You are on page 1of 32

NOTE: Text in BLUE and BOLD are optional items that require editing based on system design

SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM (Voice Evacuation)

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Fire-alarm control unit with intergraded Voice Evacuation.


2. Manual fire-alarm boxes.
3. System smoke detectors.
4. Multi-criteria photoelectric and heat detectors.
5. Addressable interface device.
6. Heat detectors.
7. Notification appliances.
8. Magnetic door holders.
9. Remote annunciator.
10. Digital alarm communicator transmitter.
11. System printer.

1.3 DEFINITIONS

A. General: Definitions contained in NFPA 72 shall apply to fire alarm terms used in this Section.

B. DACT: Digital Alarm Communicator Transmitter.

C. Digital Addressable Fire Alarm System: An addressable fire alarm system employing a digital
peer-to-peer protocol where detectors allow for configurable sensitivity settings.

D. FACP: Fire Alarm Control Panel.

E. FCS: Fire Command Station.

F. LED: Light-emitting diode.

G. NICET: National Institute for Certification in Engineering Technologies.

H. UL: Underwriters Laboratories, Inc.

I. HLI: High Level Interface

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 1


J. VESDA: Very Early Smoke Detection Apparatus.

1.4 SYSTEM DESCRIPTION

A. Noncoded, [UL-certified] [FMG-placarded] addressable system, with automatic sensitivity


control of certain smoke detectors and multiplexed signal transmission, dedicated to fire-alarm
service only.

1.5 PERFORMANCE REQUIREMENTS

A. Seismic Performance: Fire-alarm control unit and raceways shall withstand the effects of
earthquake motions determined according to [SEI/ASCE 7] <Insert requirement>.

1. The term "withstand" means "the unit will remain in place without separation of any parts
from the device when subjected to the seismic forces specified [and the unit will be fully
operational after the seismic event]."

1.6 SUBMITTALS

A. General Submittal Requirements:

1. Submittals shall be approved by authorities having jurisdiction prior to submitting them to


Architect.
2. Shop Drawings shall be prepared by persons with the following qualifications:

a. Trained and certified by manufacturer in fire-alarm system design.


b. NICET-certified fire-alarm technician, [Level III] [Level IV] minimum.
c. Licensed or certified by authorities having jurisdiction.

B. Product Data: For each type of product indicated.

C. Shop Drawings: For fire-alarm system. Include plans, elevations, sections, details, and
attachments to other work.

1. Comply with recommendations in the "Documentation" Section of the "Fundamentals of


Fire Alarm Systems" Chapter in NFPA 72.
2. Include voltage drop calculations for notification appliance circuits.
3. Include battery-size calculations.
4. Include performance parameters and installation details for each detector, verifying that
each detector is listed for complete range of air velocity, temperature, and humidity
possible when air-handling system is operating.
5. Include plans, sections, and elevations of heating, ventilating, and air-conditioning ducts,
drawn to scale and coordinating installation of duct smoke detectors and access to them.
Show critical dimensions that relate to placement and support of sampling tubes, detector
housing, and remote status and alarm indicators. Locate detectors according to
manufacturer's written recommendations.
6. Include fire alarm signaling-service equipment rack or console layout, grounding
schematic and single-line connection diagram.
7. Include floor plans to indicate final outlet locations showing address of each addressable
device. Show size and route of cable and conduits.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 2


D. Delegated-Design Submittal: For smoke and heat detectors indicated to comply with
performance requirements and design criteria, including analysis data signed and sealed by the
qualified professional engineer responsible for their preparation.

1. Drawings showing the location of each smoke and heat detector, ratings of each, and
installation details as needed to comply with listing conditions of the detector.
2. Design Calculations: Calculate requirements for selecting the spacing and sensitivity of
detection, complying with NFPA 72.

E. Qualification Data: For qualified Installer list local requirements of State/Local License
requirements, bonding and other AHJ/Owner requirements of installer.

F. Seismic Qualification Certificates: For fire-alarm control unit, accessories, and components,
from manufacturer.

1. Basis for Certification: Indicate whether withstand certification is based on actual test of
assembled components or on calculation.
2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate
and describe mounting and anchorage provisions.
3. Detailed description of equipment anchorage devices on which the certification is based
and their installation requirements.

G. Field quality-control reports.

H. Operation and Maintenance Data: For fire-alarm systems and components to include in
emergency, operation, and maintenance manuals. In addition to items specified in Division 01
Section "Operation and Maintenance Data," include the following:

1. Comply with the "Records" Section of the "Inspection, Testing and Maintenance" Chapter
in NFPA 72.
2. Provide "Record of Completion Documents" according to NFPA 72 article "Permanent
Records" in the "Records" Section of the "Inspection, Testing and Maintenance" Chapter.
3. Record copy of site-specific software.
4. Provide "Maintenance, Inspection and Testing Records" according to NFPA 72 article of
the same name and include the following:

a. Frequency of testing of installed components.


b. Frequency of inspection of installed components.
c. Requirements and recommendations related to results of maintenance.
d. Manufacturer's user training manuals.

5. Manufacturer's required maintenance related to system warranty requirements.


6. Abbreviated operating instructions for mounting at fire-alarm control unit.
7. Copy of NFPA 25.

I. Software and Firmware Operational Documentation:

1. Site-specific software operating and upgrade manuals.


2. Program Software Backup: On magnetic media or compact disk, complete with data
files.
3. Device address list.
4. Printout of software application and graphic screens.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 3


1.7 QUALITY ASSURANCE

A. Manufacturer Qualifications:

1. ISO 9001 Certified.

2. AS 9100 Certified.

B. Installer Qualifications: The installer shall be regularly engaged in the business of installing,
maintain and service fire alarm systems.
1. Installation shall be by personnel certified by NICET as fire-alarm [Level II] [Level III]
[Level IV] technician.
2. Installation shall be supervised by personnel certified by NICET as fire-alarm [Level II]
[Level III] [Level IV] technician.
3. Installation Company shall be licensed by local or state licensing entity. A copy of the
license shall be required as part of the submittal.
4. Installation Company shall be insured in accordance with the General Conditions of the
project and design documentation.
5. Installation Company shall provide Performance and Payment Bond(s) in accordance
with the General Conditions of the project and design documentation.
6. Personnel shall be trained and certified by manufacturer for installation of units required
for this Project. Personnel shall be recertified every two years by the fire alarm equipment
manufacturer through an authorized factory training and recertification program

C. Source Limitations for Fire-Alarm System and Components: Obtain fire-alarm system from
single source from single manufacturer. Components shall be compatible with, and operate as,
an extension of a new [existing] system.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.

E. NFPA Certification: Obtain certification according to NFPA 72 by an NRTL.

F. NFPA Certification: Obtain certification according to NFPA 72 by a UL-listed alarm company.

G. NFPA Certification: Obtain certification according to NFPA 72 in the form of a placard by an


FMG-approved alarm company.

H. NFPA Certification: Obtain certification according to NFPA 72 by <Insert certification


agency>.

1.8 PROJECT CONDITIONS

A. Interruption of Existing Fire-Alarm Service: Do not interrupt fire-alarm service to facilities


occupied by Owner or others unless permitted under the following conditions and then only after
arranging to provide temporary guard service according to requirements indicated:

1. Notify [Architect] [Construction Manager] [Owner] no fewer than [two] <Insert


number> days in advance of proposed interruption of fire-alarm service.
2. Do not proceed with interruption of fire-alarm service without [Architect's] [Construction
Manager's] [Owner's] written permission.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 4


1.9 SEQUENCING AND SCHEDULING

A. Existing Fire-Alarm Equipment: Maintain existing equipment fully operational until new
equipment has been tested and accepted. As new equipment is installed, label it "NOT
IN SERVICE" until it is accepted. Remove labels from new equipment when put into
service and label existing fire-alarm equipment "NOT IN SERVICE" until removed from
the building.

B. Equipment Removal: After acceptance of new fire-alarm system, remove existing


disconnected fire-alarm equipment and wiring.

C. New Fire Alarm Installation: for new installation maintain a clean, proper safe work
environment per OSHA and local AHJ requirements. As new equipment is installed, label
it "NOT IN SERVICE" until it is accepted. Remove labels from new equipment when put
into service.

1.10 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or


replace [components of] the digital addressable fire alarm system that fail in materials or
workmanship within specified warranty period.

1. Warranty Period: [One year, for systems not certified and covered] [Five years, for
systems certified and covered under manufacturer's maintenance service
agreement signed by an authorized Installer 120 days from date of Substantial
Completion].

1.11 SERVICE AND PREVENTATIVE MAINTENANCE

A. Service: Manufacturer's shall provide for multiple factory authorized service companies to
provide post-installation service in the service area of the project. Service companies shall
provide for 24/7/365 Emergency Service capabilities. Local service companies shall carry
significant stock to perform emergency repairs of the system including but not limited to fire
alarm control panel components and field devices.

B. Factory Service Support: Manufacturer shall provide in house factory technical support for
authorized factory service companies. Service helpdesk shall be available during normal
business hours.

C. Advance Replacement Support: Manufacturer shall provide advance replacement of control


panel components in the event it is determined by the manufacturers technical support
helpdesk technician that the field issue is related to a hardware defect or anomaly, and cannot
be repaired in the filed without replacement of the part. The advance replacement will be sent
overnight on the day of the service call for next day delivery with out delay or need for return
authorization to minimize system downtime and fire-watch requirements.

D. Preventive Maintenance: The manufacturer authorized service company shall provide as part of
the contract a comprehensive maintenance program in compliance with NFPA and
manufactures requirements. A separate line item for the Preventive Maintenance Contract shall
be provided as indicated on the Bid Documents.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 5


1. Preventive Maintenance Period: [One-Two-Three-Four-Five (select) year] for all
system components installed for this project. Additional devices added after system
certification shall be added to the maintenance service agreement. The Preventative
Maintenance agreement will be in effect within 120 days from date of Substantial
Completion.
a. Preventive Maintenance Contract shall include all required permits, fees,
insurance, labor and expendable material to fully comply with NFPA, Local AHJ
and Manufacturers requirements.
b. Preventative Maintenance Contract that includes standard or extended
Manufactures warranty shall include associated labor to perform warrant service
at no additional cost to the owner during the life of the warranty period.

1.12 EXTRA MATERIALS

A. Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.

1. Lamps for Remote Indicating Lamp Units: Quantity equal to [10] <Insert number>
percent of amount installed, but no fewer than 1 unit.
2. Lamps for Strobe Units: Quantity equal to [10] <Insert number> percent of amount
installed, but no fewer than 1 unit.
3. All types of Initiating Device Detectors: Quantity equal to [10] <Insert number> percent
of amount of each type installed, but no fewer than 1 unit of each type.
4. Detector Bases: Quantity equal to [2] <Insert number> percent of amount of each type
installed, but no fewer than 1 unit of each type.
5. Keys and Tools: One extra set for access to locked and tamper-proofed components.
6. Audible and Visual Notification Appliances: [One] <Insert number> of each type
installed.
7. Fuses: [Two] <Insert number> of each type installed in the system.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Basis-of-Design Product: Subject to compliance with requirements provide Fike Corporation;


CyberCat, or a comparable product by one of the following:
1. Honeywell Building Solutions XLS3000, a Honeywell Company.
2. EST, EST-3 System, a GE Security/UTC Company.
3. Notifier Fire Systems; NFS Series Systems, a Honeywell Company.
4. Siemens, Inc. MXL/CXL Series; Siemens Building Technologies Fire Safety Division.
5. <Insert manufacturer's name>.

2.2 SYSTEMS OPERATIONAL DESCRIPTION

A. Fire-alarm signal initiation shall be by one or more of the following devices[ and systems]:

1. Manual alarm stations.


2. Photoelectric smoke detectors.
3. Combination photoelectric smoke and heat detectors.
4. Ionization smoke detectors.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 6


5. Duct smoke detectors.
6. Heat detectors.
7. Automatic sprinkler system water flow.
8. Flame detectors.
9. Air-sampling smoke detectors.
10. Verified automatic alarm operation of smoke detectors.
11. Heat detectors in elevator shaft and pit.
12. Fire-extinguishing system operation.
13. Fire standpipe system.
14. <Delete or Insert alarm-initiating devices and systems per design>.

B. Fire-alarm signal shall initiate the following actions:

1. Continuously operate alarm notification appliances.


2. Identify alarm and specific initiating device at fire-alarm control unit, connected network
control panels, off-premises network control panels and remote annunciators.
3. Transmit an alarm signal to the remote alarm receiving station.
4. Unlock electric door locks in designated egress paths.
5. Release fire and smoke doors held open by magnetic door holders.
6. Activate alarm voice evacuation notification system.
7. Switch heating, ventilating, and air-conditioning equipment controls to fire-alarm mode.
8. Activate smoke-control system (smoke management) at firefighter smoke-control system
panel.
9. Activate stairwell and elevator-shaft pressurization systems.
10. Close smoke dampers in air ducts of designated air-conditioning duct systems.
11. Recall elevators to primary or alternate recall floors.
12. Activate emergency lighting control.
13. Activate emergency shutoffs for gas and fuel supplies.
14. Record events in the system memory.
15. Record events by the system printer.
16. Transmit system status to building management system.
17. Display system status on a PC graphics annunciation station.
18. Activate pre-action sprinkler solenoid.
19. [Delete-Insert device type activation per system design]

C. Supervisory signal initiation shall be by one or more of the following devices and actions:

1. Valve supervisory switch.


2. Low-air-pressure switch of a dry-pipe sprinkler system.
3. Elevator shunt-trip supervision.
4. User disabling of zones or individual devices.
5. Duct Smoke Detector.
6. Dorm Sleeping Room Smoke Detector.
7. [Delete-Insert device type activation per system design]

D. System trouble signal initiation shall be by one or more of the following devices and actions:

1. Open circuits, shorts, and grounds in designated circuits.


2. Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating
devices.
3. Loss of primary power at fire-alarm control unit.
4. Ground or a single break in fire-alarm control unit internal circuits.
5. Abnormal ac voltage at fire-alarm control unit.
6. Break in standby battery circuitry.
7. Failure of battery charging.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 7


8. Abnormal position of any switch at fire-alarm control unit or annunciator.
9. Fire-pump power failure, including a dead-phase or phase-reversal condition.
10. Low-air-pressure switch operation on a dry-pipe or preaction sprinkler system.
11. Loss of communication with any addressable sensors, input modules, relays, control
modules, remote annunciators, printer interfaces, or Ethernet modules.
12. Loss of communication with any panel on the network.

E. System Alarm, Trouble and Supervisory Signal Actions: Initiate notification appliance and
annunciate at fire-alarm control unit [and remote annunciators] and [Record the event on
system printer.]

1. Identify alarm, trouble or supervisory signal and specific device initiating the event at fire-
alarm control unit, [connected network control panels, off-premises network control
panels and remote annunciators.]
2. Transmit an alarm, trouble or supervisory signal to the remote alarm receiving
station.
3. Transmit system status to building management system (Field Server).
4. Display system status on a PC graphics annunciation station.

2.3 FIRE-ALARM CONTROL UNIT/FIRE COMMAND STATION

A. General Requirements for Fire-Alarm Control Unit/Fire Command Station:

1. Field-programmable, microprocessor-based, modular, power-limited design with


electronic modules, complying with UL 864, Version 9 and listed and labeled by an
NRTL.

a. System software and programs shall be held in non-volatile flash electrically


erasable programmable read-only memory (EEPROM), retaining the information
through failure of primary and secondary power supplies.
b. Include a real-time clock for time annotation of events on the event recorder and
printer.

2. Addressable initiation devices that communicate device identity and status.

a. Smoke sensors shall additionally communicate sensitivity setting.


b. Temperature sensors shall communicate the sensitivity range of the device.

3. Addressable control circuits for operation of notification appliances, sprinkler solenoids


and other mechanical equipment.

B. Alphanumeric Display and System Controls: Arranged for interface between human operator at
fire-alarm control unit and addressable system components including annunciation and
supervision. Display alarm, supervisory, and component status messages and the
programming and control menu.

1. Annunciator and Display: Liquid-crystal type, 4 line(s) of 20 characters, minimum.


2. Keypad: Arranged to permit entry and execution of programming, display, and control
commands.
3. Panel Mounted Annunciator Control Modules for operation of auxiliary control functions or
supplemental annunciation of connected devices and systems.
4. Panel Mounted Annunciators for UL UUKL Listed Smoke Control Station.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 8


C. Circuits:

1. Initiating Device, Notification Appliance, and Signaling Line Circuits: NFPA 72


a. Notification Appliance Circuits: Class A.
b. Signaling Line Circuits: Class X
c. Device Isolators shall be provided for full Class X compliance
d. Devices must communicate peer-to-peer.

2. Initiating Device, Notification Appliance, and Signaling Line Circuits: NFPA 72


a. Notification Appliance Circuits: Class B.
b. Signaling Line Circuits: Class Y. Device Isolators shall be used for all T-Tap
branch circuits, or when an SLC Loop service multiple fire zones or building floors.
c. Devices must communicate peer-to-peer.

3. Serial Interfaces:

a. One dedicated RS-485 port for [central station] [remote station] operation using
point ID DACT.
b. One RS-485 port for remote annunciators, Ethernet module, or multi-interface
module (printer port).
c. One [USB] [RS-232] port for PC configuration.
d. One RS-232 port for VESDA HLI interface connection.
e. One RS-232 port for voice evacuation interface.

D. Remote Smoke-Detector Sensitivity Adjustment: Controls shall select specific addressable


smoke detectors for adjustment. Allow controls to be used to program repetitive, time-
scheduled, and automated changes in sensitivity of specific detector groups.

E. Smoke-Alarm Verification:

1. Initiate audible and visible indication of an "alarm-verification" signal at fire-alarm control


unit.
2. Activate an NRTL-listed and -approved "alarm-verification" sequence at fire-alarm control
unit and detector.
3. Record events by the system printer.
4. Sound general alarm if the alarm is verified.
5. Cancel fire-alarm control unit indication and system reset if the alarm is not verified.

F. Transmission to Remote Alarm Receiving Station: Automatically transmit point alarm,


supervisory, and trouble signals to a remote alarm station.

G. Printout of Events: On receipt of signal, print alarm, supervisory, and trouble events.
Identify zone, device, and function. Include type of signal (alarm, supervisory, or trouble)
and date and time of occurrence. Differentiate alarm signals from all other printed
indications. Also print system reset event, including same information for device,
location, date, and time. Commands initiate the printing of a list of existing alarm,
supervisory, and trouble conditions in the system and a historical log of events.

H. Primary Power: 24-V dc obtained from [120-V] [240-V] ac service and an on-board power-
supply. Initiating devices, notification appliances, signaling lines, trouble signals, [supervisory
signals] [supervisory and digital alarm communicator transmitters] shall be powered by
24-V dc source.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 9


1. Alarm current draw of entire fire-alarm system shall not exceed 80 percent of the power-
supply rating, in order to allow for system expansion.

I. Secondary Power: 24-V dc supply system with batteries, automatic battery charger, and
automatic transfer switch.

1. Batteries: Sealed, valve-regulated, recombinant lead acid. Batteries shall be calculated


for stand-by operation of [Select hours] and [minutes] of full alarm activation per
NFPA/Local AHJ requirements for [service type].

J. System Software and Programming Utility: The fire alarm control panel shall be programmable
from the front panel or via a laptop program utility. The laptop program utility shall be a common
program utility regardless of panel size and configuration. The program utility shall provide for a
simple table/spreadsheet format. The utility shall provide cut and paste functionality to speed
programming of common points and functions. The utility shall provide for archival of system
programming, off-site editing and reports. The utility shall provide for system diagnostics to
assist in the set up and troubleshooting of the system during commissioning or service calls.
The control panel shall be able to upload the current system configuration without the need for
the software utility to have a previous copy. The fire alarm control panel and software utility shall
be password protected to prevent unauthorized changes, downloading or uploading of system
configuration. The software shall provide for reports to assist in battery calculations and
historical system/device data and error checking.

K. System devices shall be programmable from the fire alarm control panel, via front panel menus
or form the laptop software utility, a handheld programmer device or an Infrared Program Tool.

L. Instructions: Computer printout or typewritten instruction card mounted behind a plastic or glass
cover in a stainless-steel or aluminum frame. Include interpretation and describe appropriate
response for displays and signals. Briefly describe the functional operation of the system under
normal, alarm, and trouble conditions. Mount as directed by local AHJ.

M. Notification Appliance Circuit: ["System Sensor" and "Gentex" synchronization protocols]


[Silenceable or non-silenceable 24V dc output].

N. Voice Evacuation and Communications System: The Voice Evacuation system shall be an
integrated part of the fire alarm control panel. The Voice system will provide for centralized
control of the communication functions. Voice Evacuation system components shall be located
as indicated on the design document.

2.4 INTEGRATED VOICE EVACUATION SYSTEM

A. General requirements for the Integrated Voice System: Provide as an integral part of the fire
alarm system a full digital voice evacuation and communication control system as indicated on
the design documents. The system shall provide but not be limited to alarm evacuation tones,
digital recorded evacuation and alert messages, live voice paging and two way communication
elements. The Voice Evacuation System shall be provided with primary and standby power
equal to the requirements of the fire alarm control panel. Signals shall not stop in response to
alarm acknowledge signals, but may be silenced from signal silence commands as accepted by
local AHJ.

B. Paging System shall consist of automatic controls (via FACP System Software) and manual
controls located within a common enclosure (FCS). Amplifiers shall provide for continuous

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 10


supervision of the speaker circuits. The system shall provide for [single] [dual]
[multiple/unlimited] channels of simultaneous message broadcasting.
1. The audio system shall be provided to maximize reliability, redundancy and survivability.
The amplifiers shall be mounted with in the [FCS] [Distributed in approved equipment
enclosures]. The amplification system will be provided with full 100% redundant back-up
(one-to-one). Systems that utilized one-to-multiple amplifier back up schemes will not be
accepted. The installer shall demonstrate redundancy during system acceptance tests.
2. Digital messages will be distributed and stored within the amplifier unit to provide
survivability in case of loss of paging riser. Systems that utilize a central digital message
generator will be permitted provided a class A return loop is installed and separated by a
minimum of 10 feet and 4 hour fire rated partitions.
3. Amplifiers shall be provided with local microphone input for testing or future local paging
microphone applications.
4. Amplifier shall be provided with a NAC output and provide a sync to visual notification
circuits.
5. Amplifier shall be provided with a line level input activated by a contact closure for future
Mass Notification or other event management use.
6. Digital messages shall be standard .WAV format files managed and programmed from
the fire alarm control panel software utility suite. The prerecorded digital messages shall
be loaded in to the amplifiers as part of the regular download routine of the system
software utility.
7. The amplifier shall provide a minimum of 50 watts output and support four speaker
circuits at the amplifier (Class A or B). Each speaker circuit shall be controlled via the
FACP software for activation and tone or message broadcast. Speaker circuits shall be
calculated to provide 20% spare capacity. Speaker circuits shall be arranged so that each
floor or fire zone is served by [one] [two] circuits. Each stairwell [and elevator] shall be
provided with a separate circuit.
8. Manual control of speaker circuits shall be provided from switch modules located in the
Fire Command Station in sufficient quantity to provide for individual control of all paging
zones. [The switch module shall provide on/off control and positive indication of
circuit connection (LED light shall indicate speaker circuit status as blinking
=selected/steady=active). Each module will provide 20 circuits.] [The voice evac
switch module shall provide 6 paging and evacuation control zones. The switches
shall be arrange to provide a tactile type switch to manual activate the Evac
Message, Alert Message or make a live Page announcement. It shall be possible to
record a live message by holding the page button; the system shall repeat the
newly recorded message until deselected.]
9. The FCS shall be provided with a digital paging module (DPM). The DPM will provide for
master microphone, telephone. Audio and fire fighter riser connections. A volume control
setting will provide for stepped adjustment to compensate for nearby speaker feedback.
The Digital Paging Control Module shall provide simple page source control to allow
announcements from the master microphone or the fire fighters phone system. [The
system shall permit the patching of remote fire fighters phone to the paging
system to make live announcements.]

C. Fire Fighters Communications System


1. The system shall provide for two way fire fighters communication via a master
handset at the FCS and remote firefighters portable phone jacks or permanently
mounted fire fighters telephone stations.
2. [The system shall provide for a common talk line from the FCS to remote locations
with out the need for switches or operator intervention. Lifting the FCS master
handset will provide connection to any connected/in use remote station. A
maximum of 9 remote phones may be in service at one time.] [The system shall
provide for a full addressable phone control system. An addressable control
module will be connected to the Fire Fighter Phone Control Module via a dedicated

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 11


SLC loop. The module shall support up to 99 addressable phone circuits. Each
module can support multiple jacks or telephone stations. The Switch Module shall
provide for tactical control switch for simple on/off function, a LED shall provide
status of connection. A local sounder shall annunciate new call-in from field
stations until silenced. A maximum of 9 remote phones may be in service at one
time.]
3. [The remote fire fighter jacks shall provide a means for a portable fire fighters
handset to connect to the FCS. A storage cabinet shall be provided to house a
minimum of 5 handsets at the location approved by the local AHJ. Jacks shall be
located in areas as indicated on the design documents.
4. [The remote fire fighter handset stations shall provide a means for permanently
located two way communication stations to the FCS. The station shall be provided
with door and a lock for access to the handset. A break-glass option shall be
provided to allow access.

2.5 Auxiliary Control/Function Systems

A. Stairwell Pressurization: Provide input and output signal using an addressable modules to start
the stairwell pressurization system. Signal shall remain on until alarm conditions are cleared
and fire-alarm system is reset. Signal shall not stop in response to alarm acknowledge or signal
silence commands.

1. Pressurization starts when any alarm is received at fire-alarm control unit.


2. Alarm signals from smoke detectors at pressurization air supplies have a higher priority
than other alarm signals that start the system.
3. Provide manual control of stair pressurization functions via panel mounted control
annunciator modules as required. Control functions shall provide a minimum of positive
status of control equipment and manual control switches.

B. Smoke Control: Provide input and output signal using an addressable modules to perform
smoke control functions of the smoke management system. Signal shall remain on until alarm
conditions are cleared and fire-alarm system is reset. Signal shall not stop in response to alarm
acknowledge or signal silence commands.

1. Smoke Control starts when any alarm is received at fire-alarm control unit.
2. Alarm signals from smoke detectors at smoke control air supplies have a higher priority
than other alarm signals that start the system.
3. Provide manual control of smoke control functions via panel mounted control annunciator
modules as required. Control functions shall provide a minimum of positive status of
control equipment and manual control switches with a UL UUKL Listed Smoke Control
Station. Systems that require an external mounted annunciator shall not be acceptable.
Smoke Control Station Annunciator: Provide a UL UUKL Listed smoke control station that
provides for six zones of control per module (provide total number of zones required to
perform all smoke control functions per design documents.
4. Smoke control system shall receive the signals for action and monitoring form the
addressable control modules providing positive feedback and operation of system.
5. System shall be arranged to provide On-Auto-Off operation of controlled systems.
6. Each switch shall be capable of controlling up to 25 remote addressable relay modules.
7. System shall provide for 6 Green On, 6 Red Off and 6 White Normal and 6 Yellow
Fault LED Lights and 18 tactile switches grouped in to 6 zones. Each switch and LED
Light shall be fully programmable to provide smoke control functions and annunciation.

C. Elevator Recall:

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 12


1. Smoke detectors at the following locations shall initiate automatic elevator recall. [Alarm-
initiating devices, except those listed, shall not start elevator recall.]

a. Elevator lobby detectors except the lobby detector on the designated floor.
b. Smoke detector in elevator machine room.
c. Smoke detectors in elevator hoist way.

2. Elevator lobby detectors located on the designated recall floors shall be programmed to
move the cars to the alternate recall floor.
3. Water-flow alarm connected to sprinkler in an elevator shaft and elevator machine room
shall shut down elevators associated with the location without time delay.

a. Water-flow switch associated with the sprinkler in the elevator pit may have a delay
to allow elevators to move to the designated floor.

D. Alternative Signaling: When permitted by FNPA/Local AHJ, provide the ability to


manually activate signal circuits for use during non-fire emergency such as Tornado,
Medical Emergency, or other non-fire condition. Signals shall not operate from automatic
or manual fire alarm devices, but require a separate manual activating device or via panel
mounted annunciator control switch.

E. Door Controls: Door hold-open devices that are controlled by smoke detectors at doors in
smoke barrier walls shall [be] [not be] connected to fire-alarm system.

F. Mechanical Equipment Systems: Provide manual control switches and positive status of
mechanical systems connected to the fire alarm system for programmed automatic functions.
Provide input and output signal using an addressable modules to start the stairwell
pressurization system. Signal shall remain on until alarm conditions are cleared and fire-alarm
system is reset. Signal shall not stop in response to alarm acknowledge or signal silence
commands.

1. Automatic control starts when any alarm is received at fire-alarm control unit (or as
indicated on the control sequence of operation).
2. Provide manual control of mechanical system functions via panel mounted control
annunciator modules as required. Control functions shall provide a minimum of positive
status of control equipment and manual control switches.

G. Add other manual control or annunciation requirements to be located within the fire
alarm control panel here.

2.6 REMOTE ANNUCIATORS, PRINTERS AND NETWORKING

A. General Requirements: The fire alarm control panel shall support the addition of remote
annunciators, printers or networking as indicated on the design documents and herein specified.
All remote annunciators shall follow operational requirements of panel mounted annunciator
modules specified elsewhere.

B. Remote Annunciators description: Remote annunciators are provided to duplicate or


supplement fire alarm control panel information, annunciation, command and control and
auxiliary functions at a location indicated on the design documents separate from the fire alarm
control panel.
1. The remote annunciators shall be fully supervised from the fire alarm control panel for
data communications and power.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 13


2. Remote annunciators shall be protected from unauthorized use by key switch or other
mechanical means.
3. Remote Annunciators can be located up to 4,000 feet from the fire alarm control panel
(total wire length run).

C. Remote Alpha-numeric type Display: Annunciator functions shall be similar to those of fire-alarm
control unit for alarm, supervisory, and trouble indications, with an 80 character display.
<Manual switching functions shall match those of fire-alarm control unit, including
acknowledging, silencing, resetting and drill testing protected by a key switch enable>
<Manual switching functions shall match those of fire-alarm control unit, including
acknowledging, silencing, resetting and drill testing and eight programmable switches>

1. Mounting: [Flush using standard electrical RACO box] [Surface cabinet].

D. LED Point type Display: Annunciator functions shall provide 40 LED lights to be arranged by
device or group of zones and devices as programmed to provide general annunciation of event
status. Annunciator panel shall be provided with slide in zone descriptor labels protected from
tampering or altering. The annunciator shall provide for 20 zones, two LED lights per zones.
Each LED light shall be fully configurable to be programmed from a single device, group of
devices or zone.

E. LED/Switch Point type Display: Annunciator shall provide 20 LED Lights and 20 tactile style
switches to be arranged by device or group of zones and devices as programmed to provide
general annunciation of event status. Annunciator panel shall be provided with slide in zone
descriptor labels protected from tampering or altering. The annunciator shall provide for 20
zones, one LED light per zones. Each LED light shall be fully configurable to be programmed
from a single device, group of devices or zone. The annunciator shall provide for 20 zones, one
switch per zones. Each switch shall be fully configurable to be programmed from a single
device, group of devices or zone.

F. Smoke Control Station Annunciator: Provide a UL UUKL Listed smoke control station that
provides for six zones of control per module (provide total number of zones required to perform
all smoke control functions per design documents).
1. Smoke control system shall receive the signals for action and monitoring form the
addressable control modules providing positive feedback and operation of system.
2. System shall be arranged to provide On-Auto-Off operation of controlled systems.
3. Each switch shall be capable of controlling up to 25 remote addressable relay modules.
4. System shall provide for 6 Green On, 6 Red Off and 6 White Normal and 6 Yellow
Fault LED Lights and 18 tactile switches grouped in to 6 zones. Each switch and LED
Light shall be fully programmable to provide smoke control functions and annunciation.

G. Smoke Control Graphic Annunciator Panel: Provide as indicated on the design drawings a
Graphic Smoke Control Station Panel. The Graphic Smoke Control Station panel shall be UL
UKLL Listed. Provide for zones of control and annunciation (provide total number of zones
required to perform all smoke control functions per design documents).
1. Smoke control system shall receive the signals for action and monitoring form the
addressable control modules providing positive feedback and operation of system.
2. System shall be arranged to provide On-Auto-Off operation of controlled systems.
3. Each switch shall be capable of controlling up to 25 remote addressable relay modules.
4. System shall provide for Green On, Red Off and White Normal and Yellow Fault
LED Lights and switches grouped in to logical zones on the panel. Each switch and LED
Light shall be fully programmable to provide smoke control functions and annunciation.
5. Control Switches shall be toggle, rotary or key switch type as required by local AHJ.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 14


6. Graphic layout shall provide a layout of controlled systems; color coded and represents
all associated smoke control systems. Layout shall be submitted to the local AHJ for
approval and acceptance prior to fabrication and installation.

H. Multi-Interface Module: provide an interface module to provide gateway communications to the


peripheral devices:
1. Multi-Interface Module shall be located within the fire alarm control panel or remote. If
mounted remote the Multi-Interface Module shall be provided in a dedicated enclosure
with an interface port on the front panel to provide final field connection of supported
device.
2. The Multi-Interface Module shall support communications to the following peripheral
devices:
a. Panel or Remote Printer: Printer shall be listed and labeled by an NRTL as an
integral part of fire-alarm system.
b. Graphic Event Management Workstation

I. System Printer: The fire alarm control panel shall provide communications to a printer for the
purpose of printing events in real time or to print reports as initiated from the fire alarm control
panel.
1. The printer shall be supervised for connection and power.
2. The printer shall be provided with a UPS back up system of equal capacity as the fire
alarm control panel.
3. The printer shall be listed by a NRTL for the use as a fire alarm printer.

J. System Networking: The fire alarm control panel shall provide the ability to network to other fire
alarm control panels.
1. Peer-to-Peer Networking: Systems shall provide for all control panels to participate in
shared information and command and control functions as programmed to provide a
single life safety fire protection system. No master controller will be required.
a. The network shall permit up to 128 control panels or a minimum of 130,000
addressable points per total network.
b. Network shall be UL S2203 Listed.
c. Network topology shall utilize standard networking technologies, and available for
installation over cooper wiring or multi-mode fiber optic cabling.
d. System shall be capable of Class B Style 4 or Class A Style 7 wiring
configurations.
e. Network Modules shall provide for regeneration of network signal to boost panel-
to-panel distance. Limitations of wiring will be based on cable type (cooper or fiber)
per manufacturers requirements. A maximum distance of 4,000 feet for cooper
wiring and 3KM for Fiber Optic cable shall be possible.
f. In the event of communication failure, the fire alarm control panel, or associated
panels still communicating, shall continue to operate and respond to alarm
conditions and perform programmed functions.
2. Ethernet Networking: Systems shall provide for all control panels to participate in network
using standard IP topology. The system will provide annunciation information only to a
designated master control panel.
a. The network shall permit up to 128 control panels or a minimum of 130,000
addressable points per total network.
b. Network topology shall utilize standard networking technologies each panel shall
be assigned a network address (IP address) and connected to the facility network.
c. Network Modules shall be located in the control panel or remote from the control
panel at a maximum distance of 4,000 feet.
d. Panel to Panel distance limitations will be limited only by network connectivity.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 15


e. In the event of communication failure, the fire alarm control panel, or associated
panels still communicating, shall continue to operate and respond to alarm
conditions and perform programmed functions.

2.7 DIGITAL ALARM COMMUNICATOR TRANSMITTER

A. Digital alarm communicator transmitter shall be acceptable to the remote central station and
shall comply with UL 632 and be listed and labeled by an NRTL.

B. Functional Performance: Unit shall receive an alarm, supervisory, or trouble signal from fire-
alarm control unit and automatically capture [one] [two] telephone line(s) and dial a preset
number for a remote central station. When contact is made with central station(s), signals shall
be transmitted. If service on [either] line is interrupted for longer than 45 seconds, transmitter
shall initiate a local trouble signal and transmit the signal indicating loss of telephone line to the
remote alarm receiving station over the remaining line. Transmitter shall automatically report
telephone service restoration to the central station. If service is lost on both telephone lines,
transmitter shall initiate the local trouble signal.

C. Local functions and display at the digital alarm communicator transmitter shall include the
following:

1. Verification that both telephone lines are available.


2. Programming device.
3. LED display.
4. Manual test report function and manual transmission clear indication.
5. Communications failure with the central station or fire-alarm control unit.
6. <Insert local function>.

D. Digital data transmission shall include the following:

1. Address of the alarm-initiating device.


2. [Address] [Zone] of the supervisory signal.
3. [Address] [Zone] of the trouble-initiating device.
4. Loss of ac supply or loss of power.
5. Low battery.
6. Abnormal test signal.
7. Communication bus failure.
8. <Insert signal to be transmitted>.

E. Secondary Power: Integral rechargeable battery and automatic charger.

F. Self-Test: Conducted automatically every 24 hours with report transmitted to central station.

G. DACT shall be located with in the fire alarm control panel or remotely located as approved by
the local AHJ, in accordance with applicable codes and regulations.

2.8 MANUAL FIRE-ALARM BOXES

A. General Requirements for Manual Fire-Alarm Boxes: Comply with UL 38. Boxes shall be
finished in red with molded, raised-letter operating instructions in contrasting color; shall show
visible indication of operation; and shall be mounted on recessed outlet box. If indicated as
surface mounted, provide manufacturer's surface back box.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 16


1. Double-action mechanism requiring two actions to initiate an alarm, [pull-lever]
[breaking-glass] [plastic-rod] type; with [integral] [attached] addressable module
arranged to communicate manual-station status (normal, alarm, or trouble) to fire-alarm
control unit.
2. Station Reset: Key-operated switch keyed to match fire alarm control panel, shall not
cause alarm condition to be transmitted when opened.
3. Device Status LED shall be visible from the front of the station without opening the station
to reveal the LED.
4. Indoor Protective Shield: Factory-fabricated clear plastic enclosure hinged at the
top to permit lifting for access to initiate an alarm. Lifting the cover actuates an
integral battery-powered audible horn intended to discourage false-alarm
operation.
5. Weatherproof Protective Shield: Factory-fabricated clear plastic enclosure hinged
at the top to permit lifting for access to initiate an alarm.

2.9 SYSTEM SMOKE DETECTORS

A. General Requirements for System Smoke Detectors:

1. Comply with UL 268; operating at 24-V dc, nominal.


2. Detectors shall be two-wire type.
3. Provide [Class X isolator] [Style 6 non-isolator] type detectors.
4. Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
5. Base Mounting: Detector and associated electronic components shall be mounted in a
twist-lock module that connects to a fixed base. Provide terminals in the fixed base for
connection to building wiring.
6. Self-Restoring: Detectors do not require resetting or readjustment after actuation to
restore them to normal operation.
7. Integral Visual-Indicating Light: Two Tri-color LED type indicating lights shall be
programmed independently or to follow detector status.
8. Remote Control: Unless otherwise indicated, detectors shall be digital-addressable type,
individually monitored at fire-alarm control unit for calibration, sensitivity, and alarm
condition and individually adjustable for sensitivity.
a. Provide multiple levels of detection sensitivity for each sensor.
9. Provide different sensitivity levels based upon time of day.
Device Summing: Detectors shall provide the ability to participate in detection groups,
providing a group summing alarm, based upon a combined obscuration level for up to 8
detectors of equivalent device type.
10. Detectors shall provide up to two pre-alarm smoke obscuration levels in addition to the
alarm obscuration level.
11. Detectors shall be programmable from the control panel, a handheld programmer and or
a remote IR Programming tool to set address, detector operating parameters.

B. Photoelectric Smoke Detectors:

1. Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Present sensitivity selected.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 17


d. Sensor range (normal, dirty, etc.).

C. Ionization Smoke Detector:

1. Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system.
2. An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:

a. Primary status.
b. Device type.
c. Present sensitivity selected.
d. Sensor range (normal, dirty, etc.).

D. Duct Smoke Detectors: Photoelectric type complying with UL 268A.

1. Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Present sensitivity selected.
d. Sensor range (normal, dirty, etc.).
3. Each sensor shall have multiple levels of detection sensitivity.
4. Sampling Tubes: Design and dimensions as recommended by manufacturer for specific
duct size, air velocity, and installation conditions where applied.

E. Combination Photoelectric Smoke and Heat Detectors:

1. Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Present sensitivity selected.
d. Sensor range (normal, dirty, etc.).
3. The system shall provide for discrimination between the Smoke and Heat sensor. The
system shall permit the Smoke Sensor to report as a Supervisory condition while the
Heat Sensor reports as an Alarm condition based on its respective alarm threshold set-
point.
4. The detector shall use one address point on the system SLC Loop.
5. Devices not capable for discrimination of Smoke and Heat functions shall provide
separate units programmed to operate as noted in this section.

2.10 HEAT DETECTORS

A. General Requirements for Heat Detectors: Comply with UL 521.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 18


1. An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:

a. Primary status.
b. Device type.
c. Present sensitivity selected.
d. Sensor range (normal, dirty, etc.),

B. Heat Detector, Combination Type: Actuated by either a fixed temperature of [135 - 190 deg F
(57 - 88 deg C)] <Insert temperature> or a rate of rise that exceeds 15 deg F (8 deg C)
between 135 and 70 deg F (57 - 77 deg C) per minute unless otherwise indicated.

1. Mounting: [Adapter plate for outlet box mounting] [Twist-lock base interchangeable
with smoke-detector bases].
2. Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
3. Provide two pre-alarm levels between 70 and 190 deg F (21 - 88 deg C).

C. Continuous Linear Heat-Detector System:

1. Detector Cable: Rated detection temperature [155 deg F (68 deg C)] [172 deg F (78
deg C)] [190 deg F (88 deg C)] [220 deg F (104 deg C)] <Insert temperature>. NRTL
listed for "regular" service and a standard environment. Cable includes two steel actuator
wires twisted together with spring pressure, wrapped with protective tape, and finished
with PVC outer sheath. Each actuator wire is insulated with heat-sensitive material that
reacts with heat to allow the cable twist pressure to short- circuit wires at the location of
elevated temperature.
2. Control Unit: Two-zone or multi-zone unit as indicated. Provide same system power
supply, supervision, and alarm features as specified for fire-alarm control unit.
3. Signals to Fire-Alarm Control Unit: Any type of local system trouble shall be reported to
fire-alarm control unit as a composite "trouble" signal. Alarms on each detection zone
shall be individually reported to central fire-alarm control unit as separately identified
zones.
4. Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.

2.11 ADDRESSABLE DETECTOR BASES

A. General Requirements for System Addressable Detector Bases:

1. Comply with UL 268; operating at 24-V dc, nominal.


2. Detectors shall be two-wire type.
3. Provide for compatibility with [Class X isolator] [Style 6 non-isolator] type detectors.
4. Base Mounting: Detector and associated electronic components shall be mounted in a
twist-lock module that connects to a fixed base. Provide terminals in the fixed base for
connection to building wiring.
5. Detector bases shall be available in a number of configurations and provided as indicated
on the design documents as follows:
a. Standard Base: Standard bases shall be provided for all installation locations. The
base shall be available in a 6 diameter flangeless option to provide a finished
appearance. The 6 base shall mount directly to a 3 1/2 or 4 octagon box, 4
square box (with or without plaster ring) or a single gang box.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 19


b. Standard Base: Standard bases shall be provided for all installation locations. The
base shall be available in a 4 diameter. The 4 base shall mount directly to a 3
1/2 or 4 octagon box, 4 square box (with or without plaster ring) or a single gang
box.
c. Relay Base: Relay base shall provide for installation to a 4 square box minimum
11/2 deep. The relay base shall provide relay functions that follow the detector or
programmed to follow independent control from the fire alarm control panel. The
relay shall be rated at 2A 30VDC. The relay base shall be powered from the SLC
Loop. Relay bases that require separate 24VDC power sources shall be installed
as to supervise the power via additional power supervision relays and addressable
modules. No more than 4 relay bases requiring separate power shall be provided
to a single power circuit.
d. Sounder Base: Sounder base shall provide for installation to a 4 square box
minimum 11/2 deep. The sounder base shall provide audible functions that follow
the detector or programmed to follow independent control from the fire alarm
control panel. The sounder base shall receive a dedicated 24VDC power source
that is installed and supervised by an end of line relay and addressable monitor
module. No more than 15 sounder bases shall be powered from a single power
circuit. The sounder base shall provide a minimum 85db audible signal. The signal
shall be programmed from the control panel to annunciate a tone pattern of
constant on; slow; fast; temporal; walk-test; alert; action.
1) For hotel suite application the system shall provide the activation of a suite
smoke detector shall sound the local detector sounder base and the
associated sounder bases of the suite. The sounder base will also be
activated in case of general alarm. Systems that cannot provide this
program feature shall provide a dedicated NAC for the suite and mini-
sounder horns equivalent in operation to the sounder base functions listed
above.
e. All bases shall support remote LED functions as required or indicated on the
design documents.

2.12 ADDRESSABLE INTERFACE MODULES

A. General Requirements for System Addressable Interface Modules:

1. Comply with UL 268; operating at 24-V dc, nominal.


2. Modules shall be two-wire type.
3. Provide [Class X isolator] [Style 6 non-isolator] type modules.
4. Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
5. Module Mounting: Module and associated electronic components shall be mounted to a
standard electrical box with sufficient depth to permit all connections and wire. Provide
terminals in the module for connection to building wiring.
6. Self-Restoring: Modules do not require resetting or readjustment after actuation to
restore them to normal operation.
7. Integral Visual-Indicating Light: One Red LED type indicating light shall be programmed
independently or to follow detector status.
8. Remote Control: Unless otherwise indicated, modules shall be digital-addressable type,
individually monitored at fire-alarm control unit for change of status: alarm condition and
supervisory condition or activation of output.
9. Number of settable levels in fire-alarm control unit varies among manufacturers and
between detector types. Indicate specific number of levels on Drawings or in "Remarks"
column of a detector schedule.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 20


10. Modules shall be compatible with Remote LED to provide status of module when hidden
from view.
11. Modules shall be programmable from the control panel, a handheld programmer and or a
remote IR Programming tool to set address, detector operating parameters.

B. Addressable Monitor Module (full size):

1. Module address shall be accessible from fire-alarm control unit and shall be able to
identify the monitor module's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Input type (alarm, supervisory, trouble).
d. Sensor activation type (open, short)
3. Provide for a single input, Class A or B wiring.
4. Monitor modules will be used to interface dry contact closures from auxiliary devices such
as sprinkler devices, sub-systems, HVAC controls or other devices/systems that require
status and indication at the fire alarm control panel.

C. Addressable Monitor Module (mini):

1. Module address shall be accessible from fire-alarm control unit and shall be able to
identify the monitor module's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Input type (alarm, supervisory, trouble).
d. Sensor activation type (open, short)
3. Provide for a single input, Class B wiring.
4. Mini-Module shall fit within a device or the devices backbox to be monitored or mounted
in an approved enclosure.

D. Addressable Dual Monitor Module (full size):

1. Module address shall be accessible from fire-alarm control unit and shall be able to
identify the monitor module's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Input type (alarm, supervisory, trouble).
d. Sensor activation type (open, short)
3. Provide for two inputs, Class B wiring.
4. Monitor modules will be used to interface dry contact closures from auxiliary devices such
as sprinkler devices, sub-systems, HVAC controls or other devices/systems that require
status and indication at the fire alarm control panel.
5. Dual Monitor Module shall provide for two input zones to the fire alarm control panel
utilizing one SLC Loop address. The inputs shall be programmable as follows:

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 21


a. Input 1: No Input; Detection; Waterflow; PreAlarm 1; PreAlarm 2; Supervisory;
Trouble; Process; PAS Inhibit; Reset; Silence; Acknowledge; Drill; Fan Restart.

E. Addressable Zone Interface Monitor Module (full size):

1. Module address shall be accessible from fire-alarm control unit and shall be able to
identify the monitor module's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Input type (alarm, supervisory, trouble).
d. Sensor activation type (open, short)
3. Provide for a single input, Class A or B wiring.
4. Monitor modules will be used to interface two wire smoke (conventional) detectors.
a. Zone Interface Monitor Module will receive 24VDC resettable power from the fire
alarm control panel.

F. Addressable Control Module (Notification Circuit):

1. Module address shall be accessible from fire-alarm control unit and shall be able to
identify the monitor module's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Output type (Notification, Solenoid Release).
d. Sensor activation type (open, short)
3. Provide for a single output, Class A or B wiring.
a. Control modules will be used to external power supplies to the device circuit
b. Control modules will provide supervision of wiring while in normal state.
c. Control modules shall be programmable for output pattern of:
1) Continuous; Slow; Fast; Temporal; Walk-test; Timed; or Custom.

G. Addressable Relay Module:

1. Module address shall be accessible from fire-alarm control unit and shall be able to
identify the monitor module's location within the system.
2. An operator at the protected premises, having the designated access level, shall be able
to manually access the following for each detector:

a. Primary status.
b. Device type.
c. Output type (Notification, Solenoid Release).
d. Sensor activation type (open, short)
3. Provide for a single relay output, DPDT.
a. Provide a single non-supervised input for positive indication of the controlled
device. The input shall not require an additional address from the SLC Loop.
Modules that do not provide the positive input feedback point shall be provided
with a separate addressable input monitor module for current or future use.
b. The module Tri-color LED for device status.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 22


2.13 VESDA EARLY WARNING SMOKE DETECTION SYSTEM

A. General Requirements for VESDA Early Warning Smoke Detection Systems: The VESDA
System shall be connected to the fire alarm control panels via a High-Level Interface
(HLI). The VESDA system will communicate status via the HLI and not require the use of
addressable device addresses. .

B. High Level Interface (HLI): The HLI will provide a gateway from the VESDA Network to the
fire alarm control panel. The connection will create a virtual point that in turn activates
the fire alarm control panel functions. The interface allows for bi-direction
communications and will annunciate activity of the Vesda System(s) connected. The HLI
shall be housed in a dedicated enclosure, receive primary and secondary power from the
fire alarm control panel.

C. VESDA Detection systems shall be installed in accordance with manufactures


recommendations. Vesda Detection Systems are as follows:
1. Vesda LaserCOMPACT: Aspiration Based Laser Smoke Detection System
providing a single zone of protection. Unit provides for relay and VESDAnet
communications to the HLI. Maximum area of coverage is 8,000 square feet.
Sensitivity range is 0.0015-6.0 obs/ft.
2. Vesda LaserPLUS: Aspiration Based Laser Smoke Detection System providing a
single zone of protection from four separate sources (piping networks). Unit
provides for 7 programmable relays and VESDAnet communications to the HLI.
Maximum area of coverage is 20,000 square feet. Sensitivity range is 0.0015-6.0
obs/ft. The detector provides programmable outputs for Alert, Action, Fire 1 and
Fire 2 levels based on sensitivity settings.
3. Vesda LaserSCANNER: Aspiration Based Laser Smoke Detection System
providing a single zone of protection from four separate sources (piping
networks). An internal manifold system allows for the Unit to provide four zones of
detection. Unit provides for 7 programmable relays and VESDAnet
communications to the HLI. Maximum area of coverage is 20,000 square feet.
Sensitivity range is 0.0015-6.0 obs/ft. The detector provides programmable outputs
for Alert, Action, Fire 1 and Fire 2 levels based on sensitivity settings.
4. Vesda LaserFOCUS: Aspiration Based Laser Smoke Detection System providing a
single zone of protection. Unit provides for relay and VESDAnet communications
to the HLI. Maximum area of coverage is 2,500/5,000 square feet. Sensitivity range
is 0.008-6.25 obs/ft.
5. Optional Modules: Vesda Display Modules provide real time status of VESDA
detection unit (available for LaserPLUS, LaserSCANNER and LaserCOMPACT only.
Display Module provides for local control/reset functions. Programmer Module
allows for VESDA detection programming from a single unit or via the VESDAnet
communications connection.

2.14 NOTIFICATION APPLIANCES

A. General Requirements for Notification Appliances: Connected to notification appliance signal


circuits, zoned as indicated, equipped for mounting as indicated and with screw terminals for
system connections.

1. Combination Devices: Factory-integrated audible and visible devices in a single-


mounting assembly, equipped for mounting as indicated and with screw terminals for
system connections.
2. Audible Devices: Capable of driving code in three temporal patterns and user definable
four-second pattern.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 23


B. Chimes, Low-Level Output: Vibrating type, 75-dBA minimum rated output.

C. Chimes, High-Level Output: Vibrating type, 81-dBA minimum rated output.

D. Alarm Notification Appliances: Electric-vibrating-polarized type, 24-V dc; with provision for
housing the operating mechanism behind a grille. Comply with UL 464. Horns shall produce a
sound-pressure level of 90 dBA, measured 10 feet (3 m) from the horn, using the coded signal
prescribed in UL 464 test protocol.

E. Speakers: All speakers shall operate on 25 [70.7] VRMS or with field selectable output taps
from 0.5 to 2.0 Watts. Speakers in corridors and public spaces shall produce a nominal sound
output of 84 dBA at 10 feet (3m). Frequency response shall be a minimum of 400 HZ to 4000
HZ. The back of each speaker shall be sealed to protect the speaker cone from damage and
dust.

F. Visible Notification Appliances: Xenon strobe lights comply with UL 1971, with clear or nominal
white polycarbonate lens mounted on an aluminum faceplate. The word "FIRE" is engraved in
minimum 1-inch- (25-mm-) high letters on the lens.

1. Rated Light Output:

a. [15] [15/75] [30] [75] [110] [135] [150] [177] [185] <Insert value> cd.
b. 15/30/75/110 cd, selectable in the field.

2. Mounting: Wall mounted unless otherwise indicated.


3. For units with guards to prevent physical damage, light output ratings shall be determined
with guards in place.
4. Flashing shall be synchronized with other units in accordance with NFPA 72.
5. Strobe Leads: Factory connected to screw terminals.
6. Mounting Faceplate: Factory finished, [red] [white].

G. Combination Alarm/Visual Notification Appliances:


1. Shall comply with all requirements as listed above for individual units and be approved as
a single unit by a NRTL.

2.15 REMOTE NOTIFICATION POWER SUPPLIES

A. Remote Notification Appliance Power Supplies shall be provided to accommodate system


design requirements of audible and visual notification circuits.

B. Notification Appliance Circuit Power Supplies shall provide for the following features:
1. Listed NAC Synchronization using System Sensor, Wheelock, or Gentex (Commander
Series) appliances.
2. Cascade up to 10 power supplies (four with Gentex) with strobe timing maintained.
3. Operates as a sync follower or a sync generator (default).
4. Contains two, fully-isolated input/control circuits (triggered from FACP
5. Notification Appliance Circuit [NAC expander mode] or jumper permanently on
[standalone mode]).
6. Four Class B (Style Y) or four Class A (Style Z) (with 27-034 Module) Notification
Appliance Circuits.
7. 8.0 A full load output (3.0 A maximum per circuit) in NAC expander mode (UL 864).
8. 6.0 A continuous output in stand-alone mode (UL 1481).
9. Compatible with coded inputs; signals passed through.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 24


10. Optional power supervision relay (27-035).
11. In stand-alone mode, output power circuits may be configured as resettable (reset line
from FACP required) or non-resettable or a mix of two and two.
12. Fully regulated and filtered power output (optimal for powering four-wire smoke detectors,
annunciators and other system peripherals requiring regulated/filtered power).
13. Power-limiting technology meets power-limiting requirements.
14. Normally-closed trouble contact.
15. Fully supervised power supply, battery and Notification Appliance Circuits.
16. Selectable earth fault detection.
17. AC trouble report selectable for immediate or 8 hour delay.
18. Works with any UL 864 fire alarm control which utilizes an industry standard reverse-
polarity notification circuit (including unfiltered and unregulated bell power).
19. Requires input trigger voltage of 9.0 - 32 VDC.
20. Self-contained in compact, lockable cabinet (15" [38.1 cm] H x 14.5" [36.8 cm] W x 2.75"
[7.0 cm] D).
21. Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet
capable of housing 7.0 AH batteries.

2.16 MAGNETIC DOOR HOLDERS

A. Description: Units are equipped for wall or floor mounting as indicated and are complete
with matching doorplate.

1. Electromagnet: Requires no more than 3 W to develop 25-lbf (111-N) holding force.


2. Wall-Mounted Units: Flush mounted unless otherwise indicated.
3. Rating: 24-V ac or dc.
4. Rating: 120-V ac.

B. Material and Finish: Match door hardware.

2.17 DEVICE GUARDS

A. Description: Welded wire mesh of size and shape for the manual station, smoke
detector, gong, or other device requiring protection.

1. Factory fabricated and furnished by manufacturer of device.


2. Finish: Paint of color to match the protected device.

2.18 VIDEO IMAGE DETECTION SYSTEMS

A. Description: A Video Image Detection (VID) system shall be provided as indicated on the
fire alarm drawings. The system shall provide connection to the fire alarm control panel
via addressable interface modules, and receive primary and secondary power from an
approved fire alarm power supply system.

B. The VID System shall utilize an IP Camera with the required analytics to detect flame,
smoke, radiated (reflected) flame and motion located within the camera (analytics on the
edge), to facilitate speed and accuracy of detection without lowering bandwidth of
traditional network systems. Analytics located in the camera will provide additional
redundancy and survivability in the event of network communication loss, providing that
each IP camera can operate independently of the system NVR or software. The system

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 25


shall be monitored by the fire alarm panel and a network video recorder with user
interface software compatible with standard web browsers. Systems that utilize detection
analytics at a central collection point shall not be acceptable.

1. The IP Camera shall be capable of detection and alarming of a variety of events.


Once in alarm state it can signal the fire alarm control panel via a series of contact
closures located on the IP Camera. The IP Camera shall be capable of signaling
system software via an IP connection through the network to the system Network
Video Recorder (NVR). Type of events shall be defined as:
a. Flaming Fires: a specific flame pattern consisting of a bright cone of the
flame and the flickering corona.
b. Reflected Fire Light: detects the flickering component of the fire light
reflected off of a surface facing the fire, but not in direct view of the IP
Camera.
c. Smoke Plumes: identifies the anomalies that are caused by smoke and
analyze the progression over a period of time to identify a growing smoke
plume.
d. Ambient Smoke: monitors the light diffusion from light sources and bright
objects in the video image to detect a pattern that is consistent with slow
accumulations of smoke.
e. Intrusion Detection: Monitor multiple areas of the video image for motion of
objects within the field of view.
2. The IP camera shall provided with the following outputs:
a. Three relays (dry contacts) programmable for user defined operations, with a
minimum of one relay designated for supervision/trouble conditions, one for
alarm condition of smoke and one for the alarm condition of flame.
b. An IP connection to the network the connection shall also be RJ45 and
compatible with Non-PoE or PoE network switches as an additional source
of camera power. The network connection shall provide for a pathway to the
VID software and NVR.
c. A BNC connector shall provide standard analog video output for local
aiming/focus assistance or connection to security related systems.
3. The IP Camera shall provide a minimum 640x480 NTSC video image.
4. The IP Camera shall be provided with a fixed focus lens. The lens options shall
provide a 2.8MM lens, 8MM lens or 6.1MM lens (82, 44 or 34 Degree field of view).
5. The IP camera nominal operating temperature range is 32-122 Degree F. For
applications that require operation below 32 Degree F or above 122 Degree F
provide an environmental housing suitable for the application. For areas that
require a hazard rating for explosion proof provide a rated camera housing
suitable for the application.
6. The IP Camera shall be FM and UL 286B Approved.

C. The VID System shall be provided with a Network Video Recorder (NVR) Server to
provide archive or event recordings.

1. Each Server shall consist of a 3U rack mounted assembly. The mounting rack shall
be installed in a surface or recess cabinet as indicated on the drawings. All
switches, indicator lamps and meters shall be visible and accessible. The VID NVR
server shall perform but not necessarily be limited to, the following functions:
a. Each NVR shall operate from a 120 VAC supply and be capable of operating
from a stand-by battery
b. Each NVR shall have a built-in watchdog circuit to monitor the NVRs
integrity.
c. Each NVR unit shall communicate with a user interface. The user interface
shall provide an alarm-reset switch, alarm delay switch, alarm confirmation

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 26


switch, system trouble indicator, and audible indications of trouble or alarm
events.
d. The NVR shall be capable of support a minimum of eight (8) IP Cameras and
expandable to 32 IP Cameras.
e. The NVR shall be provided with a minimum of 1TB of storage, expandable to
8TB. The unit shall provide a minimum of 30 days of recorded storage.

D. The VID System User Interface (software) shall be provided as a Graphical User Interface
(GUI).
1. The GUI shall provide the following:
a. The GUI shall connect to an unlimited number of servers to provide user
interface for event management of connected servers.
b. The system shall permit remote viewing regardless of physical location.
Network administration shall control access via password/administration
rights to the network.
c. The servers shall be protected from unauthorized access via user login and
password protection. The software shall provide two levels of password
protection Administrator and Operator.
d. The GUI shall provide for viewing in multiple levels from maps, floor plans
and live video.
e. System shall provide for email notification of events, to include a text of the
event condition and a snapshot of the alarm event.
f. The system shall provide for voice annunciation of change of event states.
g. Events shall automatically bring the GUI to the front of all other applications
during alarm events.
h. The software shall provide administrative and operator tools for viewing,
searching and downloading archived and live events. The software shall
provide administrative tools for the setting of IP Camera parameters,
detection sensitivity and zones, and relay operation.
i. For UL Listed systems, the PC shall be provided as part of a UL listed
system package, provide a touch screen interface as well as keyboard,
mouse and speakers.
j. Coordinate network communication devices (switches, routers, servers) with
IT support to insure all devices are compatible and provided with power
requirements equal to or in excess fo the fire alarm control panel
requirements.

2.19 GRAPHIC EVENT MANAGEMENT SYSTEM

A. Description: A Graphic Event Management Windows PC Based Graphic User Interface to


the fire alarm system to provide enhanced information and instructions to the system
user and first responders. The system shall be UL S3217 listed.

B. The software shall provide easy to use intitive graphics and directions to assist operator
to view information related to fire, supervisory, trouble and other system condition.
System shall automatically have priority over other applications on the workstation. The
software shall priorities events based on programming and event type, with fire
conditions taking highest priority. Events shall be color-coded and dynamically change
in real time.

C. The workstation shall provide for password protection for administrative and operator
levels.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 27


D. The workstation shall provide for a shortcut onscreen navigation soft-key area to provide
basic user functions such as device detail, group view, zone view, all devices, print, page
or device navigation, action key, system alarm silence, system acknowledge, system drill
and system reset. Tally counters shall be provided to indicate number of events active
and in total in the system by alarm, supervisory and trouble status.

E. The system shall permit programmable views for each individual point of the fire alarm
system. The views shall be determined to provide an overview of the alarm location, a
floor plan of the device location in respect to immediate areas, and a detail view of the
immediate area in alarm. The system shall permit field programming without the need of
offsite support. The system shall receive updated information of alarm points added from
the fire alarm systems being monitored, updating the text description without user
interaction. New devices added to fire alarm panels shall be transmitted the workstation
for programming without need for additional data input. The system shall permit the
importing of the fire alarm system data base directly to the workstation to assist in
programming and insure all fire alarm control points are accounted for.

F. The system shall provide a table style format of all event conditions, allowing the
operator to filter between alarm, supervisory and trouble conditions.

G. The system shall provide for the import of AutoCAD drawings in .WMF format, as well as
other standard formats such as .TIFF, .JPEG, and other standard media formats. The
system will also allow for voice instructions per monitored point to provide voice
instructions of event.

H. The system shall provide for automatic E-mail notification to emergency, administrative
or maintenance staff.

I. The system shall provide dynamic take action documents per device monitored for both
alarm and trouble conditions. The message will be fully customized to provide plan text
operator action notes for each event device. Separate alarm and trouble messages will
be provided per point. Alarm event messages shall be coordinated with facility fire safety
plan to coordinate emergency response efforts. Trouble conditions shall direct operator
to preventive actions to take, notification requirements for maintenance and service
provider.

J. The system shall provide for the hyperlink of device icons to call up external links or to
open IP Cameras on the network for live camera video feed.

K. The system shall provide for archival of all event and operator actions. The system shall
provide for reports of system status, device status, history and be fully customized by
the administrator. Search tools shall be provided to assist the operator or administrator
to find devices based on a word search utility.

L. The workstation shall have the following minimum capabilities and hardware
requirements:
a. Pentium 4 Processor (minimum)
b. Microsoft Windows XP Professional or Server 2003 Operating System
c. 2GB RAM Memory
d. 1GB hard drive
e. RS232 and RS485 connections for control panel and network interfaces
f. Sound card with speakers
g. Keyboard and mouse
h. XGA or WXGA video card
i. 19 VGA Monitor (touch-screen)

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 28


j. Wall or desk mount as a single enclosure
k. USB port

PART 3 - EXECUTION

3.1 EQUIPMENT INSTALLATION

A. Comply with NFPA 72, NFPA 101 and requirements of authorities having jurisdiction for
installation of fire-alarm equipment. Install all electrical wiring in compliance with requirements
of NFPA 70, including but not limited to, article 760 Fire Alarm Systems.

B. Equipment Mounting: Install fire-alarm control unit on concrete base with tops of cabinets not
more than 72 inches (1830 mm) above the finished floor. Comply with requirements for
concrete base specified in Division 03 Section "[Cast-in-Place Concrete] [Miscellaneous Cast-
in-Place Concrete]."

1. Install seismic bracing. Comply with requirements in Division 26 Section "Vibration and
Seismic Controls for Electrical Systems."
2. Install dowel rods to connect concrete base to concrete floor. Unless otherwise
indicated, install dowel rods on 18-inch (450-mm) centers around the full perimeter of
concrete base.
3. For supported equipment, install epoxy-coated anchor bolts that extend through concrete
base and anchor into structural concrete floor.
4. Place and secure anchorage devices. Use setting drawings, templates, diagrams,
instructions, and directions furnished with items to be embedded.
5. Install anchor bolts to elevations required for proper attachment to supported equipment.

C. Equipment Mounting: Install fire-alarm control unit on finished floor with tops of cabinets not
more than 72 inches (1830 mm) above the finished floor.

1. Comply with requirements for seismic-restraint devices specified in Division 26 Section


"Vibration and Seismic Controls for Electrical Systems."

2. Comply with requirements for seismic-restraint devices specified in Division 26 Section


"Vibration and Seismic Controls for Electrical Systems."

D. Connecting to Existing Equipment: Verify that existing fire-alarm system is operational


before making changes or connections.

1. Connect new equipment to existing control panel in existing part of the building.
2. Connect new equipment to existing monitoring equipment at the supervising
station.
3. Expand, modify, and supplement existing [control] [monitoring] equipment as
necessary to extend existing [control] [monitoring] functions to the new points.
New components shall be capable of merging with existing configuration without
degrading the performance of either system.

E. Smoke- or Heat-Detector Spacing:

1. Comply with NFPA 72, "Smoke-Sensing Fire Detectors" Section in the "Initiating Devices"
Chapter, for smoke-detector spacing.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 29


2. Comply with NFPA 72, "Heat-Sensing Fire Detectors" Section in the "Initiating Devices"
Chapter, for heat-detector spacing.
3. Smooth ceiling spacing shall not exceed [30 feet (9 m)] <Insert distance>.
4. Spacing of detectors for irregular areas, for irregular ceiling construction, and for high
ceiling areas shall be determined according to Appendix A [or Appendix B] in NFPA 72.
5. HVAC: Locate detectors not closer than [3 feet (1 m)] [5 feet (1.5 m)] from air-supply
diffuser or return-air opening.
6. Lighting Fixtures: Locate detectors not closer than 12 inches (300 mm) from any part of
a lighting fixture.

F. Duct Smoke Detectors: Comply with NFPA 72 and NFPA 90A. Install sampling tubes so they
extend the full width of duct.

G. Heat Detectors in Elevator Shafts: Coordinate temperature rating and location with sprinkler
rating and location.

H. Single-Station Smoke Detectors: Where more than one smoke alarm is installed within a
dwelling or suite, they shall be connected so that the operation of any smoke alarm causes the
alarm in all smoke alarms to sound.

I. Remote Status and Alarm Indicators: Install near each smoke detector and each sprinkler
water-flow switch and valve-tamper switch that is not readily visible from normal viewing
position.

J. Audible Alarm-Indicating Devices: Install not less than 6 inches (150 mm) below the ceiling.
Install bells and horns on flush-mounted back boxes with the device-operating mechanism
concealed behind a grille.

K. Visible Alarm-Indicating Devices: Install adjacent to each alarm bell or alarm horn and at least 6
inches (150 mm) below the ceiling.

L. Device Location-Indicating Lights: Locate in public space near the device they monitor.

M. Fire-Alarm Control Unit: Surface mounted, with tops of cabinets not more than 72 inches (1830
mm) above the finished floor.

3.2 System Sequence of Operation

A. The system shall function and operate in accordance with NFPA and local AHJ requirements.
Refer to System Sequence of Operation Matrix [in appendix ##] [on the fire alarm shop
drawings].

1. Verify that hardware and devices are NRTL listed for use with fire-alarm system in this
Section before making connections.

3.3 CONNECTIONS

A. For fire-protection systems related to doors in fire-rated walls and partitions and to doors in
smoke partitions, comply with requirements in Division 08 Section "Door Hardware." Connect
hardware and devices to fire-alarm system.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 30


1. Verify that hardware and devices are NRTL listed for use with fire-alarm system in this
Section before making connections.

B. Make addressable connections with a supervised interface device to the following devices and
systems. Install the interface device less than 3 feet (1 m) from the device controlled. Make an
addressable confirmation connection when such feedback is available at the device or system
being controlled.

1. Alarm-initiating connection to smoke-control system (smoke management) at firefighter


smoke-control system panel.
2. Alarm-initiating connection to stairwell and elevator-shaft pressurization systems.
3. Smoke dampers in air ducts of designated air-conditioning duct systems.
4. Alarm-initiating connection to elevator recall system and components.
5. Alarm-initiating connection to activate emergency lighting control.
6. Alarm-initiating connection to activate emergency shutoffs for gas and fuel supplies.
7. Supervisory connections at valve supervisory switches.
8. Supervisory connections at low-air-pressure switch of each dry-pipe sprinkler system.
9. Supervisory connections at elevator shunt trip breaker.
10. Supervisory connections at fire-pump power failure including a dead-phase or phase-
reversal condition.
11. Supervisory connections at fire-pump engine control panel.
12. <Insert connections>.

3.4 IDENTIFICATION

A. Identify system components, wiring, cabling, and terminals. Comply with requirements for
identification specified in Division 26 Section "Identification for Electrical Systems."

B. Install framed instructions in a location visible from fire-alarm control unit.

3.5 GROUNDING

A. Ground fire-alarm control unit and associated circuits. Install a ground wire from main service
ground to fire-alarm control unit. If shielded cabling is utilized in the installation, attach the drain
at the panel and connect through or insulate at junction boxes or devices, then leave open and
insulated at the last device.

3.6 FIELD QUALITY CONTROL

A. Field tests shall be witnessed by [Architect] [authorities having jurisdiction] <Insert names
or titles of witnesses>.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to install,


inspect, test, and adjust components, assemblies, and equipment installations, including
connections, in compliance with NFPA 72 inspection, testing, and maintenance requirements.

C. Perform tests and inspections.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to


inspect components, assemblies, and equipment installations, including connections, and
to assist in testing.

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 31


D. Tests and Inspections:

1. Visual Inspection: Conduct visual inspection prior to testing.

a. Inspection shall be based on completed Record Drawings and system


documentation that is required by NFPA 72 in its "Completion Documents,
Preparation" Table in the "Documentation" Section of the "Fundamentals of Fire
Alarm Systems" Chapter.
b. Comply with "Visual Inspection Frequencies" Table in the "Inspection" Section of
the "Inspection, Testing and Maintenance" Chapter in NFPA 72; retain the
"Initial/Reacceptance" column and list only the installed components.

2. System Testing: Comply with "Test Methods" Table in the "Testing" Section of the
"Inspection, Testing and Maintenance" Chapter in NFPA 72.
3. Test audible appliances for the public operating mode according to manufacturer's written
instructions. Perform the test using a portable sound-level meter complying with Type 2
requirements in ANSI S1.4.
4. Test audible appliances for the private operating mode according to manufacturer's
written instructions.
5. Test visible appliances for the public operating mode according to manufacturer's written
instructions.
6. Factory-authorized service representative shall prepare the "Fire Alarm System Record of
Completion" in the "Documentation" Section of the "Fundamentals of Fire Alarm
Systems" Chapter in NFPA 72 and the "Inspection and Testing Form" in the "Records"
Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72.

E. Reacceptance Testing: Perform reacceptance testing to verify the proper operation of added or
replaced devices and appliances.

F. Fire-alarm system will be considered defective if it does not pass tests and inspections.

G. Prepare test and inspection reports.

H. Maintenance Test and Inspection: Perform tests and inspections listed for weekly, monthly,
quarterly, and semiannual periods. Use forms developed for initial tests and inspections.

I. Annual Test and Inspection: One year after date of Substantial Completion, test fire-alarm
system complying with visual and testing inspection requirements in NFPA 72. Use forms
developed for initial tests and inspections.

3.7 DEMONSTRATION

A. Engage a factory-authorized service representative to demonstrate to Owner or Owner's


maintenance personnel the features and normal operation of the fire-alarm system. The
training session shall include reference to the documentation package created for the Project by
the Installer, including, but not limited to, the Owner's manual, record drawings, and site-specific
software information.

END OF SECTION 283111

DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 32

You might also like