You are on page 1of 12

Rule of Thumb for RC Design

Reinforcement for beams

Spacing
The minimum spacing of steel reinforcement bars is

1. Maximum size of coarse aggregate plus 5mm


Or
2. Bar size(whichever is greater)

Number of bars
Max bars per layer for beams = (beam width 2 x cover 2 x link diameter)/(2 x bar diameter)

Size of bars
Areas of reinforcement

Max of tension or compression reinforcement is 6% of cross sectional area of concrete


Min percentages are shown in the table below, which is Table 3.25 of BS 8110

Shear Links

Shear links should be spaced no more than 0.75d. No longitudinal bars should be spaced more than
150mm or d from a vertical leg. Shear links should follow the following requirements:
Reinforced Concrete Design
Elastic response is due to applied loads but plastic behavior can be below and above yield stress.
Creep rate depends on the composition of the concrete and environmental conditions.
Similar to steel, concrete multi-storey buildings can either consist of portal frames or braced frames that
depend on bracing or diaphragms with concrete core walls for lateral stability. However, for multi-storey
buildings, lateral stability has several requirements:

1. Stiff horizontal diaphragms must need to be used with core walls, such as constructing floors with
insitu reinforced concrete. Concrete core walls (with a minimum thickness of 200mm for steel
reinforcement placement and concreting) can be in the form of lift shafts or the surrounding walls
of staircases.

2. Bracing should be used throughout the height of the building, unless transfer structures are used.

The shear center should be coinciding with the point of where the resultant of overturning forces is.

Reinforced Concrete: Column Design


Scheme Design

We will always design columns and other compression members where their vertical loads act
concentrically to the neutral axis of the structural members. In these situations, these structural members
are axially loaded by direct compressive stresses.

Concrete columns are structural members that help structural durability and resist and supports vertical
loads. To distinguish concrete columns from concrete piers and walls, the bigger cross-section dimension
should not be larger than four times its smaller dimension.

In practical applications, vertical loads act eccentrically to the neutral axis of the structural member.
Therefore, in actual practice, both the compressive stresses that act concentrically to the neutral axis of
the structural member AND the bending stresses induced by the compressive stresses that act
eccentrically to the neutral axis of the structural member need to be accounted for in the structural design.

We will only focus on compressive stresses that act concentrically to the neutral axis in scheme
designs.

Concrete columns are considered to be braced when the overall structure is designed to resist lateral
loads. Braced columns are columns in a stability system with shear or core walls. Unbraced columns are
columns in a system where the only structural elements supporting the overall stability of the structure are
the columns.

Columns are short if slenderness is less than 15 for braced columns or 10 for unbraced columns.

Short columns - Crushing failure is caused by direct compression stresses

Slender columns - Lateral buckling and crushing failure are caused by direct compression
stresses and bending stresses caused by eccentric compression stresses. The amount of failure
depends on the end fixity conditions and the slenderness ratio, which is effective length divided
by radius of gyration.

1. Determine fy and fcu

2. Determine applied Live Load and Dead Load on the column

3. Determine tributary load area on the column

4. Determine the number of floors the column supports

5. Determine the total loads acting on the column by using the equation below

Total Load, N = (LL + DL) x ULS Factor x # of Floors x Tributary Load Area x Elastic Shear
Factor
where LL = Live Load
DL = Dead Load
ULS Factor = 1.6 (for conservative purposes)
Elastic Shear Factor = 1.25

6. Determine the percentage of reinforcement the column should have and the X value. For
example, if 3% reinforcement was chosen, we would use N/21.

Column area (Ac) can be estimated by

The maximum amount of reinforcement in concrete members (beams, columns, or slabs) should not
exceed 4%.

7. Determine the required concrete area

Ac_req = N/X
where X is value given in table above

8. Determine the dimensions of the concrete column that has dimensions, b and h, which would
give Ac_prov = b x h > Ac_req

9, Determine applied moment on the columns

To estimate the applied moment on the columns, it is suggested to multiply the axial load from the floor
above the column by:

25 interior columns

5 edge columns
2 corner columns

Detail Design

1. Find the effective height, le, of the column

le = x l
where l = full length
= Values from table below
End condition 1 = column end is fully restrained by moment connection
End condition 2 = column end is partially restrained by monolithic connection
End condition 3= column end is simply supported

2. Determine whether the column is a short column.

If ley / b < 15 and lex / h < 15, it is a short column.


If both ratios are larger than 15, it is a slender column.
where lex = effective height in respect of the major axis
ley = effective height in respect of the minor axis,
Normally, reinforced columns should be designed as short, not slender.

3. Find required area of steel reinforcement, Asc_req

Sufficient steel reinforcement content and reinforcement placement help to resist cracking in the concrete
column. Additional reinforcement should be used, such as binders, vertical links, or ties. These additional
reinforcement resist lateral buckling induced by compressive stresses of main reinforcement. A tie should
be placed for every corner bar. The distance from one reinforcement bar to another should be no less
than 150mm.

Reinforcement near the concrete surface are more effective at resisting bending moment forces than
reinforcement placed at the centre of the column.

Equation for a short and braced column which supports roughly symmetrical arrangement of beams and
where these beam properties and sizes do not differ by more than 15% is shown below.

N = 0.35 x fcu x Ac + 0.67 x Asc_req x fy


Where fcu = characteristic strength of concrete (N/mm^2)
Ac = area of concrete (mm^2)
Fy = yield strength of reinforcement (N/mm^2)
Asc = area of reinforcement

Note: If Asc_req is negative, use the equation below.


Asc_req = 0.4% x Ac_nominal
Note: The design moment for slender columns includes an additional moment induced by eccentricity of
the geometry section.

4. Find a suitable number of reinforcement bars and the size of the reinforcement bars, ______ T
______

5. Find the area provided by the reinforcement bars designed, As_provc

Reinforced Concrete: Beam Design


Scheme Design

The applied loads include direct compression forces, as well as, compressive and tensile stresses that
are caused by sagging bending moments to the beam. The induced compressive stresses are located in
the material fibres above the neutral axis of the member and the induced tensile stresses are located
below the neutral axis.

1. Determine fy and fcu according to required material properties

2. Determine preliminary dimensions of the beam, b and h

3. Find effective depth, d

d = h - cover - bar diameter


Concrete covers are to be designed for requirements of fire resistance and durability.

4. Find span/depth ratio, L/d and make sure that L/d is less than 20

Deflection should be checked using the span/depth ratio.


Cracking should be designed for SLS and should meet the requirements of minimum reinforcement
needed and spacing.

Detail Design

1. Find w

w = 1.4DL + 1.6LL

2. Find the design moment and shear, M and V

Simply supported with Uniformly Distributed Load

Simply supported with Concentrated Load


Cantilever Beam with Uniformly Distributed Load

Fixed ends with Uniformly Distributed Load

Fixed Ends with Concentrated Load at the Center

t
The effective span of beams, l, should be assumed to be the effective span of the member in its simply
supported condition for conservative purposes. This span equals the exact distance between supports.

2. Establish concrete grade, fcu, in N/mm^2

3. Find the depth to neutral axis, x, in mm

Depth to neutral axis, x, from compression face is limited to:


x 0.5d for fcu 45 N/mm^2
x 0.4d for 45 < fcu 70 N/mm^2
x 0.33d for 70 < fcu 100 N/mm^2

3. Design rectangular beams for flexure

The design ultimate moment M should be designed greater than the ultimate bending moment.
*Also applicable to flanged beams when the neutral axis of the beam lies within the flange
K' = 0.156 for fcu 45 N/mm^2
K' = 0.120 for 45 < fcu 70 N/mm^2
K' = 0.094 for 70 < fcu 100 N/mm^2

If K K', compression reinforcement not required

x = (d-z)/0.45 for fcu 45 N/mm^2


x = (d-z)/0.40 for 45 < fcu 70 N/mm^2
x = (d-z)/0.36 for 70 < fcu 100 N/mm^2

If K > K', compression reinforcement required

x = (d-z)/0.45 for fcu 45 N/mm^2


x = (d-z)/0.40 for 45 < fcu 70 N/mm^2
x = (d-z)/0.36 for 70 < fcu 100 N/mm^2

The maximum amount of reinforcement in concrete members (beams, columns, or slabs) should not
exceed 4%.

5. Design rectangular beams for shear

Shear stress in beams


Usually, the shear force and the shear stress should be obtained from the face of the support.

Shear reinforcement

Shear reinforcement should be designed for ULS and should be provided in the form of vertical links or
bent-up bars. Shear forces are transferred to the vertical links that act with diagonal concrete struts in
compression. Therefore, in beams, the links will act in tension and the concrete in compression.
Shear reinforcement are required to resist the following failure mode caused by shear:

Inclined tensile cracks on beam

Inclined tensile stress failure caused by shear

a. If v < 0.5vc, minimum links should be provided.


b. If 0.5vc < v < vc + vr, links should be provided, in which the area of shear reinforcement provided is

and where fcu not reater than 80.

c. If vc +vr < v < 0.8fcu or v = 7 N/mm, links or links with bent-up bars should be provided. Links should
not be more than 50% of shear resistance.

Concrete shear stress, vc

5. Determine whether maximum deflection is below deflection capacity

Allowable Limit = L/250

Reinforced Concrete: Slab Design


Types of suspended slabs that are considered (slabs which are supported by beams, columns, or walls)

Solid slabs
o These slabs are made out of solid concrete with reinforcement that resist tension. Slabs
can be in-situ or profiled metal decking. The top reinforcement can be a steel mesh for
the use of fire resistance. The bottom reinforcement can be a metal decking for tension
reinforcement purposes.

Ribbed slabs

o These slabs can achieve the same structural strength than solid slabs with less concrete
required. Ribbed slabs can be series of in-situ concrete ribs that are cast monolithically
with voids caused by removable formers. Ribbed slabs can also be a hollow slabs with
permanent void formers.

Flat slabs

o These slabs with flat soffits do not require the support of beams. Drops are often used to
form a thick stiffening part between the columns and the slab.

Waffle slabs

o These slabs are solid and flat with void formers in the soffits. There are series of 1m wide
concrete beams that can be designed for moment bending.

No slabs should be less than 125 mm thick due to fire resistance requirements.

Two way spanning slabs can be 90% of thickness of one way spanning slabs

1. Find w

w = 1.4DL + 1.6LL

2. Find the design moment and shear, M and V

Find M and V equations above (Refer to beam calculations).

3. Design slab for flexure using One Way Slab method

Find K and z

Find percentage of reinforcement in concrete area (Ast/bd = %)

Reinforcement bars should be designed to fulfill the minimum area capacity and should be constructed in
both directions in the slab. Steel reinforcements help to resist cracking and to distribute concentrated
loads throughout the slab.
The maximum amount of reinforcement in concrete members (beams, columns, or slabs) should not
exceed 4%.

4. Find the number of reinforcement bars and the size of the reinforcement bars, ____ T ______.

5. Find Asprov.

6. Design slab for shear.

Refer to here for rules for each constant in the concrete shear stress equation below.

Minimum steel required = 0.13%

7. Check punching shear

Punching shear forces (shear forces around the perimeter of columns) are usually the critical design case
for flat slab foundations. Effective shear is the shear force that takes moment forces caused between the
slab and the column and the shear force over the area supported by the column.

Effective shears

o Internal columns -> Veff = 1.15V

o Corner columns -> Veff = 1.25V

o Edge columns -> Veff = 1.4V

Punching shear checks in flat slabs

Shear stress, vo = Veff/ Uod < 0.8sqrt(Fcu) or 7 N/mm^2

o Uo is the column perimeter that touches the slab


Shear forces should be checked at certain perimeters of slab enveloping the column. Shear
forces should be checked starting at the first perimeter of 1.5d around the column face. Then,
shear forces should be checked subsequently at perimeters of 0.75d intervals.

You might also like