17

17
TO 110 kV
Substation

200 meters O.H line/underground cable 110kV

LIGHTING ARRESTER
16

16
10kA, 5kJ

110kV LINE PT As per local grid


110kV /110V /110V requirements
3 3 3
CORE:1
CL0.2,20VA
CORE:2
CL0.2,20VA

110kV CT
15

15
150/1/1A ABT ABT
31.5kA FOR 1 SEC
Symbol Description
CORE:1 MAIN CHECK
CL0.2S,30VA METER METER
CORE:2 (Spare) Spare Potential Transformer 3 core
CL0.2S,30VA

110kV LINE PT Lightning Arresters


110kV /110V /110V
3 3 3
CORE:1 CL0.2,20VA
CORE:2 CL3P,20VA Isolator with Earth switch
M
14

14
ISO Horizontal double break type
110kV,630A M
31.5kA FOR 1 SEC
WITH ONE E/S ABT Availability Based Tariff meter

MFM Multi Function Meter


CONTROL AND
ON OFF TRIP SC TST SER RELAY PANEL
Current Transformer
110 kV CT MFM WITH R Y B
150/1/1/1/1A ASS A
RS 485 PORT PQM Power Quality Meter
13

13
31.5kA FOR 1 SEC
CORE:1 67 67N 81
PQM 49 86 95A 27 59 50 Instantaneous Overcurrent Relay
CLO.5,30VA 50 50N O/U
CL 0.2
CORE:2 63X 51 Inverse Definite Mean Time (IDMT) Overcurrent Relay
CL5P20,30VA 50 51 50N 51N 95B 50BF 24
50N Instantaneous Earth Fault Relay

CORE:3 87TL 87T 64R 51NS 51N Inverse Definite Mean Time Earth Fault Relay
CL PS LV
27 Undervoltage Protection Relay
12

12
132kV,630A
31.5kA FOR 1 SEC
59 Overvoltage Protection Relay
SF6 CIRCUIT BREAKER 51NS
LV Standby Earth Fault Protection Relay
67
50 Directional and IDMT Overcurrent Relay
M
110kV ISOLATOR 81
Over and Under Frequency Protection Relay
O/U
630A 31.5KA FOR
1SEC WITH 1 E/S 67N
Directional and IDMT Earth Fault Relay
50N
11

11
86 Master Trip Relay
LIGHTING ARRESTER
10kA 74 Alarm Relay

95 Trip Circuit Supervision Relay


150/1A HVCT
CORE:1 CLPS,15VA 95A Trip Circuit 1 Supervision Relay
Vk>=250 V, Imag<=30mA@Vk/2, Rct<=2
ohm 95B Trip Circuit 2 Supervision Relay
POWER TRANSFORMER
110/11kV 23MVA 50
BF Circuit Breaker Failure Protection Relay
10

10
Power
ONAN/ ONAF
Transformer-1
Dyn11 (+5.0% TO -15.0%@ 63X Transformer Protection Relay
1.25% T1 NGR
(100A)
At each tap) 21 Distance Protection Relay
CT 1000/1/1A
1500/1A LVCT CORE 1:CL5P20,15VA
CORE:1 CLPS,15VA CORE 2: PS, 15VA 87L Differential Protection Relay
Vk>=250 V, Imag<=30mA@Vk/2, Rct<=2 Vk>=250 V, Imag<=30mA@Vk/2, Rct<=2 ohm
ohm 24 dV/dF Protection Relay

66 KV OUTDOOR Potential Transformer 2 core


11kV PT
SWITCHYARD
9

9
(11kV/3)/(110V/3):(110V/3) ASS Ampere Selector Switch
CORE:1
VSS V
CL0.2,100VA
CORE:2 R Y B VSS Voltage Selector Switch
CL3P,100VA
Vacuum Circuit Breaker (Draw-out Type)

1500/1/1A CT MFM WITH ASS A


RS 485 PORT SF6 Circuit Breaker
CORE:1, CLO.2,15VA
OTI Oil Temperature Indicator
CORE:2
50 51 50N 51N 27 59 WTI Winding Temperature indicator
8

8
CL5P20,15VA
PRV Pressure Relief Valve
2
3R/phase 1Cx630mm 11kV(E)
A2XCEFY Cable MOG Magnetic Oil Guage

BCH Buchholz Relay


ON OFF TRIP SC TST SER
Miniature Circuit Breaker
R Y B
11kV,50Hz,3P, M 86 95 TVM Trivector Meter
VCB,2000A
Voltage Indicator
7

7
25kA FOR 3 SEC

Load Break Switch With Fuse link


11KV,TP,2500A,25KA FOR 3 SEC AL BUSBAR

ON OFF TRIP SC TST SER ON OFF TRIP SC TST SER ON OFF TRIP SC TST SER ON OFF TRIP SC TST SER ON OFF TRIP SC TST SER ON OFF TRIP SC TST SER ON OFF TRIP SC TST SER
Note:
1) PQM: Class 0.5, Harmonics measurement upto 1st to
63rd.
2) 21 - Distance protection and 87L Differential protection
as per local grid requirement.
6

6
12kV,50Hz 12kV,50Hz 12kV,50Hz 12kV,50Hz 12kV,50Hz 12kV,50Hz 12kV,50Hz 3) All meters should be import-export type, communicable
3P,VCB 3P,VCB 3P,VCB 3P,VCB 3P,VCB 3P,VCB 3P,VCB
630A,25KA
M 86 95
630A,25KA
M 86 95
630A,25KA
M 86 95
630A,25KA
M 86 95
630A,25KA
M 86 95
630A,25KA
M 86 95
630A,25KA
M 86 95 through RS 485/MODBUS.
FOR 3SEC FOR 1SEC FOR 1SEC FOR 1SEC FOR 1SEC FOR 1SEC FOR 1SEC 4) Tariff metering, Relay CT and PT sizing shall be as per
local grid requirements.
From line PT
From line PT From line PT From line PT From line PT From line PT From line PT 5) CT, PT sizing to be done as per calculations.
6) Equipment sizes shown are tentative and will be
10A/1A MFM WITH
200A/1A/1A MFM WITH 200A/1A/1A MFM WITH 100A/1A/1A MFM WITH 200A/1A/1A MFM WITH 200A/1A/1A MFM WITH 200A/1A/1A MFM WITH
RS 485 PORT
changed after detail engineering.
CORE1 RS 485 PORT CORE1 RS 485 PORT CORE1 RS 485 PORT CORE1 RS 485 PORT CORE1 RS 485 PORT CORE1 RS 485 PORT CORE 1
CL0.5,15VA CL0.5,15VA CL0.5,15VA CL0.5,15VA CL0.5,15VA CL0.5,15VA CL0.2S,15VA T8 7)NGR possibility to be checked in design to limit earth
5

5
AUX.TRANSFORMER
CORE 2
50 51
CORE 2
50 51
CORE 2
50 51
CORE 2
50 51
CORE 2
50 51
CORE 2
50 51
CORE 2
50 51 50 51 63 11kV/415V fault current
CL 5P10,15VA 50 51 CL 5P10,15VA 50 51 CL 5P10,15VA 50 51 CL 5P10,15VA 50 51 CL 5P10,15VA 50 51 CL 5P10,15VA 50 51 CL5P10, 15VA N N X
N N N N N N N N N N N N 200kVA,Dyn11

TO AUX LT Panel.
1R 3Cx 300/400mm2 11kV(E) E E
A2XCEFY Cable(Typical)
4

4
11 KV RMU PANEL 11 KV RMU PANEL 11 KV RMU PANEL 11 KV RMU PANEL 11 KV RMU PANEL 11 KV RMU PANEL
LOC: PV BOX-1 LOC: PV BOX-2 LOC: PV BOX-3 LOC: PV BOX-4 LOC: PV BOX-5 LOC: PV BOX-6

00 10/03/2016 APPROVAL NS
12kV,50Hz 12kV,50Hz 12kV,50Hz 12kV,50Hz 12kV,50Hz 12kV,50Hz REV DATE DESCRIPTION DRAWN
3P,VCB M 3P,VCB M 3P,VCB M 3P,VCB M 3P,VCB M 3P,VCB M PROJECT TITLE:
630A,20KA 630A,25KA 630A,25KA 630A,25KA 630A,25KA 630A,25KA 30 MW Solar Park
FOR 3SEC FOR 1SEC FOR 1SEC FOR 1SEC FOR 1SEC FOR 1SEC
3

3
CLIENT:-

VOLTAGE INDICATOR VOLTAGE INDICATOR VOLTAGE INDICATOR VOLTAGE INDICATOR VOLTAGE INDICATOR VOLTAGE INDICATOR

EPC CONTRACTOR:
200A/1A 50 51 63 200A/1A 50 51 63 200A/1A 50 51 63 200A/1A 50 51 63 200A/1A 50 51 63 200A/1A 50 51 63 CLEAN MAX ENVIRO ENERGY
50 51 50 51 50 51 50 51 50 51 50 51 SOLUTIONS PVT. LTD
CORE1 N N X CORE1 N N X CORE1 N N X CORE1 N N X CORE1 N N X CORE1 N N X
CL 5P10,15VA CL 5P10,15VA CL 5P10,15VA CL 5P10,15VA CL 5P10,15VA CL 5P10,15VA 1511, Prasad Chambers,
Opera House, Mumbai-400004
2

2
DRAWING TITLE:
TRAFO 4000kVA TRAFO 4000kVA TRAFO 4000kVA TRAFO 4000kVA TRAFO 4000kVA TRAFO 4000kVA
11/0.415-0.415kV 11/0.415-0.415kV 11/0.415-0.415kV 11/0.415-0.415kV 11/0.415-0.415kV 11/0.415-0.415kV AC Single Line diagram- 30MWp Solar PV Plant
Dyn11yn11 Dyn11yn11 Dyn11yn11 Dyn11yn11 Dyn11yn11 Dyn11yn11

T02 T03 T04 T05 T06 T07 DRAWING NO :


SCALE NTS
2500A 2kVA, 2500A 2kVA, 2500A 2kVA, 2500A 2kVA, 2500A 2kVA, 2500A 2kVA,
Bus duct 415/415V Bus duct 415/415V Bus duct 415/415V Bus duct 415/415V Bus duct 415/415V Bus duct 415/415V
MCB MCB MCB MCB MCB MCB DRAWN NS SHEET NO 1OF1
TO PANEL TO PANEL TO PANEL TO PANEL TO PANEL TO PANEL
1

1
1.833MW 1.833MW 1.833MW 1.833MW 1.833MW 1.833MW CHECKED RS
1000V DC 1000V DC 1000V DC 1000V DC 1000V DC 1000V DC PAPER SIZE A3
(TYP.) Inverter-1 Inverter-2 (TYP.) Inverter-1 Inverter-2 (TYP.) Inverter-1 Inverter-2 (TYP.) Inverter-1 Inverter-2 (TYP.) Inverter-1 Inverter-2 (TYP.) Inverter-1 Inverter-2 APPROVED US
REV NO. 00
DATE 10/03/2016
X W V U T S R Q P O N M L K J I H G F E D C B A