You are on page 1of 2

1 2 3 4 5 6 7 8 9 10 11 12

107.9 [
4,25]
44.5 [1,75]
60.3 [2,375]
38.1 1,5
[ ]
5

0, HAM
75 FE
C

x4 R
A A

5
$

50.8 [2]
82.6 [3,25]
5 [0,57]

[ ]
8
n 14.4

114.3 4,5
6X

44.5 [1,75]
2239
SHIPPING WIDTH 5
2318
1080 1080
PHASE SPACING PHASE SPACING 1097
2 5
PHASE SPACING
B 56 B

44.5 [1,75]
0,
920 GROUND PAD
852 METAL TO METAL DETAIL
METAL
50

METAL TO
0

CENTER OF GRAVITY
5 FRONT 3 FRONT 1 FRONT AS INSTALLED AS SHIPPED
C 6 REAR 4 REAR 2 REAR X 436 436 C
Y 2402 1260
Z 448 448
1365
FOR
INTERRUPTER
REMOVAL NOTES:
1 CONDUIT ENTRANCE (REMOVEABLE PLATE)

2. COLOR OF CABINET AND BUSHINGS WILL BE ANSI70


8

SHIPPING HEIGHT
GRAY UNLESS OTHERWISE SPECIFIED ON CUSTOMER
D PURCHASE ORDER AND CONFIRMED BY ABB D
TRANSMITTAL. STRUCTURE AND LEGS ARE

2290
GALVANIZED STEEL.

3. BUSHING CREEP = 73" (1852mm)

9 4. INDICATES CENTER OF GRAVITY


10
5 ALLOW 500mm ELEVATION ABOVE BUSHINGS FOR BUSHING

INSTALLED HEIGHT
REMOVAL.

TOP OF TERMINAL PAD


HEIGHT TO LIVE PARTS
6 BUSHING TOP TERMINALS SHIPPED SEPARATELY.
MINIMUM DISTANCE TO UNGROUNDED PARTS

3496
E E
7 USE ONLY FLEXIBLE CONNECTORS FOR CONNECTION
3341

TO BUSHING TERMINALS. MAXIMUM LINE PULL


3179

SHOULD NOT EXCEED 150 LBS./ 667 N


MINIMUM BUSHING HEIGHT

8 LOCATION FOR TRAVEL ANANYZER

9 DENSITY MONITOR LOCATION


2682

10 PRESSURE GAUGE LOCATION

"Y"
11 AVAILABLE ALSO WITH (3) DENSITY MONITOR/GAUGE, UPON
2336 REQUEST ON CUSTOMERS PURCHASE ORDER.
F F
FOUNDATION LOADS
2009

(INCLUDES OPERATIONAL LOADS, 150 LBS./667 N LINE LOADS AND


EITHER 0.2G STATIC OR 90 MPH/145KMH WIND LOADS)
GROUND PAD LOCATION

OVERTURN MOMENT 14,700 FT.LBS. / 20,000 Nm


TOTAL SHEAR 2600 LBS / 11,700 N
SEE GROUND PAD DETAIL TOTAL COMPRESSION 5900 LBS / 26,400 N
1285
1191
1141

MAXIMUM ANCHOR BOLT LOADS

TENSION 800 LBS / 3500 N


G SHEAR 700 LBS / 2900 N G
PAD COMPRESSION 3300 LBS / 14,800 N

FOUNDATION & ANCHOR BOLT LOADS PER ED 3.1.1013

TYPE 72PM40-C
MAX VOLTAGE KV 72
CONTINUOUS CURRENT AMPS 2000

RATING
"X" SHORT CIRCUIT KA 40
"Z" BASIC IMPULSE LEVEL KV 350
H H
WEIGHT WITHOUT GAS LB/KG 5115/2320
SF6 GAS PER BREAKER LB/KG 22/10
Comments Order Scale Units Format
1:4 mm A1
Prepared Based on
2015-09-08 T.Hoburn
Reviewed Responsible department Language
2015-09-08 B.Dahm PPHV/USTRA EN
Approved Part lifecycle state Page
2015-09-09 J.Johnston - 72PM40-C Breaker Outline 1 of 2
We reserve all rights in this document and in the information contained
Document id. Revision
therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden. Copyright 2010 ABB

ABB Technology Ltd 2GHV016000 D


1 2 3 4 5 6 7 8 9 10 11 12
Pro/Engineer-Drawing
1 2 3 4 5 6 7 8 9 10 11 12
REVISION HISTORY
ZONE REV. DESCRIPTION
N/A A CREATED DRAWING
NOTES C UPATED CG, ADDED FOUNDATION LOADS
25.4 (1") DIA. SHT 1 D ADDED DIMENSION FOR INTERRUPTER REMOVAL
MOUNTING BOLT
101,6
AND HARDWARE

28,575
44,45
A 28,58 A
SUPPLIED BY CUSTOMER

76 (3") MIN.

101,6

44,45
640 252,9 15
DOOR SWING
739

B B

230
ANCHOR BOLT HEX SOCKET HEAD CAP SCREW

1
DETAIL

6
7

30
TERMINAL TENSIONER
C C
60

TERMINAL
DETAIL

340
GROUND PAD

11 DENSITY MONITOR/GAUGE
DETAIL
D D

176,7
1080 1080
PHASE SPACING PHASE SPACING

E E

LOCATION OF MOUNTING HARDWARE


1092

PHASE SPACING
ASSEMBLED OVERALL WIDTH
F F

1097
2318
G G

32mm (1 1/4") DIA. HOLES


FOR (4) 1" DIA. F1554 GR.38
ANCHOR BOLTS TO BE
SUPPLIED BY CUSTOMER.
H GROUND PAD 2240 H

940 ASSEMBLED OVERALL WIDTH


LOCATION OF MOUNTING HARDWARE Comments Order Scale
1:8
Units
mm
Format
A1

Prepared Based on
2015-09-08 T.Hoburn

PRESSURE GAUGE DETAIL


Reviewed Responsible department Language
2015-09-08 B.Dahm PPHV/USTRA EN

Approved Part lifecycle state Page


2015-09-09 J.Johnston - 72PM40-C Breaker Outline 2 of 2

We reserve all rights in this document and in the information contained


Document id. Revision
therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden. Copyright 2010 ABB

ABB Technology Ltd 2GHV016000 D

1 2 3 4 5 6 7 8 9 10 11 12
Pro/Engineer-Drawing