Reprinted with permission from the April 2012 issue

How To Manage Grid the plant must facilitate grid recovery


with the resources available.
Specifically, utilities are requiring a
Impact As Solar number of grid integration features,
including voltage and frequency ride-

Deployment Increases
through, voltage control through
reactive power, and smoothing or lev-
eling of output power during sudden
changes in energy production.
Modern PV inverters can handle some grid stability tasks, This last feature is the most difficult
but energy storage may also be required. to accomplish and is typically only
achieved with battery storage. Regula-
tors are also interested in harmonics,
b Kleber Facchini which meant that some issues related voltage flicker and potential electro-
to grid interconnection magnetic transients produced by the

A s solar projects become bigger


and more numerous, grid inter-
connection issues become increas-
were not apparent. For
example, traditional
power plants typically
solar plant. In addition, they are look-
ing to understand how the plant will
manage when exposed to such events
ingly important. When the level of use conventional syn- by connecting to the grid.
solar penetration is low, the ability chronous generators. Kleber Facchini
of a solar plant to impact the grid is Such generators easily Beyond inverters?
minimal, but as solar power contin- provide reactive power and are able to Either a system impact study or a
ues to expand, the potential for grid actively manage voltage dips, sags and grid interconnection study is typically
impact increases. swells. the first step toward both understand-
In the first three quarters of 2011, In the same way, renewable power ing a solar plants potential impact on
the U.S. solar market installed more also needs to provide some level of the grid and meeting the utilitys re-
than 1 GW of grid-connected pho- voltage and frequency ride-through quirements. It also determines the ap-
tovoltaics and exceeded its 2010 total or spinning reserve to prevent power proach that needs to be taken by the
of 886 MW, according to data from disturbances from adversely affecting solar project developer for meeting the
the Solar Energy Industries Associa- the grid. utilitys requirements.
tion. This brings the total U.S. grid- At the same time, solar project In some cases, controls installed
connected PV installations to more developers are also looking for grid in the solar inverter are enough to
than 3 GW - ten times the size of U.S. parity, which means avoiding unneces- meet utility requirements. However,
solar capacity in 2005. Much of this sary equipment costs. How do project if there is a high penetration of re-
2011 growth was driven by a number developers and grid operators un- newables, more complex solutions
of utility-scale project completions. derstand the potential impact on the may be needed, and the use of some
As more PV installations are de- grid? What equipment is necessary to grid-tied storage may be necessary to
veloped and integrated into the grid, support grid interconnection without meet utility ramp-rate requirements.
utility companies and independent jeopardizing progress toward reduc- A system impact study typically
system operators need to make sure ing costs? Understanding these issues includes three components: a steady-
these projects are connecting in a way is key as more solar power and other state or load-flow analysis, a transient
that avoids power disruptions. As a renewables come online. analysis and a harmonics study.
result, there is increasing regulation New grid interconnection require- By methodically analyzing these
on connecting solar power (and other ments have a similar theme across the three areas, power system engineers
renewable energy sources) to the grid. U.S.: Projects must avoid creating is- determine how much reactive support
For many years, conventional sues on the grid, and if disturbances is needed, how to supply that support,
sources of energy were the dominant do occur - even if the disturbance is the ability of the plant to ride through
presence in the electrical network, not caused by a renewable source - transient disturbances, and the quality
Subscription information is available online at www.solarindustrymag.com. Copyright 2012 Zackin Publications Inc. All Rights Reserved.
Voltage Ride-Through Time Duration Curves Voltage events are more understood
today than ever before, and the re-
1.4 sources to deal with them are applied
1.3 to solar (and wind) plants across the
1.2 U.S. Additionally, inverters are becom-
1.1 ing smarter and some vendors have
1.0 incorporated some of the controls
No Trip
POI Voltage (PU)

0.9 needed for this type of support.


Zone
0.8 Determining where a frequency dis-
0.7 turbance is originating at the POI is
0.6 key. For example, is the disturbance
0.5
coming from the plant? Or, is it being
0.4
imposed by the grid? If a frequency
0.3
disturbance comes from the grid, usu-
0.2
ally the plant is asked to ride through
0.1
these events and not trip offline. If a
0.0
-1.0 0.0 1.0 2.0 3.0 4.0 plant trips offline, the frequency dis-
turbance will often worsen.
Time (seconds)
On the other hand, if disturbances
High Voltage Duration Low Voltage Duration
occur from the plant to the grid, due
The North American Reliability Corp.s (NERC) requirements for voltage ride-through
to the inherently intermittent nature
of PV energy, there is an expectation
Source: Eaton Corp.
(not yet widely enforced) that the
of the power produced by the solar devices or the solar inverter itself can PV plant will have the resources to
plant. supply the needed VAR support. mitigate these events. This scenario
Load-flow analysis is often per- The best choice varies from plant to is more evident on high-penetration
formed in the early stages of the plant plant, and is highly dependent on plant cases, and that is where the use of en-
design and usually done by a consult- size, point of interconnection (POI) ergy storage is often most needed.
ing firm or equipment vendor with and grid requirements. That said, there An energy storage device is often
robust power engineering experi- is an increasing pressure on inverter connected in shunt with the solar
ence. The goal is to understand how suppliers to have extra current capabil- plant at the collector bus. It injects
much reactive support needs to be ity for VAR support. Once the strategy or absorbs power on a transient basis
installed in the solar plant to meet is chosen and drawn, the utility per- in order to smooth the output power
the power factor or voltage control forms a system impact study to deter- of the plant. Although energy storage
requirements. mine how the solar plant affects the equipment is not typically able to keep
The first task is to determine - or, grid it is connected to. output power constant during long
at least, estimate, depending on how periods of time, it is able to slow down
early the project is in the design pro- Frequency disturbances the positive or negative power rate of
cess - the collector bus configura- For utility-scale solar plants, a dy- change (mainly the latter).
tion. This process requires specific namic or transient performance analy- This acts as a shock absorberand
engineering data on cables, step-up sis must also be performed. This study, avoids these ramp-rate issues on the
transformers and switchgear. Once which is done after the initial con- grid. This mechanism is particularly
this configuration is finalized, the figuration of the plant is established, important in weak grid situations,
equivalent impedance is calculated, determines if plant equipment and such as where there is a high penetra-
such that the reactive losses in the col- configuration meet the transient re- tion of solar power or the local grid is
lector bus are understood. quirements imposed by the regulators. relatively small.
With the reactive losses deter- During this study, the designer sim- Advanced solar inverters for utility-
mined and a power factor require- ulates voltage and frequency distur- scale applications are equipped with
ment established by the utility, the bances on the POI to check the plant algorithms to control the positive rate
designer can start to develop a strat- response. Will the plant trip offline of change in PV power and curtail
egy for reactive power or volt-ampere during grid disturbances? Or, will it be output power when grid frequency in-
reactive (VAR) compensation. Of- able to stay online and help the grid to creases. Such conditions are indicative
ten, static synchronous compensator recover from voltage and frequency of excess power on the grid.
(STATCOM) devices, shunt switched excursion events? However, when a cloud rolls over a
Subscription information is available online at www.solarindustrymag.com. Copyright 2012 Zackin Publications Inc. All Rights Reserved.
Reactive Characteristic Curve in a specific installation and whether
its energy storage capacity is required
50.0 to meet utility requirements and/or
maximize energy harvest.
25.0
Reactive Power (MVAR)

Current harmonics
0.0
In addition to the load-flow study
and transient study, a harmonic analy-
sis needs to be performed in order to
-25.0 0 100 200 300 400 minimize resonances within the plant
electrical installation. Within the plant,
-50.0 there are many components (cables,
transformers, shunt switched banks
and other reactive elements) that, to-
Active Power (MW) gether, can resonate with one another
A solar plants reactive characteristic curve, based on VAR requirements and the plants capabilities and create harmonics within the sys-
tem. Additionally, inverters inherently
Source: Eaton Corp. create current harmonics at the collec-
tor bus, due to the internal switching
Off Nominal Frequency Capability Curve of the converter insulated gate bipolar
transistor.
65
If the system is not well tuned, the
64
presence of excessive current harmonics
63
may force solar inverters to trip offline
62
and cause unnecessary heating (and
Frequency (Hz)

61 losses) on cables and transformers. The


No Trip
60 Zone situation is worse if there are existent
59 background harmonics on the grid.
58 The proper way to mitigate har-
57 monics is by first identifying the back-
56 ground harmonics on the grid (if any),
55 and then running the electrical model
0.01 0.1 1 10 100 1,000 10,000
of the plant to identify potential har-
Time (seconds) monics and resonances. If these are
The NERCs requirements for frequency ride-through found, the designer can use de-tuning
filters at the collector bus, so that the
Source: Eaton Corp.
harmonics are attenuated.
At the solar inverter level, it is im-
solar plant, power generation drops load - deferring the cost of bringing portant to understand the impact
significantly and, in some cases, on additional power services. that background harmonics have on
abruptly. A solar plant with no en- In this case, energy is stored dur- the inverters AC filter, which acts to
ergy storage can adversely impact the ing peak power production and re- filter harmonics and, in the process,
grid POI, possibly causing voltage and leased during peak demand. When draws them to clean the electrical
frequency dips. This is worsened in load shifting is implemented, solar line. Therefore, the AC filter of an in-
regions with significant renewable power is stored mid-day and released verter connected to a harmonic-rich
toward the end of the afternoon (and grid will overheat and fail over time.
power and small amounts of spin-
wind energy is stored during the Assessing the harmonics both in the
ning reserves.
night and released in the morning or system and on the grid is key to ex-
In addition to mitigating tran- afternoon). tending equipment life.
sient power variances, energy stor- The application of energy storage is Integrating renewable energy into
age devices are also used to shift peak determined by the grid requirements. the grid requires an understanding of
power. They are able to absorb power If there is a need, the system impact the equipment and plant power sys-
that is otherwise limited by the power or grid interconnection study helps to tem, utility regulations and the nature
rates set by utilities, or to level the determine the role of energy storage of the grid itself. As utility-scale solar
Subscription information is available online at www.solarindustrymag.com. Copyright 2012 Zackin Publications Inc. All Rights Reserved.
power continues to grow, it is crucial are expecting renewables to act more implementation are able to provide
that a comprehensive system impact like conventional power plants and cost and time savings, information
study is performed and steps are taken provide grid support - with both re- transparencies and simplified main-
tenance. From the grid interconnec-
tion study to the final implementation
If the system is not well tuned, the presence of excessive and maintenance of the equipment, a
single supplier can simplify and expe-
current harmonics may force solar inverters to trip offline dite the process - so that the project
and cause unnecessary heating (and losses) on cables and developer minimizes installation cost
and maximizes energy harvest, while
transformers.
meeting utility regulations to support
grid stability. R
to prevent grid instability - avoiding active and real power. In this envi-
possible power outages. Further, equip- ronment, developers and designers
ment tapped for utility-scale solar ap- of solar plants may seek project part- Kleber Facchini is the product manager for
plications should be able to identify ners that have a holistic approach to commercial- and utility-scale solar invert-
ers for Eaton Corp., a diversified power
grid disturbances and respond to such utility needs, as in the end, they need
management company with more than 100
events in a way that will enhance volt- the utilitys approval for a solar plant
years of experience providing energy-effi-
age and frequency regulation. installation. cient solutions. Facchini can be contacted
In other words, as solar and wind Organizations able to provide at klebervfacchini@eaton.com.
come online at a faster pace, utilities equipment, analysis and project