Sr. No.

1 TRIP Description
1 Manual trip from control room
2 Manual trip from local
3 Mechanical over speed trip
3 no. electrical over speed sensors other then speed governing
4
sensors
5 Thrust bearing excess wear trip (with triple sensors)
6 Condenser very low vacuum trip (with triple sensors)
7 Lube oil pressure very low trip (with triple sensors)
8 Control oil pressure very low trip (with triple sensors)

9 Main steam temperature high trip (with triple sensors)

10 Exhaust steam temperature HI HI trip (with triple sensors)

11 Generator trip

12 Reverse power relay trip

13 Under frequency relay trip


14 Boiler trip operated trip (with triple signals)
Power failure for turbine control and protection system (triple
15
signals)
16 Turbine shaft vibration HI HI
17 Relative vibration HI HI

18 Top and bottom casing differential temperature protection.

19 HP exhaust temperature protection.

20 Top and bottom casing differential expansion protection

21 Bearing metal temperature high trip

22 DCS trip

23 DEHC - hardware malfunctioning

24 Generator Vibration HI HI
25 Hot well Level HI HI
26 Bearing Lube oil return temperature HI HI
27 MOT level LO LO
28 Main steam pressure LO LO
Turbovisory Equipment
1 Turbine Stress Evaluator
Consider by Thermax
Yes
Yes
Yes

Yes

Yes, Axial Shift HI Hi- available with 2 sensors


Yes
Yes
Yes
Not recommended, in case operators finds an
emergency condition, Turbine should be trip

Not recommended, in case operators finds an


emergency condition, Turbine should be trip
Yes
Not as per manufacturer standerd, however can be
connected
Not recommended
YES
Not recomanded, as no seprate monitoring for this
function
YES
YES

Trip not recommanded, Only alarm

Trip not recommanded, Only alarm


Not recomanded, as there is no Differential
measurement
Yes

covered in MFT

Alarm for fault and mostly 2 out of 3 logic is


implemented in different cards. if any 2 card fault It will
trip.
Yes
Yes( through ETS only )
Yes
Not recommanded , only alarm
Not recommanded
There is no separate stress evluator. Howerever , stress
is calculated based on metal temperature measurement
& it is done in DEH
MEPL/Evonik comment
Noted
Noted
Noted

Noted

Noted
Noted
Noted
Required, TL to provide 3- sensor looped with STG

Noted

Required
Required
Noted

Noted
Noted
Noted

Noted
Noted

Noted

Required, TL to provide triple temperature sensor


looped with STG DCS before MSV.

noted
noted
noted
noted
noted
noted
please refer point No. 9 b, MOM dated 18-02-11 at
Evonik office Noida. We request to TL kindly submit the
document as discussed. As per standard practice kindly
provide all the points taken from turbine side with
detailed logic of TSE. Also TL to confirm that TSE system
is interlocked with turbine governing system for initial
rolling, loading , unloading.