Professional Documents
Culture Documents
PUMP PIPING
Fig: 8-13 illustrates the components that are usually found in pump
suction and discharge piping.
-1-
JITENDRA SURVE PIPING GUIDE 01/04/03
After the suction and discharge valves have been shut off, the blind
flange is unbolted and put aside and the strainer is pulled out.
This strainer is generally used only for startup.
Fig: 8-15 shows a basket strainer that may also be used in a pump
suction line.
Although this particular strainer does not need additional fittings for its
removal and cleaning if used, it does require additional maintenance
because of the downstream flanges of the valve.
The pump nozzle and possibly the base support under the elbow must
be unbolted to pull the spool piece and remove the strainer.
The next common fitting is a reducer; this should be an eccentric type
as shown in fig: 8-16, with the flat side on top to reduce the possibility
of cavitation in the pump.
-2-
JITENDRA SURVE PIPING GUIDE 01/04/03
-3-
JITENDRA SURVE PIPING GUIDE 01/04/03
-4-
JITENDRA SURVE PIPING GUIDE 01/04/03
-5-
JITENDRA SURVE PIPING GUIDE 01/04/03
VALVES
Orientation of block valve must minimize the plot area required.
Valve handwheels or handles shall be oriented, whenever practical, to
be contained within perimeter of the pump foundation.
Valve handwheels should not interfere with pump maintenance or
create hazards for operating personnel.
Pump valves are operating valves and shall be readily operable from
grade or platform.
For larger valves, it may be necessary to rotate the handwheel for
better access.
Check valves can be installed in vertical and/or horizontal position.
Lift check valves shall be installed in horizontal only.
The discharge valve, suction strainer and suction valve may be of the
same size as the pump nozzles for economic reasons and also to avoid
comparatively heavy attachments.
Unless the pressure drop is too high, the pressure rating of the suction
valve and piping between this valve and the suction nozzle shall be
equal to the rating of the discharge.
Elevation of the valves should generally be as low as possible and
common in both lines when practical.
-6-
JITENDRA SURVE PIPING GUIDE 01/04/03
In larger lines sizes with higher pressure ratings, the valves place the
horizontal piping too high, especially if they are beneath the pipe rack.
Therefore the alternative arrangement shown in above fig. Solves the
layout problem.
Fig: 8-22 shows how a common pump is used for two primary pumps;
this is the ideal layout with flexibility loops added as requied.
-7-
JITENDRA SURVE PIPING GUIDE 01/04/03
Fig: 8-23 shows how the suction line for service B is tied into the
suction line for service A below or downstream from the block valve
and upstream from the strainer.
The discharge line for service B is tied in downstream from the check
valve.
-8-
JITENDRA SURVE PIPING GUIDE 01/04/03
Because the line requires a large flexible loop, the amount of dead leg
for the line nonoperating pump must be minimized.
The plant layout designer should discuss this particular arrangement
with the vessel engineer.
When the vessel data sheets are sent out for quotation, the split
bottom outlet connection in included in the basic design.
Making this type of decision too late can be very costly and may delay
delivery of the vessel.
The designer should not just take information as is but should look for
ways to improve the overall design or lower the cost of the plant in all
disciplines.
Pumps whose suction lines come from below grade are shown in fig: 8-
25.
This is the one time that the reducer absolutely must have the flat side
on top to avoid cavitation.
Use of a basket strainer is more practical in this case because the
spool piece containing the strainer could be lifter out as shown in fig:
8-26.
There are many solutions that can remove CO2 from the process gas,
some of which operate close to the vapor pressure of the liquid.
Fig: 8-28 shows one way to solve this problem.
- 10 -
JITENDRA SURVE PIPING GUIDE 01/04/03
- 11 -
JITENDRA SURVE PIPING GUIDE 01/04/03
- 12 -
JITENDRA SURVE PIPING GUIDE 01/04/03
Cooling water in and out of this particular pump is from above grade,
and the plant layout designer must find a suitable location for this
connection.
- 13 -
JITENDRA SURVE PIPING GUIDE 01/04/03
- 14 -
JITENDRA SURVE PIPING GUIDE 01/04/03
- 15 -
JITENDRA SURVE PIPING GUIDE 01/04/03
ELEVATION
- 16 -
JITENDRA SURVE PIPING GUIDE 01/04/03
- 17 -
JITENDRA SURVE PIPING GUIDE 01/04/03
- 18 -