You are on page 1of 1

Data Sheet

Model No NLPA-5.1

kW 9.2
Unit
charact Cooling capacity 103 kcal/h 7.9
eristics
TR 2.6
Total power KW 4.7

Total operation current A 8.6


Quantity 1
Compressor
Input power kW 3.9
Operation
A 6.9
current
Water pipe
mm 26
connection
Chilled water
Water flow L/min 25

Condenser Input power KW 0.42


fan Input current A 0.85

Chilled water Input power KW 0.37


pump Head MH20 21
Tank nominal volume L 75
L mm 1150
Overall
W mm 700
dimensions
H mm 1120
Total weight KG 200

Note: 1, the cooling conditions: cold water inlet temperature 0 , the water
temperature -5 ; ambient temperature 35 ; cold side must use antifreeze, it is
recommended to use 25% (V / V) ethylene glycol solution.
2 This series of units imported sealed compressorfrom Europe and the United States,
with superior performance, anti-liquid strike ability;
3, the unit safe working range: chilled water inlet temperature -3 -10 ;
4, the power system: 3P-380V-50Hz, the proposed three-phase four-wire system,
allowing voltage fluctuations 5%, frequency fluctuations 2%;
5, the host of the actual head for the pump head less than the host internal head loss.
(1 mH2O = 9.8 kPa)