You are on page 1of 21

Type Test Report AMTR04423-01

Test object Air insulated metal-enclosed switchgear

Type PIX 17

Manufacturer AREVA T & D

Test Laboratory AREVA AMT, Testing laboratory

Location of tests Mcon

Date of tests March 26th 2004

Test Specification IEC 60271-200 and IEC60271-102 standards

Tests performed Mechanical endurance 1000 operations on earthing switch

Test results The requirements were met.

Mcon, May 17th, 2004

Eric Pillon Alain QUEMIN


Project Leader Test engineer
AMTR04423-01

Contents

Page
1. Technical data of the test object .................................................................................... 3

2. Dimensional drawing ...................................................................................................... 4

3. Tests witnesses ............................................................................................................... 5

4. Test object........................................................................................................................ 5

5. Test arrangement ............................................................................................................ 5

6. Test- and measuring circuits.......................................................................................... 6

7. List of measuring instruments ....................................................................................... 6

8. Test results ...................................................................................................................... 7

9. Oscillograms.................................................................................................................... 8

10. Photo ........................................................................................................................... 14

11. Drawings ..................................................................................................................... 16

This Type Test Report consists of 21 pages.


The results of this Type Test Report refer only to the test object.
The reproduction of excerpts of this report is only permitted with written approval of the Test Laboratory.
This Type Test Report is according to EN 45001.

Page 2 of 21
AMTR04423-01

1. Technical data of the test object

Identification number of the test object IO 5865 N6

Year of manufacturing 2003

Rated voltage 17,5 kV

Rated lightning impulse withstand voltage 95 kV

Rated power frequency withstand voltage 42 kV

Rated frequency 50/60 Hz

Rated normal current 2500 A

Width of function unit 1000 mm

Distance between phases 254 mm

Short time withstand current - Main circuit 40 kA / 3s


- Earthing switch 40 kA / 1s
Peak withstand current 100 kAp

Peak making capacity of earthing switch (at 17,5kV) 100 kAp

Degree of protection IP3X

Page 3 of 21
AMTR04423-01

2. Dimensional drawing

Page 4 of 21
AMTR04423-01

3. Test witnesses

J.P. Haegeman LABORELEC


D.Melchior AREVA T&D Belgium
N.Deb AREVA T&D Macon
D.Thomas AREVA T&D Macon

4. Test object

Three-phase metal enclosed air insulated switchgear partition class PM type PIX 1000mm
wide - (17,5kv-40kA-2500A).
Earthing switch endurance class : M0.
The cable compartment was equipped with 3-off DIN current transformers 2500/5A-10VA-
10P10 Ref : 02/10273731 , 02/10273732, 02/10273733.
The earthing switch micro-switches arrangement was also fitted and the operations counter
was connected to one of the micro-switches.

Condition before the tests: brand-new

5. Test arrangement

The test procedure was based on IEC62271-102.

- Test procedure

Before tests :
Record of earthing switch travel.
Record of operating torque.
Record of earthing switch contact resistance.

Tests :
1000 manual operating cycles of the earthing switch

After tests :
Record of earthing switch travel.
Record of operating torque.
Record of earthing switch contact resistance.

Photo of the test object and of the test arrangement : see page 14 and 15.

Page 5 of 21
AMTR04423-01

6. Test- and measuring circuits

Travels were measured with a rotary displacement transducer connected to a data


acquisition system to display and capture readings.

Torques were recorded with a calibrated torque meter.

Contact resistances were measured with a 100A micro-ohmmeter.

7. List of measuring instruments

Measuring instrument Identification number


Torque meter 5-20 daN.m -
Micro-ohmmeter MOM200A -
Voltage supply 300v 15A C61447
Voltage supply 60v 60A C61443
Acquisition system C61444, C61445
C64136, C64160
Rotary 350 displacement transducer -

Page 6 of 21
AMTR04423-01

8. Test results

8.1. MEASUREMENTS BEFORE THE ENDURANCE TESTS

See oscillograms on page 8 to 10

Travel :

Closing speed : 45,0 rad/s (measured 10ms before contact make)


Total stroke : 91,6

Operating torque :

Maximum opening torque : 153Nm


Maximum closing torque : 37,8Nm

Contact resistances between jaws and knifes : R1 = 16 , R2 =18 , R3= 19

8.2. MEASUREMENTS AFTER 1000 OPERATIONS

See oscillograms on page 11 to 13

Travel :

Closing speed : 42,5 rad/s


Total stroke : 92,9

Operating torque :

Maximum opening torque : 188Nm


Maximum closing torque : 44,1Nm

Contact resistances between jaws and knifes : R1 = 15 , R2 =19 , R3= 19

After 1000 operations the closing speed and the maximum opening torque remain within
acceptable limits.

After the tests the earthing switch was in good operating condition. And so was the
associated micro-switches arrangement.

By this it is proven:

Mechanical endurance 1000 operations of the earthing switch of PIX-17,5 unit


according to IEC 62271-102 6.102.3

In order to verify the good condition of the earthing switch, an additionnal 200 operations
were carried out without any problem.

Page 7 of 21
AMTR04423-01

9. Oscillograms

Travel, operating torque and contact separation on C/O operation before test

Page 8 of 21
AMTR04423-01

Travel and operating torque on C/O operation before test

Page 9 of 21
AMTR04423-01

Travel and contact separation on close operation before test

Page 10 of 21
AMTR04423-01

Travel , operating torque and contact separation on C/O operation after 1000 C/O operations

Page 11 of 21
AMTR04423-01

Travel and operating torque on C/O operation after 1000 C/O operations

Page 12 of 21
AMTR04423-01

Travel and contact separation on close operation after 1000 C/O operations

Page 13 of 21
AMTR04423-01

10. Photos

PIX 17.5 unit before earthing switch endurance tests

Page 14 of 21
AMTR04423-01

PIX 17.5 unit before earthing switch endurance tests

Page 15 of 21
AMTR04423-01

11. Drawings

Title of the drawing Drawing number Remark Page


PIX 17,5 2500A Outline AMT002236-01/00 Enclosed 17
Earthing switch operating part AMT000234-19/00 Checked
Earthing switch power part AMT000157-12/01 Enclosed 18
Knife AMT000299-02/05 Enclosed 19
Contact AMT001178-01/02 Enclosed 21
Jaws AMT000236-01/02 Enclosed 20
Tumbler equipped AMT000298-01/01 Checked
Compression spring AMTC35511-01/02 Checked
Indicator ES AMT000401-26/00 Checked

Page 16 of 21
AMTR04423-01

Page 17 of 21
AMTR04423-01

Page 18 of 21
AMTR04423-01

Page 19 of 21
AMTR04423-01

Page 20 of 21
AMTR04423-01

Page 21 of 21

You might also like