Professional Documents
Culture Documents
Textbook to read:
Textbook#1, pp.158-159, 173-175, 249-254
1.Space heating load
Ans:
a) The heat gain is generally greater than the cooling load during the
morning hours when sunlight first strikes a building and the internal loads
first begin. Heat is being stored in the building structure, furnishings, etc.
b) Late at night when occupants are not present, lights and equipment are
off and solar radiation is zero, the building gives up stored heat to the air,
which the equipment removes as cooling load. The heat gain may be quite
small, zero, or negative.
c) At some time during the day, probably early evening, as heat gain is
decreasing, and equilibrium condition can be established when heat gain
and cooling load are equal. Or, some interior zones, where the cooling load
is driven only by internal heat gains may reach equilibrium if the heat gain
remains constant for a number of hours.
Q3. Estimate the heat loss from air at 120 oF
flowing in a 16-inch round duct. The volume
flow rate of air in the duct is 1000 ft3/min; The
duct length is 35 ft. The duct has 1 inch of
fibrous glass insulation. The overall heat
transfer coefficient is 0.2 Btu/hr-ft2-F. The
environment temperature is 12 oF. Determine
the temperature of air leaving the duct. The
density of air is 0.067 lbm/ft3; the specific heat
is 0.24 Btu/lbm-F.
Find the sensible cooling load of the system. (Ans: 7160 Btu/hr)
Q6. If there is no system heat transfer, find the
zone air temperature in Q5.
(Ans: 77.4 oF)