Professional Documents
Culture Documents
C
MONTHLY DIURNAL AVERAGES - Weather in Surabaya.csv,
W/m 3%, this acceptance value based on accuracy in digital
40 1.0k
thermometer.
30 0.8k
D. Scenario
20 0.6k
Three scenarios will be estimated in this study is shown in
Table 2. The scenarios consist: use high efficiency AC, change
window material and add roofs insulation. Scenario II and III
10 0.4k
0 0.2k
are followed scenario I which use high efficiency AC.
-10 0.0k
J an Feb Mar Apr May J un J ul Aug Sep Oct Nov Dec
Table 2 Detailed scenarios for reducing energy consumption in cooling.
C
DAILY CONDITIONS - 1st J anuary (1)
W/m
Numbe
r Detailed Scenario
40 1.0k
C. Validation
Figure 4 Comparison inside temperature (C) in meeting room, ground
Inside temperature in simulation will be validating with real
floor on 3rd August 2013.
temperature measurement. The temperature measurement was
taken by digital thermometer (resolution: o.o1 4C, accuracy:+- Figure 4 shows comparison of inside temperature between
3%). The temperature data taken hourly in daytime (08.00- measurement and simulation in meeting room ground floor on
18.00), in three rooms: meeting room in ground floor, 3rd August 2013. Rooms conditions when taken data are
international office in first floor, and dean FMIPA (Fakultas turned off AC, two people inside the room, and 19.3 W/m 2
Matematika dan Ilmu Pengetahuan Alam) in second floor. The sensible gains from appliances. The line graph shows that the
acceptance error between simulation and measurement data is simulation temperature below the measurement temperature
JURNAL SISTEM INSTRUMENTASI INDUSTRI 4
around 0.24 C to 0.74C. All of temperature difference or error is load remove room the room. For actual electricity
below 3% with average 1.63%. consumption, it calculates 65% from electricity consumption
per month in 2012.
Most of electricity consumption for cooling are higher than
actual cooling load. The exception in September, electricity
consumption for cooling is lower than cooling load because in
this month has long holiday in ITS but the simulation calculate
same HVAC schedule for weekend and weekday for all day.
Difference amount for one year between actual cooling load
and electricity consumption for cooling is 139690.7 kWh. This
value is potential saving for cooling.
Figure 7 Comparison between actual cooling load from simulation and actual
electricity consumption for cooling space.
V. KESIMPULAN
In summary, the study to reduce electricity consumption for
cooling space has been conducted in Rektorat Building, ITS
Surabaya. The validation inside temperature carried in three
rooms give error in the acceptance range, below than 3%.
Difference value between actual cooling load and electricity
consumption for cooling is 139690.7 kWh for one year. Four
scenarios were estimated: increase efficiency of AC, change
window material to double glazed aluminum frame, change to
double glazed low emission aluminum frame, and add
insulation to roof have potential saving in electricity
consumption for cooling 35%, 40%, 47%, and 33%,
respectively.
Figure 8 Comparison each scenario on meeting room temperature in hottest DAFTAR PUSTAKA
day. [1] IPCC. (2007). Climate Change 2007: Working Group III: Mitigation of
Climate Change. Retrieved August 10, 2013, from IPCC Fourth
D. PEMBAHASAN (ANINDITA ADIKAPUTRI V.) Assessment Report:
http://www.ipcc.ch/publications_and_data/ar4/wg3/en/ch6.html.
Even the decreasing temperature does not cahange [2] Nelson A. J. (2008). Globalization and Global Trends in Green Real
significantly in one day. But it affect significantly in elecricity Estate Investment, RREEF Research No.64.
consumption for one year, in the case of 2012. Actual [3] Metrological Station Juanda Surabaya. (2013). Weather Data 2012-
2013.
electricity consumption for cooling is 416946.85 kWh in one [4] Dewi Larasati Z.R. and Said Mochtara. (2013). Application of
year. In the scenario I, electricity consumption for cooling bioclimatic parameter as sustainability approach on multi-story building
decrease 35% by increase performance of split AC to 90%. design in tropical area. Procedia Environmental Science, 822 830..
The action that should be take is check AC performance one [5] ETS. (2011). Eco-campus ITS. Retrieved January 31, 2013, from Eco-
Campus ITS: www.ecocampus.its.ac.id
by one, mainly for old split AC and maintenance the [6] ASHRAE. (2013). HVAC Fundamental Handbook. Atlanta: ASHRAE..
cleanliness regularly. In the scenerio IIia, the saving is 168631 [7] Florida Solar Energy Center. (2007). Building Science Basics. Retrieved
kWh by add glass and make double glazed window with October 3,2013, from Florida Solar Energy Center.
aluminum frame. In scenario IIb, change window material to http://www.fsec.ucf.edu/en/consumer/buildings/homes/priorities.htm
[8] MIT Open Course Ware. (2006). Introduction to building technology.
double glazed low emission has potential saving 198628 kWh Retrieved August 10, 2013, from MIT:
or 47% from baseline. For the scenario III by add insulation in http://ocw.mit.edu/courses/architecture/4-401-introduction-to-building-
roof has highest electricity consumption than others. technology-spring-2006/
[9] Karyono, Tri Harso. Report on thrmal comfort and building energy
studies in Jakarta-Indonesia. Elsevier Building and Environment 35
(2000), 77-90.
[10] Jemur, B. (2012). Green Design Architecture Energy Efficient: Graha
wonokoyo Building. Surabaya: 1st National Annual Energy Efficiency
Conference.
[11] Bakar, S. K., & Abdullah, A. H. (2012). Simulation of Thermal
Performance in an Office Building. IEEE Business, Engineering &
Industrial Applications Colloquium (BEIAC) , 318-323.
[12] Ossen, D. R., & et.al. (2008). Tropical Building Design Principles For
Comfortable Indoor Environment. Kuala Lumpur: Universiti Teknologi
Malaysia..