You are on page 1of 8

International Journal of Emerging Technology and Advanced Engineering

Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)

Short Circuit Stress Calculation in Power Transformer Using


Finite Element Method on High Voltage Winding Displaced
Vertically
Ashfaq Ahmad1, Iqra Javed2, Waseem Nazar3
1,3
The University of Lahore Department of Electronics
2
University of Management and Technology Department of Informatics and Systems
Abstract The objective of this research is to compute the Data collected from the High Voltage testing laboratory
mechanical stresses in power transformer resulting from the shows that one fifth of the transformers under test are failed
currents more than rated value during its operation. Due to due to weak insulation which ultimately bear short-circuit
this high fault current, mechanical stresses are produced current. It is important to mention that the transformers
indifferent directions which may cause the damage of winding
which have to undergo this test, are manufactured with
insulation. Various techniques have been adopted to analyze
the stresses on transformer windings. For the almost and special care in the manufacturers premises
accomplishment of research, FEM (Finite Element Method) is [9, 10]. Lack of insulation strength of transformers imposed
utilized for the calculation of short circuit forces. All by manufacturers can cause severe damages to the
mechanical generated in transformers are calculated transformer as well as the system. System disruption
mathematically and verified through software. For the include following effects;
verification of results, real time measurements on 20MVA 132
/11.5KV power transformer are made. Various failure
Deformation of LV and HV windings
mechanisms due to these forces have been discussed. Broken pressure plates on windings
Moreover, design parameters which determine the maximum Bending of clamping structure
stresses in different parts of the transformer are also the part Bulging of tank body
of research. Effects of asymmetrical current and forces in Collapse of bushings
various parts of transformer have also been narrated. Short-Circuited tapping leads
Moreover, Different properties of materials have been studied
and the usage of proper material for withstanding the Rest of the paper organized as follows;
dynamic effects of short circuits is discussed. Workmanship
errors on short circuit withstand capability have also been
Section-II discusses types of short circuits in power
elucidated. Finally, a complete model for the study of dynamic system, section III narrates the forces which are produced
effects of short-circuits in a power transformer and due to short circuit current while remaining sections
comparison with forces calculated with FEMM soft ware [13]. include axial and radial forces acting on windings, and last
section describes the fem calculations results of forces
Keywords Finite element method; Power transformer; acting on transformer windings [5].
Short circuit stress; Mechanical Stresses; Axial and Radial
Stresses. II. SHORT CIRCUIT CURRENTS
I. INTRODUCTION Almost all types of faults cause the sudden rise of
current in power system which results in malfunction and
Due to continuous growth in demand of electricity, inconsistent operation of installed equipment along with
Government and utility companies have started expansion severe effect on transformer insulation.
of generation stations which include interconnections of Usually, the three-phase faults are the most severe of all;
national grids. Due to these additions, the short circuit hence the transformer should be designed to withstand the
current of the system has increased where many sources of effects of symmetrical three phase faults. It must be
power are available to feed faulty location on the mentioned here that in some cases (Where a tertiary
occurrence of event. All the components in the system are connected winding is present), the single-phase to line fault
affected by this change including transformers which have short-circuit current can be higher than the three-phase
to bear heavy currents. A large number of transformers in fault on those windings, since it is related to very special
power system have been reported to fail due to prolonged cases, emphasis is made on symmetrical three-phase faults
heavy current. only.

301
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
A. Value of symmetrical short-circuit current
For three-phase transformers with two separate
windings, the r.m.s value of the symmetrical short-circuits
current I shall be calculated as in equation (i) [1].

(i)

Where: Fig.2 A Sinusoidal voltage source switched on to an RL network

U: is the rated voltage of the winding under The mechanical strength of the transformer windings
consideration, in Kilovolts should be such that it shall withstand the highest short-
Zt: is the short-circuit impedance of the transformer circuit forces generated which correspond to the first
referred to the winding under consideration, in ohms per current peak in the figure above, since this current peak has
phases the highest magnitude due to presence of DC component in
the current pattern.
Zs: is the short-circuit impedance of the system, in ohms
per phase C. Thermal withstand during short-circuit
As mentioned above, due to addition of more and more During short-circuit, a very high current flows within the
generating stations within an interconnected system, the windings of the transformer. However, the duration of
source impedance Zs is very small and generally neglected short-circuit is very small, the temperature of the windings
for calculations purpose. generally do not rise high enough to damageable values.
Hence, this effect can generally be neglected.
B. Nature of short-circuit current
IEC 60076-5 however, gives a formula for the
Consider the circuit given alternate voltage source. calculation of temperature rise during short-circuits. This
Assuming that the below with an switch is closed at t=0 formula assumes that all the heat produced by the winding
instant, which simulates the short-circuit, the expression for during short-circuits stays in it and none is dissipated. This
the current i(t) can be written as follows: is a poor assumption, but since the limit of allowable
temperature rise is high (250oC), almost all the
transformers qualify this requirement during short-circuit
testing.
According to IEC 60076-5, the average temperature
1attained by the winding after short circuit is calculated
by the equation (ii) [2].
Fig 1A Sinusoidal voltage source switched on to an RL network

i(t) = Imax[sin(t-)] (ii)


Where:
Imax: Maximum value of the current i Where
t: Time, in seconds o: is the initial winding temperature, in degrees
: Phase angle of the circuit impedance [tan-1(L/R)] Celsius
: Time constant [L/R]
J: is the short-circuit current density,
The plot of this current expression with respect to time is
as under:
t: is the duration, in seconds (s)

302
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
III. SHORT-CIRCUIT FORCES Position of tank causes the leakage flux pattern to
When a current carrying conductor lies in a magnetic change which is again ignored in the analytical
field, a force is produced upon that current carrying formula of short-circuit forces calculations.
conductor, whose magnitude is given by equation (iii). Portion of windings under the yoke have a different
leakage field pattern compared to portion outside the
F=B.I.L sin (iii) window. Again this phenomenon is ignored in the
Where: analytical formula.
Effect and presence of mechanical bracings of the
B: flux density, in Tesla windows is ignored in the analytical formula.
I: Current in the conductor, in Amps Combined (axial and radial) forces at the winding
L: length of current carrying element, in meters ends which are the major cause of tilting of the
: angle between flux density vector and current vector conductors are neglected in analytical formula.
Axial imbalance of windings during manufacturing is
This force is called the electromagnetic force because
neglected in the analytical method of forces
it is produced both by combined effect or electric current
calculation. This imbalance usually occurs during
and magnetic flux. [12] The direction of this force can be
shifting over of windings over the core where the
easily computed using the well-Known Left-hand rule.
centerline of windings is not exactly the same.
A. Electromagnetic Forces Axial imbalance within the winding (which is
In transformers, electromagnetic forces may have three normally due to presence of radial spacers in the
components if we model it in 3D cylindrical coordinates. windings) is ignored. During manufacturing of
winding on the winding machines, height of windings
r-component has to be maintained by placement of radial spacers
z-component within it. The position of placement of these
-component stabilization spacers can shift the centerline of the
The r-component of the electromagnetic forces results in winding which cannot be ignored.
the radial forces that act on the windings [8]. The z-
component is the originator of the axial forces that act on IV. FINITE ELEMENT MODELING
the windings. Finally, the -component can cause twisting
motion of the windings, but it is never present because the A. Introduction to finite element method
center axis of the windings is always coinciding with each Finite element method (FEM) is a numerical method
other. mainly used for solving Differential and Integral Equations.
The conventional way to calculate the short-circuit Essence of this method is to divide the application
forces is by solving equation (iii), using data of the domain in very small sub domain elements called as finite
transformer from the design calculation sheets. This elements. Problem is subdivided into Finite size sub
calculation, however, assumes a lot of data which can problems and is independently dealt to find complete
sometimes result in a very safe calculation and, else wise, problem solution.
could result in unsafe margins during calculations. There are many software commercially available
incorporating the Finite Element Method Solution. In this
B. Approximations in analytical formula thesis, a software tool titled meshing and finite element
The analytical method of calculating the short-circuit solver has been used [3]. The model has been drawn using
forces assumes certain data, most prominent of which are: MATLAB with complete computation of leakage flux and
Conductors are tightly wound radially on top of each therefore short-circuit forces.
other and thus the radial short-circuit forces act over B. Finite element method in transformer
the average circumference of the windings.
In transformers, finite element method can be used to
Presence of axial cooling ducts can result in
calculate the following quantities:
appreciable error in the short-circuit forces
calculations which is ignored in the analytical formula Eddy currents and winding stray losses
[8]. Electric field analysis

303
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
Temperature gradient calculations
Short-circuit stresses
Stress-strain analysis of the clamping structure
C. Steps of finite element modeling.
Finite Element modeling is a highly accurate method of
calculating the transformer parameters. The FEM formation
makes use of the fact that poisons partial-differential
equation is satisfied when total magnetic energy function is
a minimum [4].
1- The geometry to solve (which is basically the core
and set of transformer winding represented simple as
rectangular blocks) can be drawn using most CAD
programs. In this work, Auto Cad 2010 is used to
drawn the geometry in .dxf format.
2-
Fig. 4 Meshing of the transformer geometry

4- The properties of each of the blocks drawn, is then


assigned along with the boundary conditions. Since
core has a very high relative permeability value, it
will not store any appreciable energy. Hence, it
doesnt matter whether core is given a relative
permeability of 10,000 or 100,000. When assigning
the properties to the windings, it must be made sure
that the ampere-turns of all the winding regimes must
be equal and opposite, so that no mutual component
of flux in the core should exist.
5- The space filled with oil is assigned a relative
Fig. 3 Geometry of the transformer
permeability of 1, including the windings.
6- The geometry is solved in the FEM solver and the
3- Once the geometry is ready, it is then divided in to flux leakage plot obtained:
finite elements i.e. small elements. The smaller the
size of each mesh or element, the higher will be the
accuracy of the results can be obtained if problem is
divided into number small problems. Different models
and geometries of transformer for the application and
calculations are given in fig 4, 5, 6 and 7. while fig. 8
and 9 gives flux plots of transformer which are
important to obtain while calculating short circuit
effect on power transformer windings.

Fig. 5 Flux pattern of a transformer

304
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
V. ANALYSIS ON STRESSES BASED ON VERTICAL The geometries are solved in the FEM solver software
MOVEMENT and the flux leakage plots obtained as in fig.8.
Analysis of HV winding in vertical of power transformer
performed.
The winding rotation steps were chosen arbitrary as per
design approach. The movement step is 0-mm, 2-mm, 5-
mm, 10-mm, 15-mm is chosen for vertical respectively.
The results and geometry model for these movements
are given as below in fig.6.

Fig. 8 Flux plot

Following is the comprehensive simulation results of


Fig. 6 Geometrical model fluxes obtained from FEM measured forces obtained from
Fig.7 Gives mesh model in these cases would be FEMM by setting properties of core, oil, LV, HV windings
displaced in vertically as shown below etc. It also includes comparison plots of forces obtained by
mat lab.
There are number of findings from the simulation results
of FEMM.
The direction of short-circuit flux (arrows in the fig.)
Total effect of the forces appears to cancel out.
Forces at the winding centre are purely radial.
Inner winding is subject to buckling effect.
Outer winding tends to stretch out.
Forces at the winding ends have both axial and radial
direction [7, 11].
The flux simulation results at vertical movement are
given below which are extracted from [6,7].The minimum
flux density is shown with light color while maximum flux
density is present at top middle and bottom turns of
winding. Different colors show the level of flux produce in
windings followed by measurement of H.V and L.V forces
at bottom and in different positions in windings with the
help of FEM. Results are concluded by comparing the
results of FEMM and measurements made mathematically.
In given below flux density plots as in fig. 9, various levels
Fig. 7 Mesh model of flux densities are presented by different colors.
305
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)

Fig. 11 Comparison of HV forces in windings

From above plot it is clear that in early turns the


negative forces are dominant and in middle of the turns the
Fig. 9 Flux density plot forces approach to zero because of cancelation of effect of
the negative and positive forces. This force applied on
VI. VERTICAL WINDING FORCES winding pattern is same for the displacements of 0-mm, 2-
The comparison plot of LV forces in windings at mm and 15-mm. The only difference is the windings
different displacement is given below in fig. 10. having less displacement has tendency of negative forces to
approach from negative to zero more quickly and forces
approach from zero to positive more slowly and vice versa.
The left side of the above plot of fig.11 is the forces plot
when high voltage winding displaced at 5-mm and 10-mm,
it is clear that in early turns the negative forces are
dominant and the middle turn positive forces are dominant,
in the last turns forces are approach positive to negative
and saturated.
The Fig.10 and Fig.11 shows the complete comparison
plots of LV and HV forces in windings at different
displacement. The Fig.12 and Fig.13 shows the individual
plots of forces in winding at different displacements 0-mm,
Fig. 10 Comparison of LV forces in winding 2-mm, 5-mm, 10-mm and 15-mm respectively.
From the above plot in fig. 10, it is clear that in early
turns the negative forces are dominant and in middle of the
turns the forces approach to zero because of cancelation of
effect of the negative and positive forces. This force
applied on winding pattern is same for the displacements of
0-mm, 2-mm and 15-mm. The only difference is the
windings having less displacement has tendency of
negative forces to approach from negative to zero more Fig.12 Individual LV forces in winding at different displacement
quickly and forces approach from zero to positive more
slowly and vice versa. The left side of the above plot of
fig.10 is the forces plot when high voltage winding
displaced at 5-mm and 10-mm, it is clear that in early turns
the negative forces are dominant and the middle turn forces
approach negative to positive, in the last turns again
negative forces are dominant.
The comparison plot of HV forces in windings at
different displacement is given below in fig. 11. Fig.13 Individual HV forces in winding at different displacement

306
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
A. x-axis forces at winding The accumulated force increases from zero to a constant
The comparison plot of LV forces at bottom of windings maximum value earlier at winding having less
at different displacement is given below in fig. 14. displacement and decreases from maximum value to zero
late in bottom turns and vice versa for windings with more
displacement.
This force applied on winding pattern is same for the
displacements of 0-mm, 2-mm and 15-mm. The forces plot
when high voltage winding displaced at 5-mm and 10-mm,
it is clear that in early turns the positive forces are
dominant and the middle turn negative forces are dominant,
and in the last turns forces are approaches to zero.
The Fig.16 and Fig.17 shows the individual plots of
forces at winding on different displacements 0-mm, 2-mm,
Fig. 14 Comparison of LV forces At windings
5-mm, 10-mm and 15-mm.
From the above plot it is clear that accumulated forces
are minimal in upper and bottom turns. Whereas
accumulated force is maximum at middle turns of
windings. The accumulated force increases from zero to a
constant maximum value earlier at winding having less
displacement and decreases from maximum value to zero
late in bottom turns and vice versa for windings with more
displacement. This force applied on winding pattern is
same for the displacements of 0-mm, 2-mm and 15-mm. Fig.16 Individual LV forces in winding at different displacement
The forces plot when high voltage winding displaced at 5-
mm and 10-mm, it is clear that in early turns the positive
forces are dominant and the middle turn negative forces are
dominant, and in the last turns forces are approaches to
zero and saturated
The comparison plot of HV forces at bottom of windings
at different displacement is given below in fig.15.

Fig.17 Individual HV forces in winding at different displacement

VII. CONCLUSIONS
The results of mechanical forces generated due to
prolonged high currents in power transformer windings
have been evaluated. High temperatures generated inside
transformer may puncture its insulation which causes
breakdown. As Power transformer is very expensive power
system apparatus which is needed to be protected with first
priority. That is why its failure avoided and comprehensive
analysis is done to cater all drastic situations which may
Fig. 15Comparison of HV forces at windings
cause its complete failure. This research will enable the
transformer manufacturers for careful design of transformer
From the above plot it is clear that accumulated forces and the power utility authorities to ensure its safe operation
are minimal in upper and bottom turns. Whereas in power system.
accumulated force is maximum at middle turns of
windings.

307
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
REFERENCES [8] Kojima, H., Miyata, H., Shida, S., and Okuyama, K. Buckling
strength analysis of large power transformer windings subjected to
[1] Bertagnolli, Georgio, Short-circuit Duty of Power Transformers, electromagnetic force under short circuit, IEEE Transactions on
Second revised edition, Legnano, Italy, ABB Transformatori, 1996. Power Apparatus and Systems, Vol. PAS- 99, No. 3, May/June
[2] IEC 60076 Part 5, 2000-07, Power Transformers Ability to 1980, pp. 12881297.3, pp. 15671576.
withstand short circuit. [9] Moser, H.P., Dahinden V. Transformerboard II, Weidmann AG,
[3] Meeker, D., (September 2006) Finite Element Method Magnetics - second edition, Rapperswil, 1999.
Version 4.2 Online available: http://femm.foster-miller.com. [10] Kulkarni, S.V., Khaparde, S.A. Transformer Engineering Design
[4] Andersen, O.W. Transformer leakage flux program based on Finite and Practice, Marcel Dekker, New York, 2004.
Element Method, IEEE Transactions on Power Apparatus and [11] Gee, F.W. and Whitaker, J.D. Factors affecting the choice of pre-
Systems, Vol. PAS-92, 1973, pp. 682689. stress applied totransformer windings, IEEE Summer General
[5] Salon, S., LaMattina, B., and SivaSubramaniam, K. Comparison of Meeting, Toronto, Canada, 1963, Paper No. 631012.
assumptions in computation of short circuit forces in transformers, [12] Kurtz, R.A. Comparison of Mechanical Strengths of Three
IEEE Transactions on Magnetics, Vol. 36, No. 5, September 2000, Materials Used as Pressure Plates in Oil-Filled Transformers,
pp. 35213523. Proceedings: Electrical Electronics Insulation Conference and
[6] Patel, M.R. Dynamic response of power transformers under axial Electrical Manufacturing and Coil Winding Conference, October
short circuit forces, Part I: winding and clamp as 1993, pp. 519-523.
individualcomponents, IEEE Transactions on Power Apparatus and [13] National Transmission and Despatch Company Specification
Systems, Vol. PAS-92, September/October 1973, pp. 15581566. P46:2008 Power Transformer.
[7] Patel, M.R. Dynamic response of power transformers under axial
short circuit forces, Part II: windings and clamps as a combined
system, IEEE Transactions on Power Apparatus and Systems, Vol.
PAS-92, September/October 1973, pp. 15671576.

308

You might also like