Preaction System with DV-5 Deluge Valve


Single Interlock, Supervised Electric Actuation
1-1/2 thru 8 Inch (DN40 thru DN200)
General
Description
The TYCO DV-5 Supervised Single In-
terlock Preaction System with Elec-
tric Actuation (Fig. 1) utilizes automatic
sprinklers and a supplemental detec-
tion system. The supplemental detec-
tion system is typically comprised of 24
VDC heat detectors, smoke detectors,
manual pull stations, etc. Actuation
of the detection system automatically
operates (releases) the DV-5 Deluge
Valve, allowing water to flow into the
sprinkler piping system and to be dis-
charged from any sprinklers that may
be open.
In accordance with the requirements
of the National Fire Protection Asso-
ciation, a preaction system employing
more than 20 automatic sprinklers is
to have the sprinkler piping automati-
cally supervised to monitor the overall
integrity of the system. In the case of water damage that might result from Solenoid Valve. In turn, the energized
a Supervised Single Interlock Preac- damaged automatic sprinklers or pip- Solenoid Valve opens to release wa-
tion System, a Riser Check Valve (that ing. Typically, such areas include com- ter from the Diaphragm Chamber fast-
does not require the use of priming wa- puter rooms, storage areas for valuable er than it can be replenished through
ter) provides an air check so that the artifacts, libraries, and archives. the 1/8 inch (3,2 mm) restriction pro-
system can be automatically pressur- vided by the Model ASV-1 Automatic
Single interlock preaction systems are
ized with a nominal supervisory air or Shut- Off Valve in the diaphragm sup-
also effectively used to protect prop-
nitrogen pressure of 10 psi (0,69 bar). A ply connection (Item 5 - Fig. 3A, also
erties where a pre-alarm of a possible
supervisory low pressure alarm switch described in Technical Data Sheet
fire condition may allow time for fire ex-
that is set to transfer its contacts at TFP1384). This results in a rapid pres-
tinguishment by alternate suppression
nominally 5 psi (0,34 bar), on decreas- sure drop in the Diaphragm Chamber
means, prior to a sprinkler discharge.
ing pressure, is utilized to indicate to below the valve trip point. The wa-
In the event the fire cannot otherwise
whether there are any abnormal leaks ter supply pressure then forces the
be extinguished, the preaction sprinkler
in the sprinkler system piping. Loss of Diaphragm open, permitting water to
system will then perform as the primary
air pressure from the system as a re- flow into the system piping, as well as
fire protection system.
sult of a damaged sprinkler or broken through the Alarm Port to actuate the
piping will not cause the DV-5 Valve to The DV-5 Deluge Valve (described in system alarms.
open the air pressure is for supervi- Technical Data Sheet TFP1305) is a
As water flows into the system, the pi-
sory alarm only. diaphragm style valve that depends
lot chamber of the Model ASV-1 Auto-
upon water pressure in the Diaphragm
Typically, the system designer selects matic Shut-Off Valve (Item 5 - Fig. 3A)
Chamber to hold the Diaphragm closed
the detection components for a single becomes pressurized and the ASV-1
against the water supply pressure.
interlock preaction system that will re- automatically shuts off the diaphragm
When the DV-5 Valve is set for service,
spond to a fire sooner than the auto- chamber supply flow to the DV-5 Di-
the Diaphragm Chamber is pressurized
matic sprinklers. Consequently, the aphragm Chamber. Shutting off the
through the trim connections from the
system will experience a minimal de- diaphragm chamber supply flow pre-
inlet side of the systems main control
lay in water delivery over that for a wet vents the DV-5 Diaphragm Chamber
valve, such as an O.S.&Y. gate valve or
pipe sprinkler system because the sys- from becoming re-pressurized, there-
butterfly valve (Fig. 1).
tem will have begun to fill with water by preventing inadvertent closing of the
before a sprinkler operates. Operation of an electrical detection de- DV-5 during a fire (as may be the case
vice such as a heat sensitive thermo- should the Solenoid Valve become de-
Supervised single interlock preaction stat, smoke detector, or electrical man- energized after its initial operation).
systems are generally used to protect ual control station signals the deluge
areas where there is danger of serious Continued on Page 4
valve releasing panel to energize the

Page 1 of 14 OCTOBER 2014 TFP1420


TFP1420
Page 2 of 14

13

6
19

15
17

16
9
11

14
7

8
3
4

1
2

18

1 - DV-5 Deluge Valve 9 - System Drain Valve (N.C.) 16 - Riser Check Valve
2 - Main Control Valve (N.O.) 10 - Main Drain Valve (N.C.) 17 - Supervisory Air Pressure Gauge
3 - Diaphragm Chamber Supply (Shown at Rear of Valve) 18 - Automatic Supervisory Air/Nitrogen
Control Valve (N.O.) 11 - Diaphragm Chamber Automatic Supply
4 - Local Manual Control Station Shut-Off Valve 19 - Supervisory Low Pressure Alarm
5 - Automatic Sprinklers 12 - Waterflow Pressure Alarm Switch Switch
(Shown at Rear of Valve)
6 - Heat Detectors, Smoke Detectors,
etc. (Fire Detection) 13 - Water Motor Alarm (Optional)
7 - Water Supply Pressure Gauge 14 - Solenoid Valve
8 - Diaphragm Chamber Pressure 15 - Deluge Valve Releasing Panel
Gauge

FIGURE 1 (1 OF 2)
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC ACTUATION
SYSTEM SCHEMATIC (FRONT VIEW)
TFP1420
Page 3 of 14

5
6

19
9
13

16

14

12

15
3

18
1 10

1 - DV-5 Deluge Valve 8 - Diaphragm Chamber Pressure 16 - Riser Check Valve


2 - Main Control Valve (N.O.) Gauge (Shown at Front of Valve) 17 - Supervisory Air Pressure Gauge
3 - Diaphragm Chamber Supply 9 - System Drain Valve (N.C.) (Shown at Front of Valve)
Control Valve (N.O.) 10 - Main Drain Valve (N.C.) 18 - Automatic Supervisory Air/Nitrogen
4 - Local Manual Control Station 11 - Diaphragm Chamber Automatic Shut-Off Supply
(Shown at Front of Valve) Valve (Shown at Front of Valve) 19 - Supervisory Low Pressure Alarm
5 - Automatic Sprinklers 12 - Waterflow Pressure Alarm Switch Switch
6 - Heat Detectors, Smoke Detectors, 13 - Water Motor Alarm (Optional)
etc. (Fire Detection) 14 - Solenoid Valve
7 - Water Supply Pressure Gauge 15 - Deluge Valve Releasing Panel
(Shown at Front of Valve)

FIGURE 1 (2 OF 2)
SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC ACTUATION
SYSTEM SCHEMATIC (REAR VIEW)
TFP1420
Page 4 of 14

LOW AIR
The trim arrangement is provided with
PRESSURE galvanized or black nipples and fittings.
WATERFLOW ALARM The galvanized trim is intended for
PRESSURE PREACTION
SWITCH
SINGLE non-corrosive or corrosive conditions,
ALARM CHECK
SWITCH INTERLOCK whereas the black trim is principally in-
VALVE
ELECTRIC tended for use with AFFF systems.
ACTUATION
TRIM NOTE: When the system pressure is
greater than 175 psi (12,1 bar), provi-
NOTES: sion is to be made to replace the stan-
1. SEE FIGURE 3, PER VALVE SIZE dard order 300 psi (20,7 bar) Water
AS APPLICABLE, FOR TRIM Pressure Gauges, shown in Figure 3A
ARRANGEMENT WITH BILL OF or 3B with separately ordered 600 psi
MATERIALS AND COMPONENT (41,4 bar) Water Pressure Gauges.
PART NUMBERS.
2. TRIM SHOWN FULLY ASSEMBLED; Detection System
COMPONENTS SUCH AS GAUGES In order for a single interlock preaction
DV-5 AND SWITCHES MAY REQUIRE system to be hydraulically calculated
DELUGE ASSEMBLY IN TRIM AT VALVE
VALVE INSTALLATION.
as a wet pipe system, as opposed to a
dry pipe sprinkler system, the detection
system must be designed to operate
SYSTEM sooner than the automatic sprinklers
GROOVED SHUT-OFF
VALVE
on the sprinkler piping.
COUPLING
The Supervised Single Interlock Pre-
FIGURE 2 action System with Electric Actuation
DV-5 PRE-TRIMMED DELUGE VALVE, Trim provides for electric operation of
ELECTRIC ACTUATION the DV-5 Valve by a detection system
consisting of electrical devices such as
NOTICE Valve Trim heat sensitive thermostats, smoke de-
The TYCO DV-5 Supervised Single In- The Supervised Single Interlock Pre- tectors, and/or electric manual pull sta-
terlock Preaction System with Electric action System with Electric Actuation tions. Information on the various types
Actuation Trim described herein must Trim (Fig. 3A or 3B) forms a part of the of separately ordered Solenoid Valves
be installed and maintained in compli- laboratory listings and approvals. The that may be used with this trim pack-
ance with this document, as well as trim is necessary for proper operation age is given in Technical Data Sheet
with the applicable standards of the of the DV-5 Valve. TFP2180. Nominal installation dimen-
National Fire Protection Association, in sions for the Supervised Single Inter-
Each package of trim includes the fol-
addition to the standards of any other lock Preaction System with Electric Ac-
lowing items:
authorities having jurisdiction. Failure tuation Trim are shown in Figure 4.
to do so may impair the performance Water Supply Pressure Gauge
NOTEs:
of the related devices. Diaphragm Chamber Approval by Factory Mutual is contin-
The owner is responsible for main- Pressure Gauge gent on the use of an FM Approved
taining their fire protection system Diaphragm Chamber Connections 24VDC Solenoid Valve (P/N 52-287-1-
and devices in proper operating con- 024 or P/N 52-287-1-124). FM only ap-
dition. Contact the installing contrac- Manual Control Station proves solenoid valves for use in non-
tor or product manufacturer with any Main Drain Valve hazardous locations.
questions. Consult with the authority having ju-
System Drain Valve
risdiction regarding installation cri-
Technical Alarm Test Valve
Automatic Drain Valve
teria pertaining to electric actuation
circuitry.
Data System Air Pressure Gauge The Supervised Single Interlock Pre-
action System with Electric Actuation
Approvals Air Supply Connections Trim is provided with a Model ASV-1
UL and C-UL Listed Low Air Pressure Supervisory Switch Automatic Shut-Off Valve (Item 5 - Fig.
FM Approved 3A); consequently, the release circuit
Waterflow Pressure Alarm Switch of the releasing panel need only pro-
Deluge Valve (PS10-2) vide the standard ten minutes of alarm
DV-5 The following items are included in the condition intended to energize the So-
Pre-trimmed Valve Assembly and can lenoid Valve. After the ten minute dura-
Riser Check Valve tion, should the Solenoid Valve become
Model CV-1FR be ordered separately for the valve
trim: de-energized and closed (especially
NOTE: 1-1/2 inch (DN40) risers utilize while operating under battery back-up),
a 2 inch (DN50) Model CV-1FR Riser Model BFV-N Butterfly Valve the Automatic Shut-Off Valve will have
Check Valve connected to the 1-1/2 Figure 577 Grooved Coupling already automatically closed thereby
inch (DN40) DV-5 Deluge Valve by a preventing the DV-5 Diaphragm Cham-
2 x 1-1/2 inch Figure 716 Reducing To ease field assembly of the trim ar- ber from becoming re-pressurized and
Coupling. rangement, the trim components are preventing an inadvertent closing of the
provided partially assembled as shown DV-5 during a fire event.
in Figure 3B.
Continued on Page 10
TFP1420
Page 5 of 14

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 24 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH P4 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-019
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 25 3/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P5 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 26 3/4" x 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . 1 CH P6 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH P7 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P8 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
6 Waterflow Pressure Alarm Switch, 29 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P9 1/2" x 1/4" Reducing Bushing. . . . . . . . . . . . 1 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P10 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 31 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P11 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 32 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 3 CH P12 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 33 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 11 CH P13 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 34 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P14 1" x 3/4" x 1/2" Tee. . . . . . . . . . . . . . . . . . . . 1 CH
11 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 35 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 3 CH P15 1/4" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
12 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 36 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P16 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH
13 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 37 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P17 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
14 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 38 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P18 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
15 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 39 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P19 1" x 2" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
16 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 40 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH E1 Solenoid Valve Ordered Separately Refer to
17 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 41 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet
18 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 42 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH E2 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
19 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 E3 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
20 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 E4 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
21 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH P3 Low Air Pressure Alarm Switch,
22 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 COMPONENTS INCLUDED ONLY IN
23 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH PRE-TRIMMED VALVE ASSEMBLIES:
A1 Model CV-1FR Check Valve, 2" (DN50) . . . 1 59-590-1-020
A2 Butterfly Valve, Power Ball 300:
1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 51024A
P16 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 51021A
P5 P4 A3 Figure 577 Coupling:
1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 57715ACP
P11 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57720ACP
P10 A4 Coupling for 1-1/2" (DN40) DV-5:
P3 P16 P13 Figure 716 Reducing Coupling, 2" x 1-1/2". . 1 7162015ES
Coupling for 2" (DN50) DV-5:
6 P16 P9 P16 Figure 577 Coupling, 2" . . . . . . . . . . . . . . . . 1 57720ACP
P16 P15
P1 P6
15 P12 26 Select Appropriate Nipple Sizes
Nipple
(GREEN per DV-5 Deluge Valve Size
TINT) 16 40 Number
1-1/2" (DN40) 2" (DN50)
P2
38 1/2" x Close 1/2" x 2"
P17 33
28 39 1/2" x 5" 1/2" x 5-1/2"
P8
30 P18
P19 27 E1
20 P7
4 (ORDERED
P14 SEPARATELY)
35 PLUG 12 E3
29
UNUSED 14 E2 E4
41 40 PORTS
LOCATION 22 13 36 21 32 21
FOR OPTIONAL 40 33
ELECTRICALLY 40
P8 27
SUPERVISED 33 10
40 A1 24 39
N.O. ALARM 40
35 24 24
CONTROL 30 1
P8 27
VALVE A4
38 25 33 32
24 11 42 33 28
7
37
8
35 1 33 3
A3 9
NOTES:
1. Supervised Single Interlock 21 5
19 2 24 21
Preaction Trim with Electric A2
Actuation is comprised of 36 32
Items 1-42 plus Items P1-P19 33 34
33 18
and Items E2-E4. Item E1 33
31 28 33 17
ordered separaetly. Items 2" (DN50) 24 24
A1-A4 included only in 23 31 GROOVE x GROOVE 21
pre-trimmed valve assemblies DV-5 DELUGE VALVE
as applicable; otherwise SHOWN NOTES:
ordered separately. 33 4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are Deluge Valve Port identification.
galvanized (Standard Order). 7 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. Item 14.
FIGURE 3A (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC ACTUATION TRIM EXPLODED VIEW
TFP1420
Page 6 of 14

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 18 1/2" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 36 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 19 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 37 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 20 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 38 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 21 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH 39 1/2" x 5-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 22 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 40 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
6 Waterflow Pressure Alarm Switch, 23 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH 41 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 24 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH 42 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 25 3/4" x 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . 1 CH 43 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 26 1-1/4" 90 Elbow. . . . . . . . . . . . . . . . . . . . . . 1 CH 44 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 27 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 28 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012
11 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007 29 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
12 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P3 Low Air Pressure Alarm Switch,
13 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 31 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710
14 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 32 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P4 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-019
15 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 33 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 13 CH P5 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004
16 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 34 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P6 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
17 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 35 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P7 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007
P8 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
P9 1/2" x 1/4" Reducing Bushing. . . . . . . . . . . . 1 CH
P4 P10 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
P16 P11 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
P16 P13 P12 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
P13 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
P6 P14 1-1/4" x 1-1/4" x 1/2" Tee. . . . . . . . . . . . . . . 1 CH
P16 P15 1/4" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
P5 25 P16 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
P1 P17 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
P11 P3 41
P10 P18 1-1/4" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH

33 E1 Solenoid Valve Ordered Separately Refer to


Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet
6 P16 P9 E2 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
P15 E3 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
P16 P2 E4 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
15 P12 4 COMPONENTS INCLUDED ONLY IN
27
(GREEN PRE-TRIMMED VALVE ASSEMBLIES:
TINT) 16 P8 14
A1 Model CV-1FR Check Valve, 3" (DN80) . . . 1 59-590-1-030
P16 A2 Model BFV-N Butterfly Valve, 3" (DN80) . . . 1 59300F030N
12 A3 Figure 577 Coupling, 3" (DN80) . . . . . . . . . . 2 57730ACP
28 P17
30 13 E1
P7 P18
20 PLUG (ORDERED
P14 UNUSED SEPARATELY)
PORTS E3
34 29 E4
E2
41 P8 21
42 22 A1 39 21 33
LOCATION 33
FOR OPTIONAL 41 36
41 P8
ELECTRICALLY 27
SUPERVISED 33 10 24 40
N.O. ALARM 41 24 24
24 A3 1
CONTROL 30 27
VALVE 33
33 33
26 33 28
7 43 44 40
11 5 33 3
38
1
8
21
NOTES: 21
1. Supervised Single Interlock 19 2 A3
24 32
Preaction Trim with Electric 35
18
Actuation is comprised of 37 A2 9
Items 1-44 plus Items P1-P18 33 17
33 24 24
and Items E2-E4. Item E1 31 33 33
28
ordered separaetly. Items
23 31
A1-A3 included only in
3" (DN80) 21
pre-trimmed valve assemblies
as applicable; otherwise GROOVE x GROOVE NOTES:
ordered separately. DV-5 DELUGE VALVE 33 4. See Figure 2 of TFP1305 for
SHOWN
2. All Fittings and Nipples are Deluge Valve Port identification.
galvanized (Standard Order). 7 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. Item 14.
FIGURE 3A (2 OF 3)
3 INCH (DN80) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC ACTUATION TRIM EXPLODED VIEW
TFP1420
Page 7 of 14

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 27 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P4 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-019
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 28 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P5 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 29 1" x 1/2" 90 Elbow. . . . . . . . . . . . . . . . . . . . 1 CH P6 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 30 1" x 3/4" x 1" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH P7 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009
5 Model ASV-1 Automatic Shut-Off Valve . . . 1 92-343-1-021 31 2" 90 Elbow. . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P8 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
6 Waterflow Pressure Alarm Switch, 32 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P9 1/2" x 1/4" Reducing Bushing. . . . . . . . . . . . 1 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 33 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P10 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 34 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 10 CH P11 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
8 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 35 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P12 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 36 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P13 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
10 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 37 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P14 2" x 2" x 1/2" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH
11 Item No. Not Used 38 1/2" x 6" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P15 1/4" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
12 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 39 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P16 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 40 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P17 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 41 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH E1 Solenoid Valve Ordered Separately Refer to
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 42 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 43 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH E2 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
17 1/4" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 44 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH E3 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH 45 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH E4 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 46 1" x Close Nipple . . . . . . . . . . . . . . . . . . . . . 2 CH
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 47 1" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH COMPONENTS INCLUDED ONLY IN
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 48 Item No. Not Used PRE-TRIMMED VALVE ASSEMBLIES:
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH 49 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
23 1" Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH A1 Model CV-1FR Check Valve:
P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-040
24 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
25 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-060
P3 Low Air Pressure Alarm Switch, 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-080
26 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 A2 Model BFV-N Butterfly Valve:
4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F040N
6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F060N
P6 P4 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F080N
P16 P13 A3 Figure 577 Coupling:
4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57740ACP
P16 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57760ACP
P16 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57780ACP
P5
P1 29
P11 P3 46
P10 Select Appropriate Nipple Sizes
Nipple per DV-5 Deluge Valve Size
6 36 No. 4" 6" 8"
P16 P9 (DN100) (DN150) (DN200)

P16 P15 40 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8 -1/2"


16 P2 41 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
(GREEN P12 42 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
26 4
TINT) 17 45 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
P8
P16
27 13 15
P14 PLUG E1
28
P17 UNUSED (ORDERED
21 14 SEPARATELY)
P7 P17 PORTS E3
35 P8 E2 E4
30 A1 38 22 41 22
44 34
LOCATION 23 P8
FOR OPTIONAL
43 26
ELECTRICALLY 25 42
SUPERVISED 10 46
34 25 25
N.O. ALARM 47 35
25 45 1
CONTROL A3 26
28
VALVE 34 33
40 34 27
31 39
7
49 49 5 34 3
12
8
1 9 22
NOTES: 39
1. Supervised Single Interlock 22 25 33
Preaction Trim with Electric 20 2 37
A3 19
Actuation is comprised of
Items 1-49 plus Items P1-P17 37 34 18
25 25
and Items E2-E4. Item E1 34 A2 34
34
ordered separaetly. Items 32 27
A1-A3 included only in
32 22
pre-trimmed valve assemblies 24
as applicable; otherwise 4" (DN100) NOTES:
ordered separately. GROOVE x GROOVE 34 4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are DV-5 DELUGE VALVE Deluge Valve Port identification.
galvanized (Standard Order). SHOWN 7 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. Item 15.
FIGURE 3A (3 OF 3)
4, 6, AND 8 INCH (DN100, DN150 AND DN200) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC ACTUATION TRIM EXPLODED VIEW
TFP1420
Page 8 of 14

NOTES: Nipple Select Appropriate Nipple Sizes per DV-5 Deluge Valve Size
1. Use only 2" (DN50) Model CV-1FR Riser Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
Check Valve in 1-1/2" (DN40) and 2" (DN50)
1 1/2" x Close 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
assemblies. Use CV-1FR Valve size equal
to mating DV-5 Valve in larger assemblies. 2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
2. Nipples 1-4 vary in length relative to DV-5 3 1/2" x 5" 1/2" x 5-1/2" 1/2" x 7" 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
size. Select per table. All other nipples 4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
packed unassembled shall be installed per System
appropriate trim exploded view, Figure 3A Main Drain 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
Part 1, 2, or 3. Size
3. Install subassemblies in alphabetical order.
Main Drain
4. See Figure 2 of TFP1305 for Deluge Valve 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
Size
Port identification.
5. Route all Tubing to Drip Funnel.
VENT FITTING SYSTEM LOW AIR
(GREEN TINT) AIR SUPPLY PRESSURE
CONTROL VALVE ALARM SWITCH
WATERFLOW (NORMALLY
PRESSURE OPEN) 1/2 INCH NPT
ALARM SWITCH
CONNECTION
DRIP
FOR SYSTEM
3/4 INCH NPT AUTOMATIC FUNNEL
AIR SUPPLY SOLENOID VALVE,
CONNECTION FOR DRAIN WITH 1-1/4
WATER MOTOR B VALVE INCH NPT ORDERED SEPARATELY 1/2 INCH
ALARM SYSTEM (NORMALLY CLOSED) CONDUIT
NIPPLE CONNECTION
AIR SUPPLY CONNECTION
4 TO DRAIN
PRESSURE FOR "ELECTRIC
LOCATION GAUGE DETECTION"
FOR OPTIONAL PLUG F
ELECTRICALLY UNUSED
SUPERVISED SYSTEM PORTS RISER
N.O. ALARM MAIN DRAIN CHECK VALVE NIPPLE
CONTROL CONNECTION (NOTE 1) 2
VALVE (SIZED PER
TABLE)
SYSTEM MAIN NIPPLE
NIPPLE AUTOMATIC 3
1 DRAIN VALVE
(NORMALLY SHUT-OFF VALVE
CLOSED) (NORMALLY DIAPHRAGM
MAIN
OPEN) CHAMBER
DRAIN VALVE
(NORMALLY E PRESSURE
CLOSED) GAUGE
ALARM
TEST VALVE A
(NORMALLY MANUAL
CLOSED) D CONTROL
STATION
SYSTEM
DIAPHRAGM
WATER C 4" (DN100) CHAMBER SUPPLY
SUPPLY
FLANGE x GROOVE CONTROL VALVE
PRESSURE
DV-5 DELUGE (NORMALLY
GAUGE MAIN DRAIN 1/2 INCH NPT
VALVE SHOWN OPEN)
CONNECTION CONNECTION FROM
(SIZED PER TABLE) WATER SUPPLY
FIGURE 3B
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION
WITH ELECTRIC ACTUATION TRIM OPERATIONAL COMPONENTS
SEMI-PREASSEMBLED TRIM EXPLODED ARRANGEMENT
TFP1420
Page 9 of 14

Valve Nominal Installation Dimensions in Inches and (mm)


Size A B C D E F G H J K L M N
1-1/2" 7.00 8.88 13.00 10.50 20.50 4.00 5.81 5.81 3.00 7.00 4.00 14.81 4.02
(DN40) (177,8) (225,4) (330,2) (266,7) (520,7) (101,6) (147,6) (147,6) (76,2) (177,8) (101,6) (376,2) (102,1)
2" 7.13 9.13 13.00 10.50 21.06 3.13 6.00 6.00 3.00 7.00 3.13 15.38 4.09
(DN50) (181,0) (231,8) (330,2) (266,7) (535,0) (79,4) (152,4) (152,4) (76,2) (177,8) (79,4) (390,5) (103,9)
3" 7.81 10.44 14.50 10.50 25.00 1.69 6.69 6.69 4.25 7.00 0.25 21.13 3.85
(DN80) (198,4) (265,1) (368,3) (266,7) (635,0) (42,9) (170,0) (170,0) (108,0) (177,8) (6,4) (536,6) (98,0)
4" 10.00 11.75 17.88 10.50 29.13 1.75 6.50 8.56 6.25 7.13 0.38 25.38 4.56
(DN100) (254,0) (298,5) (454,0) (266,7) (739,8) (44,5) (165,1) (217,5) (158,8) (181,0) (9,5) (644,5) (116,0)
6" 11.38 14.31 18.75 10.50 31.94 3.50 7.88 9.94 6.25 7.13 1.56 29.63 5.86
(DN150) (289,0) (363,5) (476,3) (266,7) (811,2) (88,9) (200,0) (252,4) (158,8) (181,0) (39,7) (752,5) (149,0)
8" 12.00 16.00 21.25 10.50 36.75 1.75 10.75 10.63 6.25 7.13 7.13 36.50 5.26
(DN200) (304,8) (406,4) (539,8) (266,7) (933,5) (44,5) (273,1) (269,9) (158,8) (181,0) (181,0) (927,1) (134,0)

* MINIMUM CLEARANCE.

A* B C* D*

E*
M

N
F
G

H J K

LEFT VIEW FRONT VIEW


FIGURE 4
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION
WITH ELECTRIC ACTUATION TRIM NOMINAL INSTALLATION DIMENSIONS
TFP1420
Page 10 of 14

System Air Pressure Requirements


The supervisory air (nitrogen) pressure Installation Step 9. A suitable automatic supervi-
sory air (nitrogen) supply, as described
is to be 10 2 psi (0,69 plus or minus in the Technical Data section, is to be
0,07 bar). The use of a higher supervi- General Instructions installed in accordance with the appli-
sory pressure is subject to approval by Proper operation of the DV-5 Deluge cable technical data sheet and set for
the authority having jurisdiction, and it Valve depends upon its trim being in- 10 2 psi (0,69 0,14 bar).
should be understood that the use of stalled in accordance with the instruc-
tions given in this technical data sheet. Step 10. A desiccant dryer, when re-
a higher supervisory pressure may in-
Failure to follow the appropriate trim quired for the supervisory air supply, is
crease water delivery time. The use of
diagram may prevent the DV-5 Valve to be installed between a drip leg and
a lower supervisory pressure may pre-
from functioning properly, as well as the Model AMD-1 Air Maintenance De-
vent clearing the alarm of the Supervi-
void listings, approvals, and the manu- vice or between the Model G16AC812
sory Low Pressure Alarm Switch (Item
facturers warranties. Automatic Supervisory Air Supply and
P3 - Fig. 3A), which is factory set to the Preaction Trim.
alarm at 5 1 psi (0,34 0,07 bar) on 1-1/2 inch (DN40) risers utilize a 2 inch
decreasing pressure. The supervisory (DN50) Riser Check Valve in combina- Step 11. The Supervisory Low Pres-
air supply pressure of 10 2 psi (0,69 tion with the 1-1/2 inch (DN40) DV-5 sure Alarm Switch is to be wired to the
0,07 bar) can be provided by any of Deluge Valve. supervisory alarm initiating circuit of an
the following methods. Refer to the ap- alarm panel.
plicable data sheet for laboratory ap- The DV-5 Valve must be installed in a
readily visible and accessible location. Step 12. Conduit and electrical con-
proval information. nections are to be made in accordance
Model G16AC812 (self contained) The DV-5 Valve associated trim must with the requirements of the authority
Automatic Supervisory Air Supply be maintained at a minimum tempera- having jurisdiction and/or the National
described in Technical Data Sheet ture of 40F (4C). Electric Code.
TFP1620. Heat tracing of the DV-5 Valve or its Step 13. Before a system hydrostatic
A maximum 200 psi (13,8 bar) plant associated trim is not permitted. Heat test is performed in accordance with
air supply in combination with the tracing can result in the formation of NFPA 13 system acceptance test re-
Model AMD-1 Air Maintenance De- hardened mineral deposits that are ca- quirements, the DV-5 Diaphragm
vice described in Technical Data pable of preventing proper operation. Chamber is to be depressurized; the
Sheet TFP1221. The DV-5 Deluge Valve is to be in- Automatic Drain Valve (Item 4, Fig. 3A)
stalled in accordance with the follow- is to be temporarily replaced with a 1/2
A maximum 3000 psi (206,9 bar) ni-
ing criteria: inch NPT plug, the 3/32 inch Vent Fit-
trogen cylinder in combination with ting (16 - Fig. 3A) is to be temporarily
the Model AMD-3 Nitrogen Mainte- Step 1. All nipples, fittings, and de- replaced with a 1/4 inch NPT plug, and
nance Device described in Technical vices must be clean and free of scale the Diaphragm Cover Bolts must be
Data Sheet TFP1241. and burrs before installation. Use pipe uniformly and securely tightened using
NOTE: The dew point of the air or ni- thread sealant sparingly on male pipe a cross-draw sequence. After tighten-
trogen supply for a system exposed to threads only. ing, double-check to make certain that
freezing conditions must be maintained Step 2. The DV-5 Valve must be all of the Diaphragm Cover Bolts are
below the lowest ambient temperature trimmed in accordance with Figure 3A securely tightened.
to which the system piping will be ex- or 3B.
posed. Introduction of moisture into
the system piping can create ice build-
Step 3. Care must be taken to ensure
that check valves, strainers, globe
Valve Setting
up that could prevent proper operation
of the system.
valves, etc. are installed with the flow
arrows in the proper direction.
Procedure
The Supervisory Low Pressure Alarm Steps 1 through 12 are to be performed
Step 4. Drain tubing to the Drip Funnel
Switch (Item P3 - Fig. 3A) is factory set when initially setting the DV-5 Deluge
must be installed with smooth bends
at 5 1 psi (0,34 0,07 bar) on de- Valve after an operational test of the
that will not restrict flow.
creasing pressure. The Pressure Relief fire protection system, or, after system
Valve (Item P4- Fig. 3A) is factory set to Step 5. The main drain and Drip Funnel operation due to a fire.
fully open at 25 2 psi (1,72 0,14 bar) drain may be interconnected provided
Step 1. Close the Main Control Valve.
and it begins to crack open at a pres- a check valve is located at least 12
sure of about 18 psi (1,24 bar). inches (300 mm) below the Drip Funnel. Step 2. Close the Diaphragm Cham-
ber Supply Control Valve, the Dry Pilot
Friction Loss Step 6. Suitable provision must be
Line Air Supply Control Valve, and the
The nominal pressure loss versus flow made for disposal of drain water. Drain-
Supervisory Air Supply Control Valve.
data for the DV-5 Deluge Valve plus age water must be directed such that
Riser Check Valve is provided in Graph it will not cause accidental damage to Step 3. Open the Main Drain Valve,
A. property or danger to persons. System Drain Valve, and all auxiliary
drains in the system. Close the System
Step 7. Connect the Diaphragm Cham-
Drain Valve and auxiliary drain valves
ber Supply Control Valve to the inlet
after water ceases to discharge. Leave
side of the systems Main Control Valve
the Main Drain Valve open.
in order to facilitate setting of the DV-5
Valve (Ref. Figure 4). Step 4. Depress the plunger of the Au-
tomatic Drain Valve to verify that it is
Step 8. Unused pressure alarm switch
open and that the DV-5 Valve is com-
connections must be plugged.
pletely drained.
Continued on Page 12
TFP1420
Page 11 of 14

FLOW RATE IN LITRES PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
200 400 600 1000 2000 3000 5000 7000 10000
15.0 1,00
0,90
0,80
10.0 0,70
9.0
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

0,60

0)
8.0

N4
0,50
(D
7.0

0)
CH

N5
6.0
(D
IN

H 0,40
1/2

NC

5.0

NOMINAL PRESSURE DROP IN BAR


1-

2I

0)
0,30

N8
4.0

(D

)
00

(1 PSI = 0,06895 BAR)


H

N1
NC

(D
3.0
3I
0,20

H
NC

)
50
4I

N1
(D
2.0

)
00
H
NC

N2
(D
6I
0,10

H
NC
0,09

8I
0,08
1.0 0,07
0.9 0,06
0.8
0.7 0,05

0.6 0,04
0.5
0,03
0.4
50 100 200 400 600 1000 2000 3000
FLOW RATE IN GALLONS PER MINUTE (GPM)
The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe with
C-120, is as follows:
15 feet of 1-1/2 Sch. 40 pipe for the 1-1/2 inch Valve Combination** calculated on a typical flow rate of 100 gpm.
28 feet of 2 inch Sch. 40 pipe for the 2 inch Valve Combination* calculated on a typical flow rate of 175 gpm.
37 feet of 3 inch Sch. 40 pipe for the 3 inch Valve Combination* calculated on a typical flow rate of 350 gpm.
48 feet of 4 inch Sch. 40 pipe for the 4 inch Valve Combination* calculated on a typical flow rate of 600 gpm.
73 feet of 6 inch Sch. 40 pipe for the 6 inch Valve Combination* calculated on a typical flow rate of 1500 gpm.
103 feet of 8 inch Sch. 30 Pipe for the 8 inch Valve Combination* calculated on a typical flow rate of 2500 gpm.
GRAPH A
DELUGE AND CHECK VALVE COMBINATION*
NOMINAL PRESSURE LOSS VERSUS FLOW
*DV-5 Deluge Valve combined with Model CV-1FR Riser Check Valve
**1-1/2 Inch DV-5 Deluge Valve combined with 2 Inch Model CV-1FR Riser Check Valve
TFP1420
Page 12 of 14

Step 5. Clean the Strainer in the Dia- NOTE: In order to prevent the pos- It is recommended that automatic
phragm Chamber Supply connection sibility of a subsequent operation of sprinkler systems be inspected, tested,
by removing the clean-out plug and an over-heated solder type automat- and maintained by a qualified Inspec-
strainer basket. The Strainer may be ic sprinkler, any solder type automat- tion Service in accordance with local
flushed out by momentarily opening ic sprinklers that were possibly ex- requirements and/or national codes.
the Diaphragm Chamber Supply Con- posed to a temperature greater than
trol Valve. their maximum rated ambient must be NOTICE
replaced.
Step 6. Reset the actuation system. Some of the procedures outlined in
Step 12. Slowly open the Main Con- this section will result in operation of
Manual Actuation Push the operat-
trol Valve. Close the Main Drain Valve the associated alarms. Consequently,
ing lever up; however, do not close the
as soon as water discharges from the notification must first be given to the
hinged cover at this time.
drain connection. Observe the Auto- owner and the fire department, central
Electric Actuation Reset the electric matic Drain Valve for leaks. If there are station, or other signal station to which
detection system in accordance with leaks, determine/correct the cause of the alarms are connected.
the manufacturers instructions to de- the leakage problem. If there are no
energize the Solenoid Valve. leaks, the DV-5 Valve is ready to be Annual Operation Test Procedure
placed in service and the Main Control Proper operation of the DV-5 Valve (i.e.,
Step 7. Open the Diaphragm Chamber opening of the DV-5 Valve as during a
Supply Control Valve and allow time Valve must then be fully opened.
fire condition) must be verified at least
for full pressure to build up in the Dia- NOTES: When the Main Control Valve once a year as follows:
phragm Chamber. is opened, the pressure on the Dia-
phragm Chamber may increase. This Step 1. If water must be prevented
Step 8. Operate (open) the Manu- from flowing beyond the riser, perform
al Control Station to vent trapped air increase in pressure is normal. If the
pressure is greater than 250 psi (17,2 the following steps.
from the Diaphragm Chamber. If nec-
essary, first open the hinged cover, and bar), the pressure is to be relieved by Close the Main Control Valve.
then fully pull down on the operating partially and temporarily opening the
Manual Control Station; however, do Open the Main Drain Valve.
lever. Slowly close the operating lever
by pushing it up after aerated water not allow the pressure as indicated Open the Main Control Valve one turn
ceases to discharge from the Manual on the Diaphragm Chamber Pressure beyond the position at which water
Control Station drain tubing. Close the Gauge to drop below the supply pres- just begins to flow from the Main
hinged cover and insert a new break sure shown on the Water Supply Pres- Drain Valve.
rod in the small hole through the top of sure Gauge since this action may result
in tripping of the DV-5 Valve. Close the Main Drain Valve.
the enclosing box.
After setting a fire protection system, Step 2. Test the Deluge Valve Releas-
Step 9. Inspect the drain connections ing Panel in accordance with the man-
from the Manual Control Station and notify the proper authorities and advise
those responsible for monitoring pro- ufacturers instructions to energize the
Solenoid Valve. Any leaks must be cor- Solenoid Valve.
rected before proceeding to the next prietary and/or central station alarms.
step. NOTE: Be prepared to quickly perform
Step 10. Verify the ability for the DV-5 Care and Steps 3, 4, and 5 if water must be pre-
vented from flowing beyond the riser.
Diaphragm to hold pressure as follows:
With the diaphragm chamber pres-
Maintenance Step 3. Verify that the DV-5 Valve has
tripped, as indicated by the flow of wa-
surized per Step 8, temporarily The following procedures and inspec- ter into the system.
close the Diaphragm Chamber Sup- tions must be performed in accor-
ply Control Valve, and then monitor dance with this section, in addition to Step 4. Close the systems Main Con-
the Diaphragm Chamber Pressure any specific requirements of the NFPA, trol Valve.
Gauge for a drop in pressure. and any impairment must be immedi- Step 5. Close the Diaphragm Cham-
If a drop in pressure is noted, the ately corrected. ber Supply Control Valve, the Dry Pilot
DV-5 Diaphragm is to be replaced Before closing a fire protection system Line Air Supply Control Valve, and the
and/or any leaks must be corrected main control valve for maintenance Supervisory Air Supply Control Valve.
before proceeding to the next step. work on the fire protection system that Step 6. Reset the DV-5 Deluge Valve
If the Diaphragm Chamber Pressure it controls, permission to shut down the in accordance with the Valve Setting
Gauge does not indicate a drop in affected fire protection systems must Procedure.
pressure, re-open the Diaphragm first be obtained from the proper au-
Chamber Supply Control Valve and thorities and all personnel who may be Quarterly Waterflow Alarm Test
proceed to the next step. affected by this action must be notified. Procedure
Testing of the system waterflow alarms
Step 11. Replace operated automatic The owner is responsible for the in-
must be performed quarterly. To test
sprinklers on the system piping and spection, testing, and maintenance of
the waterflow alarm, open the Alarm
then open the Supervisory Air Supply their fire protection system and devices
Test Valve, which will allow a flow of
Control Valve and allow the system to in compliance with this document, as
water to the Pressure Alarm Switch
automatically re-establish its nominal well as with the applicable standards
and/or Water Motor Alarm. Upon sat-
air pressure of 10 psi (0,69 bar). Ob- of the National Fire Protection Associa-
isfactory completion of the test, close
serve the Automatic Drain Valve for tion (e.g., NFPA 25), in addition to the
the Alarm Test Valve.
leaks. If there are leaks, determine/cor- standards of any authority having juris-
rect the cause of the leakage problem diction. Contact the installing contrac-
within the Riser Check Valve. tor or product manufacturer with any
questions.
TFP1420
Page 13 of 14

Quarterly Supervisory Low NOTE: 1-1/2 inch (DN40) risers utilize System With Electric Actuation Trim
Pressure Alarm Test Procedure a 2 inch (DN50) Model CV-1FR Riser for DV-5 Deluge Valves, P/N (specify):
Proper operation of the Supervisory Check Valve connected to the 1-1/2 1-1/2 & 2 Inch Galvanized . . . . P/N 52-478-2-119
Low Pressure Alarm Switch must be inch (DN40) DV-5 Deluge Valve by a 1-1/2 & 2 Inch Black . . . . . . . . P/N 52-478-1-119
performed quarterly as follows: 2 x 1-1/2 inch Figure 716 Reducing 3 Inch Galvanized . . . . . . . . . . P/N 52-478-2-116
Coupling. 3 Inch Black . . . . . . . . . . . . . . P/N 52-478-1-116
Step 1. Crack open the System Main 4, 6 & 8 Inch Galvanized . . . . . P/N 52-478-2-113
Drain Valve for the Riser Check Valve Replacement Trim Parts 4, 6 & 8 Inch Black . . . . . . . . . P/N 52-478-1-113
(Item P7, Figure 3A) to slowly relieve su- Specify: (description) for use with DV-5 Supervisory Air Supply (Select One)
pervisory air pressure from the system. Deluge Valve, P/N (see Figure 3A) A device capable of maintaining a nom-
Verify that the Supervisory Low Pres- inal system air or nitrogen pressure of
sure Alarm Switch is operational and Deluge Valve (Select One) nominal 10 psi (0,69 bar) must be sepa-
that the low pressure set point is ap- P/Ns are for American Standard rately ordered. Specify: (Model and de-
proximately 5 psi (0,34 bar). Groove x Groove Connections, and scription), P/N (specify):
Threaded Ports. For other configu-
Step 2. Close the System Main Drain Model AMD-1 Air Maintenance
rations refer to Technical Data Sheet
Valve (Item P7, Figure 3A) and allow the Device (TFP1221) . . . . . . . . . . P/N 52-324-2-002
TFP1305. Specify: (size) DV-5 Groove
system supervisory pressure of 10 2 Model AMD-3 Nitrogen Maintenance
x Groove Deluge Valve, P/N (specify): Device (TFP1241) . . . . . . . . . . P/N 52-328-2-001
psi (0,69 0,14 bar) to be automatical-
Model G16AC812 Automatic Supervisory
ly re-established. The Supervisory Low 1-1/2 Inch . . . . . . . . . . . . . . . . P/N 52-477-1-919
Air Supply (TFP1620) . . . . . . . P/N 52-150-1-001
Pressure Alarm Switch should return to 2 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-910
its normal condition.
3 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-912 Solenoid Valve (Select One)
4 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-913 A Solenoid Valve compatible with the
6 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-915
Pressure Relief Valve Maintenance 8 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-916
anticipated maximum water supply
Over-pressurization of the system pip- pressure must be ordered separately.
ing with air will result in the opening Riser Check Valve (Select One) Refer to Technical Data Sheet TFP2180
of the Pressure Relief Valve (Item P4, P/Ns are for American Standard for other voltage ratings and NEMA
Fig. 3A). If the Relief Valve continues Grooved Connections. For other con- classifications. Specify: 24 VDC, NEMA
to bleed air after the system pressure figurations refer to Technical Data 2, 4, and 4X, (specify 175 or 250 psi)
has been reduced to its normal su- Sheet TFP950 for the Groove x Groove Solenoid Valve, P/N (specify):
pervisory pressure range of 10 2 psi Model CV-1FR Riser Check Valve.
175 psi . . . . . . . . . . . . . . . . . . . P/N 52-287-1-024
(0,69 0,14 bar), most likely debris has Specify: (size), Model CV-1FR Groove 250 psi . . . . . . . . . . . . . . . . . . . P/N 52-287-1-124
become lodged in the seating area. To x Groove Riser Check Valve, P/N
(specify): Pre-Trimmed DV-5 Assembly with
help clean the seating area, slowly pull Butterfly Valve
up on the ring at the top of the Relief 2 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-020
Specify: (size), G x G End Connection,
Valve to allow a full flow of air through 3 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-030
4 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-040 Pre-Trimmed DV-5 Assembly with But-
the Relief Valve, and then release the 6 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-060 terfly Valve, P/N (specify):
ring to allow the Relief Valve to snap 8 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-080
closed. Repeat the cleaning procedure 1-1/2 Inch G x G . . . . . . . . . . . P/N 52-916-0-1AP
NOTE: For 1-1/2 inch (DN40) risers, use 2 Inch G x G . . . . . . . . . . . . . P/N 52-926-0-1AP
as necessary. the 2 inch (DN50) Riser Check Valve. 3 Inch G X G . . . . . . . . . . . . . P/N 52-936-0-1AP
4 Inch G x G . . . . . . . . . . . . . P/N 52-946-0-1AP

Limited Coupling (Select One)


P/Ns are for American Standard
6 Inch G x G . . . . . . . . . . . . . P/N 52-966-0-1AP
8 Inch G x G . . . . . . . . . . . . . P/N 52-986-0-1AP

Warranty Grooved Connections. For other con-


figurations and finishes refer to Tech-
Pre-Trimmed DV-5 Assembly
without Butterfly Valve
For warranty terms and conditions, visit nical Data Sheet TFP1830 or TFP1880. Specify: (specify size), (specify) End
www.tyco-fire.com. A coupling to attach the Riser Check Connection, Pre-trimmed DV-5 As-
Valve to the outlet of the Deluge Valve sembly without Butterfly Valve, P/N
must be separately ordered. Specify: (specify):
Ordering (Size), (Figure #), painted, (description),
P/N (specify). For 1-1/2 inch risers, or- 3 Inch F x G . . . . . . . . . . . . . . . P/N 52-936-2-1AP

Procedure der an additional Reducing Coupling


for the outlet of the 2 inch Riser Check
4 Inch F x G . . . . . . . . . . . . . . . P/N 52-946-2-1AP
6 Inch F x G . . . . . . . . . . . . . . . P/N 52-966-2-1AP
8 Inch F x G . . . . . . . . . . . . . . . P/N 52-986-2-1AP
The DV-5 Deluge Valve with Single In- Valve. Accessories (As Needed)
terlock Preaction Electric Actuation 2 x 1-1/2 Inch Figure 716 Specify: (description), P/N (specify):
trim can be ordered pre-trimmed or Painted Reducing Coupling . . . . P/N 7162015ES 600 psi Water Pressure
non-assembled as separate items. 2 Inch Figure 772 Gauge . . . . . . . . . . . . . . . . . . . P/N 92-343-1-004
Painted Rigid Coupling . . . . . . . . P/N 77220ASC Model WMA-1 Water Motor
For non-assembled the following items 3 Inch Figure 772 Alarm (TFP921) . . . . . . . . . . . P/N 52-630-1-001P
must be ordered separately: Painted Rigid Coupling . . . . . . . . P/N 77230ASC
4 Inch Figure 772
DV-5 Deluge Valve Painted Rigid Coupling . . . . . . . . P/N 77240ASC
CF-1FR Riser Check Valve 6 Inch Figure 772
Painted Rigid Coupling . . . . . . . . P/N 77260ASC
Couplings 8 Inch Figure 772
Painted Rigid Coupling . . . . . . . . P/N 77280ASC
Single Interlock Preaction Electric
Actuation Trim, Semi-Preassembled Preaction Trim (Select One)
Specify: (Size and finish galvanized
Supervisory Air Supply is standard) Semi-Preassembled Su-
Dry Pilot Air Supply pervised Single Interlock Preaction
Accessories
TFP1420
Page 14 of 14