You are on page 1of 14

SIRCO M and MV Load break switches for machine control

sircm_099_a
sircm_132_a

corpo_207_a
Load break switches from 16 to 160 A
Function Specific characteristics Conformity
to standards
SIRCO M and MV are manually operated SIRCO M
IEC 60947-3
modulable and modular multipolar load Fully visualised breaking. EN 60947-3
break switches. Contact point technology. IS13947-3
They make and break under load For panel mounting device, use the "Door Standard UL:
see SIRCO M UL
conditions and provide safety isolation mounting kit" (see accessories).
for any low voltage circuit, particularly for
machine control circuits. SIRCO MV
Approvals and
Visible double breaking based on contact certifications (1)
carriers equipped with sliding contacts KEMA
(type SIRCO, see page 38). RINA (Registre
Fully visualised breaking. Naval Italien)
(1) Product reference on
request.

General characteristics
Double break per phase. Other products
DIN rail mounting, panel or modular panel The changeover
with 45 mm front cut out. switches are
composed of two
IP20 devices and accessories. 3 poles SIRCO M
Severe load duty categories switches and
(AC-22 and AC-23). conversion kit.
They ensure
switching, transfer of
sources or transfer
of two low voltage
circuits on load as
well as their safety
disconnection.

18 General Catalogue 2011-2012 SOCOMEC


Load break switches for machine control
SIRCO M and MV

What you need to know

SIRCO M
SIRCO M can be operated in different ways:
sircm_028_a_2_x_cat

sircm_030_a_1_x_cat
sircm_029_c_2_x_cat

Complete switch body Direct operation with External operation


toggle operation handle front, left side or right side

The SIRCO M is a 3 pole device available from 16 to 125 A,


complete with an unswitched neutral or PE pole and type M
auxiliary pre-break and signalling contacts.
The basic 3 pole device is available enclosed in a polyester
enclosure from 16 to 100 A (see page 492).
coff_337_a_1_cat

From 16 to 80 A, it is possible to mount the device on a door and


transform a 3 pole switch into a 6 or 8 pole switch or a 3 or 4 pole
changeover switch, by adding a conversion kit and a switched 4th pole.

Compact enclosure: see page 492


SIRCO MV

3 operations are available:


sircm_034_a_2_x_cat

sircm_033_a_1_x_cat
sircm_032_c_1_x_cat

Direct operation External right side operation External front and left side operation

SIRCO MV can be ordered in 3 or 4 pole from 100 to 160 A.


Two types of auxiliary contacts are available:
- U type pre-break,
- M type signalisation.

SOCOMEC General Catalogue 2011-2012 19


SIRCO M and MV - References
sircm_133_a

SIRCO M
sircm_132_a
Shaft
External External front extensions
Complete switch front and handle for for external
Rating No. of body toggle Direct right side External left changeover front and
(A) poles operation Switch body handle handle side handle switches side handle 4e pole

1P
16 A 3P 2205 3000 2200 3000(1)(2)(3)
2200 1000
1P
20 A 3P 2205 3001 2200 3001(1)(2)(3)
2200 1001
S00 type
I-0 S00 type S00 type 1P
25 A 3P 2205 3002 2200 3002(1)(2)(3)
Black IP55 I-0 I - 0 - II 2200 1002
Blue
1471 1111(4) Black IP65 Black IP65
(1)(2)(3) 2299 5012 1P
32 A 3P 2205 3003 2200 3003 Black IP65 147A 5111 1473 1113(4)
Red 2200 1003
1473 1111(4) Red/Yellow I - I+II - II
2299 5013
Red/Yellow IP65 Black IP65 1P
40 A 3P 2205 3004 2200 3004(1)(2)(3) 150 mm
IP65 147B 5111 1473 1114(4) 2200 1004
1407 0515
1474 1111(4)
200 mm 1P
63 A 3P 2205 3006 2200 3006(1)(2)(3)
1407 0520 2200 1006
320 mm
1P
80 A 3P 2205 3008 2200 3008(1)(2)(3) 1407 0532
2200 1008

S0 type
(2) I-0 S0 type 1P
100 A 3P 2200 3010
Black IP55 I-0 2200 1010
1481 1111(4) Black IP65
Blue
Black IP65 148A 5111
2299 5032
1483 1111(4) Red/Yellow
Red/Yellow IP65 1P
125 A 3P 2200 3011(2)
IP65 148B 5111 2200 1011
1484 1111(4)

Unswitched
No. Complete switch Unswitched protective
Rating of body toggle neutral earth Auxiliary Terminal Conversion Door mounting
(A) poles operation Switch body pole module contacts shrouds kit kit

16 A 3P 2205 3000 2200 3000(1)(2)(3)

20 A 3P 2205 3001 2200 3001(1)(2)(3) Switch


1P 6/8P 3/4 P
(1)(2)(3) 1P 1P 2294 1005(5) 2269 6009(6) Complete
25 A 3P 2205 3002 2200 3002 Changeover protection
2200 5005 2200 9005 3P
M type 2294 3005(5) switches IP2X
32 A 3P 2205 3003 2200 3003(1)(2)(3) 1 contact I - 0 - II 2299 3309(7)(8)
NO + NC 2209 6009(6) Overall
40 A 3P 2205 3004 2200 3004(1)(2)(3) 2299 0001 Changeover dimensions
1 contact switches reduce
2 NC 1P I - I+II - II 2299 3409(7)(8)
63 A 3P 2205 3006 2200 3006(1)(2)(3) 2299 6009(6)
1P 1P 2299 0011 2294 1009(5)
2200 5009 2200 9009 3P
80 A 3P 2205 3008 2200 3008(1)(2)(3) 2294 3009(5)

100 A 3P 2200 3010(2) 1P


1P 1P 2294 1011(5)
2200 5011 2200 9011 3P
125 A 3P 2200 3011(2) 2294 3016(5)
(1) For 8 pole device in direct operation, order 2 x 3 pole device + 2 main poles + (4) Defeatable handle.
conversion kit (for external operation, add the shaft + the handle). (5) Top and bottom.
(2) Front and side operation. (6) Delivered with a direct handle.
(3) For 6-pole device in direct operation, order 2 x 3-pole device + conversion kit (7) Available for SIRCO M only.
(for external operation, add the shaft + the handle). (8) Delivered with a shaft.

20 General Catalogue 2011-2012 SOCOMEC


Load break switches for machine control
SIRCO M and MV

SIRCO MV
sircm_099_a

Shaft
extensions Voltage
for external Auxiliary Auxiliary sensing and
Rating No. of Direct External External right External left front and signal contacts for Terminal power supply
(A) poles Switch body handle front handle side handle side handle side contact pre-break shrouds kit

S0 type
3P 2200 3110 I-0
S0 type S0 type S0 type
100 A Black IP55
I-0 I-0 150 mm
1491 0111(2)
Black IP55 Black IP65 1409 0615
4P 2200 4110 Black IP65
1491 0111(2) 149A 9111 200 mm
1493 0111(2)
Red/Yellow Red/Yellow 1409 0620 M type
I-0
IP65 IP65 320 mm 1 contact U type
3P 2200 3012 Blue Red/Yellow 3P
1494 0111(2) 149B 9111 1409 0632 NO + NC NC contact
2299 5042(1) IP65 2294 3016(3) 2 pieces
125 A 2299 0001 3999 0701
Blue 1494 0111(2) 4P 1399 4006
S1 type S1 type S1 type 1 contact 1 contact NO
4P 2200 4012 2299 5022 2294 4016(3)
I-0 I-0 200 mm 2 NC 3999 0702
S1 type O
Black IP55 Black IP65 1401 0620 2299 0011
I-0
1415 2111 141A 2111 320 mm
3P 2200 3016 Black IP55
Red/Yellow Red/Yellow 1401 0632
1411 2111(2)
160 A IP65 IP65 400 mm
Red/Yellow
1418 2111 141B 2111 1401 0640
4P 2200 4016 IP65
1414 2111(2)
(1) Standard.
(2) Defeatable handle.
(3) Top and bottom.

Accessories

Direct operation handle

For SIRCO M
Rating (A) Handle colour Handle Reference
16 80 Blue M00 type 2299 5012
sircm_041_a_1_x_cat
sircm_071_b_1_x_cat

16 80 Red M00 type 2299 5013


100 ... 125 Blue M01 type 2299 5032

M00 handle M01 handle For SIRCO MV


Rating (A) Handle colour Handle Reference
sircm_042_b_1_x_cat

100 ... 160 Blue M0B type 2299 5042(1)


100 ... 160 Blue M0 type 2299 5022
acces_268_a

(1) Standard.

M0 handle M0b handle

SOCOMEC General Catalogue 2011-2012 21


SIRCO M and MV - Accessories (continued)

External handle operation - SIRCO M


Front and right side operation I - 0
Handle
Rating (A) colour Handle External IP Reference
16 80 Black S00 type IP55 1471 1111
16 80 Black S00 type IP65 1473 1111
16 80 Red/Yellow S00 type IP65 1474 1111
100 125 Black S0 type IP55 1481 1111(1)
100 ... 125 Black S0 type IP65 1483 1111(1)
acces_278_a_2_cat

100 ... 125 Red/Yellow S0 type IP65 1484 1111(1)


(1) Defeatable handle.

S00 handle Left side operation I - 0


Handle
Rating (A) colour Handle External IP Reference
16 ... 80 Black S00 type IP65 147A 5111
16 ... 80 Red/Yellow S00 type IP65 147B 5111
100 ... 125 Black S0 type IP65 148A 5111
100 ... 125 Red/Yellow S0 type IP65 148B 5111
acces_263_a_2_cat

Front operation for changeover switches I - 0 - II


Handle
Rating (A) colour Handle External IP Reference
16 80 Black S00 type IP65 1473 1113
S0 handle

Front operation for changeover switches I - I+II - II


Handle
Rating (A) colour Handle External IP Reference
16 80 Black S00 type IP65 1473 1114

External handle operation - SIRCO MV

S0 type handle - Front and right side operation I - 0


Rating (A) Handle colour External IP Reference
100 ... 160 Black IP55 1491 0111(1)
100 ... 160 Black IP65 1493 0111(1)
100 ... 160 Red/Yellow IP65 1494 0111(1)
(1) Defeatable handle.
acces_279_a_2_cat

S0 type handle - Left side operation I - 0


S0 handle Rating (A) Handle colour External IP Reference
100 ... 160 Black IP65 149A 9111(1)
100 ... 160 Red/Yellow IP65 149B 9111(1)
(1) Defeatable handle.

S1 type handle - Front operation I - 0


Rating (A) Handle colour External IP Reference
100 ... 160 Black IP55 1411 2111(1)
100 ... 160 Black IP65 1413 2111(1)
acces_284_a_2_cat

100 ... 160 Red/Yellow IP65 1414 2111(1)


(1) Defeatable handle.

S1 handle
S1 type handle - Right side operation I - 0
Rating (A) Handle colour External IP Reference
100 ... 160 Black IP55 1415 2111
100 ... 160 Black IP65 1417 2111
100 ... 160 Red/Yellow IP65 1418 2111

S1 type handle - Left side operation I - 0


Rating (A) Handle colour External IP Reference
100 ... 160 Black IP65 141A 2111
100 ... 160 Red/Yellow IP65 141B 2111

22 General Catalogue 2011-2012 SOCOMEC


Load break switches for machine control
SIRCO M and MV

Shaft for external handle For SIRCO M


Shaft length
Rating (A) Handle (mm) Reference
16 ... 125 S00 type 150 mm 1407 0515
16 ... 125 S00 type 200 mm 1407 0520
sircm_045_a_2_x_cat

16 ... 125 S00 type 320 mm 1407 0532

Use
Standard lengths: For SIRCO MV
- 150 mm, Shaft length
- 200 mm, Rating (A) Handle (mm) Reference
- 320 mm. 100 ... 160 S0 type 150 mm 1409 0615
Other lengths: consult us. 100 ... 160 S0 type 200 mm 1409 0620
100 ... 160 S0 type 320 mm 1409 0632
For 3/4 pole switches, shaft extensions for external front and side handle. 100 ... 160 S1 type 200 mm 1401 0620
For 6/8 pole switches and SIRCOVER M changeover switches, shaft
100 ... 160 S1 type 320 mm 1401 0632
extensions for front operation only.
100 ... 160 S1 type 400 mm 1401 0640

Shaft guide for external operation

Use
To guide the extension shaft into the external handle.
This accessory enables handle to engage extension shaft with a misalignment of up to 15 mm.
Required for a shaft length over 320 mm.
acces_260_a_2_cat

Description Handle type Reference


Shaft guide S00 and S0 1419 0000
Shaft guide S1 1429 0000

Additional pole for SIRCO M 4e pole


Use
Adds one or two poles and transforms:
- 3 pole load break switches into a 4 pole,
- 6 pole load break switches into a 8 pole,
- 3 pole changeover switches into a 4 pole.

Rating (A) No. of poles Type Reference


16 1P switched 2200 1000
sircm_072_b_1_x_cat

20 1P switched 2200 1001


25 1P switched 2200 1002
32 1P switched 2200 1003
40 1P switched 2200 1004
63 1P switched 2200 1006
80 1P switched 2200 1008
100 1P switched 2200 1010
125 1P switched 2200 1011
N or PE

N or PE

Neutral pole
Use
Transforms the 3-pole switch into a 3-pole + solid neutral.

Rating (A) No. of poles Type Reference


16 40 1P unswitched 2200 5005
sircm_078_a_1_gb_cat

N or PE
N or PE

N or PE

N or PE

63 80 1P unswitched 2200 5009


100 ... 125 1P unswitched 2200 5011

Protective earth module


Additional pole configuration
Use
Adds 1 protective earth module pole to the switch-disconnector.

Rating (A) No. of poles Type Reference


16 40 1P unswitched 2200 9005
63 80 1P unswitched 2200 9009
100 ... 125 1P unswitched 2200 9011

SOCOMEC General Catalogue 2011-2012 23


SIRCO M and MV - Accessories (continued)

Terminal shrouds
For SIRCO M
Rating (A) No. of poles Position Reference
16 40 1P top / bottom 2294 1005
16 40 3P top / bottom 2294 3005
63 80 1P top / bottom 2294 1009
sircm_049_a_1_cat

63 80 3P top / bottom 2294 3009


100 ... 125 1P top / bottom 2294 1011(1)
100 ... 125 3P top and bottom 2294 3016(1)
(1) Reference composed of 2 pieces.
Use
For SIRCO MV
Top and bottom protection against direct contact with the terminals or connection
parts. Rating (A) No. of poles Position Reference
Available in 1 or 3 pole versions for SIRCO M and 3 or 4 pole for SIRCO MV. 100 160 3P top / bottom 2294 3016
An opening on each terminal cover makes it possible to insert a probe to 100 160 4P top / bottom 2294 4016
measure temperature.

Auxiliary contacts

M type
Use
Pre-break and signalisation of positions Pre-break is not guaranteed on the
0 and I by NO+NC or 2 NO auxiliary SIRCO MV.
contacts.
They allow to anticipate the switching of Characteristics
the main poles. They can be mounted on NO+NC auxiliary contacts: IP2 with
sircm_075_b_2_cat

the left or on the right side of the device. front operation.


Max 4 auxiliary contacts (2 modules).

For SIRCO M
Rating (A) Number of AC Type of AC Reference
16 125 1 AC NO + NC 2299 0001
sircm_081_a_1_cat

16 125 1 AC 2 NC 2299 0011

For SIRCO MV
Auxiliary contacts configurations for SIRCO M Rating (A) Number of AC Type of AC Reference
100 160 1 AC NO + NC 2299 0001
1 2 1 2 100 160 1 AC 2 NC 2299 0011
sircm_098_a_1_cat

Characteristics

Operating current Ie (A)


230 VAC
Contact type Nominal current (A) AC-13 AC-15
Auxiliary contacts configurations for SIRCO MV
NO + NC 10 10 6
1. Maximum 2 "U" type auxiliary contacts.
2. Maximum 4 "M" type auxiliary contacts

U type
Use
Pre-break and signalisation by NO or NC auxiliary contact.
Maximum 2 auxiliary contacts.
sircm_048_a_1_x_cat

For use only with SIRCO MV switches.

For SIRCO MV
Rating (A) Number of AC Type of AC Reference
100 160 1 AC NC 3999 0701
100 160 1 AC NO 3999 0702

Conversion kit Use


It must be ordered at the same time SIRCOVER M changeover switches
as the handle for external control. ensure switching, transfer of sources
This accessory enables the assembly (I - 0 - II) or transfer of two low
sircm_097_b_2_x_cat

of two 3 pole switches and additional voltage circuits on load (I - I+II - II),
sircm_050_c_2_cat

poles in order to achieve: with the continuity of power supply.


- 6 or 8-pole SIRCO M load break
switches,
Conversion kit for Escutcheon for 3/4-pole changeover - 3 or 4-pole SIRCOVER M changeover
6/8 pole load break switches switches (I - 0 - II) or (I - I+II - II) switches.

Rating (A) Type Reference


16 80 Load break switches 6 / 8 P 2269 6009
sircm_086_b_1_cat

16 80 Changeover switch 3/4 pole (I - 0 - II) 2209 6009


16 80 Changeover switch 3/4 pole (I - I+II - II) 2299 6009

24 General Catalogue 2011-2012 SOCOMEC


Load break switches for machine control
SIRCO M and MV

Door mounting kit

Use
This kit enables direct mounting of the The external handle is quick and easy
switch on the door panel, on the right or to install due to an internal locking nut
left side of the panel. mounted on the inside of the enclosure.
Moreover, the connection clamps of the 2 kits are available:
switch are always accessible. - one for complete protection IP2X
- one with overall dimensions reduced.

For SIRCO M
sircm_051_b_2_cat

No. of
Rating (A) poles Description Reference
16 80 3/4 P Complete protection IP2X 2299 3309
16 80 3/4 P Overall dimensions reduce 2299 3409

Cap for side operation mounting


Use
Accessory for capping the front face This piece can be snapped on the switch
of the SIRCO M when utilising in side body directly.
operation, 20 units per pack.
sircm_126_a_2_cat

For SIRCO M
Rating (A) Pack Reference
16 ... 80 20 pieces 2299 9409

6/8 pole joining accessory


Use
40 units per pack, they allow the joining For multi-pole switches, please consult us.
of two 3 pole switches (+ additional pole)
in order to form a 6 or 8 pole switch for
external side operation.
sircm_134_a_2_cat

For SIRCO M
Rating (A) Pack Reference
16 ... 80 40 pieces 2299 9909

DIN rail locking clip

Use
This locking clip prevents the SIRCO MV from sliding when DIN rail mounted.

For SIRCO MV
sircm_128_a_2_cat

Rating (A) Type Reference


100 ... 160 M4 5000 0041
100 ... 160 M5 5000 0051

Voltage sensing and power supply tap

Use
It allows connection of 2 x 1.5 mm2 voltage sensing or power cables.

For SIRCO MV
atysm_026_a_1_cat

Rating (A) Pack Reference


100 ... 160 2 pieces 1399 4006

SOCOMEC General Catalogue 2011-2012 25


Characteristics according to IEC 60947-3

SIRCO M - 16 to 125 A
Thermal current Ith (40C) 16 A 20 A 25 A 32 A 40 A 63 A 80 A 100 A 125 A
Rated insulation voltage Ui (V) 800 800 800 800 800 800 800 800 800
Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8 8 8 8 8

Rated operational currents Ie (A)


Rated voltage Load duty category A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1)
415 VAC AC-21 A / AC-21 B 16/16 20/20 25/25 32/32 40/40 63/63 80/80 100/100 125/125
415 VAC AC-22 A / AC-22 B 16/16 20/20 25/25 32/32 40/40 63/63 80/80 100/100 125/125
415 VAC AC-23 A / AC-23 B 16/16 20/20 25/25 32/32 40/40 63/63 80/80 100/100 125/125
500 VAC AC-21 A / AC-21 B 16/16 20/20 25/25 32/32 40/40 63/63 80/80 100/100 125/125
500 VAC AC-22 A / AC-22 B 16/16 20/20 25/25 32/32 40/40 63/63 80/80 100/100 125/125
500 VAC AC-23 A / AC-23 B 16/16 20/20 25/25 25/25 25/25 63/63 63/63 80/80 100/100
690 VAC AC-21 A / AC-21 B 16/16 20/20 25/25 32/32 40/40 63/63 80/80 100/100 125/125
690 VAC AC-22 A / AC-22 B 16/16 20/20 25/25 32/32 32/40 40/63 63/80 80/100 100/125
690 VAC AC-23 A / AC-23 B 16/16 20/20 25/25 25/25 25/25 40/40 40/40 63/63 63/63

Operational power in AC-23 (kW)


At 400 VAC without pre-break in AC-23 (kW)(1)(2) 7.5 9 11 15 18.5 30 37 45 55
At 500 VAC without pre-break in AC-23 (kW)(1)(2) 7.5 9 11 15 18.5 30 37 45 55
At 690 VAC without pre-break in AC-23 (kW)(1)(2) 7.5 11 15 15 15 30 37 45 55

Fuse protected short-circuit withstand (kA rms prospective)


Prospective short-circuit (kA rms)(3) 50 50 50 50 50 50 50 25 25
Associated fuse rating (A)(3) 16 20 25 32 40 63 80 100 125

Short-circuit capacity (Ue 415 VAC)


Rated short-time withstand current 0.3 s. ICW (kA eff.) 2.5 2.5 2.5 2.5 2.5 3 3 5 5
Rated peak withstand current (kA peak)(3) 6 6 6 6 6 9 9 12 12

Connection
Minimum Cu cable section (mm) 1.5 1.5 1.5 1.5 1.5 2.5 2.5 10 10
Maximum Cu cable section (mm2) 16 16 16 16 16 35 35 70 70
Tightening torque min/max (Nm) 2 / 2.2 2 / 2.2 2 / 2.2 2 / 2.2 2 / 2.2 3.5 / 3.85 3.5 / 3.85

Mechanical characteristics
Durability (number of operating cycles) 100 000 100 000 100 000 100 000 100 000 100 000 100 000 100 000 100 000
Operating effort (Nm) 0.8 0.8 0.8 0.8 0.8 1 1
Weight of a 3 pole device (kg) 0.16 0.16 0.16 0.16 0.16 0.26 0.26 0.7 0.7
(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) The power value is given for information only, the current values vary from one manufacturer to another.
(3) For a rated operational voltage Ue = 400 VAC.

26 General Catalogue 2011-2012 SOCOMEC


Load break switches for machine control
SIRCO M and MV

Characteristics according to IEC 60947-3

SIRCO MV - 100 to 160 A


Thermal current Ith (40C) 100 A 125 A 160 A
Rated insulation voltage Ui (V) 800 800 800
Rated impulse withstand voltage Uimp (kV) 8 8 8

Rated operational currents Ie (A)


Rated voltage Load duty category A/B(1) A/B(1) A/B(1)
415 VAC AC-21 A / AC-21 B 100/100 125/125 160/160
415 VAC AC-22 A / AC-22 B 100/100 125/125 160/160
415 VAC AC-23 A / AC-23 B 100/100 125/125 125/160
500 VAC AC-21 A / AC-21 B 100/100 125/125 160/160
500 VAC AC-22 A / AC-22 B 100/100 125/125 125/160
500 VAC AC-23 A / AC-23 B 80/80 100/100 100/100
690 VAC AC-20 A / AC-20 B 100/100 125/125 160/160
690 VAC AC-21 A / AC-21 B 100/100 125/125 160/160
690 VAC AC-22 A / AC-22 B 63/80 80/100 100/125
690 VAC AC-23 A / AC-23 B 63/63 80/80 80/80

Reactive power (kvar)


At 400 VAC (kvar)(2) 45 55 75

Operational power in AC-23 (kW)


At 400 VAC without pre-break in AC-23 (kW)(1)(2) 45 55 75
At 500 VAC without pre-break in AC-23 (kW)(1)(2) 45 55 75
At 690 VAC without pre-break in AC-23 (kW)(1)(2) 45 75 75

Fuse protected short-circuit withstand (kA rms prospective)


Prospective short-circuit (kA rms)(3) 100 65 50
Associated fuse rating (A)(3) 100 125 160

Short-circuit capacity (Ue 415 VAC)


Rated short-time withstand current 0.3 s. ICW (kA eff.) 7 7 7
Rated peak withstand current (kA peak)(3) 12 12 12

Connection
Minimum Cu cable section (mm) 10 10 10
Maximum Cu cable section (mm2) 70 70 70
Tightening torque min/max (Nm) 4 / 4.4 4 / 4.4 4 / 4.4

Mechanical characteristics
Durability (number of operating cycles) 50 000 50 000 50 000
Operating effort (Nm) 4 4 4
Weight of a 3 pole device (kg) 0.7 0.7 0.7
Weight of a 4 pole device (kg) 0.9 0.9 0.9
(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) The power value is given for information only, the current values vary from one manufacturer to another.
(3) For a rated operational voltage Ue = 400 VAC.

SOCOMEC General Catalogue 2011-2012 27


SIRCO M and MV - Dimensions

SIRCO M
SIRCO M 16 to 80 A

Toggle operation Direct operation with handle

3.19 2.95
81 75
2.87 2.52 F 1
73 F 64 M 2
2.52 M 1 1
64 2 2
1
2

2.67
sircm_052_b_1_gb_cat

AC
68
G

N
sircm_053_b_1_gb_cat
2.68

AC
68
G

N 0.24 0.35 F1 T F1 0.35


0.24 0.35 F1 T F1 0.35 1.97 6 8.8 M5 8.8
1.97 6 8.8 M5 8.8 50
50
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched 1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched
neutral pole neutral pole
or 1 protective earth module or 1 auxiliary contact. or 1 protective earth module or 1 auxiliary contact.
2. Position for 1 auxiliary contact only. 2. Position for 1 auxiliary contact only.
Note: max 4 additional blocks Note: max 4 additional blocks

External front operation External side operation


36 E
81 36 D F D 36 1. Location for: 1 switched fourth pole module (1 per
M device max.) or 1 unswitched neutral pole or 1
64 1
J protective earth module or 1 auxiliary contact.
50.6 2
1 2. Position for 1 auxiliary contact only.
2 Note: max 4 additional blocks
71
AC
68
G

N
sircm_054_c_1_x_cat

8.8 F1 F1 8.8
6 T
M5
50
Terminal
Overall dimensions shrouds Switch body Switch mounting Connection
Rating (A) D min D max E min E max AC F F1 G J M N T
1640 30 235 100 372 110 45 15 68 15 30 75 15
6380 30 235 100 372 110 52.5 17.5 76 17.5 35 85 17.5

Direct front operation for 6/8-pole load break switches External front operation for 6/8-pole load break switches
or 3/4-pole changeover switches or 3/4-pole changeover switches

F
J 3.50
F2 89
1 X M 2.06 1 E 1.42
2 2 3.07 36
52.5 78
2 79
2.67

1.77
68
G
N

45
sircm_055_c_1_gb_cat

0.24
0.35 F1 F1 0.35 6 1.69 1.36
8.8 T T 0.29 8.8 43 34.7
2.06 7.5
1. Location for: 1 switched fourth pole module (1 per device max.) or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact.
2. Position for 1 auxiliary contact only.
Note: max 4 additional blocks

Overall dimensions Switch body Switch mounting Connection


Rating (A) E min E max F F1 F2 G J M N T X
1640 105 372 97.5 15 45 68 48.75 30 75 15 7.5
6380 105 372 105 17.5 52.5 76 52.5 35 85 17.5 8.75

28 General Catalogue 2011-2012 SOCOMEC


Load break switches for machine control
SIRCO M and MV

SIRCO M 100 to 125 A

Direct operation with handle External front operation External side operation

2.95 100 min.


75 3.07 37 372 max.
78 81 30 min. 30 min.
2.52 1 64 37 201 max. 78 201 max. 37
64 1.02 2 50.6 26
26 13 1
1 1
2 2
2
49.05

124.6

131.4
124.6

51.73
131.4

71
189

88
sircm_056_c_1_gb_cat

sircm_057_b_1_x_cat

0.24 6
0.35 1.02 1.02 1.02 0.35 8.8 26 26 26 8.8
6 8 8 26 26 26 8 8 53 M5
2 09
1. Location for: 1 switched fourth pole module (1 per device max.) 1. Location for: 1 switched fourth pole module (1 per device max.)
or 1 unswitched neutral pole or 1 protective earth module or 1 or 1 unswitched neutral pole or 1 protective earth module or 1 auxiliary contact.
auxiliary contact. 2. Position for 1 auxiliary contact only.
2. Position for 1 auxiliary contact only. Note: max 4 additional blocks
Note: max 4 additional blocks

SIRCO MV
SIRCO MV 100 to 160 A

Direct front operation External front operation

110 min.
2 A 2 B 357 max. C D
76 109 135 69,9 37 44
64 35 26 61 29,5

8,8 8,8
124,6

131,4

71
189

88

70
sircm_058_c_1_x_cat

6 26
53 M5 1
A. 3 pole C. S0 type handle 1. Maximum 4 "M" type auxiliary contacts
B. 4 pole D. S1 type handle 2. Maximum 2 "U" type auxiliary contacts

External side operation

A B C 30 min. D E F
69,9 109 135 300 max. 37 44
50,6 26 57 83 69,9

8,8 8,8
131,4

124,6

71
189

88

70
sircm_059_c_1_x_cat

1
6 26 2 1 2
53 M5
A. Right side operation D. S0 type handle 1. Maximum 4 "M" type auxiliary contacts
B. 3 pole E. Left side operation 2. Maximum 2 "U" type auxiliary contacts
C. 4 pole F. S1 type handle

SOCOMEC General Catalogue 2011-2012 29


SIRCO M and MV - Dimensions (continued)

Dimensions for external handles

SIRCO M
SIRCO M 16 to 80 A
Front operation Side operation
Handle type Direction of operation Direction of operation Door drilling

S00 type Right side operation IP55 with 2 fixing clips IP65 with 4 fixing screws
Load break switches 40 40
I I

90 90
71 27 47
71

0 0

28

28
36
37 31

Left side operation With fixing nut

I 3

90

13.5
sircm_177_a_1_gb_cat

22.5

Front operation
Handle type Direction of operation Door drilling
Typ S00
IP55 with 2 fixing clips IP65 with 4 fixing screws With fixing nut
Changeover switches 0
I 0 II and I - I+II - II or 13.5
37 37
I+II 22.5

71 90


90

40
40

3
71
sircm_180_a_1_gb_cat

I II

36 27 47
28 28

SIRCO M 100 to 125 A

Front operation Side operation


Handle type Direction of operation Direction of operation Door drilling

S0 type Right side operation IP55 with 2 fixing clips IP65 with 4 fixing screws
Load break switches 40 40
I I

90 90
71 27 47
88

0 0
28

28

37
37 31

Left side operation


With fixing nut
I
3
90

13.5

0
sircm_178_a_1_gb_cat

22.5

30 General Catalogue 2011-2012 SOCOMEC


Load break switches for machine control
SIRCO M and MV

SIRCO MV

SIRCO MV 100 to 160 A

Front operation Side operation


Handle type Direction of operation Direction of operation Door drilling

S0 type Right side operation IP55 with 2 fixing clips IP65 with 4 fixing screws
Load break switches 40 40
I I

90 90
71 27 47
88

0 0

28

28
37
37 31

Left side operation


With fixing nut
I 3
90

13.5
I

22.5

S1 type Right side operation IP55 with 2 fixing clips IP65 with 4 fixing screws
Load break switches 40 40
0 I
90


90

27 47
78

I 0
28

28
70

44 37 31
Left side operation
I
90

sircm_179_a_1_gb_cat

SOCOMEC General Catalogue 2011-2012 31