The setting list of GENERATOR-TRANSFORMER UNIT protection


(for commissioning )

1. ............................................................................................................................................................................1
1.01 -- GENERATOR DIFFERENTIAL................................................................................................................1
1.02 GENERATOR IMPEDANCE......................................................................................................................1
1.03 STATOR INTER-TURN FAULT......................................................................................................1
1.04 3U0 Stator ERP 3U0................................................................................................................1
1.06 Rotor ERP..........................................................................................................................................2
1.07 Gen. Overvoltage........................................................................................................................2
1.08 Gen Inv-T Overload............................................................................................................2
1.09 Gen Inv-T Overcurrent..................................................................................................3
1.10 Gen Reverse Power......................................................................................................................3
1.11 Gen Program Reverse Power..............................................................................................3
1.12 Start-Stop Protection..........................................................................................................................3
1.13 Gen over fluxing.........................................................................................................................4
1.14 -Gen. OverFreq Prot-........................................................................................................................4
1.15 -Gen. UnderFreq Prot........................................................................................................................4
1.16 Generator loss-of-field & out-of-step protection-..........................................4
2. ................................................................................................................................................................................6
2.01 MAIN TRANSFORMER DIFFERENTIAL(M-T DIFFERENTIAL)..................................................................6
2.02 OVER ALL DIFFERENTIAL(G-T DIFFERENTIAL)...............................................................................6
2.03 MT Comp Low V Over C................................................................................................................6
2.04 MT RESTRICTED EARTH FAULT......................................................................................................6
2.05 MT Zero-Seq Over C....................................................................................................................7
3. ............................................................................................................................................................................9
3.01 UNIT TRANSFORMER DIFFERENTIAL(U-T DIFFERENTIAL)..............................................................9
3.02 UT Comp Low V Over C............................................................................................................9
3.03 UT O.C.INSTANTANEOUS AND TIME RELAY..............................................................................9
3.04 AT OVERCURRENT................................................................................................................................9
3.05 AT Zero-Seq Over C................................................................................................................9
3.06 AT RESTRICTED EARTH FAULT................................................................................................10
3.07 AT Vetilation................................................................................................................................10
3.08 PT YH Wire Break.............................................................................................................................................10
4. ..........................................................................................................................................................................11
4.01 ET O.C.INSTANTANEOUS..........................................................................................................................11
4.02 ET OVERCURRENT......................................................................................................................................11
4.03 ET Overload........................................................................................................................................11

2
2600MW 2009 1 29

The setting list of #1 UNIT

1.


Name
PCPP
Device No. GENERATOR-TRANSFORMER UNIT protection
Protection device DGT801
model

1.01 -- GENERATOR DIFFERENTIAL


protection settings

NAME SYMBOL SETTINGS UNIT
1 Restraint coefficient Kz 0.40 A
2 Starting current Iq 1.25 A
3 Knee point current Ig 3.32 A
4 Instantaneous Differential current multiples Is 4.00 Multiples
5 Negative-sequence voltage U2 10.00 V
6 Rated current Ie 4.153 A

TRIPPING OUTPUT: TRIPPING ALL



1.
1.02 GENERATOR IMPEDANCE
protection settings

NAME SYMBOL SETTINGS UNIT
1 Forward impedance Z1F 2.60
2 Reverse impedance Z1B 3.11
3 Overcurrent Ig 4.57 A
4 Negative Overcurrent I2g 0.332 A
5 Time delay t1 1.3 s

TRIPPING OUTPUT: TRIPPING ALL



1.3U 03W
2. P2F1
1.03 STATOR INTER-TURN FAULT
protection settings

NAME SYMBOL SETTINGS UNIT
1 High setting 3U0h 7.00 V
2 Low setting 3U0l 5.00 V
3 3rd-humonic setting 3U03w 4.00 V
4 3rd-humonic setting restraint
KZ 0.50 *
coefficient
5 Time delay t0 0.20 S
6 Voltage difference U 8.00 V
7 Power operating direction P2F 1.00 *

TRIPPING OUTPUT: TRIPPING ALL



1.3U 03W
2. P2F1
1.04 3U0 Stator ERP 3U0
protection settings

NAME SYMBOL SETTINGS UNIT
1 Voltage at the generator terminal 3U0g1t 10.00 V
2 Voltage at the generator neutral 3U0g1n V
3 time delay t11 s

81 610016 86675156
2 33

TRIPPING OUTPUT: TRIPPING ALL



1.
1.05 3 STATOR EARTH FAULT
protection settings

NAME SYMBOL SETTINGS UNIT
1 Magnitude coefficient K1 K1 - *
2 Phase coefficient K2 K2 - *
3 Restraint coefficient K3 K3 - *
4 Operating time-delay t1 8.00 s

TRIPPING OUTPUT: SIGNAL



1. The setting of the magnitude and phase
coefficients should be done automatically at the no-load voltage of the generator (automatic setting method can be found in the
Operation Manual)

1.06 Rotor ERP


protection settings

NAME SYMBOL SETTINGS UNIT
1 Operating Resistance Rg1 Rg1 10 k
2 Operating time Delay t1 t1 20 s
3 leakage current I0 - mA
4 2nd-haumonic voltage setting U2wg 2 V
5 Operating time Delay t21 t21 0.5 s

TRIPPING OUTPUT:ROTOR TWO POIONT EARTH FAULT: TRIPPING ALL



1.
1.07 Gen. Overvoltage
protection settings

NAME SYMBOL SETTINGS UNIT
1 Operating voltage Ug1 130.00 V
2 Operating time t11 0.5 s

TRIPPING OUTPUT: TRIPPING ALL



1.
1.08 Gen Inv-T Overload
protection settings

NAME SYMBOL SETTINGS UNIT
1 Operating current (definite time-limit) Ig1 4.59 A
2 Operating time(definite time-limit) t11 9 s
3 Lower-limit current( inverse time-limit) Is 4.82 A
4 Lower- limit long time delay ( inverse
ts 100 s
time-limit)
5 Upper- limit current( inverse time-limit) Iup 37.84 A
6 Upper- limit time ( inverse time-limit) tup 0.40 s
7 Caloricity coefficient K1 38 *
8 Radiation coefficient K2 1.0 *
9 Rated current IN 4.15 A

TRIPPING OUTPUT: TRIPPING ALL



1.
3 33
1.09 Gen Inv-T Overcurrent
protection settings

NAME SYMBOL SETTINGS UNIT
1 Operating current (definite time-limit) I2g1 0.42 A
2 Operating time(definite time-limit) t11 9.00 s
3 Lower-limit current( inverse time-limit) I2s 0.44 A
4 Lower- limit long time delay ( inverse ts 800 s
time-limit)
5 Upper- limit current( inverse time-limit) I2up 6.45 A
6 Upper- limit time ( inverse time-limit) tup 2.00 s
7 Caloricity coefficient K1 10 *
8 Radiation coefficient K2 0 *
9 Rated current IN 4.15 A

TRIPPING OUTPUT: TRIPPING ALL



1.
1.10 Gen Reverse Power
protection settings

NAME SYMBOL SETTINGS UNIT
1 Reverse power setting (negative) Pg1 -13.44 W
2 Operating time delay t11 15 s
3 Operating time delay t12 60 s

TRIPPING OUTPUT: TRIPPING ALL



1.
1.11 Gen Program Reverse Power
protection settings

NAME SYMBOL SETTINGS UNIT
1 Reverse power setting (negative) Pg1 - W
2 Operating time delay t11 s

TRIPPING OUTPUT: TRIPPING ALL



1.
1.12 Start-Stop Protection
protection settings

NAME SYMBOL SETTINGS UNIT
1 3U0 setting 3U0g1 V
2 Time delay t11 1 s

TRIPPING OUTPUT: de-excition



1.
1.13 Gen over fluxing
protection settings

NAME SYMBOL SETTINGS UNIT
1 I Multiples U/f1 1.1 *
2 I Time T11 9 s
3 II Multiples U/f2 1.3 *
4 II Time T21 1.0 s
I -II -
TRIPPING OUTPUT:IREDUCE EXCTIATIONIITRIPPING ALL

4 33
1.14 -Gen. OverFreq Prot-
protection settings

NAME SYMBOL SETTINGS UNIT
1 Over Frequency operating value F1 51.0 Hz
2 Time delay t1 180 s

TRIPPING OUTPUT: PROGRAM TRIPPING



1.
1.15 -Gen. UnderFreq Prot
protection settings

NAME SYMBOL SETTINGS UNIT
5 Under Frequency operating value F3 47.00 Hz
6 Time delay T3 10 s

TRIPPING OUTPUT: SIGNAL


1.16 Generator loss-of-field & out-of-step protection-
protection settings

NAME SYMBOL SETTINGS UNIT
1 System under- voltage Uhl 57.2 V
2 Generator terminal under-voltage Ugl 88 V
3 Center of the impedance circle (negative) -Xc -16.36
4 Radius of the impedance circle Xr 14.69
5 Performance curve coefficient K

*
fd

6 Initial operating value of the rotor
Vfdl *
under- voltage
7 Reaction power Pt 0 W
8 Over power Pg 268
9 Operation time delay t1 0.5 s
10 Operation time delay t2 600 s
11 Operation time delay t3 0.5 s
12 Operation time delay t4 0.5 s
13 Resistance values Xt 1.80
14 R1 1.94
15 R2 0.94
16 Resistance values in the boundaries of the various areas R3 -0.94
17 R4 -1.94
18 1 t1 0.06 s
19 2 t2 0.13 s
Stay time in the various areas
20 3 t3 0.06 s
21 4 t4 0.05 s
22 Slip times N 2
t1-, t2, t3- t4-

TRIPPING OUTPUT: t1-loss-of-field,t2,t3--DISCONNECTION FROM SYSTEMt4-TRANSFER
out-of-stepDISCONNECTION FROM SYSTEM
5 33

2.


Name
PCPP
Device No. GENERATOR-TRANSFORMER UNIT protection
Protection device DGT801
model
2.01 MAIN TRANSFORMER DIFFERENTIAL(M-T DIFFERENTIAL)
protection settings

NAME SYMBOL SETTINGS UNIT
1 Restraint coefficient Kz 0.50 A
2 Harmoni restraint ratio 0.15
3 Starting current Iq 1.78 A
4 Knee point current Ig 3.56 A
5 Instantaneous Differential current multiples Is 4.00 Multiples
6 Differential current multiples *I
Ict 0.10 Multiples
efor canceling TA wire break
7 Rated current IN 4.445 A
8 CT switch on/off the blocking of the
CT(1,0) 0 1or0
differential protection when TA wire break

TRIPPING OUTPUT: TRIPPING ALL


2.02 OVER ALL DIFFERENTIAL(G-T DIFFERENTIAL)
protection settings

NAME SYMBOL SETTINGS UNIT
1 Restraint coefficient Kz 0.50 A
2 Harmoni restraint ratio 0.15
3 Starting current Iq 1.78 A
4 Knee point current Ig 3.56 A
5 Instantaneous Differential current multiples Is 4.00 Multiples
6 Differential current multiples *I
Ict 0.10 Multiples
efor canceling TA wire break
7 Rated current Ie 4.445 A
8 CT switch on/off the blocking of the
CT(1,0) 0 1or0
differential protection when TA wire break

TRIPPING OUTPUT: TRIPPING ALL


2.03 MT Comp Low V Over C
protection settings

NAME SYMBOL SETTINGS UNIT
1 Overcurrent setting Ig1 0.86 A
2 Operating time delay t11 1.3 s
3 Undervoltage setting U1 66 V
4 U2 Negative-sequence voltage operating value U2 8.8 V
t11 ;t12
TRIPPING OUTPUT: t11 TRIPPING BUS COUPLE; t12TRIPPING ALL

1.
2.04 MT RESTRICTED EARTH FAULT
protection settings

NAME SYMBOL SETTINGS UNIT
1 Restraint coefficient Kz 0.40 A
2 Harmoni restraint ratio 0.15
3 Starting current Iq 0.27 A
4 Knee point current Ig 0.07 A
5 Instantaneous Differential current multiples Is 8.00 Multiples
6 Differential current multiples *I
Ict 0.1 Multiples
efor canceling TA wire break
6 33
7 Rated current Ie 0.678 A
8 CT switch on/off the blocking of the
CT(1,0) 0 1or0
differential protection when TA wire break

TRIPPING OUTPUT: TRIPPING ALL


2.05 MT Zero-Seq Over C
protection settings

NAME SYMBOL SETTINGS UNIT
1 I Operating current (Zero-sequence zone I) 3I0g1 0.73 A
2 I 1 time delay 1 (Zero-sequence zone I) t11 0.9 s
3 I 2 time delay 2 (Zero-sequence zone I) t12 1.4 s
4 II Operating current (Zero-sequence zone II) 3I0g2 0.6 A
5 II 1 time delay 1 (Zero-sequence zone II) t21 1.4 s
6 II 2 time delay 2 (Zero-sequence zone II) t22 1.9 s
t11t21 :.t21t22:
TRIPPING OUTPUT: t11t21 :TRIP BUS COUPLER.t21t22::TRIPPING ALL

1.
2.06 MT Vetilation
protection settings

NAME SYMBOL SETTINGS UNIT
1 stating current setting Ig1 0.48 A
2 time delay t11 9 s

TRIPPING OUTPUT: START MT COOLER



1.
2.07 220KV Breaker Failure
protection settings

NAME SYMBOL SETTINGS UNIT
1 Operating Overcurrent Ig 0.66 A
2 Negative-sequence Overcurrent I2g 0.13 A
3 Zero-sequence Overcurrent 3I0g 0.13 A
4 Operating time delayt11 t11 0.15 s
5 Operating time delayt12 t12 0.25 s

TRIPPING OUTPUT: Start Breaker failure Releasing voltageINTER LOCK



1.
2.08 Gen ACC Energzing-
protection settings

NAME SYMBOL SETTINGS UNIT
1 Forward impedance Z1F 46.28
2 Reverse impedance Z1B 4.63
3 Overcurrent Ig 0.1 A
4 Negetive overcurrent I2 0.1 A
5 ACC Energzing time delay t11 1.0 s
6 DL back time after DL closed t12 3.0 s
7 time delay after impedance criteria t13 1.0 s
8 back time after impedance criteria t14 1.0 s

TRIPPING OUTPUT: TRIPPING ALL



1.
7 33
3.


Name
PCPP
Device No. GENERATOR-TRANSFORMER UNIT protection
Protection device DGT801
model
3.01 UNIT TRANSFORMER DIFFERENTIAL(U-T DIFFERENTIAL)
protection settings

NAME SYMBOL SETTINGS UNIT
1 Restraint coefficient Kz 0.50 A
2 Harmoni restraint ratio 0.13
3 Starting current Iq 1.34 A
4 Knee point current Ig 2.68 A
5 Instantaneous Differential current multiples Is 7.00 Multiples
6 Differential current multiples *I
Ict 0.10 Multiples
efor canceling TA wire break
7 Rated current Ie 3.35 A
8 CT switch on/off the blocking of the
CT(1,0) 0 1or0
differential protection when TA wire break

TRIPPING OUTPUT: TRIPPING ALL


3.02 UT Comp Low V Over C
protection settings

NAME SYMBOL SETTINGS UNIT
1 Overcurrent setting Ig1 4.38 A
2 Operating time delay t11 1.0 s
3 Operating time delay t12 1.5 s
4 Undervoltage setting U1 66 V
5 U2 Negative-sequence voltage operating value U2 8.8 V
t11 ;t12
TRIPPING OUTPUT: t11 FAST TRANSFER; t12 de-excition

1.
3.03 UT O.C.INSTANTANEOUS AND TIME RELAY
protection settings

NAME SYMBOL SETTINGS UNIT
1 Overcurrent setting Ig1 16.94 A
2 Operating time delay t11 0.5 s
t11
TRIPPING OUTPUT: t11 TRIPING BRANCH

1.
3.04 AT OVERCURRENT
protection settings

NAME SYMBOL SETTINGS UNIT
1 Overcurrent setting Ig1 13.40 A
2 Operating time delay t11 1.5 s
t11
TRIPPING OUTPUT: t11 TRIPING BRANCH

1.
3.05 AT Zero-Seq Over C
protection settings

NAME SYMBOL SETTINGS UNIT
1 Operating current 3I0g 2.71 A
2 1 time delay 1 t11 1.0 s
3 2 time delay 2 t12 1.5 s
t1 t2
8 33
TRIPPING OUTPUT: t1 TRIPING BRANCH t2 TRIPPING ALL

1.

3.06 AT RESTRICTED EARTH FAULT


protection settings

NAME SYMBOL SETTINGS UNIT
1 Restraint coefficient Kz 0.40 A
2 Harmoni restraint ratio 0.15
3 Starting current Iq 1.34 A
4 Knee point current Ig 0.34 A
5 Instantaneous Differential current multiples Is 8.00 Multiples
6 Differential current multiples *I
Ict 0.1 Multiples
efor canceling TA wire break
7 Rated current Ie 3.35 A
8 CT switch on/off the blocking of the
CT(1,0) 0 1or0
differential protection when TA wire break

TRIPPING OUTPUT: TRIPPING ALL


3.07 AT Vetilation
protection settings

NAME SYMBOL SETTINGS UNIT
1 stating current setting Ig1 2.35 A
2 time delay t11 9 s

TRIPPING OUTPUT: START AT COOLER



1.
3.08 PT YH Wire Break
protection settings

NAME SYMBOL SETTINGS UNIT
1 U2 Negative-sequence voltage setting U2 8 V
2 Operating time delay t1 t1 8 s
3 U2 Negative-sequence voltage setting U22 8 V
4 Operating time delay t1 t12 8 s

TRIPPING OUTPUT: SIGNAL


9 33
4.


Name
PCPP
Device No. GENERATOR-TRANSFORMER UNIT protection
Protection device DGT801
model
4.01 ET O.C.INSTANTANEOUS
protection settings

NAME SYMBOL SETTINGS UNIT
1 Overcurrent setting Ig1 18.3 A
2 Operating time delay t11 0.1 s

1.
4.02 ET OVERCURRENT
protection settings

NAME SYMBOL SETTINGS UNIT
1 Overcurrent setting Ig1 7.39 A
2 Operating time delay t11 1.5 s

1.
4.03 ET Overload
protection settings

NAME SYMBOL SETTINGS UNIT
1 Overcurrent setting Ig1 3.49 A
2 Operating time delay t11 10.5 s

SIGNAL

1.