You are on page 1of 7

Proceedings of International Interdisciplinary Conference On Engineering Science & Management

Held on 17th - 18th December 2016, in Goa, India.ISBN: 9788193137383

SIMULATION OF BREAKER SIZING AND FAULT


ANALYSIS AT 220KV SUBSTATION
Rajbir Kaur Neeraj Sharma
Department of Electrical Engineering, Department of Electrical Engineering,
Baba Bandha Singh Engineering College Baba Bandha Singh Engineering College
Fatehgarh Sahib, India Fatehgarh Sahib, India

normal and abnormal conditions. The planning of


Abstract -- With increasing load requirements day complex power system is a difficult task for engineer.
by day, electric utilities have also grown up to For this planning purpose planning tools are required.
meet the load requirements, thereby making The major power system planning tools are:-
system more complex. In this paper the short Load Flow Analysis
circuit analysis of 220 kV grid substation is Short Circuit Analysis
carried out and various ratings of circuit breakers Stability analysis
is calculated using power world simulator. For performing various switching operations steady
Further these ratings are compared with actual state flow of power must be known. Thus whole
circuit breakers at substation. system is modeled as electric network and solution is
Keywords Power World Simulator, Load Flow simulated by using various software of power system.
Analysis, Short Time Rating This solution is known as Load flow Analysis. Load
I. INTRODUCTION flow Analysis is carried out to determine the value of
Reliability and stability of power system mainly bus voltages, branch currents, real and reactive power
depends upon the engineers ability to provide in the system. After load flow analysis system is
regular supply to consumers. Generally, the loads checked for various normal and abnormal conditions.
must be fed with uninterrupted supply at different Short circuit analysis is carried out on system for
voltage levels to various consumers that may be various faults. This study helps to calculate the fault
commercial, domestic or industrial. Depending upon level of the system and according to this fault current
the requirement of loads, there are peak load hours protection system will be designed. Stability analysis
and off peak load hours. When there is requirement is performed in order to sure that system is stable
power can be transferred from one region to other after a major disturbance. Stability analysis is defined
region with the help of tie lines. as ability of system to remain in synchronism after
With increasing load requirements day by day, major disturbance.
electric utilities have also grown, to meet the load II. LOAD FLOW ANALYSIS
requirements. Thus the whole system is becoming Load flow study reveals the electrical performance
more complex. Electric utilities have to perform and power flows (real and reactive) for specified
detailed analysis of system by considering various conditions when the system is operating under steady
state. The load flow study also provides the

168
Proceedings of International Interdisciplinary Conference On Engineering Science & Management
Held on 17th - 18th December 2016, in Goa, India.ISBN: 9788193137383
information about the line and transformer loads (as
well as losses) throughout the system and voltages at
different points in the system for evaluation and
regulation of the performance of power system under
conditions known as priori. Further alternative plans
for future expansion to meet new load demands can
be analyzed and a complete information is made
available through this study.
III. SHORT CIRCUIT ANALYSIS
Fault analysis or short circuit analysis involutes
finding the voltage and current distribution through
the whole system during various faults. It is
important to determine the values of system voltages
and currents during fault conditions so that the
protective devices may be set to identify the fault and
separate the faulty section from the healthy system so
as to minimize the harmful effects of such
contingencies. When fault occurs at a point in a Figure 1 . Single line diagram of Moga 220 kV grid
power system, the corresponding MVA is referred to substation
as the fault level at that point. B. Load Flow Analysis
IV. RESULTS AND DISCUSSIONS 220 kV s/s has two 220 kV buses, coupled though
A. Block Diagram bus coupler and share their loads, 220 s/s Moga has
Single line diagram of 220 kV substation Moga has very important role in power sector in Malwa region
been developed in Power World Simulator as shown of Punjab. Because 6 nos 220 kV circuits are coming
in figure 1. out from this station and feeds the max approx 1830
mw power with the help of these buses . So these two
buses has very important role to transmit power to
Malwa region First load flow analysis is carried out
on the test system. Figure 1 shows the practical
model of 220 kV grid substation Moga. Table I
shows the bus records of the test system after load
flow analysis by Newton Rapshon Method.

169
Proceedings of International Interdisciplinary Conference On Engineering Science & Management
Held on 17th - 18th December 2016, in Goa, India.ISBN: 9788193137383

TABLE I BUS RECORDS OF TEST SYSTEM

Switched
Volt Angle Load Gen
Number Name Nom kV PU Volt Gen Mvar Shunts
(kV) (Deg) MW MW
Mvar

220 KV BUS
1 BAR (POWER 220 1 220 0 2262.1 356.75
GRID MOGA)

220 KV MOGA
2 BUS BAR NO . 220 0.999 219.8 -0.09
1

220 KV MOGA
3 220 0.999 219.9 -0.12
-BUS BAR 2

220 KV S/S
4 220 0.995 218.9 -4.35 305 51.06
SADIQ

220 KV S/S
5 220 0.97 213.4 0.2 305
BAJAKHANA

220 KV S/S
6 220 0.989 217.5 -2.84 610
KOTKRORE

220 KV S/S
7 BAGHAPURAN 220 0.995 219 -1.28 610
A
132 kv BUS
8 132 0.983 129.7 -21.61 415 201.93
BAR

9 GHTP Bathinda 220 1 220 1.59 315.43 -161.1

10 11 kv 11 0.931 10.24 -41.09 305

TABLE II LINE RECORDS OF TEST SYSTEM

From Branch Device


From Name To No. To Name Circuit Status Xfrmr R X
No. Type

220 KV BUS 220 KV


0.0000 0.0001
1 BAR (POWER 2 MOGA BUS 1 Closed Line NO
3 7
GRID MOGA) BAR NO . 1

170
Proceedings of International Interdisciplinary Conference On Engineering Science & Management
Held on 17th - 18th December 2016, in Goa, India.ISBN: 9788193137383

220 KV BUS 220 KV


0.0000 0.0001
1 BAR (POWER 3 MOGA -BUS 1 Closed Line NO
3 7
GRID MOGA) BAR 2

220 KV MOGA 220 KV


2 BUS BAR NO . 3 MOGA -BUS 1 Closed Line NO 0 0.1
1 BAR 2

220 KV MOGA 220 KV S/S


0.0033 0.0171
2 BUS BAR NO . 6 BAJAKHAN 1 Closed Line NO
2 2
1 A

220 KV MOGA
220 KV S/S 0.0015 0.0077
2 BUS BAR NO . 7 1 Closed Line NO
KOTKRORE 1 7
1

220 KV MOGA
132 kv BUS
2 BUS BAR NO . 9 1 Closed Transformer YES 0 0.1
BAR
1

220 KV MOGA 220 KV S/S 0.0045 0.0233


3 5 1 Closed Line NO
-BUS BAR 2 SADIQ 2 1

220 KV S/S
220 KV MOGA 0.0006 0.0033
3 8 BAGHAPUR 1 Closed Line NO
-BUS BAR 2 4 1
ANA

220 KV MOGA 132 kv BUS


3 9 1 Closed Transformer YES 0 0.1
-BUS BAR 2 BAR

220 KV S/S GHTP 0.0105 0.0020


6 10 1 Closed Line NO
BAJAKHANA Bathinda 8 5

132 kv BUS
9 11 11 kv 1 Closed Transformer YES 0 0.1
BAR

C. Short Circuit Capacity of Bus Bars the help of fault current Short circuit Capacity of Bus
In this section we will investigate the short circuit bars as shown in Table III. Strength of bus bar
capacity of various bus bars of 220 Kv Sub Station depends upon the ability of bus bar to bear a fault.
with the help of power world simulator .Three phase So the strength of bus bar depends upon the short
balanced fault is applied on various bus bars of circuit capacity of bus bar.
220kV substation and fault current is calculated. with

171
Proceedings of International Interdisciplinary Conference On Engineering Science & Management
Held on 17th - 18th December 2016, in Goa, India.ISBN: 9788193137383
TABLE -III SCC BEHAVIOR OF VARIOUS BUS BARS DURING 3-PHASE FAULT

Sr. No Location of fault Fault Current in Amp SCC of Bus Bar -1 (MW)

1 11 Kv Bus Bar 38803.3 7398


2 132 Kv Bus Bar 6768.280 1547
3 220 Kv Moga Bus Bar 7964.220 3034
4 220 kv S/S Baghapurana 7458.960 2842

5 220 kv S/S Bajakhana 6415.160 2444

6 220 kv S/S Kotkrore 6864.340 2615

7 220 kv S/S Sadiq 5115.460 1949

8 GHTP Bathinda 5507.320 2098

D. Calculations of Circuit Breaker Parameters


3- balanced fault is applied on various bus bars of 220 kV Substation and fault current is determined. With the
help of determined fault current different ratings of circuit breaker are tallied in Table IV.
TABLE IV DIFFERENT RATINGS OF CIRCUIT BREAKERS

Sr.No. Fault Type Voltage Short Breakin Making AC DC Short


location of fault level of Circuit g capacit compone compone time
the curren Capacit y in KA nt of nt of rating
system t in KA y in short short s
in KV MVA circuit circuit
current current
1 11 11 38.8 7398 98.94 54.87 27.435 47.5
2 9 132 7 1547 17.85 9.898 4.949 8.572
3 2 220 8 3034 20.4 11.32 5.66 9.8
4 8 3 220 8 2842 20.4 11.32 5.66 9.8
phase
5 6 Sym 220 6.4 2444 16.32 9.049 4.5245 7.835
fault
6 7 220 7 2615 17.85 9.898 4.949 8.57
7 5 220 5 1949 12.75 7.07 3.535 6.123
8 10 220 6 2098 15.3 8.484 4.242 7.348

E. Comparison between Actual and Determined TABLE -V COMPARISONS BETWEEN


Circuit Breaker Parameters EXISTING AND CALCULATED CIRCUIT
Practical model of Moga 220 kV grid substation BREAKER PARAMETERS
(shown in fig 1) has been analyzed and variousratings
of breakers are calculated as shown in Table V.

172
Proceedings of International Interdisciplinary Conference On Engineering Science & Management
Held on 17th - 18th December 2016, in Goa, India.ISBN: 9788193137383

Actual Determined [2] P. A. N. Garcia, Member, IEEE J. L. R. Pereira,


Circuit Ratings of Member, IEEE, M. P. Vinagre and E. J. Oliveira,
Parameters
Breaker Circuit Fault Analysis Using Continuation Power Flow and
ratings breaker Phase Coordinates ,Power systems, IEEE
Rated Voltage(kV) 12 12 transactions,vol-15,Issue-2(July 2000), PP 508-514

Frequency (Hz) 50 50 [3] Sharifuddin Mondal*, Goutam Chakraborty and

Rated current (A) 630 630 Kingshook Bhattacharyya, Unknown Input High

Making capacity Gain Observer for Parametric Fault Detection and


62.5 98.94 Isolation of Dynamical Systems, International
(kA)
Symmetrical MultiConference of Engineers and Computer
Scientists 2009 Vol II IMECS 2009, March 18 - 20,
breaking capacity 25 38.8
2009, Hong Kong.
(kA)
[4] Antoine Abauzit and Julien Marzat, A Multiple-
Short time rating
25 47.5 Observer Scheme for Fault Detection, Isolation and
for 3 seconds (kA)
Recovery of Satellite Thrusters, 2nd CEAS Specialist
Operating Duty O-0.3-CO- O-0.3-CO-
Conference on Guidance, Navigation & Control,
cycle 3-CO 3-CO
Delft University of Technology, Delft, The
Netherlands, April 10-12, 2013 PP-1510-1526
V. CONCLUSION
[5] Wan-SukYool , Seung-Oh Kinr' and Jeong- Hyun
As demand of electrical energy is increasing day by
Sohrr, Dynamic analysis and design of a high voltage
day, so the whole power system is becoming more
circuit breaker with spring operating mechanism,
complex these days. Due to this the fault current level
Journal of Mechanical Science and Technology Vol-
is also increasing. Circuit breaker designing must be
21 (2007) PP 2101-2107
such that to withstand this increasing short circuit
[6] Raymond D. Valentine, A Perspective of Low-
level of current. In this research work, various ratings
Voltage Circuit Breaker Interrupting Rating, Industry
of circuit breakers are calculated and are compared
applications conference IEEE, Vol-3, (October
with the existing circuit breaker for rated current of
1998), PP 2331-2335
630 A. It is seen that the circuit breaker is not able to
[7] David B. Durocher, Len Walls, Stephan Becker,
withstand the whole load. So number of circuits must
Understanding Circuit Breaker Design and Operation
be increased and feeder must be bifurcate. By doing
to Improve Safety and Reliability in Underground
this system remains stable.
Mining, Industrial applications society annual
VI. REFERENCES
meeting IEEE, Oct 2011, PP 1-7
[1] Kuljinder Kaur, Er. Simerpreet Singh, Calculation
[8] Adnan Kakilli, System Analysis with the MVA
and comparison of circuit breaker parameters in
Method for Symmetrical Three-Phase Faults, TEM
Power World Int. Journal of Engineering Research
Journal Vol- 2 , No- 1, Year 2013,PP 51-56.
and Applications www.ijera.com ISSN: 2248-9622,
[9] V.J.Rathod, Prof. G R.Patel Short Circuit
Vol. 6, Issue 1, (Part - 2) January 2016, pp.31-34
Analysis on 400 Kv Sub-Station Soja, International

173
Proceedings of International Interdisciplinary Conference On Engineering Science & Management
Held on 17th - 18th December 2016, in Goa, India.ISBN: 9788193137383
Journal of Engineering Research and Development,
Volume 6, Issue 11 (April 2013), PP. 62-67.
[10] H. Wallace Tinsley III Member, and Michael
Hodder Member, IEEE A Practical Approach to Arc
Flash Hazard Analysis and Reduction, presented in
2004 IEEE IAS Pulp and Paper Industry Conference
in Victoria.

174

You might also like