INTAKE WELL PH - STRUCTURAL DESIGN AND CALCULATIONS OF DESIGN CHECK SHEET


TITLE
INTAKE WELL CMA KK

9.0 DESIGN OF BAFFLE WALL SLAB AT OPENING LOCATION

SLAB
2.5

1.45
PLAN OF WELL WITH BAFFLE

Slab

1.45
LARSEN & TOUBRO LIMITED

POWER ENGINEERING & DESIGN SERVICES CENTER


DOC. NO. Date
PROJECT 2x660 MW KHARGONE STPP
9578-001-318A-PVC-U-293 06-03-2017

INTAKE WELL PH - STRUCTURAL DESIGN AND CALCULATIONS OF DESIGN CHECK SHEET


TITLE
INTAKE WELL CMA KK

The slab will be supported on both the side by baffle walls

Ly 1.45 m
Lx 2.55 m
Ly/Lx 1.759 >2
Hence design as one way slab

Considering the Thickness of the slab as = 500 mm


= 0.5 m
Groove for Stop log gate/ Trash Rack = 300 mm
Self wt of the slab 0.5*25= 12.5 kN/m
Load due to Stop log gate = 35 kN
Considering impacting factor = 1.5
= 52.5 kN
UDL due to Stop log gate on slab = 36.21 kN/m

Total UDL due DL+LL 36.21+12.5= 48.7 kN/m


Max Moment due to UDL 48.71*1.45^2/8= 12.8 kNm
Max shear due to UDL 48.71*1.45/2= 35.3 kN
dreq SQRT(12.801596875*10^6*6/2000)= 196.0 mm
dpro 200.0 mm

SAFE
2
Ast req 12.801596875*10^6/(240*0.907*200)= 294.0 mm
2
Ast min 0.12/100*1000*500= 600 mm
Provide 12 mm 175mmc/c on both the side
2
= 646 mm