Creep is NOT a Factor Rolled Rod Design Points Final Initial Temp Ice Wind K Weight Sag Tension RTS Sag Tension RTS C mm Kgsm Kg/M Kg/M Mtrs Kg % Mtrs Kg % -5. 35.00 25.50 .00 6.468 16.30 6145. 84.1 16.30 6145. 84.1 -5. 15.00 20.40 .00 2.368 12.92 2827. 38.7 10.19 3572. 48.9 -5. 5.00 10.20 .00 1.098 10.84 1559. 21.3 7.14 2360. 32.3 10. .00 102.00 .00 1.988 12.88 2381. 32.6 9.75 3135. 42.9 5. .00 .00 .00 .728 9.78 1145. 15.7 6.12 1826. 25.0* 10. .00 .00 .00 .728 9.87 1134. 15.5 6.28 1779. 24.4 16. .00 .00 .00 .728 9.99 1121. 15.3 6.47 1726. 23.6 20. .00 .00 .00 .728 10.07 1112. 15.2 6.60 1691. 23.2 25. .00 .00 .00 .728 10.17 1102. 15.1 6.77 1650. 22.6 75. .00 .00 .00 .728 11.12 1008. 13.8 8.47 1321. 18.1 * Design Condition Certain information such as the data, opinions or recommendations set forth herein or given by AFL representatives, is intended as a general guide only. Each installation of overhead electrical conductor, underground electrical conductor, and/or conductor accessories involves special conditions creating problems that require individual solutions and, therefore, the recipient of this information has the sole responsibility in connection with the use of the information. AFL does not assume any liability in connection with such information. ALUMINUM COMPANY OF AMERICA SAG AND TENSION DATA
110KV T/LINE Afghanistan
Sag tension Calculations for OPGW
Conductor 7 # 6 Alumoweld
Area= 93.0966 Sq. mm Dia=11.000 mm Wt= .722 Kg/M RTS= 12456 Kg
Creep is NOT a Factor Design Points Final Initial Temp Ice Wind K Weight Sag Tension RTS Sag Tension RTS C mm Kgsm Kg/M Kg/M Mtrs Kg % Mtrs Kg % -5. 35.00 25.50 .00 5.727 13.14 6723. 54.0 13.14 6723. 54.0 -5. 15.00 20.40 .00 2.022 8.74 3553. 28.5 7.90 3932. 31.6 -5. 5.00 10.20 .00 .975 6.34 2358. 18.9 5.18 2887. 23.2 10. .00 102.00 .00 1.334 7.66 2673. 21.5 6.58 3112. 25.0 5. .00 .00 .00 .722 5.75 1925. 15.5 4.44 2491. 20.0* 10. .00 .00 .00 .722 5.89 1880. 15.1 4.55 2431. 19.5 16. .00 .00 .00 .722 6.06 1828. 14.7 4.69 2360. 18.9 20. .00 .00 .00 .722 6.17 1795. 14.4 4.78 2314. 18.6 25. .00 .00 .00 .722 6.31 1755. 14.1 4.90 2258. 18.1 55. .00 .00 .00 .722 7.17 1546. 12.4 5.66 1957. 15.7 75. .00 .00 .00 .722 7.74 1432. 11.5 6.20 1787. 14.3 * Design Condition Certain information such as the data, opinions or recommendations set forth herein or given by AFL representatives, is intended as a general guide only. Each installation of overhead electrical conductor, underground electrical conductor, and/or conductor accessories involves special conditions creating problems that require individual solutions and, therefore, the recipient of this information has the sole responsibility in connection with the use of the information. AFL does not assume any liability in connection with such information.