 450 Psi, under All units are provided with a drain pan. The drain
water to avoid leakage. pan is insulated on the underside and sides to Motors
They also undergo dry chemical cleaning after prevent condensation and is coated with All motors are of the totally enclosed fan-
manufacturing for optimum system cleanness. weatherproof, polyester powder electrostatic cooled induction type. All units have their
All condenser coils have type-L design. paint, oven-baked to ensure maximum gloss, fan/motor assembly placed on a floating base
Direct-drive fans hardness and rust prevention. with rubber pad vibration isolators and a
All condenser fans are of the propeller (axial) flexible connection at the fan/casing interface.
type, which are directly mounted on the Casing All motors are of the single speed type.
motors shaft. All fans are selected for All units are constructed of heavy gauge Filters
optimum efficiency and for maximum sound galvanized steel casing without paint. All models are provided with a nominal 1.0
power reduction. Fan blades are corrosion Insulation inch thick aluminum flat filter.
resistant and are statically and dynamically Drain Pan
balanced before installation. PETRA also All units are internally lined with 0.5 inch thick
fiberglass or equivelant insulation for the coil All units are provided with a drain pan. The
provides its Patented Design for the
and fan sections. Fiber glass is coverd with drain pan is insulated to prevent condensation
mounting of the condenser fans. This new
corrogated rubber lining for low sound and and is coated with weatherproof, polyester
design offers low noise operation with high
protect the fiber against scattered. powder electrostatic paint, oven-baked to
efficiency performance. All condenser fans are
ensure maximum gloss, hardness and rust
equipped with protecting guards. B.(CM Type) prevention.
Indoor Unit Unit Description Insulation
A.(RAC & CMD Type) Units are considered to be of the Ceiling All units are internally lined with 1 inch thick
Model type. They are designed for concealed fiber glass or equivelant insulation for the coil
Unit Description ceiling installation above the false ceiling with and fan sections. Fiber glass is coverd with
Units are considered to be of the Ceiling ducted supply and free return air distribution corrogated rubber lining for low sound and
Basic with Plenum Model type. They are system. Units of this type consist of a coil, a protect the fiber against scattered.
designed for concealed ceiling installation fan and a filter.
above the false ceiling with ducted supply and
free return air distribution system. Units of this
type consist of a coil, fan and filter.
Coils
All coils are constructed of 3/8 inch diameter
copper tubes mechanically expanded into
aluminum fins. Coil fins are spaced at 12 FPI
as standard. All coils are air pressure tested at
450 Psi to avoid leakage.
2
DSP
STANDARD FEATURES
Outdoor Unit (DSP Type) CM Type
! Control and power panels include the direct- Indoor Unit Three-phase power supply
online starting for the compressor and fan RAC & CMD Type Belt driven fans
motor condenser Direct-driven fans Single-speed fan motor
! 220-240 volts as the standard control voltage Single phase power supply 1 nominal thick aluminum flat filter
(for control circuits) Expansion device
Three-speed fan motor
! Compressor time delay relay (anti re-cycling Internal thermal protection for all motors
0.5 nominal thick aluminum flat filter
protection through controller) Contactor (built-in, matching the outdoor
Nitrogen charge
! One power supply in the outdoor unit electrical panel in case unit is a complete
Internal thermal protection for all motors
! Internal thermal protection for all motors Package with indoor & outdoor units)
(compressor and condenser fan) Internal fiberglass insulation for the coil and
fan sections Digital hang-down microprocessor controller
! Service charging nipples at the valves Infrared remote handset keypad
Digital hung-down microprocessor controller
! High and low pressure protection using ! Expansion device
controller Infrared remote handset keypad
! Expansion device (Except when installed
with CM units).
! Pre-charged outdoor unit with shut off valves
(enough charge for indoor+outdoor+5 meter
pipe kit)
! Room temperature controller (hung-down
microprocessor controller)
OPTIONS
Outdoor Unit (DSP Type)
Heat pump application with a suction Power circuit breaker for motors Standard:
accumulator and 4-way reversing valve as (compressor, condenser fan motor and - Finned tube and electric heating elements
standard features in the heat pump option evaporator fan motor). - Automatic thermal safety cutout
Suction accumulator for the cooling only
unit (for low suction applications) Indoor Unit Options:
Low ambient operation control using the fan Ducted return air unit with side or bottom - Manual thermal safety cutout
speed controller (modulating type) withdrawal type filter - Contactor
Phase failure relay (only for units with three- Built-in electric heater for heating purposes If any additional options are required, please
phase power supply) (with cooling only units) or to supplement consult the PETRA factory or the nearest
External over-load for motors (compressor, heat pump PETRA sales office
condenser fan motor and evaporator fan Electric heaters are provided with the
motor only for units with three-phase power following features:
supply)
Compressor sound jacket
Ozone friendly refrigerants (R407c, R134a)
Plastic mesh protection on condenser coil
Power circuit breaker for the whole unit built
inside the electrical panel
Control circuit breaker
ACCESSORIES
3
DSP
INDOOR/OUTDOOR AVAILABLE COMBINATIONS
RAC 5
DSP 15
CMD 6
RAC 6
DSP 18
CMD 8
RAC 8
DSP 24
CMD 10
RAC 8
DSP 30 RAC 10
CMD 10
RAC 12
DSP 36
CMD 16
CMD 16
DSP 48
CM 15
CMD 20
DSP 60
CM 20
CONTROLLER
4
DSP
SELECTION PROCEDURE
The example below illustrates the step-by-step From the performance tables for cooling
selection procedure to assist any user of this data on page 17, model DSP 30 + RAC
catalog to select the appropriate unit to meet 10x3 is the closest selection to the Altitude Correction
specific requirements.
required data. [Ft] factor
5
DSP
GENERAL DATA TABLES
Outdoor Unit
MODEL [DSP] 15 18 24 30 36 48 60
Power supply Phase/Hz 1/50 (see electric data tables) 3/50 (see electric data tables)
Control voltage Volt 220-240
Unit casing Heavy gauge, galvanized steel, with oven- backed weatherproof, polyster powder electrostatic paint
Compressor Hermatically sealed
No. 1
Condenser coil Copper tube- Aluminum fins
Fins per inch 18 18 17 17 12 17 17
No.of rows 2
Face area (Total) Ft2 4.4 4.4 6.1 6.1 7.3 12.0 12.0
Tube diameter Inch 3/8
Condenser fan Propeller [Axial]
No. 1 1 1 1 1 2 2
Drive type Direct driven
Nominal air flow (50 Hz) CFM 1420 1420 2200 2200 3300 3840 3840
Refrigerant circuit 1
Refrigerant type R-22
Control Expansion device
No.of refrigerant circuits 1
Refrigerant lines sizes
Suction line diam. (Inch) 1/2 1/2 5/8 5/8 3/4 3/4 3/4
Liquid line diam. (Inch) 1/4 1/4 3/8 3/8 1/2 1/2 1/2
Operating weight Ib 97.0 97.0 132.0 152.0 165.0 260.0 260.0
Sound pressure level dB(A)
3 ft 52 53 54 57 57 55 61
10 ft 46 47 48 51 51 49 55
NOTA
6
DSP
GENERAL DATA TABLES
Indoor Unit
MODEL [RAC-CBP] 5 6 8 10 12
Power supply Phase/Hz 1/50 (see electric data tables)
Control voltage Volt 220-240
Unit casing Heavy gauge, galvanized steel, with paint
Insulation 1/2" Thick fiber-glass or equivelant
Coil Copper tube-Aluminum fins
Fins per inch 12
No.of rows 3
Face area (Total) Ft2 1.93 1.93 2.26 3.43 3.43
Tube diameter Inch 3/8
Fan Double inlet forward curved centerifugal
No. 2 2 2 4 4
Drive type Direct driven
Nominal air flow CFM 500 600 800 1000 1200
Fan motor
Type Split capacitor
No. 1 1 1 2 2
Nominal motor rating (Each) HP 1/15
Refrigerant circuit
Refrigerant lines sizes As per the matching outdoor unit
Drain connection size (Sweet) Inch 7/8
Air filter
Type Aluminum mesh type
Thickness (Nominal) Inch 1/2
Operating weight Ib 68.3 68.3 81.6 121.3 121.3
7
DSP
GENERAL DATA TABLES
Indoor Unit Sound Power Level dB
NOTA
Noise data dB
Data are measured outside the termination of the duct
8
DSP
GENERAL DATA TABLES
Indoor Unit
MODEL CMD 6 8 10 12 14 16 18 20
Power supply Volt/Phas/Hz See elctrical dat tables
Unit casing Heavy gauge galvanised steel without paint
Insulation 1" Thick fiber-glass or equivalent
Coil Copper tubes, Aluminum fins
Fins per inch 12
No. of rows 3
2
Total face area Ft 2.19 2.19 2.19 3.65 3.65 3.65 4.96 4.96
Tube Diameter inch 3/8
Fan Double inlet forward curved centrifugal
No. 1 1 1 2 2 2 2 2
Drive type Direct driven
Total air flow (Nominal) CFM 600 800 1000 1200 1400 1600 1800 2000
Fan motor Induction - TEFC - IP 55 protection - Class F insulation thermal overload protection
Type Split capacitor
No. 1 1 1 2 2 2 2 2
Nominal motor rating (Each) Kw 0.19
Refrigerant circuit
Refrigerant line sizes As per the matching outdoor unit
Drain connection size(Sweet) Inch 7/8
Air filter
Type Aluminum mesh media (Washable)
Thickness (Nominal) Inch 1/2
Operating weight Ib 66.1 66.1 66.1 119.0 119.0 119.0 149.9 149.9
9
DSP
GENERAL DATA TABLES
Indoor Unit Sound Power Level dB
NOTA
-Sound data 2 dB
-Data are taken outside the termination of the duct
10
DSP
GENERAL DATA TABLES
Indoor Unit
MODEL CM 15 20
Power supply Volt/Phas/Hz See elctrical dat tables
Unit casing Heavy gauge galvanised steel without paint
Insulation 1.0" Thick fiber-glass or equivalent
Coil Copper tubes, Aluminum fins
2
Total face area Ft 3.12 4.00
Tube Diameter Inch 3/8
Fan DWDI Forward curved centrifugal
No. 1
Type of drive Belt driven
Fan model PETRA 6
Total air flow (Nominal) CFM 1500 2000
Fan motor Induction - TEFC - IP 55 protection - Class F insulation thermal overload protection
No. 1
Drain connection size(NPT) Inch 1
Air filter Aluminum mesh type
Nominal (thickness) Inch 1
Operating weight Ib 220.5 242.5
NOTA
11
DSP
MODELS LAYOUT - DSP
Outdoor Unit
MODEL X Y Z
DSP 15, 18 30.7 9.4 20.9
5.9
Liquid Line Conn. Suction Line Conn.
Charging Nipples
Y X
11.4
5.9
MODEL X Y Z
DSP 24, 30 33.3 12.2 26.8
5.9
Liquid Line Conn. Suction Line Conn.
Charging Nipples
Y X
14.4
5.9
12
DSP
MODELS LAYOUT - DSP
Outdoor Unit
MODEL X Y Z
DSP 36 34.5 14.4 30.0
5.9
Liquid Line Conn. Suction Line Conn.
Charging Nipples
Y X
15.4
5.9
MODEL
DSP 48, 60
48.0
6.1
13.3 36.5
15.4
6.1
13
DSP
MODELS LAYOUT RAC & CMD
Indoor Units
8
.7 9.
19 0.
8
0.6
8
9. 8.
3
8
0.
6.7
9.4
Outdoor Unit
MODEL L A W
CMD Type
6 CMD 22.8 19.8 30.8
8 CMD 22.8 19.8 30.8
10 CMD 22.8 19.8 30.8
12CMD 37.1 33.6 44.8
14CMD 37.1 33.6 44.8
16CMD 37.1 33.6 44.8
28.3 0.6 18 CMD 47.1 43.6 54.9
20 CMD 47.1 43.6 54.9
11.8 0.8
10.2
0.8
14.2
16.9
14
DSP
MODELS LAYOUT CM
Indoor Units
MODEL L W H F C
CM 15 38.8 41.7 21.3 13.0 11.4
CM 20 45.9 41.7 21.4 13.0 11.4
AIR FLOW
AIR FLOW
1 inch Thick
AIR FLOW
15
DSP
MODELS LAYOUT CM
Indoor Units
FAN
COIL
40
AIR FLOW
1 inch Thick
1.57
MODEL L W H F C R X Y
CMV 15 38.8 26.5 45.7 13.0 11.4 2.4 23.6 26.8
CMV 20 45.8 25.6 45.7 13.0 11.4 3.9 30.1 26.8
16
DSP
PERFORMANCE DATA TABLES
NOTE
- All indoor units have one refrigerant circuit
17
DSP
PERFORMANCE DATA TABLES
EVAPORATOR OUTDOOR ENTERING TEMPERATURE [oF]
MODEL ON COIL 85 95 105 115 120
AFR
DB WB T.Cap S.Cap PI T.Cap S.Cap PI T.Cap S.Cap PI T.Cap S.Cap PI T.Cap S.Cap PI
76 63 21.2 17.1 1.7 20.2 16.8 1.8 19.2 16.4 2.0 18.3 16.0 2.2 17.8 15.9 2.3
849 78 65 21.9 17.1 1.7 20.9 16.7 1.9 19.9 16.3 2.0 18.9 16.0 2.2 18.4 15.8 2.3
80 67 23.0 17.1 1.7 22.0 16.8 1.9 21.0 16.4 2.1 20.0 16.0 2.3 19.4 15.9 2.4
76 63 20.4 15.2 1.7 19.5 14.8 1.8 18.6 14.4 2.0 17.7 14.1 2.2 17.2 13.9 2.3
DSP 18+CMD 8X3 675 78 65 21.2 15.1 1.7 20.3 14.8 1.8 19.3 14.4 2.0 18.4 14.0 2.2 17.9 13.9 2.3
80 67 22.2 15.1 1.7 21.2 14.8 1.9 20.3 14.4 2.1 19.3 14.1 2.3 18.8 13.9 2.4
76 63 19.8 13.7 1.6 18.9 13.4 1.8 18.0 13.0 2.0 17.1 12.7 2.2 16.7 12.5 2.3
555 78 65 20.5 13.7 1.7 19.6 13.3 1.8 18.7 13.0 2.0 17.8 12.6 2.2 17.3 12.5 2.3
80 67 21.4 13.7 1.7 20.5 13.3 1.8 19.6 13.0 2.0 18.7 12.7 2.2 18.2 12.5 2.3
76 63 26.2 20.6 1.8 25.1 20.1 2.0 24.0 19.7 2.3 23.0 19.3 2.5 22.5 19.1 2.6
1003 78 65 27.1 20.5 1.9 26.0 20.0 2.1 24.9 19.7 2.3 23.9 19.3 2.5 23.3 19.1 2.7
80 67 28.3 20.5 1.9 27.2 20.1 2.1 26.1 19.7 2.3 25.1 19.3 2.6 24.6 19.1 2.7
76 63 25.5 18.9 1.8 24.5 18.5 2.0 23.4 18.0 2.2 22.5 17.7 2.5 22.0 17.5 2.6
DSP 24+CMD 10X3 849 78 65 26.4 18.8 1.8 25.3 18.3 2.0 24.3 18.0 2.3 23.3 17.6 2.5 22.8 17.4 2.6
80 67 27.6 18.8 1.9 26.5 18.4 2.1 25.5 18.0 2.3 24.5 17.6 2.5 24.0 17.4 2.7
76 63 24.6 16.9 1.8 23.6 16.5 2.0 22.6 16.0 2.2 21.7 15.7 2.4 21.2 15.5 2.6
675 78 65 25.4 16.8 1.8 24.4 16.4 2.0 23.4 16.0 2.2 22.4 15.6 2.5 22.0 15.4 2.6
80 67 26.5 16.8 1.8 25.5 16.4 2.0 24.5 16.0 2.3 23.5 15.6 2.5 23.1 15.4 2.7
76 63 30.1 22.1 2.4 29.0 21.7 2.7 27.9 21.2 2.9 26.6 20.7 3.2 26.0 20.5 3.4
1003 78 65 31.1 22.0 2.5 30.0 21.5 2.7 28.8 21.1 3.0 27.6 20.6 3.3 26.9 20.4 3.4
80 67 32.5 22.0 2.5 31.3 21.6 2.8 30.1 21.1 3.0 28.8 20.6 3.3 28.1 20.4 3.5
76 63 29.3 20.4 2.4 28.3 20.0 2.7 27.2 19.5 2.9 26.0 19.0 3.2 25.4 18.8 3.4
DSP 30+CMD 10X3 849 78 65 30.2 20.3 2.4 29.2 19.8 2.7 28.1 19.4 3.0 26.9 18.9 3.2 26.2 18.7 3.4
80 67 31.6 20.3 2.5 30.5 19.8 2.7 29.3 19.4 3.0 28.1 19.0 3.3 27.4 18.7 3.5
76 63 28.0 18.3 2.4 27.1 17.9 2.6 26.1 17.5 2.9 25.0 17.0 3.1 24.4 16.8 3.3
675 78 65 29.0 18.2 2.4 28.0 17.8 2.6 26.9 17.4 2.9 25.8 17.0 3.2 25.3 16.7 3.3
80 67 30.2 18.2 2.4 29.2 17.8 2.7 28.1 17.4 3.0 27.0 16.9 3.3 26.4 16.7 3.4
76 63 34.9 30.5 2.2 33.5 30.0 2.5 32.0 29.4 2.8 30.4 28.9 3.2 29.5 28.5 3.4
1628 78 65 36.2 30.4 2.2 34.7 29.9 2.5 33.2 29.3 2.8 31.5 28.8 3.2 30.7 28.5 3.4
80 67 37.9 30.4 2.3 36.4 30.0 2.5 34.9 29.4 2.9 33.2 28.8 3.2 32.3 28.5 3.4
76 63 34.0 27.1 2.2 32.6 26.6 2.5 31.2 26.0 2.8 29.6 25.4 3.1 28.8 25.1 3.3
DSP 36+CMD 16X3 1312 78 65 35.2 26.9 2.2 33.8 26.4 2.5 32.3 25.9 2.8 30.7 25.3 3.2 29.9 25.0 3.4
80 67 36.8 27.0 2.3 35.4 26.5 2.5 33.9 25.9 2.8 32.3 25.4 3.2 31.5 25.1 3.4
76 63 33.0 24.5 2.2 31.8 24.0 2.4 30.4 23.5 2.8 28.9 22.9 3.1 28.1 22.6 3.3
1089 78 65 34.2 24.4 2.2 32.9 23.9 2.5 31.5 23.4 2.8 29.9 22.8 3.2 29.1 22.5 3.3
80 67 35.8 24.4 2.2 34.4 23.9 2.5 33.0 23.4 2.8 31.5 22.8 3.2 30.6 22.6 3.4
76 63 48.6 35.8 3.4 46.8 35.1 3.8 45.0 34.4 4.3 43.2 33.7 4.8 42.4 33.4 5.1
1628 78 65 50.2 35.6 3.4 48.4 34.9 3.9 46.6 34.2 4.3 44.8 33.6 4.9 43.9 33.3 5.2
80 67 52.4 35.6 3.5 50.6 34.9 3.9 48.8 34.2 4.4 46.9 33.6 5.0 46.1 33.3 5.3
76 63 46.8 32.2 3.4 45.2 31.5 3.8 43.5 30.9 4.2 41.8 30.2 4.8 41.0 29.8 5.1
DSP 48+CMD 16X3 1312 78 65 48.4 32.0 3.4 46.7 31.4 3.8 45.0 30.7 4.3 43.2 30.0 4.8 42.4 29.7 5.1
80 67 50.5 32.0 3.5 48.8 31.4 3.9 47.0 30.7 4.3 45.3 30.1 4.9 44.5 29.8 5.2
76 63 45.2 29.5 3.3 43.6 28.9 3.7 42.0 28.2 4.2 40.4 27.5 4.7 39.6 27.2 5.0
1089 78 65 46.7 29.4 3.4 45.1 28.7 3.8 43.4 28.0 4.2 41.8 27.4 4.8 41.0 27.1 5.1
80 67 48.7 29.4 3.4 47.1 28.8 3.8 45.4 28.1 4.3 43.7 27.4 4.8 42.9 27.1 5.1
76 63 52.3 40.6 3.5 50.4 39.8 3.9 48.4 39.1 4.4 46.4 38.3 4.9 45.5 37.9 5.2
1938 78 65 54.1 40.4 3.6 52.1 39.7 4.0 50.1 38.9 4.4 48.1 38.2 5.0 47.2 37.8 5.3
80 67 56.6 40.4 3.7 54.6 39.7 4.1 52.5 39.0 4.5 50.5 38.2 5.1 49.5 37.9 5.4
76 63 50.9 37.0 3.5 49.0 36.2 3.9 47.1 35.5 4.3 45.2 34.8 4.9 44.3 34.4 5.2
DSP 60+CMD 20X3 1619 78 65 52.6 36.8 3.5 50.8 36.1 3.9 48.8 35.3 4.4 46.9 34.6 5.0 46.0 34.3 5.3
80 67 55.0 36.8 3.6 53.1 36.1 4.0 51.1 35.4 4.5 49.2 34.7 5.0 48.2 34.4 5.3
76 63 48.7 32.8 3.4 47.0 32.0 3.8 45.1 31.3 4.3 43.3 30.6 4.8 42.5 30.2 5.1
1262 78 65 50.4 32.6 3.5 48.6 31.9 3.9 46.7 31.1 4.3 44.9 30.4 4.9 44.1 30.1 5.2
80 67 52.6 32.6 3.5 50.8 31.9 3.9 48.9 31.2 4.4 47.1 30.5 5.0 46.2 30.1 5.3
76 63 45.8 32.4 3.3 44.2 31.8 3.7 42.6 31.1 4.2 41.0 30.5 4.7 40.1 30.2 5.1
1404 78 65 47.4 32.3 3.4 45.7 31.7 3.8 44.0 31.0 4.3 42.4 30.3 4.8 41.6 30.0 5.1
80 67 49.4 32.2 3.4 47.8 31.6 3.8 46.0 31.0 4.3 44.3 30.4 4.9 43.6 30.0 5.2
76 63 46.6 34.1 3.4 45.0 33.5 3.8 43.3 32.8 4.2 41.6 32.2 4.8 40.8 31.9 5.1
DSP 48+CM 15X3 1560 78 65 48.2 33.9 3.4 46.5 33.3 3.8 44.8 32.6 4.3 43.1 32.0 4.8 42.3 31.7 5.1
80 67 50.3 33.9 3.4 48.6 33.3 3.9 46.8 32.6 4.3 45.1 32.0 4.9 44.3 31.8 5.2
76 63 47.3 35.8 3.4 45.6 35.1 3.8 43.9 34.4 4.2 42.2 33.8 4.8 41.4 33.5 5.1
1716 78 65 48.9 35.6 3.4 47.2 34.9 3.8 45.4 34.3 4.3 43.7 33.6 4.8 42.9 33.3 5.1
80 67 51.0 35.5 3.5 49.3 34.9 3.9 47.5 34.3 4.4 45.7 33.7 4.9 44.9 33.4 5.2
76 63 50.3 38.2 3.4 48.4 37.5 3.9 46.5 36.7 4.3 44.6 36.0 4.9 43.8 35.7 5.2
1800 78 65 51.9 38.0 3.5 50.1 37.3 3.9 48.2 36.6 4.4 46.3 35.9 4.9 45.4 35.6 5.2
80 67 54.3 38.0 3.6 52.4 37.3 4.0 50.5 36.6 4.5 48.5 36.0 5.0 47.6 35.6 5.3
76 63 51.0 40.3 3.5 49.1 39.6 3.9 47.2 38.8 4.3 45.3 38.1 4.9 44.4 37.8 5.2
DSP 60+CM 20X3 2000 78 65 52.7 40.1 3.5 50.8 39.4 3.9 48.9 38.7 4.4 46.9 38.0 5.0 46.0 37.7 5.3
80 67 55.1 40.1 3.6 53.2 39.4 4.0 51.2 38.8 4.5 49.2 38.1 5.0 48.3 37.7 5.3
76 63 51.6 42.3 3.5 49.7 41.6 3.9 47.8 40.9 4.4 45.8 40.2 4.9 44.9 39.8 5.2
2200 78 65 53.4 42.2 3.5 51.5 41.4 4.0 49.5 40.7 4.4 47.5 40.0 5.0 46.6 39.7 5.3
80 67 55.8 42.2 3.6 53.9 41.5 4.0 51.8 40.8 4.5 49.9 40.1 5.1 48.9 39.8 5.4
NOTE
- All indoor units have one refrigerant circuit
18
DSP
FAN PERFORMANCE TABLES-INDOOR UNITS
Aluminum Mesh Filter 4 Rows
All data are based on wet coil conditions with a 2-pipe system coil [Single cooling coil] and
includes 15 mm aluminum mesh flat filter pressure drop.
NOTA
All data are based on wet coil conditions with a 2-pipe system coil [Single cooling coil] and
includes 15 mm aluminum mesh flat filter pressure drop.
19
DSP
FILTER & COIL PRESSURE DROP CHARTS-INDOOR UNITS
For CM Type
62.5
50
37.5
25
12.5
0.00
0.762 1.269 1.778 2.285 2.793 3.301
Face velocity (FPM)
125
100 4-Rows
75
50
25
0
1.5 2.0 2.5 3.0
20
DSP
ELECTRICAL DATA TABLES
Legend:
NOTA
* MCA is based on 125% of the RLA for the largest motor plus 100% of the RLA/FLA for
all other loads included in the circuit (NEC-Article 430-24).
* MOP is based on 225% of the RLA for the largest motor plus 100% of the RLA for all
other loads included in the circuit (NEC-Article 440-22).
* MDS is based on 115% of the total summation of RLA/FLA for all loads included in the
circuit (NEC-Article 440- 12A1).
21
DSP
ELECTRICAL DATA TABLES
Nominal motor
Power supply FLA MCA MOP
MODEL No. power (Each)
Volt/Phase/Hz [Amp] [Amp] [Amp]
[kW]
RAC 5 220 - 240 / 1 / 50 1 0.05 0.85 1.06 15
RAC 6 220 - 240 / 1 / 50 1 0.05 0.85 1.06 15
RAC 8 220 - 240 / 1 / 50 1 0.05 0.85 1.06 15
RAC 10 220 - 240 / 1 / 50 2 0.05 0.85 1.91 15
RAC 12 220 - 240 / 1 / 50 2 0.05 0.85 1.91 15
Legend
NOTA
MCA is based on 125% of the FLA for the largest motor plus 100% of FLA for all other loads included in the circuit (NEC-Article 430-24).
MOP is based on 225% of the FLA for the largest motor plus 100% of the FLA for all other loads included in the circuit (NEC-Article 440-22).
22
DSP
ELECTRICAL DATA TABLES
Nominal motor
Power supply FLA MCA MOP
MODEL No. power (Each)
Volt/Phase/Hz [Amp] [Amp] [Amp]
[kW]
CMD 6 220 - 240 / 1 / 50 1 0.19 1.4 1.75 15
CMD 8 220 - 240 / 1 / 50 1 0.19 1.4 1.75 15
CMD 10 220 - 240 / 1 / 50 1 0.19 1.4 1.75 15
CMD 12 220 - 240 / 1 / 50 2 0.19 1.4 3.15 15
CMD 14 220 - 240 / 1 / 50 2 0.19 1.4 3.15 15
CMD 16 220 - 240 / 1 / 50 2 0.19 1.4 3.15 15
CMD 18 220 - 240 / 1 / 50 2 0.19 1.4 3.15 15
CMD 20 220 - 240 / 1 / 50 2 0.19 1.4 3.15 15
Legend
NOTA
MCA is based on 125% of the FLA for the largest motor plus 100% of FLA for all other loads included in the circuit (NEC-Article 430-24).
MOP is based on 225% of the FLA for the largest motor plus 100% of the FLA for all other loads included in the circuit (NEC-Article 440-22).
23
DSP
ELECTRICAL DATA TABLES
Legend
NOTA
24
DSP
TYPICAL WIRING DIAGRAMS
LEGEND
25
DSP
TYPICAL WIRING DIAGRAMS
26
DSP
TYPICAL WIRING DIAGRAMS
LEGEND
27
DSP
REFRIGERATION SCHEMATIC DIAGRAM
28