You are on page 1of 17

Copying of this document, and giving it to others and the use or communication of the contents there of, are

forbidden without express authority. Offenders are liable to the payment of damages. All rights reserved in
the event of the grant of patent or registration of a utility model or design.

The color scheme of the switchgear, illustrated in this document, is derived from the FEM-Model.
For the real switchgear color, see product brochures.

Customer 8DN8
Kennwort 132 kV

Date 21.09.2015
Author Kollet
Foundation loads
Appr. Niederkorn
Norm.

Page

Siemens AG (4) E50115-B0004-R102 1 of


15
Rev. Remarks Date Name
s Author: E T HP GS OE MEN / Kollet Page: 2 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

DEFINITION OF LOADS ORIENTATION OF FORCES


AND MOMENTS
LC1 Dead load
LC2 Load by thermal expansion
LC3 Static conductor tension
LC4 Windload X-direction
LC5 Windload Y-direction
LC6 Short-circuit forces
LC7 Switching forces
LC8 Earthquake load X-direction
LC9 Earthquake load Y-direction
LC10 Earthquake load Z-direction

LOADCASES

If not otherwise specified, the following load combinations shall be used:

Loadcombination for Normal Load Case


Lcomb 1: LC1
Lcomb 2: LC1 and LC2 and LC3 and LC4
Lcomb 3: LC1 and LC2 and LC3 and LC5
Loadcombination for Exceptional Load Case
Lcomb 4: LC1 and LC2 and LC6
Lcomb 5: LC1 and LC2 and LC3 and LC7
Lcomb 6: LC1 and LC2 and LC3 and LC8 and 0.4*LC10
Lcomb 7: LC1 and LC2 and LC3 and 0.4*LC8 and LC10
Lcomb 8: LC1 and LC2 and LC3 and LC9 and 0.4*LC10
Lcomb 9: LC1 and LC2 and LC3 and 0.4*LC9 and LC10

The loads shall be combined in the direction that produces the most severe mechanical stresses
at each foundation
at each foundation
point. point.

NOTES

1. All loads are working loads without safety factors. For design loads safety factors shall be regarded.
2. All foundation loads are given as action loads and refer to top of foundation.
3. Loadtype LC2, LC4, LC5, LC7, LC8, LC9 and LC10 shall be considered with the same values
in opposite direction too.
4. Foundation loads at the loadpoints (10,11,12,13,20,21,30,31,40,41)
shall be considered to act with an eccentricity of 120mm above fastening level (Z-direction).

EARTHQUAKE LOAD
Earthquake Data see Dwg.-No.: (4)E50115-B0004-R104
not applicable horizontal: 1,87g vertical: 1,13g

WIND LOAD
700Pa
s Author: E T HP GS OE MEN / Kollet Page: 3 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

+
X

X
+ +
X
+
X.

X.

X X.2
+ +
X X.4

+
X.3 X
X.
+ +
X. X X X.
X.

Explanation of load points and fixing points:

Explanation of the application and designation of the load points and fixing points:

1. For steel structures with one fixing point, the load point - designated with a number X
is equal to the fixing point.

2. For steel structures with more than one fixing point the following has to be applied:

2.1 These steel structures have one virtual common load point in the centre of the
corresponding fixing points, designated with a number X.
2.2 The corresponding fixing points are designated with numbers X.1, X.2, X.3 and X.4.
s Author: E T HP GS OE MEN / Kollet Page: 4 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LC7
s Author: E T HP GS OE MEN / Kollet Page: 5 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP23
LP22

LP41 LP31 LP11


LP21 LP24
LP12

LP40 LP30 LP20 LP10 LP13


s Author: E T HP GS OE MEN / Kollet Page: 6 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP17 LP16

LP15 LP14
s Author: E T HP GS OE MEN / Kollet Page: 7 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP26 LP25

LP33 LP32
s Author: E T HP GS OE MEN / Kollet Page: 8 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP43 LP42

LP45 LP44
s Author: E T HP GS OE MEN / Kollet Page: 9 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP10
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -1 0 22 1 0 -1
LC2 2 -3 -8 -1 0 1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 8 1 0 0
LC8 16 6 -43 1 -1 -2
LC9 2 10 17 10 0 -1
LC10 0 0 16 2 0 0

LP11
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 3 1 8 1 0 0
LC2 4 5 23 1 0 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 8 2 0 0
LC8 17 -5 39 8 -1 -2
LC9 2 1 17 7 0 -2
LC10 1 0 5 1 0 0

LP12
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -1 0 19 -1 0 0
LC2 0 6 -7 6 0 -1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 1 0 0 0
LC8 7 -2 -17 0 -1 2
LC9 1 7 8 8 0 1
LC10 -1 0 16 -2 0 0

LP13
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 4 -1 0 0
LC2 -3 -1 -3 1 0 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 5 -1 3 -1 0 2
LC9 2 1 -3 1 0 1
LC10 0 0 3 -1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 10 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP14
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -13 -13 4 -4 2 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 1 4 1 0 0
LC8 25 10 -12 0 -3 -2
LC9 -1 29 -11 3 1 0
LC10 -1 0 4 1 0 0

LP15
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 26 1 -12 -1 -4 -3
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 -1 10 1 0 0
LC8 16 -6 25 1 -4 -2
LC9 -2 16 -21 0 1 1
LC10 2 -1 5 0 0 0

LP16
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 9 7 0 1 -1 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 7 -3 3 -1 -1 1
LC9 0 29 15 1 0 0
LC10 -1 2 6 -1 0 0

LP17
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -7 -2 0 0 1 -1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 9 1 2 0 -1 1
LC9 2 3 3 -1 0 0
LC10 1 -1 2 -1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 11 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP20
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -2 0 12 0 0 0
LC2 -10 2 5 0 1 -2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 0 2 -1 0 0
LC8 13 -1 -23 4 -1 3
LC9 -2 3 0 0 0 0
LC10 -1 0 5 -1 0 0

LP21
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 2 0 17 0 0 0
LC2 0 0 -29 0 0 -2
LC3 0 0 -1 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 -1 -1 0 0
LC7 0 0 5 -1 0 0
LC8 7 1 34 1 -1 2
LC9 -2 8 -4 11 0 1
LC10 -1 0 10 0 0 0

LP22
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 11 0 0 0
LC2 0 -1 1 -1 0 0
LC3 0 0 -1 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 -2 -1 0 0
LC7 0 0 -1 0 0 0
LC8 0 1 8 1 0 0
LC9 0 14 -2 15 0 1
LC10 -1 0 14 0 0 0

LP23
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 4 0 0 0
LC2 1 -2 -1 -3 -6 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 1 0
LC7 0 0 0 0 0 0
LC8 16 0 1 0 -52 0
LC9 0 3 -1 3 0 0
LC10 0 0 4 0 0 0
s Author: E T HP GS OE MEN / Kollet Page: 12 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP24
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 12 0 0 0
LC2 0 4 0 2 0 0
LC3 0 3 2 1 0 0
LC4 2 0 0 0 -3 0
LC5 0 2 0 1 0 0
LC6 0 6 4 3 0 0
LC7 0 0 0 0 0 0
LC8 22 0 0 0 -34 -1
LC9 0 33 5 16 0 0
LC10 0 0 13 0 0 0

LP25
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -31 63 2 12 6 -3
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 0 10 -1 -1 0
LC8 27 -8 -47 4 -3 2
LC9 -8 27 25 2 0 0
LC10 -1 2 13 -1 0 0

LP26
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 22 45 23 6 -6 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 -2 9 -2 0 0
LC8 22 4 25 -2 -3 2
LC9 -6 25 9 3 1 -1
LC10 3 1 7 -1 0 0

LP30
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -2 0 13 0 0 0
LC2 -9 -2 3 0 1 3
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 0 3 1 0 0
LC8 14 1 -24 -4 -1 -3
LC9 -1 3 4 2 0 1
LC10 -1 0 4 1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 13 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP31
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 1 0 26 0 0 0
LC2 -1 0 -18 1 0 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 3 1 0 0
LC8 5 -1 55 -1 -1 -2
LC9 -1 10 4 25 0 4
LC10 -2 0 23 1 0 0

LP32
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -26 -63 -7 -13 5 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 0 11 1 -1 0
LC8 26 8 -52 -5 -3 -2
LC9 12 27 -35 1 -1 -1
LC10 -1 -2 12 1 0 0

LP33
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 27 -45 23 -6 -6 -2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 2 10 2 0 0
LC8 22 -4 21 1 -3 -2
LC9 8 28 -7 4 -2 -1
LC10 3 -1 5 0 0 0

LP40
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -2 0 15 0 0 0
LC2 -6 0 7 0 0 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 2 0 0 0
LC8 10 0 -29 0 -1 0
LC9 1 2 -6 4 0 1
LC10 -1 0 4 0 0 0
s Author: E T HP GS OE MEN / Kollet Page: 14 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP41
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 2 0 27 -1 0 0
LC2 2 0 -20 0 0 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 -3 0 60 0 0 0
LC9 -1 6 7 26 0 3
LC10 -2 0 22 0 0 0

LP42
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -21 68 -14 14 1 -2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 -3 12 -2 0 0
LC8 15 -7 -26 1 -5 1
LC9 -3 20 30 1 1 0
LC10 1 2 11 -1 0 0

LP43
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 28 23 24 2 -3 1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 -1 2 -1 0 0
LC8 21 2 13 -1 -1 2
LC9 -10 11 -1 2 1 0
LC10 1 0 0 0 0 0

LP44
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -22 -69 -17 -15 1 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 3 11 2 0 0
LC8 15 7 -28 -2 -5 -1
LC9 -2 24 -53 -1 -2 0
LC10 1 -2 11 1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 15 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8

LP45
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 27 -23 23 -2 -3 -1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 1 2 0 0 0
LC8 21 -2 13 1 -1 -2
LC9 10 12 1 2 -1 0
LC10 1 0 0 0 0 0
Version: 2013.11.20 Page: A1.1

Annex
Version: 2013.11.20 Page: A1.2

Conversion of foundation loads from virtual common load


point to fixing point
Loadpoint
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC4 10 0 0 0 -50 0

loads at virtual common load point loads at fixing point to foundation

All loads are given as action loads in the virtual common load point 1

The loads for every fixing point to foundation (1.1, 1.2, 1.3, 1.4) can be calculated using the distances
between the fixing points belonging to a virtual common load point 1.

As an example the action loads for the fixing point to foundation corresponding to load point 1 will be:

Fx = 10kN / 4 = 2,5kN per frame leg 1.1, 1.2, 1.3, 1.4


Fz1 = 50kNm / (1,0m * 2) = 25kN per frame leg 1.1 and 1.3 (pulling forces)
Fz2 = -50kNm / (1,0m * 2) = -25kN per frame leg 1.2 and 1.4 (compression forces)

Using this method the structural engineer will be able to take into account the correct orientation of
the loads at every fixing point to foundation with respect to one another.

So for example, in this load case the orientation of the load will be:

1st load case (pos. x-direction) = compression forces at 1.2, 1.4 and pulling forces 1.1, 1.3
2nd load case (neg. x-direction) = pulling forces at 1.2, 1.4 and compression forces at 1.1, 1.3