You are on page 1of 7

11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP

ElectricalSafetyStandardsforLV/MV/HV
(Part3)

Electrical Safety Standards for LV/MV/HV part 3 (On photo transmission tower in India)

Continuedfrompart2ElectricalSafetyStandardsforLV/MV/HV(Part2)

Content
Standard:NorthernIrelandElectricity(NIE),6/025ENA

Code:IndianElectricityRules/CentralElectricityAuthority

1. RightofWayClearance(AsperGETCOStandard)
2. MinimumclearancesbetweenElectricalLinescrossingeachother
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 1/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP

3. PermissibleMingroundClearanceofElectricalLine
4. ClearanceforTelephonelineCrossingsPowerLine
5. VerticalClearancebetweenElectricalLineandrailwaytracks
6. ClearancefromBuildingstolow,medium&highvoltagelines
7. Clearanceabovegroundatthelowestconductor
8. VerticalClearanceatMiddleofSpan
9. SafetyClearancefromLivePartinOutdoorSubstation
10. LyingofTelecommunicationCableswithPowerCables(>33kV)
11. Safeapproachlimitsforpeople

Code:IndianElectricityRules/CentralElectricityAuthority
RightofWayClearance(AsperGETCOStandard)

KV MinROW
66KV 18Meter
132KV 27Meter
220KV 35Meter
400KV 52Meter(SingleCircuit)
400KV 48Meter(DoubleCircuit)
GotoContent

MinimumclearancesbetweenElectricalLinescrossingeachother

Voltage 66KV 132KV 220KV 400KV


66KV 2.4Meter 3Meter 4.5Meter 5.4Meter
132KV 3Meter 3Meter 4.5Meter 5.4Meter
220KV 4.5Meter 4.5Meter 4.5Meter 5.4Meter
400KV 4.5Meter 5.4Meter 5.4Meter 5.4Meter
GotoContent

PermissibleMingroundClearanceofElectricalLine

http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 2/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP

KV GroundClearance OverNational
Highway
66KV 6.1Meter 8.0Meter
132KV 6.1Meter 8.6Meter
220KV 7.0Meter 9.8Meter
400KV 8.8Meter 10.8Meter
GotoContent

ClearanceforTelephonelineCrossingsPowerLine

KV Clearance(Min)
66KV 2.4Meter
132KV 2.7Meter
220KV 3.0Meter
GotoContent

VerticalClearancebetweenElectricalLineandrailwaytracks

KV Clearance(Min)
66KV 14Meter
132KV 14.6Meter
220KV 15.4Meter
400KV 17.9Meter
GotoContent

ClearancefromBuildingstolow,mediumandhigh
voltagelines

http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 3/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP

Voltage Description Distance


Low&Medium Flatroof,openbalcony,verandahroof 2.5Meter
Voltage ,Whenthelinepassesabovethe
buildingaverticalclearancefromthe
highestpoint
Low&Medium Linepassesadjacenttothebuildinga 1.2Meter
Voltage horizontalclearancefromthenearest
point
Low&Medium Linepassesabovethebuildinga 2.5Meter
Voltage verticalclearance
Low&Medium Linepassesadjacentthebuildinga 1.2Meter
Voltage Horizontalclearance
11KVto33KV Linepassesaboveoradjacenttoany 3.7Meter
buildingorpartofabuilding
Above33KV Linepassesaboveoradjacenttoany 3.7+(0.3forevery
buildingorpartofabuilding additional33KV)
Upto11KV Thehorizontalclearancebetweenthe 1.2Meter
nearerconductorandanypartofsuch
building
11KVto33KV Thehorizontalclearancebetweenthe 2.0Meter
nearerconductorandanypartofsuch
building
Above33KV Thehorizontalclearancebetweenthe 2.0+(0.3forevery
nearerconductorandanypartofsuch additional33KV)
building
GotoContent

Clearanceabovegroundatthelowestconductor

http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 4/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP

Voltage Description Distance


Low&MediumVoltage Acrossastreet 5.8Meter
HighVoltage Acrossastreet 6.1Meter
Low&MediumVoltage Alongastreet 5.5Meter
HighVoltage Alongastreet 5.8Meter
Low&MediumVoltage Elsewherethanalongoracross 4.0Meter
anystreet
HighVoltage Elsewherethanalongoracross 5.2Meter
anystreet
33KV&EHV Clearanceaboveground(Add0.3 Min6.1Meter
Meterforevery33KVVoltsin5.2
Meter)
GotoContent

VerticalClearanceatMiddleofSpan

Span VerticalClearance(AtMiddleof
Span)
200Meter 4.0Meter
300Meter 5.5Meter
400Meter 7.0Meter
500Meter 8.5Meter
GotoContent

SafetyClearancefromLivePartinOutdoorSubstation

http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 5/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP

KV SafetyWorkingClearance
12KV 2.6Meter
36KV 2.8Meter
72.5KV 3.1Meter
145KV 3.7Meter
220KV 4.3Meter
400KV 6.4Meter
800KV 10.3Meter
GotoContent

LyingofTelecommunicationCableswithPowerCables(>33kV)

Cable Min.Distance
Powercableofvoltageexceeding33kVshallbe Min1.2Meterdepth
laid
Undergroundtelecommunicationcableshallbewith Min0.6MeterSeparatefrom
undergroundpowercableofvoltageexceeding33 PowerCable
kV.
GotoContent

Safeapproachlimitsforpeople

Voltage 214Vto 11KV 33KV 66KV 132KV 275KV


415KV
Personusingmanuallyoperated 1.3 2.0 3.0 4.0 5.0 6.0
tool Meter Meter Meter Meter Meter Meter
Personusingpoweroperated 3.0 3.0 3.0 4.0 5.0 6.0
tool Meter Meter Meter Meter Meter Meter
GotoContent
Get
PDF

TOP

RecommendedEEarticles//
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 6/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP

RecommendedEEarticles//
SHARE


Sharewithengineers//


AboutAuthor//

Jignesh Parmar
jiguparmarJigneshParmarhascompletedM.Tech(Power
SystemControl),B.E(Electrical).HeismemberofInstitutionof
Engineers(MIE),India.MembershipNo:M1473586.Hehas
morethan13yearsexperienceinTransmissionDistribution
ElectricalEnergytheftdetectionElectricalMaintenance
ElectricalProjects(PlanningDesigningTechnicalReview
coordinationExecution).HeisPresentlyassociatewithoneof
theleadingbusinessgroupasaDeputyManageratAhmedabad,India.Hehas
publishednumbersofTechnicalArticlesin"ElectricalMirror","ElectricalIndia",
"LightingIndia","IndustrialElectrix"(AustralianPowerPublications)Magazines.Heis
FreelancerProgrammerofAdvanceExcelanddesignusefulExcelbaseElectrical
ProgramsasperIS,NEC,IEC,IEEEcodes.HeisTechnicalBloggerandFamiliarwith
English,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&
Knowledgeandhelptechnicalenthusiaststofindsuitablesolutionsandupdating
themselvesonvariousEngineeringTopics.

2015EEPElectricalEngineeringPortal.AllRightsReserved|PrivacyPolicy|TermsofService |51queriesin0.177
seconds.
PoweredbyCsanyiGroup

http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 7/7

You might also like