You are on page 1of 48

EOLO Maior kW

EOLO Maior kW
EOLO Maior kW X
Instantaneous wall-hung
boilers with sealed-room

EOLO Maior kW X
Wall-hung boilers with sealed-
room for central heating only
or with external storage tank

S.C FUTURE LINE INSTAL S.R.L


str. Biharia nr.67-77, sector 1, Bucuresti, ROMANIA
serviceimmergas.ro
Dispecerat Non Stop
Tel. Fix : 021-201.11.14

http://serviceimmergas.ro
http://serviceimmergas.ro
Technical Documentation Technical Documentation

EOLO Maior 24-28-32 kW

Wall-hung boiler for heating and instantaneous


production of domestic hot water, with sealed
chamber and forced draught

EOLO Maior 24 kW
EOLO Maior 28 kW
EOLO Maior 32 kW

General features.
EOLO Maior kW is a wall-hung boiler room sealed fan assisted Combustion air ow into the sealed chamber and ue
(C type) for heating and production of domestic hot water. extraction are ensured by a fan; the correct operation of which
This boiler can be installed also in B22 conguration thanks to is controlled by a dierential pressure switch.
a special (optional) kit. The boiler functioning parameters are set by turning the control
EOLO Maior kW boilers are approved for outdoor installation panel knobs.
in partially protected places. The functioning status and possible anomalies are easily signal-
N.B.: We mean partially protected place when the appliance is not led by leds on the panel.
directly exposed to weather conditions (rain, snow, hail, etc..).
There are 3 versions in the range, with powers of 24 kW
(20,640 kcal/h), 28 kW (24,080 kcal/h) and 32 kW (27,520
kcal/h).
The regulation and the control functions are managed by an
electronic control board microprocessor with continuous 2-
sensor ame modulation (d.h.w. and central heating).
Thanks to which the appliance can be connected to the Amico
Remote Control.
The boiler features a standard antifreeze safety device that
protects it against temperatures as low as -5C (optional as
low as -15C).
The hydraulic circuit features a copper water-gas
exchanger as well as a new hydraulic unit in a compound
material.
Besides the pump and 3-way electric diverter valve, that,
depending on needs, lets boiler water circulate in the central
heating system or in a stainless steel plate exchanger for the
instant production of domestic hot water, this unit also
houses the devices that control the hydraulic circuit (system
absolute pressure switch, system adjustable by-pass, etc.).

STEkW ed 12/06 1http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior 28 kW X

Wall-hung boiler sealed chamber and forced


draught for heating only, pre-arranged for the
connection to a separate storage tank

EOLO Maior 28 kW X

General features.
EOLO Maior kW X is a wall-hung boiler room sealed fan The boiler functioning parameters are set by turning the control
assisted (C type) that provides space heating only, pre-arranged panel knobs.
for the connection to a separate storage tank of 80, 105, 120, The functioning status and possible anomalies are easily signal-
e 200 litres, thanks to a special (optional) kit. led by leds on the panel.
This boiler can be installed also in B22 conguration thanks to
a special (optional) kit.
EOLO Maior kW X boilers are approved for outdoor instal-
lation in partially protected places.
N.B.: We mean partially protected place when the appliance is not
directly exposed to weather conditions (rain, snow, hail, etc..).
The boiler is available with a power of 28 kW (24,080 kcal/
h).
The regulation and the control functions are managed by an
electronic control board microprocessor drive.
Thanks to which the appliance can be connected to the Amico
Remote Control.
The boiler features a standard antifreeze safety device that
protects it against temperatures as low as -5C (optional as
low as -15C).
The hydraulic circuit features a copper water-gas exchanger
as well as a new hydraulic unit in a compound material.
Besides the pump, this unit also houses the devices that con-
trol the hydraulic circuit (system absolute pressure switch, system
adjustable by-pass, etc.).
Combustion air ow into the sealed chamber and ue
extraction are ensured by a fan; the correct operation of which
is controlled by a dierential pressure switch.

STEkW ed 12/06 2http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior kW main dimensions and connections.

Legend:
G - Gas supply
AC - D.h.w. outlet
AF - D.h.w. (cold) inlet
R - System return
M - System delivery
V - Electrical connection

Height (mm) Width (mm) Depth (mm)

830 440 350

CONNECTIONS
DOMESTIC
GAS SYSTEM
HOT WATER
G AC AF R M

1/2 1/2 1/2 3/4 3/4

EOLO Maior kW control panel.

Legend:
1 - Stand by LED 9 - Temperature LED Delivery probe faulty
2 - Burner on LED 10 - Temperature LED Domestic hot water probe faulty
3 - D.h.w. on LED 11 - Temperature LED Overheating lock
4 - Central heating on LED 12 - Stand-by-D.h.w./Remote Control (CAR)-D.h.w. and Heating-Reset-
5 - Temperature LED Ignition stop malfunction selector switch
6 - Temperature LED Flue pressure switch malfunction 13 - D.h.w. temperature knob
7 - Temperature LED System pressure insucient malfunction 14 - Central heating temperature knob
8 - Temperature LED Circulation insucient malfunction 15 - Boiler manometer

STEkW ed 12/06 3http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior kW X Main dimensions and connections.

Legend:
G - Gas supply
RR - System lling
R - System return
M - System delivery
V - Electrical connection

Height (mm) Width (mm) Depth (mm)

830 440 350

CONNECTIONS

GAS WATER SYSTEM

G RR R M

1/2 1/2 3/4 3/4

EOLO Maior kW X Control panel.

Legend:
1 - Stand by LED 9 - Temperature LED Delivery probe faulty
2 - Burner on LED 10 - Temperature LED Domestic hot water probe faulty (optional)
3 - D.h.w. on LED 11 - Temperature LED Overheating lock
4 - Central heating on LED 12 - Stand-by-D.h.w./Remote Control (CAR)-D.h.w. and Heating-Reset-
5 - Temperature LED Ignition stop malfunction selector switch
6 - Temperature LED Flue pressure switch malfunction 13 - D.h.w. temperature knob (optional)
7 - Temperature LED System pressure insucient malfunction 14 - Central heating temperature knob
8 - Temperature LED Circulation insucient malfunction 15 - Boiler manometer

STEkW ed 12/06 4http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior kW main components.

Legend: 13 - Delivery NTC probe


1 - Gas valve 14 - Overheating Safety thermostat
2 - D.H.W. NTC probe 15 - Draught diverter
3 - D.H.W. ow switch 16 - Primary exchanger
4 - D.H.W. heat exchanger 17 - System expansion vessel
5 - Burner 18 - Ignition and detection electrodes
6 - Combustion chamber 19 - Automatic air vent
7 - Sealed chamber 20 - Circulator
8 - Fan 21 - System pressure switch
9 - Intakes (air A) - (ues F) 22 - 3-bar safety valve
10 - Positive signal pressure point 23 - Three-way valve (motorized)
11 - Negative signal pressure point 24 - System draining cock
12 - Flue pressure switch 25 - System lling valve

STEkW ed 12/06 5http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior kW X main components.

Legend: 12 - Draught diverter


1 - Gas valve 13 - Primary exchanger
2 - Burner 14 - Ignition and detection electrodes
3 - Combustion chamber 15 - System expansion vessel
4 - Sealed chamber 16 - Automatic air vent
5 - Fan 17 - Circulator
6 - Intakes (air A) - (ues F) 18 - System pressure switch
7 - Positive signal pressure point 19 - 3-bar safety valve
8 - Negative signal pressure point 20 - Three-way valve plug
9 - Flue pressure switch 21 - System draining cock
10 - Delivery NTC probe 22 - System lling valve
11 - Overheating Safety thermostat

STEkW ed 12/06 6http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior kW hydraulic diagram.

Legend: 15 - Circulator
1 - D.H.W. ow switch 16 - Three-way valve (motorized)
2 - D.H.W. NTC probe 17 - System draining cock
3 - D.H.W. heat exchanger 18 - System lling valve
4 - Gas valve 19 - Adjustable by-pass
5 - Burner 20 - System pressure switch
6 - Primary exchanger 21 - 3-bar safety valve
7 - Draught diverter 22 - One-way valve
8 - Fan 23 - Flow limiter
9 - Sealed chamber
10 - Flue pressure switch G - Gas supply
11 - Delivery NTC probe AC - D.h.w. outlet
12 - Overheating Safety thermostat AF - D.h.w. (cold) inlet
13 - System expansion vessel R - System return
14 - Automatic air vent M - System delivery

Hot water for central heating and domestic use is produced


by a primary and secondary (d.h.w.) circuit that are engaged
according to requirements.

STEkW ed 12/06 7http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior kW X hydraulic diagram.

Legend: 12 - Circulator
1 - Gas valve 13 - System draining cock
2 - Burner 14 - Three-way valve (without motor)
3 - Primary exchanger 15 - Adjustable by-pass
4 - Draught diverter 16 - System pressure switch
5 - Fan 17 - 3-bar safety valve
6 - Sealed chamber 18 - System lling valve
7 - Flue pressure switch
8 - Delivery NTC probe G - Gas supply
9 - Overheating Safety thermostat RR - System lling
10 - System expansion vessel R - System return
11 - Automatic air vent M - System delivery

The primary circuit with relevant control and safety devices


is triggered each time there is a request for central heating or
antifreeze.

STEkW ed 12/06 8http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Primary circuit (boiler circuit).

The primary circuit with relevant control and safety devices (16) which, when idle, lets the water ow through the d.h.w.
is triggered each time there is a request for central heating exchanger (3); on the other hand, when responding to a heat-
or domestic hot water. ing request, the ow is diverted to the system delivery (M)
and return (R) pipes.
Operation (see EOLO Maior kW).
The heat contained in the ue produced by combustion is ab- Flow-head graph.
sorbed by the copper blades of the primary water-gas exchanger The trend of the curve that represents the systems ow-head
(6) which, in turn, transfers it to the water circulating inside ratio depends on how fast the pump is working and on how
it by means of the boiler pump (15). the system by-pass is adjusted. Depending on the position,
The water is transferred directly into the system or else can it provides the system with a higher or a smaller head. The
be diverted inside the stainless steel instantaneous plate ex- characteristic curves are shown in the following graphs.
changer (3).
This depends on the position of the motorised 3-way valve

EOLO Maior 24 kW

Head (m H2O)
Head (kPa)

B A

Flow rate Litres/h

EOLO Maior 28 kW - 28 kW X
Head (m H2O)
Head (kPa)

Flow rate Litres/h

A = Head available to the system on maximum speed with the by-pass o (adjustment screw fully tightened)
B = Head available to the system on maximum speed (screw tightened 1.5 turns compared to the adjustment screw completely loose)
C = Head available to the system on maximum speed with the by-pass open (adjustment screw completely loose)

STEkW ed 12/06 9http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior 32 kW

Head (m H2O)
A
Head (kPa)

Flow rate Litres/h

A = Head available to the system on maximum speed with the by-pass o (adjustment screw fully tightened)
B = Head available to the system on maximum speed (screw tightened 1.5 turns compared to the adjustment screw completely loose)
C = Head available to the system on maximum speed with the by-pass open (adjustment screw completely loose)

Boiler circulator (1). Primary exchanger (1).


It works on the primary circuit return, located immediately It is a water-gas lamellar exchanger with copper pipes and
after the 3-way diverter valve to which it is connected. ns (N 75 ns 24 kW version) (N 98 ns 28 and 32 kW
It is part of the integrated multi-function unit made in a version). The central heating delivery NTC probe (2) and the
compound material. overheating safety thermostat (3) are located on the exchangers
A space on the body houses the automatic air vent (2). outlet (delivery).
The four pipes it is made of are connected in series (4).
It is connected to the pump delivery and primary circuit deli-
very by means of pipes with threaded ttings.

3 4

Return
Delivery

STEkW ed 12/06 10http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Motorised 3-way diverter valve for combi mod-


els.
Whenever a request is made (for domestic hot water or central
Circulator
heating) thanks to this 3-way electric diverter valve, working on delivery
the primary circuit return, boiler water is transferred either to
the heating system or to the d.h.w. exchanger (plate type).
This depends on the position of the shutter (5) which shuts
o passage to the system and simultaneously opens the way
to the d.h.w. exchanger (domestic hot water position) or, vice
versa (central heating position).
This shutter (5) is moved in either position by powering the
motor (1).
The hydraulic part of the boiler consists of a unit made in a
composite material (2) that also includes the circulator and it is 2 5
operated by a motor (1) which causes it to move as required.

Operation.
When the central heating or domestic hot water position has
to be reached the motor (1) is switched on by the integrated 1
board. System
Each time the motor turns of 180 it causes the shutter (5) to return
move and it compresses (central heating position) or releases the 3 4
shutters contrast spring (4) (domestic hot water position).
Both the spring (4) and shutter (5) are inside the 3-way car-
tridge (3).
When the position requested is reached hydraulically, one of
two limit switches (6) located inside the motor box (1) opens
and closes alternately.
When idle, the shutter (5) is positioned in d.h.w. functio-
ning.
Each time an heating request is satised the motor (1) turns
and releases the shutter's contrast spring (4).
On the contrary, at the end of each d.h.w. request, the shutter
(5) remains in the position reached.

CIRCULATOR
RETURN

D.H.W.
EXCHANGER
RETURN

SYSTEM
RETURN

STEkW ed 12/06 11http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Safety devices and controls for combi versions.

Adjustable system by-pass (2).


This device guarantees the circulation of water in the primary
circuit (between delivery and return) even when it would be
prevented by the high resistance of the system. 1
It is mounted on the delivery manifold (1) and adjusted by a
screw that can be accessed from the bottom of the valve sup-
porting plate.
2

System lling unit (3).


This is a ball cock located between the boiler circuit and the
domestic cold water inlet and it makes possible to pressurise
the central heating system.
The cock is connected to a lling up tting (4) which, in turn,
is connected to the motorised 3-way diverter valve unit. System
delivery

System pressure switch (5).


6
This switch detects the pressure inside the primary circuit. It
is housed in the delivery manifold unit (1) and coupled to a
microswitch that prevents the burner working when the pres-
sure measured is below 0.3 bar.
It prevents the primary exchanger overheating.
4
Automatic air vent (6).
It automatically expels any gaseous substances from the boiler
circuit.
3
It is mounted on the circulator delivery, directly on the hy-
draulic unit.

Safety valve 3 bar (7).


It prevents the safety pressure being exceeded in the primary 1
circuit (3 bar). 5
It is located at the front of the delivery manifold unit (1) and
xed on the outside by a fork.
When this valve trips it causes water to come out through the 7
delivery pipe.

System expansion vessel (8).


It compensates the changes in volume following the heating
of water and permits to reduce pressure changes.
It has an 10-litre capacity (7.4 useful litres) and a 1.0 bar
preload pressure.
It is located at the back of the appliance.
8

STEkW ed 12/06 12http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Motorized 3-way valve for "X" models heating


only (optional).
This electrical three-way valve operates on the primary circuit
return and it allows, according to the specic request (d.h.w. Circulator
or heating), the water circulation in the heating circuit or in delivery
the cylinder coils (Separate storage tank of 80, 105, 120 e 200
litres).
This depends on the position of the shutter (5) wich shuts
o passage to the system and simultaneously opens the way
to the cylinder coils (domestic hot water position), or viceversa
(central heating position).
The shutter (5) switching in both the positions is realized by
supplying the (optional) electric motor (1).
The hydraulic part of the boiler consist of a unit made in a 6
composite material (2) that also includes the circulating pump
and it is operated by a motor (1) (optional) that causes it to
move as required. 2
Before tting the motor it is necessary to remove the cap (6)
locked with the respective fork. 5
System
return
Heating only functioning.
The cap (6) pushes the shutter (5) and compresses the shutters 1
contrast spring (4) (heating position), in this way the hydraulic
group is always positioned in heating functioning mode.
Both the spring (4) and shutter (5) are inside the 3-way car-
tridge (3).
3 4
Heating and domestic hot water functioning (using the
optional motorized 3-way valve).
The functioning is the same that for combi models (see previous
pages).

CIRCULATOR
RETURN

CAP

SYSTEM
RETURN

STEkW ed 12/06 13http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Safety devices and controls for "X" models


heating only.

Adjustable system by-pass (2).


This device guarantees the circulation of water in the primary
circuit (between delivery and return) even when it would be 1
prevented by the high resistance of the system.
It is mounted on the delivery manifold (1) and adjusted by a
screw that can be accessed from the bottom of the valve sup-
porting plate.
2

System lling unit (3).


This is a ball cock located between the boiler circuit and the
domestic cold water inlet and it makes possible to pressurise
the central heating system. System
The cock is connected to a lling up tting (4) which, in turn, delivery
is connected to the motorised 3-way diverter valve unit.
4 3
System pressure switch (5). 6
This switch detects the pressure inside the primary circuit. It
is housed in the delivery manifold unit (1) and coupled to a
microswitch that prevents the burner working when the pres-
sure measured is below 0.3 bar.
It prevents the primary exchanger overheating.

Automatic air vent (6).


It automatically expels any gaseous substances from the boiler
circuit.
It is mounted on the circulator delivery, directly on the hy-
draulic unit.

Safety valve 3 bar (7).


1
It prevents the safety pressure being exceeded in the primary
5
circuit (3 bar).
It is located at the front of the delivery manifold unit (1) and
xed on the outside by a fork. 7
When this valve trips it causes water to come out through the
delivery pipe.

System expansion vessel (8).


It compensates the changes in volume following the heating
of water and permits to reduce pressure changes.
It has an 10-litre capacity (7.4 useful litres) and a 1.0 bar
preload pressure.
It is located at the back of the appliance. 8

STEkW ed 12/06 14http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Secondary circuit (domestic hot water circuit) for combi versions only.

Operation.
Running the domestic hot water causes cold water to ow
Primary circuit Primary circuit
through the d.h.w. ow switch (1) and, as a result, the electrical
delivery return
contact connected to it closes (see the electrical circuit).
After this, the integrated board starts the domestic hot water
priority function phase whereby the burner is ignited and, if
there is an on-going central heating request, the 3-way diverter
valve (2) switches and moves into the working position (see
operation of the 3-way hydraulic diverter valve).
This causes the return pipe (R) to close and the simultaneous
opening of the passage to the d.h.w. exchanger (3).
This prevents circulation in the central heating system while
it is allowed in the plate exchanger inside which the domestic
cold water absorbs the heat contained in the primary circuit
water (see d.h.w. exchanger).
This means that the central heating function is o in this phase,
the production of domestic hot water having priority.

The water-water heat exchange takes place inside the d.h.w.


exchanger (3) which is xed with screws to the d.h.w. outlet
body (1) and to the d.h.w. inlet body (2). Primary circuit
delivery Domestic cold water
The part at the top of the left body allows the delivery water to inlet
enter the primary circuit while the part at the bottom allows
the domestic hot water to exit. 3
Likewise, the top of the right body allows the domestic cold
water to enter while at the bottom, return of the primary 1
circuit.
The d.h.w. probe (4), by means of which the integrated board 4
is able to measure the temperature of the domestic hot water,
is mounted on the domestic hot water outlet body (1).

Domestic hot water


outlet

Primary circuit
return

STEkW ed 12/06 15http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

D.h.w. ow switch (1).


When domestic hot water is drawn at a rate of 2 litres/min or
less and dynamic pressure is 0.3 bar, the d.h.w. ow meter (1)
enables the boiler to work in the d.h.w. mode.
This takes place by means of a magnet that, upon lifting when
it is hit by the ow of domestic cold water, moves closer to
an electrical contact (reed relay) causing it to move due to the 2
magnetic eect.
When the contact closes, located outside the pipe through 1
which the water ows, it enables the integrated board to start
the domestic hot water priority functioning phase.
It is xed with a pin to the valve supporting plate.
A ow limiting device (2) is mounted on the outlet of the
Domestic cold water
d.h.w. ow switch, 7.55 l/min (2 bar) for model 24 kW, 9.0 inlet
l/min (2 bar) for model 28 kW and a 11.28 l/min (2 bar) for
model 32 kW.

D.h.w. exchanger.
This is a water-water exchanger consisting of stainless steel
plates placed on top of each other (16 in the 24 kW version, 1
20 in the 28 kW version, and 22 in the 32 kW version) on the
Primary
surface of which ows, in counter current, the water of the
circuit
boiler circuit and the domestic cold water and through which
delivery
heat exchange occurs between the two liquids.
For the hydraulic coupling four O rings (1) are used that al-
1
low direct coupling to the d.h.w. inlet body and to the d.h.w.
outlet body.
D.h.w.
outlet
D.c.w.
inlet

Primary
circuit
return

STEkW ed 12/06 16http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Gas circuit.
This circuit consists of an atmospheric burner and a modulat- Burner.
ing gas valve that permit, respectively, the combustion of gas The burner consists of horizontal Venturi pipes (6) inside which
and the regulation of its ow rate. gas is injected by the same number of nozzles (7) mounted on
the respective manifold (8).
Operation. The diameter of the nozzles (7) varies according to the type of
When the main coils (3) are powered it causes both shutters gas utilised (see technical data).
inside the valve to open which lets gas through to the burner. The number of the nozzles is 11 (24 kW version), 14 (28 kW
Consequently the ow rate/pressure in output is adjusted by version) and 15 (32 kW version).
acting on the gas valve stabiliser by means of the modulation Ignition occurs thanks to an integrated electronic board that
coil (1). The gas is injected into the horizontal Venturi pipes controls both the ignition (5) and detection (4) electrodes.
(shafts) through the burner nozzles (7). The air-gas mixture is
created inside these pipes and set alight by the discharge of the Ignition electrodes (5).
ignition electrodes (5). They are controlled by the integrated board that produces an
electric discharge between the electrodes.
Modulating gas valve. They are positioned on the front of the burner.
The gas valve (SIT 845) features two main coils (3) and a
modulation coil (1) controlled by the integrated board. Detection electrode (4).
The maximum and minimum outlet pressure settings can be It is controlled by the integrated board and detects burner
made on this valve (see gas regulations). ignition.
It is positioned on the front of the burner beside the ignition
Main electrical coils (3).
electrodes.
They are two ON-OFF type coils energised (230 Vac) by the
integrated board when the burner has to be ignited.
They are electrically connected in parallel and energised by
mains power through a special connector (2).
Modulation coil (1). 4
This low-voltage coil is controlled by the integrated board.
It controls the gas valve stabiliser and is used to change the 5
outlet pressure in a way proportionate to the dc current that
runs through it. 6 7
8

2 3

STEkW ed 12/06 17http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Gas adjustments.
The maximum and the minimum gas pressure adjustments SIT 845 gas valve
can be made on the gas valve respecting the values shown in Adjustment maximum pressure.
the heat outputs table, in function of the model and the gas Run o some domestic hot water after having set its tempera-
type (see technical data). ture selector on maximum.
Measurements are made using a differential manometer Turn the brass nut (3) clockwise to increase pressure to the
connecting it's positive pressure point to the gas valve outlet burner and counter clockwise to reduce it.
(4) and it's negative pressure point to the positive pressure
point in the ange with traps located at the top of the sealed Adjustment minimum pressure
chamber (see gure). (to be done after the adjustment maximum pressure).
After having cut electrical power to the modulation coil, turn
the screw (2) clockwise to increase pressure to the burner and
anticlockwise to reduce it.

Gas conversion.
There are special kits to adapt the boiler to a gas type dierent
to the one for which the boiler is set as standard (natural gas
or LPG).
Conversion consists in changing the burner nozzles and moving
the gas type selector NATURAL GAS LPG (S8) on the
integrated board.
Maximum and minimum pressures are then regulated on the
gas valve as described above.
The maximum and minimum output setting in the central
heating phase can be set via the parameters (see integrated
board operation).
The burner ignition pressure is not regulated because the
type of board operation does not require such a setting (see
integrated board operation).

Valve SIT 845

Legend:
1 - Modulation coil
2 - Minimum output adjustment
3 - Maximum output adjustment nut
4 - Gas valve outlet pressure point
5 - Gas valve inlet pressure point
6 - Protection cap

STEkW ed 12/06 18http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Flue circuit.

Operation.
The products of combustion, after having hit the water-gas The positive pressure point (10) is connected directly to the
exchanger (2), are slowed down and distributed by the plate inside of the sealed chamber.
(12) thus increasing combustion eciency. They are then Only for 32 kW model.
conveyed to a draught diverter (4) on top of which the ue (to start production)
extractor (fan) (5) is mounted. The negative pressure point (9) is connected to a Y shaped
Fan operation ensures forced expulsion of the ue and, at the pipe (11) which, in turn, is connected to the negative pressure
same time creates a vacuum in the sealed chamber (3) so the point of the ue pressure switch (6) and to the pressure point
combustion air can be extracted from outside. (1) positioned at the fans exhaust terminal.
Correct fume extraction is controlled by a dierential ue pres- The positive pressure point (10) is connected directly to the
sure switch (6) that enables or prevents burner ignition. inside of the sealed chamber.

Air-ue intake traps (7-8).


The top outer part of the sealed chamber features two intake
traps with screw closing, accessible from the front and from 8 10
where combustion air (7) and ue (8) can be sampled. 7
9
Flue pressure switch signal pressure points (9-10). 5
The top outer part of the sealed chamber features two pressure 1
points with screw closing by means of which it is possible to
measure the signal on the ends of the ue pressure switch
(6).
6
Only for 24 kW model. 12
(Up to serial number 2738489 for EOLO Maior 24 kW)
The negative pressure point (9) is connected to a Y shaped
pipe (11) which, in turn, is connected to the negative pressure
point of the ue pressure switch (6) and to the pressure point
positioned at the outlet of the Venturi pipe inserted in the 2
fans exhaust terminal.
11 4

STEkW ed 12/06 19http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Only for 28 kW model. Flue pressure switch (6).


(Up to serial number 2712127 for EOLO Maior 28 kW) Only for 24 and 28 kW models.
(Up to serial number 2711377 for EOLO Maior 28 kW X) (Up to serial number 2738489 for EOLO Maior 24 kW)
The negative pressure point (9) is connected to a Y shaped (Up to serial number 2712127 for EOLO Maior 28 kW)
pipe (11) which on one side is connected to the pressure point (Up to serial number 2711377 for EOLO Maior 28 kW X)
positioned at the outlet of the Venturi pipe inserted in the It is located at the top inside the sealed chamber and detects, by
fans exhaust terminal and on the other side it is connected means of the relative points, the dierence in pressure between
to a second "Y" shaped pipe (11) whose one end is connected the outlet of the Venturi pipe inserted in the fan exhaust
to a calibrated nozzle (13) and the other end is connected (negative signal) and the inside of the sealed chamber
through a pipe (14) to the negative pressure point of the (positive signal).
ue pressure switch (6). The signal measured by the pressure switch is variable accord-
The positive pressure point (10) is connected directly to the ing to the length of the air inlet/exhaust terminals and can be
inside of the sealed chamber. measured by the relative pressure points located at the top of
the sealed chamber (9-10).
When it triggers it causes a switch to close (S6) that acts on the
8 10 integrated board enabling or preventing burner ignition.
7
9 Flue pressure switch ON ON
triggering pressures Pa (mm H2O) Pa (mm H2O)
5
EOLO 24-28 kW 150 (15.3) 130 (13.26)

Only for 32 kW model.


6 (to start production for EOLO Maior 32 kW)
It is located at the top inside the sealed chamber and detects, by
12 means of the relative points, the dierence in pressure between
14 the fan inside (negative signal) and the inside of the sealed
chamber (positive signal).
4 The signal measured by the pressure switch is variable accord-
ing to the length of the air inlet/exhaust terminals and can be
2 measured by the relative pressure points located at the top of
the sealed chamber (9-10).
11 13
When it triggers it causes a switch to close (S6) that acts on the
integrated board enabling or preventing burner ignition.

Flue pressure switch ON ON


triggering pressures Pa (mm H2O) Pa (mm H2O)
Flue pressure switch signal pressure points (9-10). EOLO 32 kW 52 (5.3) 42 (4.3)
(see gure on previous page).
(from the serial number 2738490 for EOLO Maior 24 kW) Flue pressure switch (6).
(from the serial number 2712128 for EOLO Maior 28 kW) Only for 24 and 28 kW models.
(from the serial number 2711378 for EOLO Maior 28 kW (from the serial number 2738490 for EOLO Maior 24 kW)
X) (from the serial number 2712128 for EOLO Maior 28 kW)
(to start production for EOLO Maior 32 kW) (from the serial number 2711378 for EOLO Maior 28 kW
The top outer part of the sealed chamber features two pressure X)
points with screw closing by means of which it is possible to (to start production for EOLO Maior 32 kW)
measure the signal on the ends of the ue pressure switch It is located at the top inside the sealed chamber and detects, by
(6). means of the relative points, the dierence in pressure between
The negative pressure point (9) is connected to a Y shaped the fan inside (negative signal) and the inside of the sealed
pipe (11) which, in turn, is connected to the negative pressure chamber (positive signal).
point of the ue pressure switch (6) and to the pressure point The signal measured by the pressure switch is variable accord-
(1) positioned on the fan. ing to the length of the air inlet/exhaust terminals and can be
The positive pressure point (10) is connected directly to the measured by the relative pressure points located at the top of
inside of the sealed chamber. the sealed chamber (9-10).

STEkW ed 12/06 20http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

When it triggers it causes a switch to close (S6) that acts on the


integrated board enabling or preventing burner ignition.
Flue pressure switch ON ON
triggering pressures Pa (mm H2O) Pa (mm H2O)
EOLO 24 kW 44 (4.5) 36 (3.7)

EOLO 28 kW 44 (4.5) 36 (3.7)

EOLO 32 kW 52 (5.3) 42 (4.3)

Fan (5).
The extractor operates downstream from the combustion
chamber and is xed vertically to the top of the draught diverter
(4) from where it extracts the ue and conveys them to the
exhaust pipes to which the boiler is connected. It simultaneou-
sly guarantees the ow of air inside the sealed chamber.
It is controlled by the integrated board and its operation coin-
cides essentially with that of the burner.
N:B: Only for 24 and 28 kW models.
(Up to serial number 2738489 for EOLO Maior 24 kW)
(Up to serial number 2712127 for EOLO Maior 28 kW)
(Up to serial number 2711377 for EOLO Maior 28 kW X)
A venturi pipe is inserted inside the fan outlet terminal pipe;
the negative signal of the pressure switch (6) is detected on
the Venturi pipe outlet.

STEkW ed 12/06 21http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Air inlet and exhaust systems.


(see air inlet and exhaust terminal instructions).

EOLO Maior kW is connected to the push-tting air inlet/


exhaust pipes and can be installed either with a fan-assisted
sealed chamber (type C) conguration or, by means of the
relative kit, the fan-assisted open chamber conguration
(type B22).

Fan-assisted, open chamber conguration


(type B22) for installing outdoors in a partially
protected place.
Using a specic kit, the EOLO Maior kW boiler can be
installed outdoors in a partly sheltered place.
In this way, the appliance works in the fan-assisted open
chamber conguration (type B22) so the combustion air can
be taken directly from the environment.

Inlet.
Air inlet is possible through holes present on the external
surface of the ange (2).
The ange must be mounted on the central hole in the upper
side of the sealed chamber after inserting the respective gasket
(1) and xing it through the 4 screws.
On the ange (2) it is necessary to install the cover cap 180
(3) through the two self-tapping screws, combining the two
holes present on the cover cap and on the ange.

Exhaust.
The connection between the 80 mm outlet pipes is realized
by push-tting with the respective ange (2), which seal is
provided by special lip gaskets.
With specic accessories it is possible to have an horizontal
(A) or a vertical (B) exhaust.
In order to prevent problems due to condensation, the outlet
pipes must not exceed 5 m lenght for standard pipes and 12
m lenght for insulated pipes.
Maximum straigth horizontal lenght is 12 m.
For the correct functioning of the boiler working in B22 con-
guration, it is necessary to set the ue shutter on position "5"
(see instruction manual of the boiler).

STEkW ed 12/06 22http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Fan-assisted, sealed chamber conguration Air inlet / ue exhaust kit.


(type C). The kits and their respective accessories allow to use four con-
centric pipe systems and two twin pipe systems.
Exhaust. In regards to pressure drops related to each accessory, the
Connection to the exhaust pipes is by means of a ange (1) or various possible combinations and the position of the ue
a anged bend to connect to tting (4) on top of the sealed shutter according to the length and type of pipes, please follow
chamber, placing a special shaped seal in between (6). the instructions for air inlet/ue outlets kits (see instruction
The ange diers according to whether the split or concentric manual of the boiler).
system is used. The connection between dierent accessories (bends, extensions,
In the rst case, the passage for the air inlet of combustion air terminals) is realized by push-tting and the seal is provided
(5) is closed while, in the second case, it is used. by special lip gaskets.
The ue shutter (7) is mounted on the exhaust tting (4) which
has to be adjusted to ensure correct boiler operation. Coupling type horizontal concentric kit 60 /100.
The appropriate adjustment depends on the type of pipe used The exhaust pipe ( 60 mm) is tted inside the extraction
and its length (see boiler instruction handbook). pipe ( 100 mm).
To adjust, unscrew the front stop screw and move the gradu- Connection to the boiler is made using a 90 curve (2) that
ated indicator to the correct position, aligning the value to the can be positioned in any direction and which, by means of
horizontal reference. the necessary extensions, must be connected to the special
extraction and exhaust end (3).
Max possible overall length beyond the rst curve (2) is 3
Air inlet. straight and horizontal metres.
Using the split system, connection to the air inlet pipes is
exactly the same as for the exhaust pipes, connecting to the 80
mm diameter hole (2) at the top of the sealed chamber. 3 4 5
2
The unused hole is closed with one of the caps (3) supplied
with the boiler.
If coaxial pipes are used, air inlet occurs by using the concentric
1
hole outside the exhaust pipe (5).

1 Coupling type horizontal concentric kit 80 /125.


The exhaust pipe ( 80 mm) is tted inside the extraction
pipe ( 125 mm).
7 Connection to the boiler is made using a 90 curve diameter
60/100 (2) that can be positioned in any direction and which,
6 by means of the adapter 60/100-80/125 (3) and necessary
extensions, must be connected to the special extraction and
exhaust end (4).
Max possible overall length beyond the rst curve (2) is 7.3
straight and horizontal metres.

3 4
3 4
5
5 2 6

1
2

STEkW ed 12/06 23http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Coupling type vertical concentric kit 80 /125. 80/80 coupling type separator kit.
The exhaust pipe ( 80 mm) is tted inside the extraction Both pipes have a diameter of 80 mm.
pipe ( 125 mm). Connections to the boiler are made using two special anges
Connection to the boiler is made using a ange (2) that, by for exhaust (4) from the centre pipe and extraction (3) from
means of the adapter 60/100-80/125 (3) and necessary exten- one of the two side holes.
sions, must be connected to the special 80/125 extraction and Max possible length (extraction + exhaust) is 33 straight hori-
exhaust end with aluminium tile (6). zontal metres and 41 straight vertical metres.
Max possible overall length is 12.2 straight and vertical To prevent condensation problems, the exhaust pipe should
metres. not be more than 5 m long.

Coupling type vertical concentric kit 60 /100.


The exhaust pipe ( 60 mm) is tted inside the extraction 9 5
6
pipe ( 100 mm). 5 7
8
Connection to the boiler is made using a ange (2) that, by
means of the necessary extensions, must be connected to the
special 60/100 extraction and exhaust end with aluminium A
B
tile. 7
Max possible overall length is 4.7 straight and vertical me- 4 3
tres. 1 2

Insulated 80/80 coupling type separator kit.


8 Both pipes have a working diameter of 80 mm.
5 Connections to the boiler are made using two special anges
for exhaust (4) from the centre pipe and extraction (3) from
7 one of the two side holes.
Insulation is obtained thanks to special seals (6) whereby an
air space can be created by means of a 125 mm external
concentric pipe.
4 Max possible length (extraction + exhaust) is 33 straight
metres.
3 To prevent condensation problems, the exhaust pipe should
6 not be more than 12 m long.
2

1 5 6
8 7
8
10 9
11

A
3 B
4 2

STEkW ed 12/06 24http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Electrical circuit.

Zone Control
Unit
230 Vac
50Hz
supply

RELAY
BOARD

E2 - Detection electrode
NAT-LPG E4 - Overheating safety thermostat
F1 - Line fuse
F2 - Neutral fuse
M1 - Circulator
M20- Fan
M30- Moterized 3-way diverter valve
Primary
P1 - Central heating timer (optional)
R5 - D.h.w. temperature trimmer
Secondary
R6 - Central heating temperature trimmer
R10 - Main selector switch
S4 - D.h.w. ow switch
Legend:
S5 - System pressure switch
A5 - CAR interface board
S6 - Flue pressure switch
B1 - Delivery probe
S8 - Gas type selector switch
B2 - D.h.w. probe
S20 - Room thermostat (optional)
B4 - External probe (optional)
T1 - Ignition transformer
CAR- Remote control (optional)
X40 - Room thermostat jumper
CZ - Zone control unit (optional)
Y1 - Gas valve
E1 - Ignition electrodes
Y2 - Gas valve modulation coil

The EOLO Maior kW electrical circuit is totally interlocked Some of the control and safety devices operate at mains
to a microprocessor-controlled p.c.b. that controls generator voltage (230 Vac) while the others at low voltage.
functions.

230 V AC circuit.

Safety devices and controls.

Detection electrode This detects ignition of the burner by whose ame it is covered.
(E2) It is connected to the integrated board.

Line fuse (F1) They interrupt power to the circuit when power input is over
Fuse
3.15 A.
3,15 AF 250 V
Neutral fuse (F2) They are tted on the integrated board.

STEkW ed 12/06 25http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Loads.

It is controlled by the integrated board that produces an electric discharge between the
Ignition electrodes
electrodes.
(E1)
Upon contact the air-gas mixture ignites.

It is powered by the integrated board following a d.h.w., central heating or antifreeze


Boiler circulator
request.
(M1)
It permits water circulation in the primary circuit.

The board is always powered, regardless of the position of the main selector switch (R10)
Integrated board
(see integrated board operation).

It is a clock that acts on a switch (see the low voltage circuit controls and safety devices) enabling
Central heating timer (P1) or preventing boiler operation in the central heating phase during preset time intervals.
(External optional) If the timer is connected it is always powered regardless of the position of the main selec-
tor switch (R10).

3-way diverter valve It diverts the primary circuit water ow from the central heating system to the d.h.w. plate
(M30) exchanger and vice versa.
(optional kW X version) It is powered by the integrated board.

It is powered at mains voltage by the integrated board when burner ignition is neces-
Gas valve (Y1)
sary.
(main coils)
It allows passage of gas to the burner.

This ensures the ow of air inside the sealed chamber and the extraction of ue produced
Fan
by combustion.
(M20)
It is powered by the integrated board.

Low voltage circuit.

Safety devices and controls.

It permits operation of the boiler with 3 zone valves or external


Zone control unit (CZ) See zone control
pumps controlled by the relevant room thermostats.
(external optional) unit operation
Zone 1 is controlled (times and temperatures) by the CAR.

It permits the remote control of the generator (SUMMER/WINTER See Remote Con-
Remote Control
switch, temperature setting and indication, alarms display, reset, etc.) trol operation
(CAR) (optional)
and acts as a weekly timer-thermostat. (CAR)

D.h.w. ow switch After running domestic hot water, it acts on the integrated board
Interrupted
(S4) that starts the d.h.w. phase.
contact
(for combi versions only) When idle it enables operation in the central heating phase.

System pressure switch When the pressure in the boiler circuit is less than 0.3 bar it turns Interrupted
(S5) the burner out. contact

STEkW ed 12/06 26http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

It acts on the integrated board and enables boiler operation when


Flue pressure switch the ue are extracted correctly. Switching
(S6) If it is closed with the fan o it does not enable start of the igni- contact
tion cycle.

Depending on the position it allows:


= With the circuit powered, the antifreeze and antilock
functions remain active, the various post-circulation and post-
ventilation functions are terminated.
Main selector switch (R10) ( ) = Domestic hot water function and CAR (optional). Trimmer
( ) = Domestic hot water and central heating function.
RESET = Reset after an ignition failure or if the overheating safety
device triggers, it allows the chimney sweep function to be activated,
it allows access to boiler parameter setting.

External probe It detects the external temperature and lets the board change system PTC probe
(B4) (optional) delivery temperature according to it. 1 kohm 25 C

It lets the integrated board detect the temperature of the primary


circuit delivery water.
Delivery NTC probe NTC probe
If it breaks, burner operation stops in both the central heating and
(B1) 10 kohm 25 C
domestic hot water mode.
It is positioned on the main exchanger outlet.

Allows the electronic control board to read the outlet temperature


of the domestic hot water.
The sensor fault is signalled by the ashing of Led 10 ( ), the
D.h.w. NTC probe boiler keeps working in d.h.w. mode. NTC probe
(B2) It is mounted on the d.h.w. outlet body connected to the d.h.w.
plate exchanger. 10 kohm 25 C
(optional kW X version)
For kW X models: It is inserted inside a bulb holder in contact
with the external wall of the separate storage tank eventually con-
nected.

It enables operation in the central heating phase when room tem-


Room thermostat (S20) perature is below that requested. Interrupted
(external optional) If the CAR device is installed, the room thermostat must be discon- contact
nected without re-establishing the existing jumper X40.

It acts on the integrated board enabling operation of the boiler in


the central heating phase at the selected times.
If it is mounted alone, connection is to terminals 40 and 41 of the
Central heating timer (P1) Interrupted
X14 connector after having removed jumper X40.
(external optional) contact
If it is mounted together with a room thermostat (S20) it is con-
nected to terminals 8 and 41 of the X14 connector after having
removed jumper X40.

If the safety temperature is exceeded (105 C) the burner switches Clicson thermo-
Safety thermostat
o. stat with normally
(E4)
It is positioned on the main exchanger outlet. closed contact

Loads.

Gas valve modulator It is powered by the integrated board with a variable d.c.
(Y2) With this the pressure of the gas to the burner can be varied.

STEkW ed 12/06 27http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Electrical circuit.

Central heating phase.

Operating with a room thermostat.


The central heating phase is enabled when the main selector Burner ignition is detected by the integrated board by way of
switch (R10) is on WINTER. the ionisation electrode (E2).
When the room thermostat contact is closed (S20), the inte-
grated board powers the boiler circulator (M1) by means of Operating with the remote control.
relay K3 and, by deviating the contact of relay K1, powers the The remote control (CAR) is enabled when the main selector
motor (M) of the 3-way diverter valve (M30) that continues switch (R10) is on SUMMER and CAR.
working until limit switch 1 opens when the central heating If the conditions found by the remote control (CAR) require
position is reached. ignition in the central heating phase (SUM/WIN selector of the
In the meantime, if the ue pressure switch (S6) contact is CAR on WINTER, central heating temperature setting higher
idle, NC, the adjustment circuit powers the fan (M20) by than what the heating sensor (B1) detects, request for the hourly
means of relay K4. programmer, room temperature setting higher than the temperature
If the contact of the system pressure switch (S5) is closed (the measured), the integrated board powers the boiler circulator
pressure measured in the primary circuit is higher than the mini- (M1) by means of relay K3 and burner ignition occurs as
mum value), with the enable of the safety thermostat (E4) and described above.
consequent switching over of the ue pressure switch to NO
(S6) and if the temperature measured by the delivery NTC pro- NOTE: Each time the control unit switches o when the set
be (B1) is below the temperature set on the control panel with temperature is reached, the integrated board stops burner
the central heating temperature trimmer, the integrated board operation in the central heating phase for the length of time set
energizes the K2 request relay which closes the 2 contacts al- with the board parameters (see integrated board operation).
lowing to start of the ignition cycle, rst controlling the ignition
electrodes (E1) and then both the gas valve coils (Y1).

STEkW ed 12/06 28http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Electrical circuit.

Domestic hot water phase.

Operation.
The domestic hot water phase is enabled when the main selector the ionisation electrode (E2).
switch (R10) is on SUMMER or WINTER.
By running o some domestic hot water, the contact of the
d.h.w. ow switch (S4) closes and, if the temperature measured
by the d.h.w. NTC probe (B2) is less than the temperature
set on the control panel (or on the CAR if mounted), the inte-
grated board powers the boiler circulator (M1) by means of
relay K3 and, by deviating the contact of relay K1, powers the
motor (M) of the 3-way diverter valve (M30) that continues
working until limit switch 3 opens when the d.h.w. position
is reached.
In the meantime, if the ue pressure switch (S6) contact is
idle, NC, the adjustment circuit powers the fan (M20) by
means of relay K4.
If the contact of the system pressure switch (S5) is closed (the
pressure measured in the primary circuit is higher than the mini-
mum value), with the enable of the safety thermostat (E4) and
consequent switching over of the ue pressure switch to NO
(S6), the board closes the contact of the request relay K2, so
the ignition cycle can be started, rst controlling the ignition
electrodes (E1) and then both gas valve coils (Y1).
Burner ignition is detected by the integrated board by way of

STEkW ed 12/06 29http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Integrated board.

NAT-LPG

FUSES

D.H.W.

MAIN SELECTOR SWITCH CENTRAL


HEATING

TRANSFORMER

Inside the boilers panel there is an integrated microprocessor In the meantime, if the ue pressure switch (S6) contact is
controlled board that controls the appliances electrical devices idle, NC, the adjustment circuit powers the fan (M20) by
for the linear modulation of burner output and, by means of means of relay K4.
LEDs, it shows the operating status of the appliance, signalling If the contact of the system pressure switch (S5) is closed (the
if any of its safety devices have triggered. pressure measured in the primary circuit is higher than the mi-
The integrated board is the same on all models, both natural nimum value), with the enable of the safety thermostat (E4)
draught and sealed chamber (NIKE/EOLO Maior kW), the and the consequent switching over of the ue pressure switch
recognition of dierent models is automatically done by the to NO (S6) and if the temperature measured by the delivery
board through the electrical connections. probe (B1) is below the temperature set on the control panel
The integrated board is always powered regardless of what with the central heating temperature trimmer, the integrated
position the main selector switch (R10) is in. board energizes the K2 request relay which closes the 2 contacts
The board executes a periodical self-check to make sure it is allowing to start of the ignition cycle.
working properly. During the central heating functioning During the rst few seconds from when the gas valve (Y1) was
mode or with the boiler in Stand-by, this function is activated powered, the current to the modulation coil (Y2) is limited to
every 18 hours from the last boiler check/powering. During the predened slow ignition current.
the d.h.w. functioning mode, this self-check starts within Subsequently, the burner goes to the minimum pressure value
10 minutes from the last time water was drawn and lasts 10 set with the Minimum central heating power*parameter and
seconds. after it reaches the maximum pressure value set (if required)
NOTE: the boiler stops working (together with indications) with the Maximum central heating power* parameter in a
during the self-check operation. time xed by the Central heating timer ramp* parameter.
After this, the signal is varied in a way directly proportionate
Operation. to the dierence between the temperature set with the central
heating temperature trimmer (R6) and the temperature mea-
sured with the delivery probe (B1).
Central heating request. When the set temperature is exceeded (+5 C), the contact
The central heating phase is enabled when the main selector
of relay K2 opens and the burner switches o. Re-ignition
switch (R10) is on WINTER.
time depends on the setting of the Central heating ignition
When the room thermostat contact is closed (S20), the inte-
timer* parameter.
grated board powers the boiler circulator (M1) by means of
Each time the burner switches o the fan keeps working
relay K3 and, by deviating the contact of relay K1, powers the
for another 30 seconds and the circulator for another 150
motor (M) of the 3-way diverter valve (M30) that continues
seconds.
working until the limit switch 1 opens when the central
heating position is reached.

STEkW ed 12/06 30http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

D.h.w. request for instant boilers. ture set with the d.h.w. potentiometer, the relays are energised
After the d.h.w. ow meter (S4) has closed, burner ignition again to start a new ignition cycle.
proceeds in exactly the same way as it does for the heating If, during operation, the heating delivery probe (B1) measures
mode. a temperature higher than 90C, the K2 relay contact opens,
In the rst few seconds after the gas valve (Y1) has been closing again as soon as the temperature drops to 75C.
powered, current to the modulating coil (Y2) is limited to the
predened soft ignition current. C.h. antifreeze request.
When the ame has been detected, the signal to the modulating When the temperature read by the heating delivery probe
coil is increased so as to instantly reach maximum power (if (B1) drops below 4C, the board enables ignition and keeps
required) set on the gas valve. the boiler working with the burner at minimum power until a
Subsequently, ame modulation occurs with reference to boiler temperature of 42C is reached (radiator antifreeze).
the dierence between the temperature set with the d.h.w.
temperature trimmer (R5) and that measured by the d.h.w. D.h.w. antifreeze request.
probe (B2). If the temperature read by the d.h.w. probe (B2) drops below
When the set value (+5C) is exceeded the relay K2 contact 4C, the board enables boiler ignition and keeps it working
opens, closing again as soon as the temperature drops (+4C) with the burner at minimum power until a temperature of
(factory set with the correlated d.h.w. set-point). 8C is reached after which a post-circulation cycle starts in
The boiler can be set via the D.h.w. thermostat* parameter the heating mode that lasts 150 seconds.
so that when the set value is exceeded the burner continues During operation, the water in the primary circuit remains
working at minimum power, switching o only when the below 42C because when this temperature is reached the
d.h.w. probe (B2) measures a temperature higher than 65C board switches the burner o.
(xed d.h.w. set-point). If the d.h.w. antifreeze function is activated simultaneously
If, during operation, the heating delivery probe (B1) measu- with a central heating request, they are alternatively served
res a temperature higher than 80C, modulation occurs with (continuously): d.h.w. antifreeze for 2 minutes and the heating
reference to the delivery temperature with a xed set-point request for 6.5 minutes.
of 80C.
Chimneysweep request.
D.h.w. request for boilers with storage tank (if By turning the main selector switch (R10) round to the Reset
the optional 3-way valve for external storage position for 8 to 15 seconds, as soon as you let it go the board
tank is used). enables boiler ignition and keeps it working at the maximum
If the temperature measured by the d.h.w. NTC probe (B2), heating power set for 15 minutes.
situated on the storage tank, is below that set with the d.h.w. During this time only the limit thermostat function is enabled
temperature trimmer (R5) and if the contact of the system (90C) thanks to the heating delivery probe (B1).
pressure switch (S5) is closed (pressure measured in the primary The function is signalled by the simultaneous blinking of
circuit higher than the minimum value), the low voltage circuit LEDs (3) and (4) and code E07 on the CAR display panel
energises the K3 relay whose contact, upon closing, powers the (if connected).
boiler circulator (M1). It cannot be used if there is an ongoing d.h.w. request.
In the meantime, by means of the relay K1 contact, the motor It can be stopped by cutting power to the circuit, turning the
(M) of the 3-way valve (M30) is powered, moving into the main selector switch round to the (Stand-by) position or
d.h.w. position, after which burner ignition occurs in exactly after 15 minutes.
the same way as it does for the heating mode.
In the rst few seconds after the gas valve (Y1) has been
powered, current to the modulating coil (Y2) is limited to the * see Integrated board programming.
predened soft ignition current.
When the ame has been detected, the signal to the modulating
coil is increased so as to instantly reach (if required) maximum
power set on the gas valve.
Subsequently, ame modulation occurs with reference to
the dierence between the temperature set with the d.h.w.
temperature trimmer (R5) and that measured with the d.h.w.
probe (B2).
When the temperature measured by the d.h.w. probe (B2)
exceeds the value requested, the K2 relay contact opens (burner
switches o) followed by the contacts of the K4 (fan) and K3
(circulator) relays after the post-operation times.
When the temperature of the domestic water inside the sto-
rage tank drops below the value dened and settable with the
D.h.w. thermostat* parameter with respect to the tempera-

STEkW ed 12/06 31http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Inputs.

Zone control unit (CZ) It sends signals to the board concerning operating requests of zone valves or connected
(external optional) external pumps (see zone control unit operation).

Remote control It sends signals to the board of the SUMMER/WINTER selector switch concerning d.h.w.
(CAR) (optional) and central heating temperature adjustment and the central heating request (times, room
(see CAR operation) temperature, error codes, etc).

It indicates that a d.h.w. request is ongoing.


D.h.w. ow switch
After domestic hot water has been run, it enables operation of the Closed = d.h.w.
(S4)
boiler in the domestic hot water phase which is given priority with request
(for combi versions only)
respect to the system central heating phase.

Central heating timer Open = Central


This is a free contact switch, controlled by a clock that enables or
switch heating OFF
prevents boiler operation in the central heating phase at the set
(P1) Closed = Central
times.
(external optional) heating ON

Open =
low pressure
System pressure switch When the primary circuit pressure is below 0.3 bar, it cuts power
(S5) to the K2 relay, preventing the ignition cycle starting.
Closed =
pressure OK

It enables burner ignition, powering the K2 relay when the ue


Flue pressure switch are expelled correctly. Switching
(S6) If the NO contact is closed with the fan o, it does not enable contact
the start of the ignition cycle.

It is a signal that indicates ame detection.


It lets the board increase current to the modulation coil (Y2) after having limited it during
Flame detection
the ignition phase.
It keeps the gas valve (Y1) open.

It is a resistor that varies in a proportionate way to the external


External probe (B4) temperature. PTC probe
(optional) It enables to change the system delivery temperature in accordance 1 kohm 25 C
with external temperature.

It is a resistor inversely proportionate to the temperature of the


Delivery probe NTC probe
primary circuit delivery water.
(B1) 10 kohm 25 C
It is used as a limit thermostat (90 C).

It is a variable resistor inversely proportional to the temperature


of the d.h.w. in outlet.
D.h.w. probe Note: For the EOLO Maior 28 kW X model it is a variable resistor
inversely proportional to the temperature of the d.h.w. inside the NTC probe
(B2) storage tank. 10 kohm 25 C
(optional kW X version) It is connected to the terminals where the resistor (R8) is con-
nected which must be eliminated together with the coupling to
the Storage tank.

Open = Central
Room thermostat It is a switch with free contacts that sends a (low voltage) signal to
heating OFF
(S20) the board, enabling operation in the central heating phase when
Closed = Central
(external optional) room temperature is below that requested.
heating ON

STEkW ed 12/06 32http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Outputs.

230 Vac = coils


Gas valve power supply It is a 230 V ac signal indicating that the main gas valve coils are energised
(Y1) energised (Y1). 0 Vac = coils not
energised

Ignition electrodes It is a high voltage signal (higher than 16 kV) that determines an electrical discharge at the
(E1) ends of the ignition electrodes located on the burner.

This is a signal that lets the zone control unit know the operating status of the appliance
Zone control unit (CZ)
(domestic hot water/central heating) and to recognise the CAR, if mounted, as the room
(external optional)
thermostat of zone 1 (see Zone control unit technical data sheet operation).

It is a signal (BUS) by means of which it is possible to see on the remote control display
Remote control
- boiler temperature, operation either in the domestic hot water or central heating phase,
(CAR)(optional)
the codes of the alarms triggered and the temperature measured by the external probe (if
(see CAR operation)
installed).

Gas valve modulator It is a d.c. signal that controls the modulation coil and with this it is possible to vary
(Y2) pressure of the gas to burner according to the output required.

Relay board piloting


It is a d.c. signal that controls the relay board circuits.
(external optional)

Circulator relay It is a unipolar relay for controlling the circulator (M1) that is energised when its opera-
(K3) tion is requested.

Request relay This is a bipolar relay that is excited when the burner has to be ignited.
(K2) By means of its contact, boiler ignition is enabled.

3-way diverter valve relay With this relay the electric 3-way diverter valve (M30) motor (M) is powered.
(K1) It is excited with a central heating request, it remains idle with a domestic hot water
(optional kW X version) request.

Fan relay This is a unipolar relay that controls the fan (M20) that is excited when its operation is
(K4) requested.

Central heating clock It allows the programmer clock to be powered (external optional) at 230 Vac.
(P1) The signal is always present regardless of what position the main selector switch (R10)
(external optional) is in.

Adjustments.

Gas type selector switch


Depending on the position (Natural gas/LPG) it adapts the modulating parameters to the
Natural gas/LPG
type of gas the boiler is set for.
(S8)

STEkW ed 12/06 33http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Safety devices.

The circulator (M1) and the 3-way diverter valve (M30) are turned on for 30 seconds
Circulator / 3-way diverter after:
valve antilock - 24 hours of inactivity with the main selector switch on SUMMER.
- 3 hours of inactivity with the main selector switch on WINTER.

Electromechanical contacts
In the event of high resistance of the system pressure switch, safety thermostat or ue
block
pressure switch contact (not completely closed or worn), the integrated board eects a reset
(system pressure switch,
and starts a new contact verication cycle; if, after 6 such cycles the problem persists,
safety thermostat and ue
boiler operation is stopped.
pressure switch)
To start the boiler again, turn the main selector switch (R10) round to Reset and then
eect a d.h.w. or heating request.
(from December 2005)

In the case of dispersion of the detection circuit or a malfunction with ame control that
Parasitic ame block generates an ionisation current (without the gas valve being open) lasting at least 20 seconds,
boiler operation if stopped.
(from December 2005) To start the boiler again, turn the main selector switch (R10) round to Reset and then
eect a d.h.w. or heating request.

If, within 10 seconds from the start of the ignition cycle, the detection electrode (E2) has
not detected the ame on the burner, boiler operation is stopped.
The integrated board eects 2 ignition attempts lasting 10 seconds with a 30 second
interval in between after which it shuts down.
Failed ignition lock To start the boiler again, turn the main selector switch (R10) round to Reset followed
by either a d.h.w. or central heating request.
Note: The malfunction can be reset up to 5 consecutive times after which the function is
inhibited for at least one hour, gaining one attempt each hour or gaining 5 attempts by
putting the boiler on (Stand-by) or cutting power to the circuit.

If the ue pressure switch contact opens while the fan is working, the boiler is stopped.
Flue pressure switch lock
If normal conditions are restored, the boiler restarts without having to be reset.
(S6)
If it closes with the fan off, it does not enable start of the ignition cycle.

If the overheating safety thermostat contact opens, boiler operation is blocked.


Safety thermostat lock
To restore boiler operation, turn the main selector switch (R10) round to the Reset
(E4)
position and then make either a domestic hot water or central heating request.

To prevent the water-gas exchanger from overheating in the case of a blocked pump or
if there is little water circulating in the primary circuit, when the NTC central heating
Insucient circulation probe (B1) detects an increase in temperature that exceeds 5 C/second, the burner is
switched o.
It restarts when delivery temperature drops below 43 C.

STEkW ed 12/06 34http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

To prevent the water-gas exchanger from overheating, at the end of each central heating, an-
Post-circulation pump
tifreeze or chimneysweep request, the circulator (M1) keeps working for 150 seconds.

Sealed chamber post-ven- After the burner has been switched o at the end of any type of request, the combustion
tilation chamber is washed and the fan is kept running for 30 seconds.

Breakage of the delivery


Breakage of the central heating delivery probe (B1) stops boiler operation.
NTC probe (B1)

Breakage of the d.h.w. NTC


probe (B2) Breakage of the d.h.w. probe (B2) is signalled by the ashing of LED 10 ( ), and the
(optional kW X version) boiler continues working in the d.h.w. mode.

To prevent the water-gas exchanger from overheating, if the boiler temperature detected
Delivery overheating
by the NTC central heating probe (B1) exceeds 90 C, the fan is switched on until the
ventilation
temperature drops below 85 C.

STEkW ed 12/06 35http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Indications and alarms.

The EOLO Maior kW boiler signals malfunctions with the * from December 2005
ashing of one of the LEDs, from 5 to 11, coupled to the
(alternate) ashing of LED 1.

Operating indications LED Remote display

Boiler powered but no ame LED 1 on --


Burner on LED 2 on --
LED 3 and 4 simultaneous
Chimneysweep function on E07
ashing ( )
LED 3 and 4 on xed
Connection to the CAR
( )

LED
Operating malfunction signalled Remote display
ashing
LED 3 and 4 ashing alter-
CAR oine malfunction, not compatible or RS232 oine E31
nately ( )
No ignition block LED 5 ( ) E01
Flue pressure switch failure LED 6 ( ) E11
Insucient system pressure LED 7 ( ) E10
Insucient circulation LED 8 ( ) E27
Delivery NTC probe malfunction LED 9 ( ) E05
D.h.w. NTC probe malfunction LED 10 ( ) E06
Overheating safety thermostat block LED 11 ( ) E02
LED 6 ( ) and LED 10 E02 + E04
Electromechanical contacts block*
( ) ashing simultaneously ashing alternately
LED 2 ( ) and LED 11 ( ) E02 + E20
Parasitic ame block*
ashing simultaneously ashing alternately

STEkW ed 12/06 36http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Programming the integrated board.


The EOLO Maior kW boiler is designed for programming For the association of the LED to the value, see the following
some operating parameters if wanted. tables:
By modifying these parameters the boiler can be adapted to
meet ones specic requirements. Heating output. The boiler is made and calibrated in the cen-
To access the programming phase you have to put the main tral heating phase at nominal output. In addition, it features
selector switch on Reset for 15 to 20 seconds; upon activation an electronic adjustment that adapts boiler potential to the
LED 1 starts ashing and will continue to do so throughout homes actual heating requirements.
programming. At this point, put the main selector switch back This means that the boiler works normally in a variable eld
on domestic hot water-central heating position ( ). of gas pressures, ranging from minimum to maximum output
When the programming phase is activated, the rst level is depending on the systems heating load.
accessed where it is possible to choose the parameter to set.
This one is indicated by the fast ashing of one of the LEDs, NOTE: selection of the Minimum heating output and
between 2 and 11, simultaneously with LED 1. Maximum heating output parameters, when there is a cen-
Selection is made by turning the domestic hot water tempera- tral heating request, allows boiler ignition and powering of
ture knob. the modulation with current equal to the value of the relative
For the association of the LED to the respective parameter, parameter selected.
see the following table:
Minimum heating output LED ashing
(continuous variation) (slow)
List of parameters LED ashing (fast)
0% Imax. (Standard setting) LED 2
Minimum heating output LED 2
7% Imax. LED 3
Maximum heating output LED 3
14% Imax. LED 4
Central heating ignitions timer LED 4
21% Imax. LED 5
Central heating output supply ramp LED 5
28% Imax. LED 6
Central heating ignitions delayed due
to room thermostat or Remote Control LED 6 35% Imax. LED 7
requests
42% Imax. LED 8
Domestic hot water thermostat LED 7
49% Imax. LED 9
Circulator operation LED 8
56% Imax. LED 10
D.h.w. exchanger preheating LED 9
63% Imax. LED 11
Operating gas LED 10

Relay 1 operation LED 11 e 2 Maximum heating output LED ashing


(continuous variation) (slow)
Relay 2 operation LED 11, 2 and 3
0% Imax. LED 2
Relay 3 operation LED 11, 2, 3 and 4
11% Imax. LED 3
Once you have chosen the parameter to change conrm selec- 22% Imax. LED 4
tion by temporarily turning the main selector switch round to
RESET until the LED relative to the parameter switches o 33% Imax. LED 5
and then release it.
44% Imax. LED 6
When the ok has been given for the selection, go to the second
level where the value of the parameter selected can be set. 55% Imax. LED 7
The value is indicated by the slow ashing of one of the LEDs
- 2 to 11 - together with the ashing of LED 1. The value is 66% Imax. LED 8
selected by turning the central heating temperature knob.
77% Imax. LED 9
To exit the programming mode, do nothing for 30 seconds
or, if you are on the parameter setting level, put the main 88% Imax. LED 10
selector switch on position .
100% Imax. (Standard setting) LED 11

STEkW ed 12/06 37http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Permanent timing reduction. The boiler is tted with an Central heating ignitions delayed due to Room thermostat
electronic timer that prevents the burner igniting too frequently or Remote control requests. The boiler is set to turn on im-
in the central heating phase. mediately after a request.
The boiler is supplied with a timer as a standard feature, set In the case of particular systems (i.e. zone systems with mo-
at 180 seconds. torised thermostat valves, etc.) it might be necessary to delay
ignition.
Central heating ignitions timer LED ashing
(continuous variation) (slow) Central heating ignitions delayed due to
LED ashing
Room thermostat or Remote control reque-
30 seconds LED 2 (slow)
sts (continuous variation)
55 seconds LED 3 0 seconds (Standard setting) LED 2
80 seconds LED 4 57 seconds LED 3
105 seconds LED 5 113 seconds LED 4
130 seconds LED 6 170 seconds LED 5
155 seconds LED 7 226 seconds LED 6
180 seconds (Standard setting) LED 8 283 seconds LED 7
205 seconds LED 9 340 seconds LED 8
230 seconds LED 10 396 seconds LED 9
255 seconds LED 11 453 seconds LED 10

Central heating ramp timing. The boiler supplies the maxi- 510 seconds LED 11
mum output set in the previous parameter.
The boiler executes an ignition ramp of about 650 seconds to Domestic hot water thermostat. With the setting of the
go from minimum to maximum central heating output. correlated thermostat the boiler switches o according to
the temperature set with the domestic hot water adjustment
Central heating ignitions timer LED ashing knob.
(continuous variation) (slow)
On the other hand, with the setting of the xed domestic
65 seconds LED 2 hot water thermostat, the switching o temperature is set at
65C.
130 seconds LED 3
LED ashing
195 seconds LED 4 Domestic hot water thermostat
(slow)
260 seconds LED 5 Correlated (Standard setting) LED 2

325 seconds LED 6 Fixed LED 11

390 seconds LED 7


Circulator function. Two circulator functioning modes can
455 seconds LED 8 be selected in the central heating phase.
In the intermittent mode, it is activated either by the room
520 seconds LED 9
thermostat or by the Remote control, in the continuative
585 seconds LED 10 mode the circulator works all the time when the main selector
switch is on heating.
650 seconds (Standard setting) LED 11
LED ashing
Circulator function
(slow)
Intermittent (Standard setting) LED 2

Continuous LED 11

STEkW ed 12/06 38http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

D.h.w. exchanger preheating. When this function is active Relay 3 operation*.


it is possible to maintain the d.h.w. exchanger at a constant Relay 3 operation LED ashing
temperature of 50 C in order to have a quicker supply of (single, free contacts) (slow)
domestic hot water.
O (Standard setting) LED 2
LED ashing
D.h.w. exchanger preheating Aqua Celeris system powered LED 5
(slow)
O (Standard setting) LED 2 General alarm LED 6

On LED 11 Central heating phase on LED 7

External gas valve powered LED 8


Gas G110 China Gas. The setting of this function serves to
adjust the boiler to work with the gases of the rst family.
LED ashing
Gas G110 - China Gas (rst family gas)
(slow)
* In case of connection to the relay control board (op-
tion).
O (Standard setting) LED 2

On LED 11

Relay 1 operation*.
Relay 1 operation LED ashing
(switching, free contacts) (slow)
O LED 2

Main zone command (Standard setting) LED 3

General alarm LED 6

Central heating phase on LED 7

External gas valve powered LED 8

Relay 2 operation*.
Relay 2 operation (single, contacts energised LED ashing
with SELV contact in series) (slow)
O (Standard setting) LED 2

Remote lling LED 4

General alarm LED 6

Central heating phase on LED 7

External gas valve powered LED 8


Secondary zone command (from S20 on relay
LED 9
card contact)

STEkW ed 12/06 39http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior kW operating sequence.


Central heating phase Domestic hot water phase
Power on Power on
Main selector switch on WINTER Main selector switch on SUMMER or WINTER

Integrated board operation enabled Integrated board operation enabled
Closing of the main selector switch contacts (WINTER position) Closing of the main selector switch contacts (SUMMER position)
enables operation in the central heating phase enables operation in the domestic hot water phase


Closing of the Room thermostat switch / CAR operation
request Closing of the d.h.w. ow switch
Request of the room thermostat or CAR (if mounted) detects Running of domestic hot water
conditions that require operation in the central heating phase


Powering the circulator and 3-way diverter valve Powering the circulator and 3-way diverter valve
The integrated board powers the boiler circulator and the electric The integrated board powers the boiler circulator and the electric
3-way diverter valve, the valve is moved into the heating position 3-way diverter valve, the valve is moved into the d.h.w. position


System pressure micro switch closes
The pressure in the primary circuit higher than the minimum cut-o value, causes the system pressure switch contact to close


Flue pressure switch contact control
The integrated board checks the correct position of the ue pressure switch (NC contact)


Fan powered
The integrated board powers the fan


Flue pressure switch contact control
The integrated board checks switching of the ue pressure switch contact resulting from fan operation (NO contact)


Ignition electrodes powered
The integrated board powers the ignition electrodes


Gas valve coils powered
Enabled by the overheating safety thermostat, the integrated board powers the gas valve coils


Burner ignition (automatic slow ignition)
The integrated board sends the slow ignition current to the modulation coil


Flame detection
By means of the ionisation electrode, the integrated board detects burner ignition


Boiler working
The burner works at a power that varies according to the type of request, to the adjustments/settings made and to the temperatures
detected by the NTC probes

STEkW ed 12/06 40http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

Technical data.

EOLO Maior 24 kW technical data.

Nominal heat input kW (kcal/h) 25,9 (22241)


Minimum heat output kW (kcal/h) 10,7 (9195)
Nominal heat output (working) kW (kcal/h) 24,0 (20640)
Minimum heat output (working) kW (kcal/h) 9,3 (8000)
Working heat performance at nominal output % 92,8
Working heat performance at 30% load of nominal output % 90,7
Loss of heat at shell with burner On/O % 0,80 / 0,70
Loss of heat at stack with burner On/O % 6,40 / 0,02
G20 G30 G31
Gas nozzle diameter mm 1.35 0.79 0.79
Supply pressure mbar (mm H2O) 20 (204) 29 (296) 37 (377)

Max. operating pressure of heating circuit bar 3


Max. operating temperature of heating circuit C 90
Adjustable heating temperature C 35 - 85
Total volume of heating expansion vessel l 7,4
Expansion vessel preloading bar 1,0
Generator water content l 0,6
Available head with a ow rate of 1000 l/h kPa (m H2O) 35,30 (3,6)
Working heat output for the production of hot water kW (kcal/h) 24,0 (20640)
D.h.w. adjustable temperature C 30 - 60
D.h.w. ow limiting device at 2 bar l/min 7,5
D.h.w. circuit min. (dynamic) pressure bar 0,3
D.h.w. circuit maximum operating pressure bar 10
Minimum domestic hot water run o l/min 2,0
Specic ow rate (T 30C) l/min 11,2
Specic ow rate in continuous duty (T 30C) l/min 11,5
Full boiler weight kg 44,3
Empty boiler weight kg 43,0

Electrical connection V/Hz 230/50


Rated power input A 0.62
Installed electrical power W 130
Power absorbed by the circulator W 90
Power absorbed by the fan W 25
Appliance electrical system cutout - IPX4D

G20 G30 G31


Rated power fumes mass ow kg/h 51 57 60
Minimum power fumes mass ow kg/h 54 60 59
CO2 at Q. Nom./Min. % 7,40 / 2,70 7,50 / 2,80 7,00 / 2,80
CO at 0% of O2 at Q. Nom./Min. ppm 62 / 83 47 / 17 35 / 15
NOX at 0% of O2 at Q. Nom./Min. ppm 150 / 100 200 / 50 190 / 50
Fumes temperature at nominal output C 119 110 105
Fumes temperature at minimum output C 94 87 87
NO X class - 2
NO X weighted mg/kWh 176
CO weighted mg/kWh 54
Type of appliance C12 /C32 / C42 / C52 / C82 / B22 / B32
Category II2H3+

STEkW ed 12/06 41http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior 28 kW technical data.

Nominal heat input kW (kcal/h) 30,1 (25920)


Minimum heat output kW (kcal/h) 12,2 (10488)
Nominal heat output (working) kW (kcal/h) 28,0 (24080)
Minimum heat output (working) kW (kcal/h) 10,5 (9030)
Working heat performance at nominal output % 92,9
Working heat performance at 30% load of nominal output % 90,9
Loss of heat at shell with burner On/O % 0,40 / 0,62
Loss of heat at stack with burner On/O % 6,70 / 0,02
G20 G30 G31
Gas nozzle diameter mm 1.35 0.77 0.77
Supply pressure mbar (mm H2O) 20 (204) 29 (296) 37 (377)

Max. operating pressure of heating circuit bar 3


Max. operating temperature of heating circuit C 90
Adjustable heating temperature C 35 - 85
Total volume of heating expansion vessel l 7,4
Expansion vessel preloading bar 1,0
Generator water content l 2,2
Available head with a ow rate of 1000 l/h kPa (m H2O) 38,24 (3,9)
Working heat output for the production of hot water kW (kcal/h) 28,0 (24080)
D.h.w. adjustable temperature C 30 - 60
D.h.w. ow limiting device at 2 bar l/min 9,0
D.h.w. circuit min. (dynamic) pressure bar 0,3
D.h.w. circuit maximum operating pressure bar 10
Minimum domestic hot water run o l/min 2,0
Specic ow rate (T 30C) l/min 13,3
Specic ow rate in continuous duty (T 30C) l/min 13,4
Full boiler weight kg 48,3
Empty boiler weight kg 45,0

Electrical connection V/Hz 230/50


Rated power input A 0.83
Installed electrical power W 150
Power absorbed by the circulator W 88
Power absorbed by the fan W 48
Appliance electrical system cutout - IPX4D

G20 G30 G31


Rated power fumes mass ow kg/h 64 64 65
Minimum power fumes mass ow kg/h 68 66 68
CO2 at Q. Nom./Min. % 6,8 / 2,4 7,8 / 2,9 7,6 / 2,8
CO at 0% of O2 at Q. Nom./Min. ppm 45 / 85 65 / 100 40 / 95
NOX at 0% of O2 at Q. Nom./Min. ppm 118 / 80 190 / 85 150 / 65
Fumes temperature at nominal output C 117 118 116
Fumes temperature at minimum output C 92 95 93
NO X class - 3
NO X weighted mg/kWh 124
CO weighted mg/kWh 62
Type of appliance C12 /C32 / C42 / C52 / C82 / B22 / B32
Category II2H3+

- The ues temperature values refer to an air inlet temperature - Maximum sound power emitted when the boiler is working
of 15C. is < 55dBA. This measurement refers to tests in a semi free
- Data relative to domestic hot water performance refer to a eld with the boiler working at full power and with the
dynamic inlet pressure of 2 bar and an inlet temperature of 15C; extension of the ue accessories complying with product
these values can be measured at boiler outlet considering that to standards.
achieve these values it is necessary to mix with cold water.

STEkW ed 12/06 42http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior 32 kW technical data.

Nominal heat input kW (kcal/h) 34,4 (29579)


Minimum heat output kW (kcal/h) 12,5 (10750)
Nominal heat output (working) kW (kcal/h) 32,00 (27520)
Minimum heat output (working) kW (kcal/h) 10,5 (9030)
Working heat performance at nominal output % 93,0
Working heat performance at 30% load of nominal output % 91,5
Loss of heat at shell with burner On/O % 0,50 / 0,46
Loss of heat at stack with burner On/O % 6,50 / 0,01
G20 G30 G31
Gas nozzle diameter mm 1.35 0.79 0.79
Supply pressure mbar (mm H2O) 20 (204) 29 (296) 37 (377)

Max. operating pressure of heating circuit bar 3


Max. operating temperature of heating circuit C 90
Adjustable heating temperature C 35 - 85
Total volume of heating expansion vessel l 7,4
Expansion vessel preloading bar 1,0
Generator water content l 2,3
Available head with a ow rate of 1000 l/h kPa (m H2O) 39,42 (4,0)
Working heat output for the production of hot water kW (kcal/h) 32,00 (27520)
D.h.w. adjustable temperature C 30 - 60
D.h.w. ow limiting device at 2 bar l/min 9,0
D.h.w. circuit min. (dynamic) pressure bar 0,3
D.h.w. circuit maximum operating pressure bar 10
Minimum domestic hot water run o l/min 2,0
Specic ow rate (T 30C) l/min 14,8
Specic ow rate in continuous duty (T 30C) l/min 15,3
Full boiler weight kg 49,5
Empty boiler weight kg 46,0

Electrical connection V/Hz 230/50


Rated power input A 0,96
Installed electrical power W 170
Power absorbed by the circulator W 98
Power absorbed by the fan W 60
Appliance electrical system cutout - IPX4D

G20 G30 G31


Rated power fumes mass ow kg/h 66 68 70
Minimum power fumes mass ow kg/h 67 70 72
CO2 at Q. Nom./Min. % 7,5 / 2,5 8,4 / 2,8 8,1 / 2,7
CO at 0% of O2 at Q. Nom./Min. ppm 110 / 70 95 / 77 60 / 80
NOX at 0% of O2 at Q. Nom./Min. ppm 160 / 100 211 / 111 210 / 100
Fumes temperature at nominal output C 122 121 118
Fumes temperature at minimum output C 116 115 113
NO X class - 2
NO X weighted mg/kWh 190
CO weighted mg/kWh 56
Type of appliance C12 /C32 / C42 / C52 / C82 / B22 / B32
Category II2H3+

- The ues temperature values refer to an air inlet temperature - Maximum sound power emitted when the boiler is working
of 15C. is < 55dBA. This measurement refers to tests in a semi free
- Data relative to domestic hot water performance refer to a eld with the boiler working at full power and with the
dynamic inlet pressure of 2 bar and an inlet temperature of 15C; extension of the ue accessories complying with product
these values can be measured at boiler outlet considering that to standards.
achieve these values it is necessary to mix with cold water.

STEkW ed 12/06 43http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior 28 kW X technical data.

Nominal heat input kW (kcal/h) 30,1 (25923)


Minimum heat output kW (kcal/h) 12,2 (10488)
Nominal heat output (working) kW (kcal/h) 28,0 (24080)
Minimum heat output (working) kW (kcal/h) 10,5 (9030)
Working heat performance at nominal output % 92,9
Working heat performance at 30% load of nominal output % 90,9
Loss of heat at shell with burner On/O % 0,40 / 0,62
Loss of heat at stack with burner On/O % 6,70 / 0,02
G20 G30 G31
Gas nozzle diameter mm 1,35 0,77 0,77
supply pressure mbar (m H2O) 20 (204) 29 (296) 37 (377)

Max. operating pressure of heating circuit bar 3


Max. operating temperature of heating circuit C 90
Adjustable heating temperature C 35 - 85
Total volume of heating expansion vessel l 7,4
Expansion vessel preloading bar 1,0
Generator water content l 1,8
Available head with a ow rate of 1000 l/h kPa (m H2O) 37,75 (3,9)
Specic ow rate S.T.U. 80 litres (T 30C) l/min 20,9
Specic ow rate S.T.U. 105 litres (T 30C) l/min 23,8
Specic ow rate S.T.U. 120 litres (T 30C) l/min 26,6
Specic ow rate S.T.U. 200 litres (T 30C) l/min 35,4
Specic ow rate in continuous duty with S.T.U. (T 30C) l/min 13,3
Full boiler weight kg 47,5
Empty boiler weight kg 45,0

Electrical connection V/Hz 230/50


Rated power input A 0,83
Installed electrical power W 150
Power absorbed by the circulator W 88
Power absorbed by the fan W 48
Appliance electrical system cutout - IPX4D
G20 G30 G31
Rated power fumes mass ow kg/h 64 64 65
Minimum power fumes mass ow kg/h 68 66 68
CO2 at Q. Nom./Min. % 6,80 / 2,40 7,80 / 2,90 7,60 / 2,80
CO at 0% of O2 at Q. Nom./Min. ppm 45 / 85 65 / 100 40 / 95
NOX at 0% of O2 at Q. Nom./Min. ppm 118 / 80 190 / 85 150 / 65
Fumes temperature at nominal output C 117 118 116
Fumes temperature at minimum output C 92 95 93

NOX class - 3
NOX weighted mg/kWh 124
CO weighted mg/kWh 63

Type of appliance C12 /C32 / C42 / C52 / C82 / B22 / B32


Category II2H3+

- The ues temperature values refer to an air inlet temperature


of 15C.
- Maximum sound power emitted when the boiler is working
is < 55dBA. This measurement refers to tests in a semi free
eld with the boiler working at full power and with the
extension of the ue accessories complying with product
standards.

STEkW ed 12/06 44http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior 24 kW variable heat output.

NATURAL GAS (G20) BUTANE (G30) PROPANE (G31)


GAS NOZZLE GAS NOZZLE GAS NOZZLE
HEAT HEAT
FLOWRATE PRESSURE FLOWRATE PRESSURE FLOWRATE PRESSURE
OUTPUT OUTPUT
BURNER BURNER BURNER BURNER BURNER BURNER

(kW) (kcal/h) (m3/h) (mbar) (mm H2O) (kg/h) (mbar) (mm H2O) (kg/h) (mbar) (mm H2O)

24,0 20640 2,74 12,20 124,4 2,04 27,50 280,5 2,01 36,20 369,2
21,5 18500 2,47 9,94 101,4 1,84 22,02 224,6 1,81 29,08 296,6
19,8 17000 2,28 8,50 86,7 1,70 18,63 190,0 1,68 24,62 251,2
19,2 16500 2,22 8,04 82,0 1,65 17,58 179,3 1,63 23,23 237,0
18,6 16000 2,16 7,60 77,5 1,61 16,57 169,0 1,58 21,89 223,3
18,0 15500 2,10 7,17 73,1 1,56 15,60 159,1 1,54 20,60 210,1
17,4 15000 2,03 6,75 68,8 1,51 14,67 149,6 1,49 19,35 197,4
16,9 14500 1,97 6,34 64,7 1,47 13,78 140,6 1,45 18,16 185,2
16,3 14000 1,91 5,95 60,7 1,42 12,94 131,9 1,40 17,00 173,4
15,7 13500 1,84 5,57 56,8 1,37 12,13 123,7 1,35 15,90 162,2
15,1 13000 1,78 5,20 53,0 1,33 11,36 115,9 1,31 14,85 151,4
14,5 12500 1,72 4,84 49,4 1,28 10,64 108,5 1,26 13,84 141,2
14,0 12000 1,65 4,50 45,9 1,23 9,95 101,5 1,21 12,88 131,4
13,4 11500 1,59 4,17 42,5 1,18 9,31 95,0 1,17 11,97 122,1
11,0 9500 1,33 2,97 30,2 0,99 7,16 73,0 0,98 8,83 90,0
9,3 8000 1,13 2,20 22,4 0,84 6,00 61,2 0,83 7,00 71,4

EOLO Maior 28 kW - 28 kW X variable heat output.

NATURAL GAS (G20) BUTANE (G30) PROPANE (G31)


GAS NOZZLE GAS NOZZLE GAS NOZZLE
HEAT HEAT
FLOWRATE PRESSURE FLOWRATE PRESSURE FLOWRATE PRESSURE
OUTPUT OUTPUT
BURNER BURNER BURNER BURNER BURNER BURNER

(kW) (kcal/h) (m3/h) (mbar) (mm H2O) (kg/h) (mbar) (mm H2O) (kg/h) (mbar) (mm H2O)

28,0 24080 3,19 10,50 107,1 2,38 27,41 279,6 2,34 36,30 370,3
26,7 23000 3,05 9,54 97,3 2,27 25,29 258,0 2,24 33,40 340,7
25,6 22000 2,92 8,71 88,9 2,18 23,42 238,9 2,14 30,85 314,6
24,4 21000 2,79 7,93 80,9 2,08 21,62 220,6 2,05 28,40 289,7
23,3 20000 2,67 7,19 73,4 1,99 19,90 203,0 1,96 26,07 265,9
22,1 19000 2,54 6,50 66,3 1,89 18,25 186,2 1,87 23,84 243,1
20,9 18000 2,42 5,86 59,7 1,80 16,67 170,0 1,78 21,70 221,4
19,8 17000 2,29 5,25 53,6 1,71 15,14 154,4 1,68 19,66 200,5
18,6 16000 2,17 4,68 47,8 1,62 13,68 139,5 1,59 17,70 180,6
17,4 15000 2,05 4,16 42,4 1,52 12,27 125,2 1,50 15,83 161,5
16,3 14000 1,92 3,67 37,4 1,43 10,92 111,4 1,41 14,04 143,2
15,1 13000 1,80 3,22 32,8 1,34 9,62 98,1 1,32 12,33 125,8
14,0 12000 1,67 2,80 28,6 1,24 8,37 85,4 1,23 10,70 109,2
12,8 11000 1,54 2,43 24,8 1,15 7,17 73,1 1,13 9,15 93,3
11,6 10000 1,42 2,09 21,3 1,06 6,02 61,4 1,04 7,67 78,2
10,5 9030 1,29 1,80 18,4 0,96 4,95 50,5 0,95 6,30 64,3

STEkW ed 12/06 45http://serviceimmergas.ro EOLO Maior kW


Technical Documentation Technical Documentation

EOLO Maior 32 kW variable heat output.


NATURAL GAS (G20) BUTANE (G30) PROPANE (G31)
GAS NOZZLE GAS NOZZLE GAS NOZZLE
HEAT HEAT
FLOWRATE PRESSURE FLOWRATE PRESSURE FLOWRATE PRESSURE
OUTPUT OUTPUT
BURNER BURNER BURNER BURNER BURNER BURNER

(kW) (kcal/h) (m3/h) (mbar) (mm H2O) (kg/h) (mbar) (mm H2O) (kg/h) (mbar) (mm H2O)

32,0 27520 3,64 12,40 126,5 2,71 28,20 287,6 2,67 36,00 367,2
29,7 25500 3,39 10,54 107,5 2,52 24,33 248,1 2,49 31,00 316,2
27,9 24000 3,20 9,29 94,7 2,38 21,67 221,1 2,35 27,59 281,4
26,7 23000 3,08 8,50 86,7 2,29 20,01 204,1 2,26 25,45 259,6
25,6 22000 H 2,95 7,76 79,2 2,20 18,42 187,9 2,17 23,41 238,8
E
24,4 21000 A 2,83 7,07 72,1 2,11 16,91 172,4 2,08 21,48 219,1
T
23,3 20000 I 2,71 6,41 65,4 2,02 15,46 157,7 1,99 19,64 200,3
N
22,1 19000 G 2,58 5,79 59,0 1,93 14,09 143,7 1,90 17,89 182,5
20,9 18000 2,46 5,21 53,1 1,83 12,79 130,5 1,81 16,23 165,6
19,8 17000 2,34 4,66 47,6 1,74 11,55 117,9 1,72 14,67 149,6
18,6 16000 2,21 4,16 42,4 1,65 10,39 105,9 1,63 13,19 134,6
17,4 15000 2,09 3,69 37,6 1,56 9,29 94,7 1,53 11,81 120,4
16,3 14000 1,96 3,26 33,3 1,46 8,25 84,1 1,44 10,51 107,2
15,1 13000 1,84 2,87 29,3 1,37 7,28 74,3 1,35 9,30 94,9
12,5 10750 1,55 2,13 21,7 1,15 5,34 54,5 1,14 6,91 70,5
10,5 9030 DOMESTIC 1,32 1,70 17,3 0,99 4,10 41,8 0,97 5,40 55,1

STEkW ed 12/06 46http://serviceimmergas.ro EOLO Maior kW

You might also like