General NTPF100
Specications Exaopc
OPC Interface Package
GS 36J02A10-01E

GENERAL FUNCTION SPECIFICATIONS


As data sharing between information systems Exaopc supports the following OPC specications:
increases, the requirement to efciently access
and use plant information to meet business needs Data Access (DA) Server Function
in a timely manner also increases. Within the
The DA Server reads and writes process data using
process industry, the control room contains valuable
item IDs as identiers.
information that has previously been inaccessible.
Exaopc was created to provide an open OPC (OLE for
Process Control) interface bridge between the control Alarms & Events (A&E) Server Function (*1)
room and the outside world. The A&E Server provides alarms and events from
Exaopc is an OPC server running on a Microsoft plants that occur asynchronously. The following
Windows platform which can be connected to a variety messages are available from Yokogawa DCSs:
of PCSs (Process Control Systems) providing OPC - System alarm messages
clients with process data and alarm events. - Process alarm messages
- Mode/status change messages
This GS contains the specication for the Exaopc
- Sequence messages
OPC Server Interface Package.
- Operation guide messages
- Engineering maintenance messages
- Operation record messages
- Server internal errors

Historical Data Access (HDA) Server


Function
Exaopc automatically saves instantaneous values
acquired from the DA Server and A&E Server, to an
HDA historical database. The OPC client can access
historical data by rst connecting to the HDA Server.

Batch Server Function


[VP Batch(*3), CS Batch 3000]
(Exaopc R3.01 or later)
The Exaopc batch server function (Exaopc/Batch)
reads and writes batch data and its related information
with VP Batch and CS Batch 3000.

OPC Security Interface


(Exaopc R2.10 or later)
Exaopc provides security by using an OPC Security-
compliant interface whenever an OPC Client uses the
DA, A&E and/or Batch servers.
*1: Alarms & Events function does not support for
Consolidated Alarm Management Software
(CAMS) for HIS.
*2: OPC client is dedicated to Exaquantum/Batch.
*3: Exaopc R3.60 or later.

Yokogawa Electric Corporation GS 36J02A10-01E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright June 1999 (YK)
Tel.: 81-422-52-6375 Fax.: 81-422-52-5994 26th Edition Jan. 31, 2011 (YK)
<<Contents>> <<Index>> 2
GENERAL CONFIGURATION
OPC Client

Exaopc

<Server Common>
Exaopc DA Server Exaopc HDA Server Exaopc A&E Server Exaopc Batch Server

Exaopc Historical Exaopc Exaopc


DA Server Common Database A&E Server Common Batch Server Common

DA A&E Batch
I/O Cassette I/O Cassette I/O Cassette
<I/O Cassette>

PCS

OPC Interface Process Data Engineering Data


Event Batch Data/Batch Information PCS: Process Control System
F01E.ai

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Sep. 13, 2004-00
<<Contents>> <<Index>> 3
FEATURES
Major Applications Security
The Exaopc OPC Interface can be used in a wide [CENTUM VP (*1)/CS 3000/CS 1000/CS]
variety of OPC client applications. Exaopc security (account, scope of monitoring,
- Yokogawa packages, including Exaquantum PIMS operation ID, operator console group and access level)
and Exapilot (Operation Efciency Improvement is dependent on the CENTUM.
Package)
- OPC standard compliant general-purpose Trafc Control
applications
When an OPC client attempts to access a large volume
- User applications created using VB or VC++
of data from a CENTUM CS system loading problems
Compliance with OPC Specications may occur (load concentration on control stations and
control buses, in particular). To prevent problems,
The Exaopc package supports OPC standard interface access from OPC clients are restricted to avoid the
functions (DA/A&E/HDA, Batch, Security) specied by maximum accessible data rate being exceeded.
the OPC Foundation, and additional functions such as
data item browsing.
Expanded Test Functions
[CENTUM VP (*1)/CS 3000/CS 1000]
Exaopc supports Compliance Test Tool
(Supported by Exaopc R1.10 or later)
(CTT) [CENTUM VP/CS 3000/CS 1000]
(Exaopc R3.50 or later) By connecting to the Expanded Test Functions on
CENTUM VP/CS 3000/CS 1000, users can access the
Exaopc supports Compliance Test Tool (CTT) provided FCS simulator on a station with CENTUM VP/CS 3000/
by the OPC Foundation. (Custom Interface for DA3.0, CS 1000 engineering functions. Therefore, users can
DA2.05a, A&E1.10, or HDA1.20) perform engineering and testing OPC clients without
Note: On CTT Compliance mode, some functions of using actual FCSs.
Exaopc R3.21 or earlier version may not operate.
If OPC client is Exaquantum, Exapilot, Exasmoc,
or Exarqe, the conventional mode should be Multiple Project Connection
used. [CENTUM VP (*1)/CS 3000]
When use DA3.0, the CTT Compliance mode (Supported by Exaopc R1.20 or later)
should be used.
On Exaopc, users can use Multiple Project Connection
Connectivity with CENTUM Systems functions for CENTU VP/CS 3000, which enables
integrated monitoring of multiple projects. This allows
Exaopc can be connected to Yokogawa CENTUM users the ability to handle CENTUM VP/CS 3000/CS
VP/CS 3000/CS 1000/CS DCSs. 1000/CS project data on Exaopc as well as the data
from their own project.
I/O Cassette To use these functions, the supervisory CENTUM VP/
Exaopc consists of two layers: Server Common Part CS 3000 system requires a Multiple Project Connection
for user interfaces and common processing, and Package.
I/O Cassette Part for processing by the connected Function specications, restrictions, and the operational
PCSs. Connection with new target systems can be environment for these functions are the same as for
implemented by creating an Exaopc I/O Cassette. CENTUM VP/CS 3000. See GS 33M05K20-40E/GS
33Q02S10-31E LHS5450/LHS4450 Multiple Project
Automatic Backup Connection Package for further information.
The process data acquired by the DA server is
automatically saved and stored in the historical Viewer Function and Tool Function
database as backup data. Access to the stored data is These functions provide various kinds of viewer and
enabled by the HDA server function. tool to check and monitor Exaopc operation status.
Software Conguration Viewer, Station Viewer (only
Equalization when connected to Vnet/IP or V net),
[CENTUM VP (*1)/CS 3000/CS 1000/CS]
OPC Connection Conrm, Exaopc Server Monitor
A list of tags in CENTUM can be equalized by Exaopc.
*1: Exaopc R3.50 or later.
When function blocks (tags) are added, deleted or
changed in the FCS builder and they are loaded, a
IT Security support (Exaopc R3.60 or later)
change notication is sent to Exaopc. Exaopc will then
update function block data based on the received data. Several security models (standard, strengthened,
and legacy types) are available for users to select the
Browsing suitable security level.
[CENTUM VP (*1)/CS 3000/CS 1000/CS]
Users can view the content of the OPC server from
OPC client. The OPC client can access CENTUM tag
list Exaopc acquired by Equalization functions.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
<<Contents>> <<Index>> 4
CONNECTED SYSTEMS
System Connection Method Communication Method
CENTUM VP (Including Entry Class)
CENTUM CS 3000 (Including Entry Class) Directly connected to VI702/VF702/VI701/VF701
Vnet/IP or V net
CENTUM CS 1000 Control Bus Interface Card
CENTUM CS
PCS from other vendors Depends on each specications (*1) Ethernet

*1: Please contact us.

SYSTEM CONFIGURATION
Server/Client Composition
The following two client/server congurations can be used:
- The OPC client exists on a PC with Exaopc installed.
- The OPC client exists on a supervisory computer (Windows PC).

Multiple Clients
A single Exaopc can be accessed from multiple OPC clients.

Multiple Servers
Users can access multiple Exaopcs from a single OPC client.

Duplicated OPC Server Conguration (Exaopc R3.01 or later)


Exaopc-RD (installed on the OPC client machine) supports OPC Server redundancy by monitoring two Exaopc
servers and automatically switching from the Master to the Standby Exaopc server if the Master becomes unavailable.
Please contact Yokogawa for additional information.

Client PC
OPC Client (*1)
OPC Interface
Process Data Acquire/Setting
OPC Server
Redundancy Function
(Redundant DA, Redundant A&E, Redundant HDA)

Ethernet Ethernet

Master OPC Server 1 OPC Server 2 Standby


Exaopc Redundant Exaopc
(DA, A&E, HDA) (DA, A&E, HDA)

Control Network

CENTUM

*1: OPC client is dedicated to Exaquantum or Exapilot.


F04E.ai

Figure: Conguration Example for Duplicated OPC Server

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
<<Contents>> <<Index>> 5
CENTUM VP/CS 3000/CS 1000/CS System Conguration
- Exaopc is directly connected to the DCS control buses using the VF702/VF701 Control Bus Interface Card to
communicate with control stations. This provides Exaopc with the ability to read and write tag data and receive
process messages.
- Exaopc automatically equalizes engineering data from the CENTUM ENG/EWS Engineering Station.
- Multiple Exaopc servers can be connected to one CENTUM system. Those servers are counted as control bus
stations equivalent to HIS/ICS on the system.
- Please congure the entire system considering the CPU loading of the control stations and the bus loads of the
control buses.
- Exaopc for VP Batch and CS Batch 3000 can be connected to VP Batch and CS Batch 3000 packages.
- Connection to CENTUM VP Entry Class and CS 3000 Entry Class is similar to that of CENTUM VP/CS 3000.
.

Application PC
(OPC Client)

Ethernet

HIS ENG

Exaopc
(OPC Server)
Control Network

LFCS LFCS

OPC Interface
Process data
Engineering data
F02E.ai

Figure: Conguration Example for CENTUM VP/CS 3000

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
<<Contents>> <<Index>> 6
APPLICATION CAPACITY
OPC Server
Item Application capacity
function
A number of clients (A number of server objects) 100 clients
A number of groups (A number of group objects) 1000 groups
10000 item IDs/group
DA Server A number of Item IDs
100000 item IDs/all groups
Cache update period (Data gathering period) 1 to 3600 sec
Max. throughput of data access (*1) 2000 item IDs/sec (CENTUM VP/CS 3000/CS 1000/CS)
A number of clients (A number of server objects) 100 clients
A&E Server
(*2) Max. number of event-registered objects
1000 objects
(Max. number of event subscription objects)
A number of clients (A number of server objects) 100 clients
100 browser/server object
A number of browser (A number of browser objects)
HDA Server 10000 browser/all server objects
(*3) A number of item IDs 100000 item IDs/server object
Not restricted (Depends on disk capacity, its area is dened
Max. historical data save period (*4)
with a Record parameter)
A number of clients (A number of server objects) 100 clients
A number of groups (A number of group objects) 1000 groups
Batch Server
10000 item IDs/group
A number of item IDs
100000 item IDs/all groups

*1: It depends on the conditions of the project and the application.


*2: On Exaopc, process alarms are treated as condition events. A table is provided to manage process alarm occurrence,
ACK and recovery events. In case of overow on the table due to numerous process alarms, the OPC client will receive the
process alarm occurrence events only. DCS will receive a system alarm to notify the overow situation on the table.
*3: If the data requests for a HAD are more than 20000 ItemIDs (2880 default recodes per each ItemIDs), the response may
take a long time. It may be necessary to use one or more Exaopc. (Example: the phenomenon may occur when using the
catch up function of Exaquantum.)
*4: The PC performance may be inuenced when the number of records increases from the default value.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Apr. 1, 2010-00
<<Contents>> <<Index>> 7
OPERATING ENVIRONMENT
Hardware
Machine: IBM PC / AT -compatible (DOS/V)
For Windows Vista and Windows Server 2008:
CPU:
Minimum: Intel Pentium 4 2.8 GHz
Recommended: Core 2 Duo 2.13 GHz or faster
Memory:
Minimum: 1 GB
Recommended: 2 GB or more
Disk:
Minimum: 10 GB free space
Recommended: 40GB free space or more

For Windows XP and Windows Server 2003:


CPU:
Minimum: Intel Pentium 800 MHz
Recommended: Core 2 Duo 2.13 GHz or faster
Memory:
Minimum: 256 MB
Recommended: 2 GB
Disk:
Minimum: 4 GB /Free space of 1 GB
Recommended: of 40 GB free space or more

Communication device:
Ethernet-ready network card
To connect to CENTUM VP/CS 3000/CS 1000/CS with Vnet conguration
NTP//VF702 Control Bus Interface Card
The 3.3 V PCI-Express specications apply to VF702 style S1.
NTP//VF701 Control Bus Interface Card
The 5 V PCI specications apply to VF701 style S2. (The PCI power supply of the PC must support 5
V DC specications.)
The 5 V PCI, 3.3 V PCI or 3.3 V PCI-X specications apply to VF701 style S3.
NTP//YCB141 V net Cable (10Base-2 cable)
NTP//YCB147 Control Bus Adapter
NTP//YCB149 Control Bus Converter Unit
NTP//YCB146 T-type Connector of Control Bus
NTP//YCB148 Control Bus Terminator
To connect to CENTUM VP/CS 3000 with Vnet/IP conguration
(CS 3000 R3.05 or later, and Exaopc R3.10 or later)
NTP//VI701 Vnet/IP Interface Card

Intel Pentium 800 MHz or greater CPU and 512 MB or greater main memory are required for Exaopc OPC Server
Redundancy (Exaopc-RD) on Windows Server 2003

Compatibility of PC extended slot, Vnet Interface Card (VF702/VF701) and Exaopc release
number [CENTUM VP/CS 3000/CS 1000/CS]
The table below shows the compatibility of the PC extended slots, the VF702/VF701 styles, and the Exaopc release
numbers.

Compatibility of PC extended slot, VF702/VF701 and Exaopc release number

PC Extended slot VF701 style S2 VF701 style S3 VF702 style S1


(PCI for 5 V) (PCI for 5 V, 3.3 V) (PCI Express)
Exaopc Exaopc Exaopc Exaopc Exaopc
R3.01.50 or R3.10 or later R3.01.50 or R3.10 or later R3.10 or later
earlier earlier
5 V, 32 bit X X X X -
PCI R2.X
3.3 V, 32 bit - - - X -
PCI-X 3.3 V, 64 bit - - - X (*1) -
PCI-Express 3.3V - - - - X
X: Available -: Not available
*1: The transfer rate of both style S2 and style S3 are 32 bit at 33 MHz.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
<<Contents>> <<Index>> 8
Software
The following lists the software requirements for Exaopc and the OPC Client connected to Exaopc according to the
Exaopc release numbers.

Exaopc release number Windows (Exaopc, OPC Client) Service Pack (Exaopc)
Windows 2000 Professional or Windows 2000 Server 4
R3.01
Windows XP Professional 1, 2
Windows 2000 Professional or Windows 2000 Server 4
R3.10, R3.11, R3.20 Windows XP Professional 1, 2
Windows Server 2003 Standard Edition 1
Windows 2000 Professional or Windows 2000 Server 4
Windows XP Professional 2
R3.21
Windows Server 2003 Standard Edition 1, 2
Windows Server 2003 R2 Standard Edition 2
Windows Vista Business Edition 1
Windows XP Professional 2, 3
R3.50
Windows Server 2003 Standard Edition 2
Windows Server 2003 R2 Standard Edition 2
Windows Vista Business Edition 1, 2
Windows XP Professional 2, 3
R3.60 Windows Server 2003 Standard Edition 2
Windows Server 2003 R2 Standard Edition 2
Windows Server 2008 Standard Edition 2

Only the latest release number of Exaopc can be purchased.


Exaopc supports only the 32-bit OS version.
The Exaopc Package and the Operating system (Windows) must share the same language environment.
(English version or Japanese version)
The OPC server redundancy function (Exaopc-RD) is supported for Windows Server 2003/2008.
Software compatibility
Software compatibility of Exaopc and CENTUM

CENTUM CS CENTUM CS 1000/CENTUM CS 3000/CENTUM VP (*2)


Exaopc R2.1x R3.04
R2.09 R3.01 R3.02 R3.03 R3.06 R3.07 R3.08 R3.09 R4.01 R4.02 R4.03
(*1) R3.05
R2.01 X X XX X (*3) X (*3) X (*3) X (*3) X (*3) X (*3) X (*3) NC NC NC
R2.02, R2.10 X X X XX X (*3) X (*3) X (*3) X (*3) X (*3) X (*3) NC NC NC
R3.01 - X XX (*4) XX (*4) XX (*4) X (*3) X (*3) X (*3) X (*3) X (*3) - -
R3.10 - X XX (*5) XX (*5) XX (*5) XX (*5) X (*3) X (*3) X (*3) X (*3) - -
R3.11 - X XX (*5) XX (*5) XX (*5) XX (*5) XX (*5) X (*3) X (*3) X (*3) - -
R3.20 - X XX (*5) XX (*5) XX (*5) XX (*5) XX (*5) XX (*5) X (*3) X (*3) - -
R3.21 - X XX (*5) XX (*5) XX (*5) XX (*5) XX (*5) XX (*5) XX (*5) X (*3) - -
X (*3)
R3.50 - X XX (*6) XX (*6) XX (*6) XX (*6) XX (*6) XX (*6) XX (*6) XX X (*3) X (*3)
(*6)
R3.60 - X XX (*6) XX (*6) XX (*6) XX (*6) XX (*6) XX (*6) XX (*6) XX (*6) XX XX X (*7)

XX: Compatible. Exaopcs Expanded Test Functions is available only with this combination.
X: Compatible, however, Exaopcs Expanded Test Functions is not available.
-: Contact Yokogawa, for the details of compatibility.
NC: Not Compatible
*1: CENTUM CS R2.1x includes R2.10, R2.11, R2.12, R2.13, R2.14, R2.15.
*2: CENTUM VP R4.01 or later.
*3: Some of the CENTUMs new functions are not available because the release of these Exaopc was preceded to the
CENTUM systems.
*4: Install Windows XP SP2 to use the Extended Test Function on Windows XP.
*5: Install the newest service packs that each Exaopc release number complies to use the Extended Test Function on
Windows Server 2003 or Windows XP.
*6: Changes in User Account setting is required.
*7: When the user authentication is set to Windows authentication mode on CENTUM, it is necessary to install Exaopc patch
R3.60.06.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
<<Contents>> <<Index>> 9
Compatibility of Exaopc Batch Server and VP Batch/CS Batch 3000/CS Batch 1000
CS Batch 3000/CS Batch 1000 VP Batch
Exaopc/Batch R3.03
R3.01 R3.02 R3.05 R3.06 R3.07 R3.08 R3.09 R4.01 R4.02 R4.03
R3.04
R3.01 NC NC X - - - - - - NC NC
R3.10 NC NC - X - - - - - NC NC
R3.11 NC NC - - - - - - - NC NC
R3.20 NC NC - - - X - - - NC NC
R3.21 NC NC - - - - X - - NC NC
R3.50 NC NC - - - - X - X - NC
R3.60 NC NC - - - - - X - X X

X: Compatible NC: Not compatible -: Contact Yokogawa, for the details of compatibility.
Exaopc Batch Server does not support Multiple Project Connection function.
Version of Visual Basic and Visual C++
The following version of Visual Basic and Visual C++ is prerequisite to develop and execute a client application.

Exaopc Exaopc and user AP are on the same PC Exaopc and user AP are on different PCs
R3.01 VB 6.0, VC++6.0 (SP6) (*1) VB 5.0/6.0, VC++5.0/6.0
VB 6.0, VC++6.0 (SP6) (*1) VB 5.0/6.0, VC++5.0/6.0
R3.10, R3.11, R3.20, R3.21
VC++ .NET VC++ .NET
R3.50 VB 6.0, VC++6.0 (SP6) (*1), VC++ .NET, VC++2005 VB 6.0, VC++6.0, VC++ .NET, VC++2005
R3.60 VB 6.0,VC++6.0(SP6)(*1), VC++ .NET/, VC++ 2008 VB 5.0/6.0 VC++ 5.0/6.0, VC++ .NET, VC++ 2008

*1: Verify in user application program, if any other versions are used.

When OPC client program that accesses Exaopc DA/A&E/HDA Server is congured with the VB application, it
is recommended to use the Exaopc Client Library of Yokogawa Solutions Corporation (model: NTPT900) for VB
programmer. The Library provides OPC connection functionality with the ActiveX component.
The recent versions for Exaopc R3.10 or later will support VB.NET development environment.
When OPC client program accesses Exaopc A&E server R3.10 or later using NTPT900, use the new version of
NTPT900 supporting Exaopc R3.10 for revision compatibility.

Installation of Multiple Exaopc


Only one Exaopc can be installed in one PC. Two or more Exaopc can not be installed in one PC.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
<<Contents>> <<Index>> 10
Limitation on coexistence of Solution-based Package (SBP)
It is called coexistent when one or more SBP products and the Exaopc are installed on a single PC.
The applicable combination of a server and client(s) for Exaopc and other SBP products are as shown below.
The release number of the other SBP products are the latest once at the release of Exaopc R3.60.

[SBP Products complied with IT Security Support]


Exapilot R3.80
Exaplog R3.30
Exasmoc R4.02
Exarqe R4.02
[SBP Products not complied with IT Security Support] (The latest release number at the publication of this
document.)
Exaquantum R2.50
Exaquantum/Batch R2.50

Other SBP products


Server Client
Exaopc
Server Case1 Case1
Client Case1 Case2

Case1: The coexistent combination of SBP products and Exaopc.

Exapilot Exaquantum Exaplog Exasmoc Exarqe


Exaquantum /Batch
(R3.80) (R2.50) (R3.30) (R4.02) (R4.02)
Exaopc
OK OK (*1) N/A OK OK OK
(R3.60)
OK: Applicable
N/A: Not Applicable
*1: Set Exaopcs IT Security as Legacy model.
Note: The applicable combinations between the latest release number of the SBP products and the Exaopc R3.60
have passed the coexistence test criteria at the issuance date of this GS.

Case2: Basically all the SBP products can coexistent with Exaopc. In case Exaopc client is resided with
Exasmoc and Exarque clients in one PC with their IT Security levels are set as standard or
strengthened types, it requires special attention for installation.
For details, please contact Yokogawa.
[ Limitation ]
- When Exaopc R3.60 resides with other SBP products, all the IT Security models must be identical.
- When Exaopc R3.60 resides with other SBP products without IT Security level setting function, set Exaopcs IT
Security as Legacy model.
- Exaquantum/Batch server and Exaopc R3.60 cannot coexist.
- Exaquantum open interface (NTPP007) and Exaopc R3.60 cannot coexist.
- When Exacuantum has a multi-server conguration, Exaquantum server and Exaopc R3.60 cannot coexist.

Remarks when connecting to other SBP via network


When Exaopc R3.60 is connected with other SBP products that can coexist (e.g. Exapilot, Exaplog, Exaquantum, and
AAASuite) via network, please pay attention if each package has its own IT security setting and the different levels of
the security models for each package.

Document Browser
- Adobe Reader 9.3
Note: It is necessary to install Adobe Reader to read document of Exaopc.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
<<Contents>> <<Index>> 11
SUPPORTED OPC SPECIFICATIONS
The Exaopc R3.60 package provides the OPC client with an interface with the following specications:

DA Server
- OPC Data Access Custom Interface Specication Version 2.05a/3.0
- OPC Data Access Automation Specication Version 2.0
- OPC Security Custom Interface Specication Version 1.0

A&E Server
- OPC Alarms and Events Version 1.10 (Exaopc R3.10 or later) (*1)
- OPC Alarms and Events Automation Specication Version 1.0 (draft)
- OPC Security Custom Interface Specication Version 1.0

*1: OPC Alarms and Events Version 1.0 had been supported by Exaopc R3.01.50 or earlier.
The specication range of the severity for the SetFilter method is changed from 0 to 1000 (A&E1.0) to 1 to 1000
(A&E1.10).
When severity=0 value is set for the SetFilter method to Exaopc A&E1.10 OPC server, an error code will be returned by
Exaopc because it is out of range.
Be sure to use A&E version compatible with both Exaopc and an OPC client accordingly.

HDA Server
- OPC Historical Data Access Custom Interface Version 1.2
- OPC Historical Data Access Automation Interface Version 1.0 (draft)

Batch Server
- OPC Batch Custom Interface Specication Version 1.0
- OPC Batch Automation Specication Version 1.0
- OPC Security Custom Interface Specication Version 1.0
Visit the web site of OPC Foundation at http://www.opcfoundation.org for OPC interfaces.

ANNUAL MAINTENANCE AGREEMENT


Annual maintenance agreement is required from the rst year. The agreement must be renewed every year. Services
by the agreement covers providing remedies for troubles and providing updated package (*2).

*2: For NTPF100-S1, -S2, -S3, -SB, -SC, when upgrading from Exaopc R3.21 or earlier to R3.50, it is necessary to download
the system conguration, tag list le, and so on generated in CENTUM system generation builders.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Apr. 1, 2010-00
<<Contents>> <<Index>> 12
MODEL AND SUFFIX CODE
Description
Model NTPF100 Exaopc OPC Interface Package
-S Basic Software License (with media)
1 For CENTUM VP/CS 3000, CENTUM VP/CS 3000 Entry Class (DA, A&E, HDA Server Functions)
2 For CENTUM CS 1000 (DA, A&E, HDA Server Functions)
3 For CENTUM CS (DA, A&E, HDA Server Functions)
Sufx Codes A For general-purpose system (*1)
B For VP Batch, CENTUM CS Batch 3000 (DA, A&E, HDA, Batch Server Functions; Exaopc/Batch) (*2)
C For CENTUM CS Batch 1000 (DA, A&E, HDA, Batch Server Functions; Exaopc/Batch) (*2)
X For OPC Server Redundancy (Exaopc-RD) (*3)
1 English version
/Y-QTM For Yokogawa OPC Clients: Exaquantum
/Y-PLT For Yokogawa OPC Clients: Exapilot (*4)
/Y-SMC For Yokogawa OPC Clients: Exasmoc
/Y-RQE For Yokogawa OPC Clients: Exarqe
Option Codes /Y-OMS For Yokogawa OPC Clients: Exaoms
/Y-CTM For Yokogawa OPC Clients: CENTUM Optional-Software
/Y-CLB For Yokogawa OPC Clients: Exaopc Client Library (for NTPT900)
/Y-TRF For Yokogawa OPC Clients: TriFellows
/Y-OTH For Yokogawa OPC Clients: Other products

*1: Consult with Yokogawa to use this Sufx Code.


*2: Dedicated to Exaquantum/Batch.
*3: Dedicated to Exaquantum or Exapilot.
*4: AAASuite (Advanced Alarm Administrator) Alarm Rationalization Assistance Package is included.

ORDERING INFORMATION
Specify model and sufx codes.

TRADEMARK
- Exaopc, Exapilot, Exaquantum, Exasmoc or Exarqe are registered trademarks of Yokogawa Electric Corporation.
- CENTUM is a registered trademark of Yokogawa Electric Corporation.
- Windows, Windows Vista, ActiveX, Visual Basic, Visual C++ are registered trademarks of Microsoft Corporation.
- Ethernet is a registered trademark of XEROX Corporation.
- Pentium, Core 2 Duo are registered trademarks of Intel Corporation.
- Adobe Reader is either registered trademakrs or trademarks of Adobe Systems Incorporated in the United States
and/or other countries.
- All other company and product names in this GS are registered trademarks or trademarks of respective companies.

All Rights Reserved. Copyright 1999, Yokogawa Electric Corporation GS 36J02A10-01E Jan. 31, 2011-00
Subject to change without notice.

You might also like