CONSULTANTS HANDBOOK
Specifications Division 33 6353
Steam Traps and Strainers
2.03 STRAINERS
A. Strainers less than 2 shall be cast steel, screwed ends, s.s. 60 mesh screen, Spirax
Sarco Fig. CT or approved equal.
B. Strainers greater than 2 shall be cast steel, 300 # flanged, s.s. standard mesh screen,
Spirax Sarco Fig. 34 or approved equal.
2.04 VALVES
A. Shut-off valves to the steam traps shall be 800# Forged Steel Gate Valve (ASTM A105),
13% Cr. Trim, Conventional Port, Rising Inside Screw Stem, Union Bonnet, Solid Wedge
2.05 APPROVAL
A. No materials shall be incorporated in the steam trap system unless they have been
shown on the shop drawings and approved by the Owner. Decision by the Owner on
product suitability shall be binding.
PART 3: EXECUTION
3.01 GENERAL
A. The Contractor shall receive all materials and components and shall inspect them for
condition, completeness and suitability for the service intended, prior to the start of work.
B. Installation shall be performed by workmen skilled in the piping trade working under the
direct supervision of a competent, assigned field superintendent.
C. The superintendent shall be responsible for coordination of the work and cooperation
with the Owner and other trades.
D. All threaded joints shall be made up using non-hardening joint compound.
E. Materials and workmanship shall be first class in every respect and shall be subject to
Owner's inspection to any time after award of contract.
F. Welding procedures and welder qualification data shall be submitted for the Owner's
review and approval prior to the initiation of the work.
G. At the close of the project, the Contractor shall provide the Owner with a marked up sepia
of each drawings showing the "as built" condition of the system.
3.02 INSTALLATION
A. Steam Traps and trapping systems shall be installed at all low points in the steam mains,
at maximum distances between joints of XXX feet, at all expansion joints and as shown
on the drawings. Bypasses shall be installed only around traps as shown.
B. Traps shall be installed after system testing and cleaning.