Professional Documents
Culture Documents
forbidden without express authority. Offenders are liable to the payment of damages. All rights reserved in
the event of the grant of patent or registration of a utility model or design.
The color scheme of the switchgear, illustrated in this document, is derived from the FEM-Model.
For the real switchgear color, see product brochures.
Customer 8DN8
Kennwort 132 kV
Date 21.09.2015
Author Kollet
Foundation loads
Appr. Niederkorn
Norm.
Page
LOADCASES
The loads shall be combined in the direction that produces the most severe mechanical stresses
at each foundation
at each foundation
point. point.
NOTES
1. All loads are working loads without safety factors. For design loads safety factors shall be regarded.
2. All foundation loads are given as action loads and refer to top of foundation.
3. Loadtype LC2, LC4, LC5, LC7, LC8, LC9 and LC10 shall be considered with the same values
in opposite direction too.
4. Foundation loads at the loadpoints (10,11,12,13,20,21,30,31,40,41)
shall be considered to act with an eccentricity of 120mm above fastening level (Z-direction).
EARTHQUAKE LOAD
Earthquake Data see Dwg.-No.: (4)E50115-B0004-R104
not applicable horizontal: 1,87g vertical: 1,13g
WIND LOAD
700Pa
s Author: E T HP GS OE MEN / Kollet Page: 3 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
+
X
X
+ +
X
+
X.
X.
X X.2
+ +
X X.4
+
X.3 X
X.
+ +
X. X X X.
X.
Explanation of the application and designation of the load points and fixing points:
1. For steel structures with one fixing point, the load point - designated with a number X
is equal to the fixing point.
2. For steel structures with more than one fixing point the following has to be applied:
2.1 These steel structures have one virtual common load point in the centre of the
corresponding fixing points, designated with a number X.
2.2 The corresponding fixing points are designated with numbers X.1, X.2, X.3 and X.4.
s Author: E T HP GS OE MEN / Kollet Page: 4 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LC7
s Author: E T HP GS OE MEN / Kollet Page: 5 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP23
LP22
LP17 LP16
LP15 LP14
s Author: E T HP GS OE MEN / Kollet Page: 7 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP26 LP25
LP33 LP32
s Author: E T HP GS OE MEN / Kollet Page: 8 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP43 LP42
LP45 LP44
s Author: E T HP GS OE MEN / Kollet Page: 9 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP10
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -1 0 22 1 0 -1
LC2 2 -3 -8 -1 0 1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 8 1 0 0
LC8 16 6 -43 1 -1 -2
LC9 2 10 17 10 0 -1
LC10 0 0 16 2 0 0
LP11
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 3 1 8 1 0 0
LC2 4 5 23 1 0 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 8 2 0 0
LC8 17 -5 39 8 -1 -2
LC9 2 1 17 7 0 -2
LC10 1 0 5 1 0 0
LP12
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -1 0 19 -1 0 0
LC2 0 6 -7 6 0 -1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 1 0 0 0
LC8 7 -2 -17 0 -1 2
LC9 1 7 8 8 0 1
LC10 -1 0 16 -2 0 0
LP13
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 4 -1 0 0
LC2 -3 -1 -3 1 0 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 5 -1 3 -1 0 2
LC9 2 1 -3 1 0 1
LC10 0 0 3 -1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 10 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP14
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -13 -13 4 -4 2 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 1 4 1 0 0
LC8 25 10 -12 0 -3 -2
LC9 -1 29 -11 3 1 0
LC10 -1 0 4 1 0 0
LP15
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 26 1 -12 -1 -4 -3
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 -1 10 1 0 0
LC8 16 -6 25 1 -4 -2
LC9 -2 16 -21 0 1 1
LC10 2 -1 5 0 0 0
LP16
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 9 7 0 1 -1 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 7 -3 3 -1 -1 1
LC9 0 29 15 1 0 0
LC10 -1 2 6 -1 0 0
LP17
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -7 -2 0 0 1 -1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 9 1 2 0 -1 1
LC9 2 3 3 -1 0 0
LC10 1 -1 2 -1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 11 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP20
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -2 0 12 0 0 0
LC2 -10 2 5 0 1 -2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 0 2 -1 0 0
LC8 13 -1 -23 4 -1 3
LC9 -2 3 0 0 0 0
LC10 -1 0 5 -1 0 0
LP21
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 2 0 17 0 0 0
LC2 0 0 -29 0 0 -2
LC3 0 0 -1 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 -1 -1 0 0
LC7 0 0 5 -1 0 0
LC8 7 1 34 1 -1 2
LC9 -2 8 -4 11 0 1
LC10 -1 0 10 0 0 0
LP22
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 11 0 0 0
LC2 0 -1 1 -1 0 0
LC3 0 0 -1 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 -2 -1 0 0
LC7 0 0 -1 0 0 0
LC8 0 1 8 1 0 0
LC9 0 14 -2 15 0 1
LC10 -1 0 14 0 0 0
LP23
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 4 0 0 0
LC2 1 -2 -1 -3 -6 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 1 0
LC7 0 0 0 0 0 0
LC8 16 0 1 0 -52 0
LC9 0 3 -1 3 0 0
LC10 0 0 4 0 0 0
s Author: E T HP GS OE MEN / Kollet Page: 12 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP24
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 12 0 0 0
LC2 0 4 0 2 0 0
LC3 0 3 2 1 0 0
LC4 2 0 0 0 -3 0
LC5 0 2 0 1 0 0
LC6 0 6 4 3 0 0
LC7 0 0 0 0 0 0
LC8 22 0 0 0 -34 -1
LC9 0 33 5 16 0 0
LC10 0 0 13 0 0 0
LP25
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -31 63 2 12 6 -3
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 0 10 -1 -1 0
LC8 27 -8 -47 4 -3 2
LC9 -8 27 25 2 0 0
LC10 -1 2 13 -1 0 0
LP26
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 22 45 23 6 -6 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 -2 9 -2 0 0
LC8 22 4 25 -2 -3 2
LC9 -6 25 9 3 1 -1
LC10 3 1 7 -1 0 0
LP30
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -2 0 13 0 0 0
LC2 -9 -2 3 0 1 3
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 0 3 1 0 0
LC8 14 1 -24 -4 -1 -3
LC9 -1 3 4 2 0 1
LC10 -1 0 4 1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 13 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP31
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 1 0 26 0 0 0
LC2 -1 0 -18 1 0 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 3 1 0 0
LC8 5 -1 55 -1 -1 -2
LC9 -1 10 4 25 0 4
LC10 -2 0 23 1 0 0
LP32
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -26 -63 -7 -13 5 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 0 11 1 -1 0
LC8 26 8 -52 -5 -3 -2
LC9 12 27 -35 1 -1 -1
LC10 -1 -2 12 1 0 0
LP33
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 27 -45 23 -6 -6 -2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 2 10 2 0 0
LC8 22 -4 21 1 -3 -2
LC9 8 28 -7 4 -2 -1
LC10 3 -1 5 0 0 0
LP40
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 -2 0 15 0 0 0
LC2 -6 0 7 0 0 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 2 0 0 0
LC8 10 0 -29 0 -1 0
LC9 1 2 -6 4 0 1
LC10 -1 0 4 0 0 0
s Author: E T HP GS OE MEN / Kollet Page: 14 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP41
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 2 0 27 -1 0 0
LC2 2 0 -20 0 0 0
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 0 0 0 0 0 0
LC8 -3 0 60 0 0 0
LC9 -1 6 7 26 0 3
LC10 -2 0 22 0 0 0
LP42
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -21 68 -14 14 1 -2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 -3 12 -2 0 0
LC8 15 -7 -26 1 -5 1
LC9 -3 20 30 1 1 0
LC10 1 2 11 -1 0 0
LP43
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 28 23 24 2 -3 1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 -1 2 -1 0 0
LC8 21 2 13 -1 -1 2
LC9 -10 11 -1 2 1 0
LC10 1 0 0 0 0 0
LP44
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 -22 -69 -17 -15 1 2
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 1 3 11 2 0 0
LC8 15 7 -28 -2 -5 -1
LC9 -2 24 -53 -1 -2 0
LC10 1 -2 11 1 0 0
s Author: E T HP GS OE MEN / Kollet Page: 15 of 15
Foundationloads Appr: E T HP GS OE MEN / Niederkorn
Customer Date: 21.09.2015
Kennwort
8DN8
LP45
Load Fx[kN] Fy[kN] Fz[kN] Mx [kNm] My [kNm] Mz [kNm]
LC1 0 0 0 0 0 0
LC2 27 -23 23 -2 -3 -1
LC3 0 0 0 0 0 0
LC4 0 0 0 0 0 0
LC5 0 0 0 0 0 0
LC6 0 0 0 0 0 0
LC7 -1 1 2 0 0 0
LC8 21 -2 13 1 -1 -2
LC9 10 12 1 2 -1 0
LC10 1 0 0 0 0 0
Version: 2013.11.20 Page: A1.1
Annex
Version: 2013.11.20 Page: A1.2
All loads are given as action loads in the virtual common load point 1
The loads for every fixing point to foundation (1.1, 1.2, 1.3, 1.4) can be calculated using the distances
between the fixing points belonging to a virtual common load point 1.
As an example the action loads for the fixing point to foundation corresponding to load point 1 will be:
Using this method the structural engineer will be able to take into account the correct orientation of
the loads at every fixing point to foundation with respect to one another.
So for example, in this load case the orientation of the load will be:
1st load case (pos. x-direction) = compression forces at 1.2, 1.4 and pulling forces 1.1, 1.3
2nd load case (neg. x-direction) = pulling forces at 1.2, 1.4 and compression forces at 1.1, 1.3