BASIS OF DESIGN

Date: 08.10.2016
1 INTRODUCTION
HVAC system shall be designed to provide year round thermal environmental control for
the proposed Interior Fit-outs for M/s. Office at Orion Park ,Ahmadabad

2 OUTDOOR DESIGN CONDITIONS


Based on meterological data, the outdoor design conditions for Gujrat have been considered as follows:
Summer
DRY BULB TEMPERATURE : 110 Deg F.
WET BULB TEMPERATURE : 78 Deg F.

3 INDOOR DESIGN CONDITIONS

DRY BULB TEMPERATURE : 74 +/- 3.6 Deg F.


RELATIVE HUMIDITY : +/- 50%

4 Fresh Air
Fresh air intake considered is 5.0 CFM / person or 0.06CFM/sqft ,additional 30% whichever is more for air conditioned
areas in accordance with ASHRAE Indoor Air Quality Standards

5 Assumptions/Considerations
Below floor is air conditioned
Lights : 1.5 watts / Sqft.
Infiltraitons have not been considered
Wall U value :
outside wall. 0.350 Btu / hr.sf.deg F
partition wall. 0.380 Btu / hr.sf.deg F

Glass exposed to sun(6mm meadow-12mm air-6mm clear) as per your specification


Peak load was considered for May -July months for Gujrat

6 Estimated Air conditioning loads

Sr. Proposed
Equipment Lighting Load Load Dehumidified
Description Area(sqft) Height Occupancy Fresh Air (CFM)
No. Load (K.W.) (Watts/Sq.Ft.) (TR) (TR) Air Qty (CFM)

1 Ground Floor 4165 121.5 Ft 100 975 10 1.5 33.28 30.72 13823.00
2 First Floor 4400 121.5 Ft 125 1156 15.62 1.5 41.21 40.39 18174.00
3 Second Floor 5700 121.5 Ft 135 1322 18.2 1.5 45.04 43.94 19773.00
4 Third Floor 6200 121.5 Ft 150 1459 22.5 1.5 59.08 60.44 27196.00
5 Fourth Floor 6900 121.5 Ft 165 1611 27.25 1.5 71.09 74.55 33546

4165 100 975 Total TR 249.7 250.03 112512.0