Professional Documents
Culture Documents
ElectricalSafetyStandardsforLV/MV/HV
(Part3)
Electrical Safety Standards for LV/MV/HV part 3 (On photo transmission tower in India)
Continuedfrompart2ElectricalSafetyStandardsforLV/MV/HV(Part2)
Content
Standard:NorthernIrelandElectricity(NIE),6/025ENA
Code:IndianElectricityRules/CentralElectricityAuthority
1. RightofWayClearance(AsperGETCOStandard)
2. MinimumclearancesbetweenElectricalLinescrossingeachother
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 1/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP
3. PermissibleMingroundClearanceofElectricalLine
4. ClearanceforTelephonelineCrossingsPowerLine
5. VerticalClearancebetweenElectricalLineandrailwaytracks
6. ClearancefromBuildingstolow,medium&highvoltagelines
7. Clearanceabovegroundatthelowestconductor
8. VerticalClearanceatMiddleofSpan
9. SafetyClearancefromLivePartinOutdoorSubstation
10. LyingofTelecommunicationCableswithPowerCables(>33kV)
11. Safeapproachlimitsforpeople
Code:IndianElectricityRules/CentralElectricityAuthority
RightofWayClearance(AsperGETCOStandard)
KV MinROW
66KV 18Meter
132KV 27Meter
220KV 35Meter
400KV 52Meter(SingleCircuit)
400KV 48Meter(DoubleCircuit)
GotoContent
MinimumclearancesbetweenElectricalLinescrossingeachother
PermissibleMingroundClearanceofElectricalLine
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 2/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP
KV GroundClearance OverNational
Highway
66KV 6.1Meter 8.0Meter
132KV 6.1Meter 8.6Meter
220KV 7.0Meter 9.8Meter
400KV 8.8Meter 10.8Meter
GotoContent
ClearanceforTelephonelineCrossingsPowerLine
KV Clearance(Min)
66KV 2.4Meter
132KV 2.7Meter
220KV 3.0Meter
GotoContent
VerticalClearancebetweenElectricalLineandrailwaytracks
KV Clearance(Min)
66KV 14Meter
132KV 14.6Meter
220KV 15.4Meter
400KV 17.9Meter
GotoContent
ClearancefromBuildingstolow,mediumandhigh
voltagelines
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 3/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP
Clearanceabovegroundatthelowestconductor
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 4/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP
VerticalClearanceatMiddleofSpan
Span VerticalClearance(AtMiddleof
Span)
200Meter 4.0Meter
300Meter 5.5Meter
400Meter 7.0Meter
500Meter 8.5Meter
GotoContent
SafetyClearancefromLivePartinOutdoorSubstation
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 5/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP
KV SafetyWorkingClearance
12KV 2.6Meter
36KV 2.8Meter
72.5KV 3.1Meter
145KV 3.7Meter
220KV 4.3Meter
400KV 6.4Meter
800KV 10.3Meter
GotoContent
LyingofTelecommunicationCableswithPowerCables(>33kV)
Cable Min.Distance
Powercableofvoltageexceeding33kVshallbe Min1.2Meterdepth
laid
Undergroundtelecommunicationcableshallbewith Min0.6MeterSeparatefrom
undergroundpowercableofvoltageexceeding33 PowerCable
kV.
GotoContent
Safeapproachlimitsforpeople
TOP
RecommendedEEarticles//
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 6/7
11/12/2015 ElectricalSafetyStandardsforLV/MV/HV(Part3)|EEP
RecommendedEEarticles//
SHARE
Sharewithengineers//
AboutAuthor//
Jignesh Parmar
jiguparmarJigneshParmarhascompletedM.Tech(Power
SystemControl),B.E(Electrical).HeismemberofInstitutionof
Engineers(MIE),India.MembershipNo:M1473586.Hehas
morethan13yearsexperienceinTransmissionDistribution
ElectricalEnergytheftdetectionElectricalMaintenance
ElectricalProjects(PlanningDesigningTechnicalReview
coordinationExecution).HeisPresentlyassociatewithoneof
theleadingbusinessgroupasaDeputyManageratAhmedabad,India.Hehas
publishednumbersofTechnicalArticlesin"ElectricalMirror","ElectricalIndia",
"LightingIndia","IndustrialElectrix"(AustralianPowerPublications)Magazines.Heis
FreelancerProgrammerofAdvanceExcelanddesignusefulExcelbaseElectrical
ProgramsasperIS,NEC,IEC,IEEEcodes.HeisTechnicalBloggerandFamiliarwith
English,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&
Knowledgeandhelptechnicalenthusiaststofindsuitablesolutionsandupdating
themselvesonvariousEngineeringTopics.
2015EEPElectricalEngineeringPortal.AllRightsReserved|PrivacyPolicy|TermsofService |51queriesin0.177
seconds.
PoweredbyCsanyiGroup
http://electricalengineeringportal.com/electricalsafetystandardsforlvmvhvpart3 7/7