After Sales Service Division

Simple Self-Diagnosis by Malfunction Code (SM-TS3)

RA, SkyAir, VRV, PA, and Heat Reclaim Ventilator

0 1 2 3 4 5 6 7 8 9 A C E F H J
Detail
code

Division

A
External protection Malfunction of Drain Level Malfunction of High pressure Malfunction of fan Malfunction of Malfunction of Malfunction Heater overheat Stop due to low Low water level no Malfunction of a Malfunction of Malfunction of
device activated indoor unit PCB Control System freezing protection control in heating, motor swing flap motor power supply or AC of electronic water level water supply humidifier system dust collector of air capacity setting
Indoor Unit

Abnormality freeze-up protection input overcurrent expansion valve cleaner (Indoor unit PCB)
control in cooling

C
Malfunction of Failure of Malfunction of drain Malfunction of liquid Malfunction of gas Malfunction of fan Front panel driving Malfunction of AC Malfunction Malfunction of Malfunction of Malfunction Malfunction of high Room temperature
sensor system transmission level sensor pipe thermistor for pipe thermistor for motor sensor or fan motor fault input current sensor of suction air discharge air humidity sensor of switch box pressure switch thermistor in
(unified) (between indoor heat exchanger heat exchanger control driver system thermistor thermistor system thermistor remote controller
unit PCB and sub abnormality
PCB)

E
Protection devices Defective outdoor Missing of earth Actuation of high Actuation of low Inverter compressor STD compressor Malfunction of Overcurrent of Malfunction Malfunction of four Malfunction of Malfunction of drain Malfunction of Malfunction of Actuation of option
activated (unified) unit PCB leakage detection pressure switch pressure switch motor or overheat motor overcurrent/ outdoor unit fan inverter compressor of electronic way valve or cool/ entering water water level thermal storage unit cooling water pump protection device
core (HPS) (LPS) lock motor system expansion valve coil heat switchin temperature

F
Malfunction of Wet alarm Abnormal Abnormal high Abnormal oil Abnormal oil level Abnormal high Abnormal exhaust
discharge pipe high pressure pressure actuation pressure or shortage of oil temperature of temperature of
temperature or refrigerant of HPS refrigerant oil engine
overcharged

H
Malfunction of Malfunction of room Malfunction of Malfunction of high Malfunction of low Malfunction of Malfunction of Malfunction of Malfunction of Malfunction Malfunction of Malfunction of (hot) Malfunction of drain Alarm in thermal High room Malfunction of
Outdoor Unit

sensor system of temperature sensor power supply pressure switch pressure switch compressor motor position detection outdoor unit fan compressor input of outdoor air discharge air water temperature water level sensor storage unit or temperature alarm thermal storage
compressor or humidifier unit sensor (HPS) (LPS) overload thermistor sensor motor signal (CT) system thermistor thermistor thermistor storage controller tank water level
damper

J
Miswiring of Malfunction of Malfunction of Malfunction of Malfunction of low Malfunction of Malfunction of Malfunction Malfunction Malfunction Malfunction of high Malfunction of low Malfunction of oil Malfunction of Malfunction of Malfunction of
thermistor pressure sensor current sensor of discharge pipe pressure equivalent suction pipe heat exchanger of thermistor of thermistor of thermistor pressure sensor pressure sensor pressure sensor or oil level sensor oil temperature engine room
compressor thermistor saturated thermistor thermistor (Refrigerant circuit) (Refrigerant circuit) (Refrigerant circuit) sub-tank thermistor or heating heat thermistor temperature
temperature sensor exchanger sensor or exhaust
system thermistor temperature

L
Malfunction of Malfunction of El.compo. box Malfunction of Inverter Inverter Total input Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Engine startup error Malfunction of Engine stop
inverter system inverter PCB temperature rise inverter radiation fin instantaneous instantaneous overcurrent overcurrent inverter inverter compressor power transistor transmission igniter system generator converter
temperature rise overcurrent (DC overcurrent (AC compressor startup error (Stall between control
output) output) prevention) and inverter PCB

P
Shortage of Power voltage Automatic Malfunction of Malfunction of Malfunction of DC Malfunction of Malfunction of Heat exchanger Automatic Refrigerant cylinder Refrigerant cylinder Automatic Malfunction of Refrigerant cylinder Improper
refrigerant amount imbalance or refrigerant charge thermistor in switch radiation fin current sensor AC or DC output total input current freezing protection refrigerant during automatic during automatic refrigerant charge starter actuation during automatic combination
(thermal storage inverter PCB operation stop box temperature sensor current sensor sensor during automatic charge operation refrigerant charging refrigerant charging operation nearly refrigerant charging between inverter
unit) refrigerant charging completed completed and fan driver

U
Shortage of Reverse phase, Malfunction of Check operation Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Improper Malfunction Malfunction of System is not Malfunction of Malfunction of
refrigerant open phase power supply or not executed or transmission transmission transmission transmission transmission transmission (other combination of of setting of transmission set yet system transmission
instantaneous transmission error between indoor and between indoor between indoor between outdoor between remote system) indoor and outdoor centralized control between indoor (accessory device)
System

power failure outdoor unit unit and remote units units or outdoor controllers units equipment address unit and centralized
controller storage unit control equipment

M
Malfunction of Malfunction of Improper Address
central remote transmission combination of duplication,
controller PCB between optional optional controllers improper setting
controllers for for centralized
centralized control control

6
External protection Malfunction of PCB Ozone density Contaminated Malfunction Malfunction Supply air passage Exhaust air Malfunction of dust Malfunction of Replace the Replace the Simplified Door switch open Replace the high
device activated abnormal sensor error of indoor air of outdoor air closed passage closed collection unit (Heat damper system humidify element deodorising catalyst remote controller (Heat reclaim efficient filter
(Heat reclaim thermistor (Heat thermistor (Heat reclaim ventilator) (Heat reclaim malfunction (Heat ventilator)
ventilator) reclaim ventilator) reclaim ventilator) ventilator) reclaim ventilator)

8
Others

Micro-computer
initialization

9
Malfunction of
transmission
(between heat
reclaim ventilator
and fan unit)
Chiller

0 1 2 3 4 5 6 7 8 9 A C E F H J
Detail
code

Division

A
Indoor Unit

Malfunction of Malfunction of Malfunction Malfunction


indoor unit PCB freezing protection of electronic of electronic
expansion valve expansion valve

C
Malfunction of liquid Malfunction of gas
pipe thermistor for pipe thermistor for
heat exchanger heat exchanger

E
Protection devices Defect of outdoor Missing of earth Actuation of high Actuation of low Inverter compressor STD compressor Malfunction of Overcurrent of Malfunction
activated (unified) unit PCB leakage detection pressure switch pressure switch motor or overheat motor overcurrent/ outdoor unit fan inverter compressor of electronic
core (HPS) (LPS) lock motor system expansion valve coil

F
Malfunction of Abnormal high
discharge pipe pressure actuation
temperature of HPS
Outdoor Unit

H
Malfunction of Malfunction of room Malfunction of Malfunction of high Malfunction of low Malfunction of Malfunction of Malfunction of Malfunction of Malfunction Malfunction of Malfunction of (hot)
sensor system of temperature sensor power supply pressure switch pressure switch compressor motor position detection outdoor unit fan compressor input of outdoor air discharge air water temperature
compressor or humidifier unit sensor (HPS) (LPS) overload thermistor sensor motor signal (CT) system thermistor thermistor thermistor
damper

J
Miswiring of Malfunction of Malfunction of Malfunction of Malfunction of low Malfunction of Malfunction of Malfunction Malfunction Malfunction Malfunction of high Malfunction of low
thermistor pressure sensor current sensor of discharge pipe pressure equivalent suction pipe heat exchanger of thermistor of thermistor of thermistor pressure sensor pressure sensor
compressor thermistor saturated temperature thermistor thermistor (Refrigerant circuit) (Refrigerant circuit) (Refrigerant circuit)
sensor system

L
Malfunction of Malfunction of El. compo. box Malfunction of Inverter Inverter Total input Malfunction of Malfunction of Malfunction of Malfunction of
inverter system inverter PCB temperature rise inverter radiation fin instantaneous instantaneous overcurrent overcurrent inverter inverter compressor power transistor transmission
temperature rise overcurrent (DC overcurrent (AC compressor startup error (Stall between control
output) output) prevention) and inverter PCB

P
Shortage of Power voltage Automatic Reactor Malfunction of Improper
refrigerant amount imbalance or refrigerant charge temperature radiation fin combination
(thermal storage inverter PCB operation stop abnormality temperature sensor between inverter
unit) and fan driver

U
Shortage of Reverse phase, Malfunction of Check operation Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Improper Malfunction Malfunction of Malfunction of
System

refrigerant open phase power supply or not executed or transmission transmission transmission transmission transmission transmission (other combination of of setting of transmission transmission
instantaneous transmission error between indoor and between indoor between indoor between outdoor between remote system) indoor and outdoor centralized control between indoor (accessory device)
power failure outdoor unit unit and remote units units or outdoor controllers units equipment address unit and centralized
controller storage unit control equipment

7
System No. 2 System No. 2 System No. 2 System No. 2 System No. 2 System No. 2 System No. 2 System No. 1 System No. 2 System No. 2 Malfunction of
Compressor Compressor Fan motor Actuation of high Actuation of low Malfunction of low Malfunction of high Malfunction of fan Malfunction of fan Malfunction of pump inter lock
overheat overcurrent overcurrent pressure switch pressure switch pressure sensor pressure sensor inter lock inter lock compressor current
(HPS) (LPS) sensor

8
Malfunction of Malfunction of System No. 1 System No. 2 System No. 1 System No. 2 System No. 1 System No. 2 Malfunction of Malfunction of System No. 1 System No. 1 Abnormal hot water
Others

entering water leaving water Malfunction Malfunction Malfunction of Malfunction of Malfunction of Malfunction of brazed-plate heat dehumidification Malfunction of Malfunction of high temperature
temperature temperature of refrigerant of refrigerant heat exchanger heat exchanger discharge pipe discharge pipe exchanger freezing or leaving water suction pipe suction pipe
thermistor thermistor or drain thermistor thermistor thermistor thermistor thermistor temperature temperature thermistor 1 for thermistor 2 for
pipe heater thermistor heating heating

9
Abnormal chilled System No. 2 System No. 2 System No. 1 System No. 2 Malfunction of Malfunction of Malfunction of System No. 2 System No. 2
water quantity or Malfunction Malfunction of Malfunction of Malfunction of thermal storage unit thermal storage thermal storage Malfunction of Malfunction of
abnormal AXP of electronic suction pipe inverter system inverter system brine pump brine tank suction pipe suction pipe
expansion valve thermistor thermistor 1 for thermistor 2 for
heating heating

Fan Coil

0 1 2 3 4 5 6 7 8 9 A C E F H J
Detail
code

Division

A
Indoor Unit

Malfunction of drain Malfunction of Malfunction of


level system freezing protection dust collector of air
cleaner

C
Malfunction of liquid Malfunction Malfunction of
pipe thermistor for of suction air thermostat sensor
heat exchanger thermistor in remote controller

U
Reverse phase, Malfunction of Check operation Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Improper Malfunction Malfunction of
open phase power supply or not executed or transmission transmission transmission transmission transmission transmission (other combination of of setting of transmission
System

instantaneous transmission error between indoor and between indoor between indoor between outdoor between remote system) indoor and outdoor centralized control between indoor
power failure outdoor unit unit and remote units units or outdoor controllers units equipment address unit and centralized
controller storage unit control equipment

M
Malfunction of Malfunction of Improper combination Address
central remote transmission between of optional controllers duplication,
controller PCB optional controllers for for centralized control improper setting
centralized control
Simple Self-Diagnosis by Malfunction Code
Objects Objects

Heat reclaim ventilator

Heat reclaim ventilator


Package

Package
Malfunction Malfunction

Fan Coil

Fan Coil
Malfunction Contents Supposed causes Malfunction Contents Supposed causes

SkyAir

SkyAir
Chiller

Chiller
code code

VRV

VRV
RA

RA
Protection devices activated Protection device connected to outdoor unit PCB actuated
A0
External protection device
activated
External protection device connected to the terminal strip
T1-T2 of indoor unit is activated k k k E0 (unified) Defective protection device connector contact k k k
Defective outdoor unit PCB Defective outdoor unit PCB
A1
Malfunction of indoor unit PCB Defective indoor unit PCB
External factor (Noise etc.) k k k k k k E1 Defective connection of inside/ outside relay wires k k k k k
Drain Level Control System Drain clogging, upward slope, etc. Actuation of high pressure switch Dirty outdoor unit heat exchanger
A3 Abnormality Defective drain pump
Defective float switch or short circuit connector
k k k k k E3
(HPS) Defective high pressure switch
Clogged refrigerant piping k k k k
Defective connector contact
Malfunction of freezing protection Shortage of water volume
A4 Low water temperature setting
Defective water temperature thermistor
k k k k k k System No.1
Actuation of high pressure switch
Dirty outdoor unit heat exchanger
Shortage of water volume

High pressure control in heating, Clogged air filter of indoor unit and short circuit
E3 (HPS) Clogged refrigerant piping
Defective connector contact
k
A5 freeze-up protection control in
cooling
Defect of indoor unit heat exchanger thermistor k k k k Defective HPS
Actuation of low pressure switch Abnormally drop in low pressure
(LPS) Defective low pressure sensor
Malfunction of fan motor Broken wires in, short circuit of, or disconnection of
connectors from the fan motor harness E4 Defective outdoor unit PCB k k k k
A6 Defective fan motor k k k k k Defective connector contact
Defective indoor unit PCB Inverter compressor motor or Inverter compressor lock
Malfunction of swing flap motor Defective swing flap motor overheat High differential pressure

A7
Defective indoor unit PCB
Defective connection cable k k E5 Defective inverter PCB
UVW connection error
k k k k k
Defective airflow direction adjusting flap-cam Defective connector contact
Malfunction of power supply or AC Defective power supply voltage STD compressor motor Defective compressor
A8 input overcurrent Defective connection on signal line k k k E6 overcurrent/lock Defective control PCB
The stop valve is not opened
k k k k
Defective wiring
System No.1 Compressor Defective electronic expansion valve
A9
Malfunction of electronic expansion Defective electronic expansion valve coil
valve Defective indoor unit PCB k k k k k E6 overcurrent Shortage of refrigerant amount
Defective compressor
k
Defective relay cables
Malfunction of outdoor unit fan Fan motor failure
AA Heater overheat 26WH is activated
k k E7
motor system Neglect to connect or defective connection of harness/
k k k k k

Outdoor Unit
Indoor Unit

connector between the fan motor and the PCB


Malfunction of a humidifier system Humidifier unit (optional accessory) leaking Fan does not rotate due to foreign matters caught in it
AF Defective drain piping (upward slope, etc.)
Defective indoor unit PCB
k k k Overcurrent of inverter compressor Defective compressor
Defective inverter main circuit capacitor
Malfunction of dust collector of air Defect of dust collecting element E8 Defect of outdoor unit PCB k k
cleaner Stained insulator part Defect of power transistor
AH Defect of high voltage power supply unit k k k k Malfunction of electronic expansion Disconnection of connectors from electronic expansion valves
Defect of indoor unit PCB
E9 valve coil Defective electronic expansion valve coil
Defective outdoor unit control PCB
k k k k
Malfunction of capacity setting The capacity setting adaptor was not installed when
AJ (Indoor unit PCB) replacing PCB.
Defective indoor unit PCB
k k k Malfunction of four way valve or
cool/heat switchin
Defective four way valve
Shortage of gas
Failure of transmission (between Defective connection of the connector between indoor
EA Defective outdoor unit PCB k
C1 indoor unit PCB and sub PCB) unit PCB k k Defective thermistor
Malfunction of entering water Cooling water temperature abnormality

C4
Malfunction of liquid pipe
thermistor for heat exchanger
Defective thermistor for liquid pipe
Defective indoor unit PCB k k k k k k k EC temperature Defective outdoor unit PCB
Defective thermistor
k
Defective connector contact
Malfunction of discharge pipe Defective discharge pipe thermistor
Malfunction of gas pipe thermistor Defective thermistor for gas pipe temperature Abnormal discharge pipe temperature
C5 for heat exchanger Defective indoor unit PCB
Defective connector contact
k k k k k F3 Defective outdoor unit control PCB k k k k k
Defective connector contact
Malfunction of fan motor sensor or Defective fan PCB Abnormal high pressure or Refrigerant overcharged
C6 fan control driver Defective connection of capacity setting adaptor k k refrigerant overcharged Disconnection of heat exchanger deicer thermistor
Field setting error
F6 Disconnection of outdoor air thermistor
Disconnection of liquid pipe temperature thermistor
k k k k
Front panel driving motor fault Defective front panel driving motor
C7 Defective limit switch k Defective outdoor unit PCB
Malfunction of sensor system of Harness is disconnected, or defective connection
Malfunction of suction air Defective thermistor for suction air H0 compressor Defective PCB k k
C9 thermistor Defective indoor unit PCB k k k k k k Malfunction of room temperature Defective limit switch
Malfunction of discharge air
Defective connector contact
Defective thermistor for discharge air
H1 sensor or humidifier unit damper Defective damper k k
CA thermistor Defective indoor unit PCB k k k k Malfunction of high pressure switch Defective high pressure switch
(HPS) Broken wire
Malfunction of humidity sensor
Defective connector contact
Defective humidity sensor
H3 Defective outdoor unit PCB k k k k k
CC system Defective connector contact k k k Defective connector contact
Malfunction of low pressure switch Defective low pressure switch
Room temperature thermistor in Defective room temperature thermistor in remote controller (LPS) Broken wire
CJ remote controller abnormality Defective remote controller PCB k k k k k H4 Defective outdoor unit PCB k k k
External factor (Noise etc.) Defective connector contact
Simple Self-Diagnosis by Malfunction Code
Objects Objects

Heat reclaim ventilator

Heat reclaim ventilator


Package

Package
Malfunction Malfunction

Fan Coil

Fan Coil
Malfunction Contents Supposed causes Malfunction Contents Supposed causes

SkyAir

SkyAir
Chiller

Chiller
code code

VRV

VRV
RA

RA
Malfunction of compressor motor Defect of compressor motor overload thermistor Malfunction of oil pressure sensor Defective connector contact
H5 k k k
overload thermistor Defective connector contact JE or sub-tank thermistor Defective sub-tank thermistor
Defective outdoor unit PCB
Malfunction of position detection Faulty contact of compress or cable
H6 sensor Defective compressor k k k Malfunction of oil level sensor or Defective connector contact
Defective outdoor unit PCB JF heating heat exchanger thermistor Defective heat exchanger thermistor k
Defective outdoor unit PCB
Malfunction of outdoor unit fan Abnormal signal from fan motor (Circuit failure)
motor signal Disconnection/Short circuit in fan motor leads or Malfunction of inverter system Shortage of power supply capacity
H7 k k k k k k
disconnection of connector
Defective inverter PCB
L0 Defective power transistor
Defective outdoor unit PCB
Malfunction of compressor input Defective power transistor Malfunction of inverter PCB Defective compressor wiring
Defective outdoor unit fan motor
H8
(CT) system Defective reactor
Faulty wiring of inverter system k k L1 Blown fuse k k k k
Defective outdoor unit PCB Defective inverter PCB
Malfunction of outdoor air Defective connection of thermistor El.compo. box temperature rise Fin temperature rise due to short circuit
H9 thermistor Defective outdoor unit PCB k k k k k L3
Defective outdoor unit fan motor
k k k k
Defective outdoor air thermistor Defective power transistor
Defective outdoor unit PCB
Malfunction of (hot) water Defective connection of thermistor
HC temperature thermistor Defective outdoor unit PCB k k k L4
Malfunction of inverter radiation fin Fin temperature rise due to short circuit
k k k k k
Defective water temperature thermistor temperature rise Defective fin thermistor
Alarm in thermal storage unit or Thermal storage group defective wiring nverter instantaneous overcurrent Defective compressor coil (such as wiring disconnection or
HF storage controller Defective setting k L5
(DC output) insulation failure)
k k k k k
Excess of thermal storage tank numbers Compressor startup failure (mechanical lock)
Defective inverter PCB
Malfunction of thermal storage Low water level
tank water level Defective switch setting Inverter instantaneous overcurrent Overcharge of refrigerant amount
HJ k k k k (AC output) Shortage of power supply capacity
Water level detecting sensor failure
Defective connector contact L6 Defective compressor k k
Defective inverter unit
Malfunction of pressure sensor Defective pressure sensor connector contact
J1 Defective pressure sensor k k k k Malfunction of overcurrent inverter Compressor overloaded

Outdoor Unit
Outdoor Unit

compressor Wiring disconnection in compressor coil


Defective outdoor unit PCB
L8 Disconnection of compressor wiring k k k k k
Malfunction of current sensor of Defective current sensor Defective inverter PCB
J2 compressor Defective compressor k k k k k
Defective outdoor unit PCB Malfunction of inverter compressor The stop valve is not opened
startup error (Stall prevention) Defective compressor
Malfunction of discharge pipe Defective connection of thermistor
L9 Error in wire connections to compressor k k k k
J3 thermistor Defective discharge pipe thermistor k k k k k Large differential pressure before compressor startup
Defective outdoor unit PCB Defective inverter PCB
Malfunction of low pressure Defective connection of thermistor Malfunction of power transistor Defective power transistor
J4 equivalent saturated temperature Defective thermistor k k LA Defective compressor k k
sensor system Defective outdoor unit PCB Defective inverter PCB
Malfunction of suction pipe Defective connection of thermistor Malfunction of transmission Defective connection between the inverter PCB and the
J5 thermistor Defective suction pipe thermistor k k k k between control and inverter PCB control PCB
Defective outdoor unit PCB LC External factors (e.g. noise) k k k k k
Defective inverter compressor
Malfunction of heat exchanger Defective connection of thermistor Defective control PCB (transmission block)
J6 thermistor Defective heat exchanger thermistor k k k k k
Defective outdoor unit PCB Malfunction of central remote Defective central remote controller PCB
M1 controller PCB k k k k k
Malfunction of thermistor Defective connection of thermistor
J7 (Refrigerant circuit) Defective liquid pipe thermistor k k k k Malfunction of transmission Other centralized control power disconnection
Defective outdoor unit PCB between optional controllers for Centralized control reset switch ON
M8 centralized control Defective transmission wiring k k k k k
Malfunction of thermistor Defective connection of thermistor Central remote controller address change
J8 (Refrigerant circuit) Defective liquid pipe thermistor k k k k k
Defective outdoor unit PCB Improper combination of optional Improper combination of optional controllers for centralized
controllers for centralized control control
Malfunction of thermistor Defective connection of thermistor
MA More than one master controller is connected k k k k k
J9 (Refrigerant circuit) Defective gas pipe thermistor k k k k k Faulty setting of centralized control
Defective outdoor unit PCB Defect of centralized control
Malfunction of high pressure Defective connector contact Address duplication, improper Address duplication of central remote controller
sensor Connection of low pressure sensor in mistake for high MC setting k k k k k
JA pressure sensor k k k k
Shortage of refrigerant amount Shortage of refrigerant
Defective high pressure sensor
Defective outdoor unit PCB P0 (thermal storage unit) Clogged refrigerant piping k k
Malfunction of low pressure sensor Defective connector contact Power voltage imbalance or Open phase
Connection of high pressure sensor in mistake for low inverter PCB Interphase voltage imbalance
JC pressure sensor k k k k P1 Defective capacitor in the main circuit k k k k
Defective low pressure sensor Defective wiring in the main circuit
Defective outdoor unit PCB Defective inverter PCB
Simple Self-Diagnosis by Malfunction Code
Objects Objects

Heat reclaim ventilator

Heat reclaim ventilator


Package

Package
Malfunction Malfunction

Fan Coil

Fan Coil
Malfunction Contents Supposed causes Malfunction Contents Supposed causes

SkyAir

SkyAir
Chiller

Chiller
code code

VRV

VRV
RA

RA
Automatic refrigerant charge The stop valve is not opened
P2 operation stop Closed valve of refrigerant tank k k k k Malfunction of transmission
between outdoor units or outdoor
Connection error of transmission wirings between outdoor
unit and external control adaptor for outdoor unit
Malfunction of thermistor in switch Defective connection of thermistor U7 storage unit Connection error of transmission wirings between outdoor k k k k k
P3 box Defective reactor thermistor k k k k k units
Defective outdoor unit PCB
Defective inverter PCB
Malfunction of radiation fin Defective radiation fin temperature thermistor Malfunction of transmission Transmission error between main and sub remote
between remote controllers controller
P4
temperature sensor Defective inverter PCB
Defective INV. compressor k k k k k U8 Connection between sub remote controllers k k k k k k
Defective fan motor Defective remote controller PCB
Heat exchanger freezing protection (Close the refrigerant cylinder. Start again from step 1.) Malfunction of transmission (other Transmission error between other indoor and outdoor units
P8 during automatic refrigerant k k k system) Defective electronic expansion valve of other indoor unit
charging U9 Defective indoor unit PCB of other indoor unit k k k k k
Improper connection of transmission wiring between
Malfunction of fan motor Defective fan motor indoor and outdoor unit
(humidifier unit) Defective outdoor unit PCB
P9 Broken relay harness k Defect of indoor/outdoor power Wrong model connections
Outdoor Unit

Defective connector contact supply Improper power supply


UA Wrong PCB connected k
Automatic refrigerant charge
P9 operation completed k k k k Defective PCB

Refrigerant cylinder during Refrigerant cylinder of master unit is empty Improper combination of indoor Excess of connected indoor units
PA automatic refrigerant charging k k k and outdoor units Defective outdoor unit PCB
UA Mismatch of the refrigerant type of indoor and outdoor unit k k k k

System
Broken wire of heater Defective heater unit Setting of outdoor unit PCB was not carried out after
PA (humidifier unit) Defective thermistor k replacing to spare PCB
Defective outdoor unit PCB
Remote temperature setting wire Remote temperature setting wire disconnection
Refrigerant cylinder during Refrigerant cylinder of slave unit 2 is empty
k k UA k
PC automatic refrigerant charging
disconnection Defective connector contact
Malfunction of setting of centralized Address duplication of centralized control equipment
PE
Automatic refrigerant charge
k k k UC control equipment address Defective indoor unit PCB k k k k k k
operation nearly completed
Refrigerant cylinder during Defective heater unit Malfunction of transmission Transmission error between optional controllers for
automatic refrigerant charging Defective connector contact between indoor unit and centralized control equipment and indoor unit
PH Defective thermistor k k k centralized control equipment Connector for setting main controller is disconnected.(or
Defective outdoor unit PCB UE disconnection of connector for independent / combined k k k k k k
use changeover switch.)
Malfunction of capacity setting Capacity setting adaptor is not installed Defective PCB for central remote controller
PJ (Outdoor unit PCB) Improper capacity setting adaptor k Defective indoor unit PCB
Defective outdoor unit PCB
System is not set yet Improper connection of transmission wiring between
Improper combination between Mis-matching of type of PCB indoor-outdoor units and outdoor-outdoor units
PJ k k k k k k k k
inverter and fan driver Improper (or no) field setting after replacing outdoor unit
main PCB UF Failure to execute check operation
Defective indoor unit PCB
Shortage of refrigeran Refrigerant shortage and refrigerant clogging (wrong Stop valve is not opened
piping)
U0 Defective thermistor k k k k k Malfunction of system Improper connection of transmission wiring between
indoor-outdoor units and outdoor-outdoor units
Defective low pressure sensor
Defective outdoor unit main PCB UH Defective indoor unit PCB k k k
Defective outdoor unit PCB
Reverse phase, open phase Power supply reverse phase
U1 T phase open phase k k k k k k k UJ
Malfunction of transmission Defect of accessory devices
k k k k k
Defective outdoor unit PCB (A1P) (accessory device) Faulty wiring
Malfunction of power supply or Abnormal power supply voltage External protection device Actuation of external protection device
U2 instantaneous power failure Instantaneous power failure k k k k k k 60 activated (Heat reclaim ventilator) Defective output signal wiring k
Defective main circuit wiring Defective control PCB
Check operation not executed or Check operation is not executed.
U3 k k k k k k k Malfunction of indoor air thermistor Defective connector contact
System

transmission error
64 (Heat reclaim ventilator) Defective indoor air thermistor k
Malfunction of transmission Short circuit in indoor-outdoor or outdoor-outdoor Defective control PCB
between indoor and outdoor unit transmission wiring (F1 / F2), or wrong wiring
Outdoor unit power supply is OFF Malfunction of outdoor air Defective connector contact
U4 k k k k k k k 65 thermistor (Heat reclaim ventilator) Defective outdoor air thermistor k
Others

System address does not match


Defective indoor unit PCB Defective control PCB
Defective outdoor unit PCB Malfunction of damper system Defective connector contact
(Heat reclaim ventilator) Defective limit switch
Malfunction of transmission
between indoor unit and remote
Transmission error between indoor unit and remote
controller 6A Defective damper motor k
controller Connection of 2 main remote controllers (when using 2 Defective control PCB
U5 remote controllers) k k k k k k System No. 2 Shortage of refrigerant amount
Defective indoor unit PCB
Defective remote controller PCB 70 Compressor overheat Defective connector contact k
Transmission error caused by noise Leakage of four way valve

Malfunction of transmission Faulty wiring System No. 2 Shortage of refrigerant amount


U6 between indoor units External factor (Noise etc.) k k k k 71 Compressor overcurrent Short circuit k
Defective indoor unit PCB Defective compressor
Simple Self-Diagnosis by Malfunction Code
Objects Objects

Heat reclaim ventilator

Heat reclaim ventilator


Package

Package
Malfunction Malfunction

Fan Coil

Fan Coil
Malfunction Contents Supposed causes Malfunction Contents Supposed causes

SkyAir

SkyAir
Chiller

Chiller
code code

VRV

VRV
RA

RA
System No. 2 Defective fan motor connector contact Abnormal hot water high Three way valve malfunction
72 Fan motor overcurrent Defective fan motor k 8H temperature Defective thermistor k
Defective PCB Defect of water temperature setting
System No. 2 Dirty heat exchanger Abnormal chilled water quantity or Shortage of water volume
Actuation of high pressure switch Shortage of water volume 90 abnormal AXP Disconnection of AXP k
73 (HPS) Clogged refrigerant piping k System No. 2 Defective connector contact
Defective connector contact
Defective HPS 91 Malfunction of electronic expansion Defective electronic expansion valve coil k
valve
System No. 2 Clogged refrigerant piping
Actuation of low pressure switch Defective connector contact System No. 2 Defective connector contact
74 (LPS) Shortage of gas k 92 Malfunction of suction pipe Defective suction pipe thermistor k
Defective LPS thermistor

Others
System No. 2 Defective connector contact Malfunction of transmission Defective fan unit PCB
75 Malfunction of low pressure sensor Defective low pressure sensor k 94 (between heat reclaim ventilator Defective connecting wire between (1) and (2) k
Defective PCB and fan unit)
System No. 1 Defective fan inverter unit
System No. 2 Defective connector contact
k 95 k
76 Malfunction of high pressure
sensor
Defective high pressure sensor
Defective PCB
Malfunction of inverter system
System No. 2 Defective fan inverter unit
System No. 1 Defective relay contact 96 k
77 Malfunction of fan inter lock Broken wire k Malfunction of inverter system

System No. 2 Defective relay contact 97 Malfunction of thermal storage unit Defective thermal storage unit
k
78 Malfunction of fan inter lock Broken wire k
Malfunction of thermal storage Actuation of thermal storage brine pump overcurrent (OC)
System No. 2 Defective current sensor 98 brine pump k
7A Malfunction of compressor current Defective compressor k Malfunction of thermal storage Low water level of thermal storage brine tank
sensor Defective outdoor unit PCB
99 brine tank k
System No. 2 Cooling water pump interlock actuated
7C Malfunction of pump inter lock k
Malfunction of entering water Defective connector contact
80 temperature thermistor Defective entering water temperature thermistor k
Malfunction of leaving water Defective connector contact
Others

81 temperature thermistor or drain Defective leaving water temperature thermistor k


pipe heater
System No. 1 Defective connector contact
82 Malfunction of refrigerant Defective refrigerant thermistor k
thermistor
System No. 2 Defective connector contact
83 Malfunction of refrigerant Defective refrigerant thermistor k
thermistor
System No. 1 Defective connector contact
84 Malfunction of heat exchanger Defective heat exchanger thermistor k
thermistor
System No. 2 Defective connector contact
85 Malfunction of heat exchanger Defective heat exchanger thermistor k
thermistor
System No. 1 Defective connecting connector
86 Malfunction of discharge pipe Defective discharge pipe thermistor k
thermistor
System No. 2 Shortage of gas
Malfunction of discharge pipe Defective discharge pipe thermistor
88 temperature Defective connector contact k
Clogged refrigerant piping
Malfunction of brazed-plate heat Dirty heat exchanger
89 exchanger freezing Shortage of refrigerant amount k
Defective thermistor
System No. 2 Defective connector contact
8A Malfunction of leaving water Defective leaving water temperature thermistor k
temperature thermistor
System No. 1 Defective connector contact
8E Malfunction of suction pipe Defective suction pipe thermistor k
thermistor 1 for heating
System No. 1 Defective connector contact
8F Malfunction of suction pipe Defective suction pipe thermistor k
thermistor 2 for heating