You are on page 1of 6

Analysis of Harmonics with Renewable Energy

Integration into the Distribution Network


1
GM Shafiullah, 2Amanullah MT Oo
1
School of Engineering and Information Technology, Murdoch University, Australia
2
School of Engineering, Geelong Waurn Ponds Campus, Deakin University, Australia
1
Email: g.shafiullah@murdoch.edu.au

Abstract Integration of large-scale renewable energy (RE) system, in which the total impact of high penetration of PV
sources in particular, wind and solar energy into the grid was evaluated. Results showed that 37% penetration of PV at
introduces current and voltage harmonics due to power Gardner was achieved without any significant problems.
electronics devices as well as inverter connected into the RE Asano et. al. [6], analyzed the impact of high penetration of
sources. Ensuring adequate harmonics in the line currents of RE
PV on grid frequency regulation which responds to short-term
integrated power system is one of the biggest challenges today.
Therefore, this study investigates the potential impacts in irradiance transients due to clouds. It was shown that break-
particular current and voltage harmonics causes due to large- even cost of PV is unacceptably high unless PV penetration
scale integration of RE into the Berserker Street Feeder, reaches 10% or higher. Therefore, PV integration needs to be
Frenchville Substation under Rockhampton distribution increased and impacts to be identified and mitigated.
network (DN), Central Queensland, Australia. From the model Characteristics of harmonics injected into a wind energy
analyses, it has clearly evident that harmonics across the integrated power system were investigated with variety of
network increases with the increase of RE integration and configuration and operating condition [7 - 10]. Muljadi et al.
causes uncertainties in the feeder as well as in the DN. This [9] explored the characteristics of self-excitation and
study also explores possible mitigation measures and it has seen
harmonics generated by a fixed-speed induction generator
that optimized STATCOM effectively reducing the adverse
harmonic impacts of integrating large-scale RE into the DN. used in wind turbine generation. The tap changer, capacitor
compensator, the power factor, and the level of generation of
Index Terms Distribution network; Harmonics; Renewable the wind turbine all influence the intensity of saturation as
energy; STATCOM. well as the characteristics and amount of the harmonic source
injection. Power quality behaviors, in particular voltage sags
I. INTRODUCTION and harmonics injection into the network, were investigated in
a study [10] on integrating wind energy into low voltage and
The intermittent nature of renewable energy (RE) sources,
medium voltage networks. A static synchronous compensator
in particular solar and wind energy, has an impact on system
(STATCOM) based control mechanism is used to reduce the
operations including voltage and frequency, harmonics and
power quality problems as well as harmonics on integrating
power quality (PQ) in general, and influences the overall
renewable energy into the grid. From literature, it was evident
performance of the power network as well as the distribution
that STATCOMs are superior compared to other mitigation
network (DN). Inverters connected with RE sources, non-
methods such as static var compensator (SVCs) and series
linear customer loads and power electronics devices introduce
saturated reactors, STATCOMs being faster, smaller and
harmonics in the distribution network that causes overheating
having better performance at low-voltage conditions [11 - 13].
of transformers, tripping of circuit breakers, and reduces the
From the literature, it is observed that most of the available
life of connected equipment [1 - 4]. Therefore, harmonics is
research was carried out primarily in US and Europe [5 10].
one of the most dominant attributes that need to be kept in a
However, Australian distribution network is different
minimum level to ensure PQ of the network. Significant
compared to other developed countries in many forms in
research and development works are undertaken by various
particular, geographical location, weather conditions and
agencies throughout the world to investigate and mitigate
population density. Therefore, research conducted by other
harmonics in power system networks. The Gardner MA PV
countries could not simply be adopted without further research
project [5] explores four areas: the effect on the system in
in Australian context. Moreover, most of the research
steady state and during slow and cloud transients; responses of
considered for small-scale RE penetration in a small network.
concentrated PV under fast transients; harmonic effects on the
This study developed a model that investigates the observed
PV system; and the overall performance of distribution
potential challenges in particular harmonics injection into the [16] in which it was indicates that reasonable solar power is
grid using power system simulator PSS SINCAL [14]. The only available from 7:30am to 5:30pm, while peak solar
Berserker Street Feeder, Frenchville Substation, radiation is at 12:30pm. Hourly average summer wind speed
Rockhampton, was selected as a suitable site for investigation of Rockhampton, Australia is used for load flow analysis.
of large-scale deployment of RE into the grid. By increasing
PV/wind integration into the network, the points at which TABLE I. CONNECTED LOAD IN DIFFERENT ZONES
distributed generation starts to have an impact on utility grid Zone Name Conventional Load Connected
operations has investigated with regards to network Name Centre Load,
or Node kVA
performance standards. Worst-case scenarios were identified
Number
and measures were taken to reduce the level of adverse Observation Zone 1 Zone 1 8 1175.07
harmonics impacts. Observation Zone 2 Zone 2_Feeder 1 7 761.584
II. MODEL DEVELOPMENT Observation Zone 3 Zone 3_Feeder 1 7 910.418
Observation Zone 4 Zone 4_Feeder 2 6 826.595
To investigate the impacts of RE integration to support the
Observation Zone 5 Zone 5_Feeder 2 9 1100.81
loading of a Feeder, this study developed a model for
Berserker St Feeder, Frenchville. Berserker Street Feeder
comprises 1442 industrial and residential customers with a
connected load of 4775 kVA. A 66/11 kV transformer with a
capacity of 6250 kVA delivers power to the customer. Ergon
Energy [15] as a local distribution network service provider
(DNSP) is fully responsible for smooth delivery of electricity
to the customers in the Berserker Street Feeder.
To monitor the PQ of the Feeder, Ergon Energy installed
an EDMI MK 10 PQ meter (PQ metering site 1689) in the LV
side of the transformer (TX: 20127) on Berserker Street
Feeder, Frenchville Substation. This PQ meter measures phase
voltages with angles, phase unbalance condition and voltage
harmonic distortion of the zone feeders. This case study
initially explored the PQ meter data and analyses the potential
PQ issues with their level of impacts on the feeder as well as
in the DN. Currently only 1% PV of total loading is integrated Figure 1: Single-phase load and PV connection.
with the feeder and hence, these results are mostly based on
the connected customer load along with line impedances.
In line with the original network facility stated above, a
III. MODELLING CASE SCENARIOS
66/11kV step-down transformer with a capacity of 6250KVA
was considered in the Frenchville Substation to deliver power Considering feeder load demand and future RE integration
supply in the Feeder. The zero sequence resistance and several case scenarios were considered and accordingly
reactance of the step-down transformer is 1.29 ohm and 25.84 developed the model. Actual line length and impedances are
ohm with 8% short circuit voltage. This case study, considered for all of the studied case scenarios. The case
subdivided the feeder into two zone feeders and several zone scenarios considered in this case study are:
observation points to observe adverse harmonics effects on to x Case 1: Grid with only load.
the different points of the distribution network. Number of x Case 2: Grid with 20% PV integration as shown
load centres with connected load of each Zone is given in in Figure 2.
Table 1. x Case 3: Grid with 50% PV integration.
Three phase HV load was transformed to three single x Case 4: Grid with 50% wind integration.
phase loads with equal amount through an 11kV/415V DT as
x Case 5: Grid with 100% PV integration.
shown in Figure 1 and hence, zone wise load allocation
x Case 6: Grid with 100% wind integration.
remains the same. Single phase RE was connected in the LV
side of the DT as shown in Figure 1 and the amount of PV and x Case 7: Grid with 100% PV and 150% Load
wind depends on the percentage of load demand based on demand.
considered case scenarios. Losses until inverter and inverter x Case 8: Grid with 100% PV integration in
efficiency were considered 5% and 97% respectively both for centralised approach: Instead of distributed PV
PV and wind. connection with individual loads this case
Daily load profiles of Rockhampton for summer was used considered centralised PV connection with each
in this study in which it was shown that maximum load was of the zone observation point. The considered
measured at 2:00PM. A PV load profile was generated for this centralised installation was 100 m apart from the
study in p.u. values from the hourly average summer solar zone observation point. This centralised
radiation of Rockhampton, Australia collected from the BOM generation expected to be deliver electricity to the
local customer located around the zone voltage harmonic distortion significantly as shown in Case 8
observation point. and Case 9 for PV and wind energy respectively. Voltage
x Case 9: Grid with 100% wind integration in harmonic distortion is less in Case 10 compared to Case 4 and
centralised approach: In this case centralised wind Case 6, though 200% RE of total loading was integrated in
generation was considered into the feeder and this case (100% PV in a decentralized approach and 100%
connected only one location in each zone. wind in a centralized approach). Voltage harmonic distortion
across the HV DN and LV DN is shown in Figure 5 in which
x Case 10: Grid with 200% RE integration in both
it can be seen that harmonic distortion approaching the
decentralised and centralised approach: In this
regulatory limits as stated in AS4777 [17] occurs across the
case, 100% PV of total loading was connected LV network for Case 4, Case 6 and Case 7, while being within
with decentralised connection and 100% wind of the safe limits in the HV DN. Case 2, Case 3 and Case 5 have
total loading was connected with centralized the same system configurations except for the level of PV
connection approach. integration, and total voltage harmonics distortion in the LV
network for Case 2, Case 3 and Case 4 are 2.56%, 2.83% and
3.16% respectively.

Figure 2: PV integration with the Feeder.

IV. RESULTS ANALYSIS


The total voltage harmonic distortion of Berserker Street
Feeder in summer and winter was measured based on the Figure 3: Voltage harmonic distortion from EDMI meter.
collected EDMI PQ meter data. It was shown that total voltage
harmonic distortion in the month of January (summer) is 1.8% Harmonic current is of most concern as most of the
as shown in Figure 3, while in the month of July (winter) it is adverse effects in the distribution network are caused due to
2.0%. The model developed with case scenario one (Case 1) these currents. From the simulation results it is clearly
considers only load with grid connection; hence model results indicated that current harmonics increase with the increase of
of this case can be compared with the PQ meter results. Total RE integration into the Berserker Street Feeder as well as into
voltage harmonic distortions for summer in different the DN. Total current harmonic distorion at different
observation nodes in the feeder were investigated and it was observation zone points is shown in Figure 6 in which it is
shown that THD across the Zone Transformer (ZT) clearly indicated that harmonic distotion increases with the
transformer is 1.75% and across the Zone 3 Feeder 1 is 1.72%. increase of PV array utlisation. Case 2, Case 3 and Case 5 are
Therefore, it can be stated that observed THD is almost the same conditions except for variations in the level of PV
identical to the THD obtained from collected data and the
integration into the network. THDs for Case 1, Case 2, Case 3
model results were validated by the real live EDMI meter data
and Case 5 are 3.02%, 3.71%, 5.49% and 8.42% respectively
with negligible error. This study further explored the THD of
the Feeder considering different RE integration and load across the Zone Transformer in which Case 5 exceeded the
demand. regulatory standard limit as shown in Figure 6. From the
figure, it can be clearly stated that current harmonic distortion
Voltage harmonic distortion of different studied case is higher for wind (Case 6) compared to same amount of solar
scenarios are shown in Figure 4 in which it is evident that PV (Case 5) integration. Current harmonic distortion for Case
voltage harmonics in different observation points increase 7 is reduced to 6.9% due to increased load demand. Current
with the increase of RE integration and load demand. Voltage harmonic distortion was reduced in the case of centralised PV
harmonics increases with the increase of PV generation into connections (Case 8) compared to decentralised PV
the Feeder as shown in for Case 2, Case 3 and Case 5.
connections (Case 5). 200% integration of total loading (Case
Harmonic distortion is also increased with the increase of load
10) reduces current harmonic distortion as this system
demand as shown for Case 7 compared to Case 5 (both Case 5
and Case 7 have the same amount of PV connections). generates more power than the household load demand and
Voltage harmonic distortion increases significantly with the causes reverse power flow in the system. Therefore, current
integration of wind turbine into the feeders compared to solar harmonic distortion at most of the observation points is within
PV integration as shown in Figure 3 for Case 4 and Case 6. the safety allowable limits as shown in Figure 6 except Case 4,
However, a centralized connection approach reduces the Case 5 and Case 6.
Figure 4: THD for studied cases.

Figure 5: THD across HV DN and LV DN.

From analysis of the results it was shown that current decentralised connection approach. It can be concluded that
harmonic distortion exceeded the regulatory limits for use of power electronic devices along with intermittent
100% PV integration and both 50% and 100% wind generation causes harmonics in the system. Therefore, this
integration. Therefore, it can be stated that wind energy study explores the possible mitigation measures that can
injected more voltage and current harmonics into the feeder potentially reduce the adverse harmonics impacts caused by
than the solar PV. Voltage and current harmonic distortion large-scale RE integration.
was less in the centralised connection approach than the

Figure 6: Current harmonic distortion of feeders.


V. OPTIMISATION MEASURES 3, Feeder 1 as shown in Figure 10. The total current
harmonic distortions across the zone transformer are 3.8%
STATCOM is the best performing device compared to and 1.39% for Base Case and Case A respectively.
other flexible AC transmission system (FACTS) devices
for reducing voltage fluctuations and harmonics as well as
improving the PQ of the DN. Therefore, this study explores
possible mitigation measures by developing a model with
STATCOM. PSS SINCAL [14] has a built in STATCOM
model with further modifications facility. This study has
developed an optimized STATCOM which was connected
in a centralized connection approach at the observation
node points and bus bars. Specifications of the
STATCOMs were selected for different observation nodes
considering load demand and RE integration levels. To
explore the mitigation outcomes, the case scenarios that had
the highest generation from RE were considered as the
Base Case.
x Base Case Grid with 100% PV in decentralized Figure 8: Berserker Street Feeder with STATCOM.
and 100% wind in centralized connection
approaches (Case Scenario 10).
x Case A STATCOM was integrated with the
Base Case.
A three-phase STATCOM was designed with 250
kVAR capacitive and 50 kVAR inductive reactive power in
which the zero sequence resistance and reactance were
assigned as 0.567 ohm and 0.453 ohm respectively as
shown in Figure 7. The lower and upper voltage limits were
considered as 95% and 105% of the rated voltage
respectively. One STATCOM was connected in each
observation node, and hence a total of five STATCOMs
were integrated with the feeder as shown in Figure 8.

Figure 9: Voltage harmonic distortion of the feeder.

Figure 7: Specifications of STATCOM for Berserker Street Feeder.

Integration of STATCOM reduces total voltage


Figure 10: Total current harmonic distortion for all cases.
harmonic distortion of the Berserker Street Feeder
significantly as shown in Figure 9 for Case A. Voltage Therefore, it can be concluded that the proposed
harmonic distortions in Zone 5, Feeder 2 are 2.61% and approach plays an active role in reducing both current and
0.71% for Base Case and Case A respectively. Voltage voltage harmonics in the Berserker Street Feeder as well as
harmonic distortions in the LV network of the feeder are in the Rockhampton power network.
3.04% and 1.13% for Base Case and Case A respectively.
The total current harmonic distortion also decreases VI. CONCLUSIONS
with the integration of STATCOM in the Berserker Street
Feeder. Integration of optimized STATCOM decreases A model was developed for Berserker Street Feeder
current harmonic distortion from 3.79% to 3.04% in Zone under the Rockhampton DN to investigate adverse
harmonic impacts on integrating large-scale RE into the [5] EPRI report (1990): EL-6754 Photovoltaic generation effects on
distribution feeders, Volume 1: Description of the Gardner,
grid. From model analyses it was shown that harmonic
Massachusetts, Twenty-First Century PV Community and Research
distortion is increases with the increased integration of RE Program, March.
into the grid. Current harmonic distortion exceeded the [6] Asano H., Yajima K., Kaya Y. (1996). Influence of photovoltaic
regulatory limits for 100% PV integration and both 50% power generation on required capacity for load frequency control,
IEEE Transactions on Energy Conversion, 11, 188-193.
and 100% wind integration, and hence it can be stated that
[7] M. Lindholm and T. Rasmussen, Harmonic analysis of doubly fed
wind energy injected more harmonics into the feeder than induction generators, Proceedings of the 5th International
the solar PV. Moreover, harmonic distortion decreases in Conference on Power Electronics and Drive Systems (PEDS),
the centralized connection approach compared to Hammel, Denmark, 17 - 20 November, 2003.
[8] S. A. Papathanassiou and M. P. Papadopoulos, Harmonic analysis
decentralized connection. This study updated the model
in a power system with wind generation, IEEE Transactions on
with optimized STATCOM to explore suitable mitigation Power Delivery, vol. 21, pp. 2006-2016, October 2006.
measures and from the analyses it was evident that the [9] E. Muljadi and C. P. Butterfield, Self excitation and harmonics in
updated model reduces the total voltage and current wind power generation, Proceedings of 43rd AIAA Aerospace
Science Meeting and Exhibit, Reno, Nevada, 10-13 January, 2005.
harmonic distortion significantly. The outcome of the study
[10] E. Vilchez and J. Stenzel, Wind energy integration into 110 kV
expected to be used as a guideline to the utilities for system impact on power quality of MV and LV networks,
integrating large-scale renewable energy sources into the Proceedings of 2008 IEEE/PES Transmission and Distribution
grid as well as developing a sustainable power system. Conference and Exposition, Latin America, 13 15 August, 2008.
[11] A. Sannino, J. Svensson, T. Larsson, Power-electronic solutions to
power quality problems, Journal of Electric Power System
Research, ELSEVIER, vol. 66, pp. 71-82, 2003.
REFERENCES [12] V. Yuvaraj, S. N. Deepa, A. P. R. Rozario and M. Kumar,
[1] A. A. Latheef, D. A. Robinson, V. I. Gosbell, V. Smith, Harmonic "Improving Grid Power Quality with FACTS Device on Integration
impact of photovoltaic inverters On low voltage distribution of Wind Energy System", Proceedings of 5th Asia Modelling
systems, Proceedings of the 12th International Conference on Symposium (AMS), Kuala Lumpur, Malayasia, 24-26 May, 2011.
Harmonics and Quality of Power, Lisbon, Portugal, 1 5 October, [13] A. M. S.Yunus, M. A. S. Masoum, and A. Abu-Siada, Effect of
2006. STATCOM on the low-voltage-ride-through capability of type-D
[2] GM Shafiullah, A. M. Oo and A. Stojcevski, Voltage regulation in wind turbine generator, Proceedings of IEEE PES Innovative
renewable energy integration into thy distribution network, Smart Grid Technologies Conference (ISGT), Perth, Australia, 13-
Proceedings of the Australasian Universities Power Engineering 16 November, 2011.
Conference (AUPEC), Hobart, Tasmania, Australia, 29 Sep. 3 [14] PSS SINCAL, PSS Product Suite, Siemens, [Online Available]:
Oct., 2013. http://www.energy.siemens.com/us/en/services/power-transmission-
[3] Eltawil M. A., Zhao Z.(2010). Grid-connected photovoltaic power distribution/power-technologies-international/software-
systems: Technical and potential problems A review, International solutions/pss-SINCAL.htm.
Journal of Renewable and Sustainable Energy Review, ELSEVIER, [15] Ergon Energy. A local Queensland based Distribution Company,
14, 112-129. [Online Available]: http://www.ergon.com.au.
[4] GM Shafiullah, Amanullah M. T. Oo, S. Ali, and P. Wolfs, [16] Bureau of Meteorology, Weather Data, Australian Government,
Integration of roof-top solar PV systems into the low voltage Melbourne, [Online Available]: http://reg.bom.gov.au/.
distribution network, vol. 6, issue 3, 2014, Journal of Renewable [17] Standards Australia, AS 4777, Grid connection of energy systems
and Sustainable Energy, AIP via inverter, 2005, [Online Available]: http://www.saiglobal.com.

You might also like