Class 1, 2 or 3 Gas Fired Igniters according to NFPA-Standard

Selection table based on heat


release
diameter.
For plants according to NFPA
max. 300 kW / max. 1000 kW / max. 6000 kW / max.10000 kW /
Heat Release 1 MBTU 3.4 MBTU 20MBTU 34 MBTU
max. 24 in max. 80 in max. 150 in max. 170 in
Flame Length max. 600 mm max. 2000 mm max. 4000 mm max. 4500 mm
2 in 2.75 in 3.75 in 5.5 in
Tube Diameter (50 mm) (65 mm) (90 mm) (135 mm)

with integrated spark


transformer and burner control PDA0... PDA1... PDA2... PDA3...
for continuous operation

Igniter, Class 2
An igniter applied to ignite the fuel input
Igniter, Class 1 through the burner under prescribed light-
An igniter applied to ignite the fuel input conditions. The range of capacity of such igniters
through the burner and to support ignition un- generally is 4 percent to 10 percent of full load
der any burner light- conditions. burner fuel input.
Its location and capacity are such that it provides Igniter, Class 3
gnition energy (generally in excess of
10 percent of fuel load burner input) at its asso- A small igniter applied particularly to gas and oil
ciated burner to raise any credible combination burners to ignite the fuel input to the burner un-
of burner inputs of both fuel and air above the der prescribed light- conditions. The capacity
minimum ignition temperature. Class 1 igniters of such igniters generally does not exceed 4 per-
also shall be permitted to operate as Class 2 or cent of the full load burner fuel input.
Class 3 igniters. Igniter, Class 3 Special
A special Class 3 high energy electrical igniter ca-
pable of directly igniting the main burner fuel.
Source: NFPA 85

Heat Release max. Common Data

300 kW Tube

Flame Length
2 in
(50 mm)
max. 23.75 in
max. 600 mm
Ignition and warm-up of boilers according
to American standard 14.25 - 197 in
Igniter Tube Length L
(360 - 5000 mm)
Gas Inlet 1/2, left or right

Gas Pressure 500 mbarg

Air Inlet 1, may be rotated 4 times


in steps of 90
10 mbar, depending on
Air Pressure tube length
Transformer part

Ignition 5 kV
-22F up to +140F
Ambient Temperature
(-30C up to +60C)
Protection IP 54

Models

with integrated spark


transf
monitor for continuous PDA0...
operation 3.25 in
(82 mm)

.43 in
n
(11 mm) 5i )
3.20 mm
(50 mm)

(8 m)
2 in

n
4 i 00 m
(44 mm)

(1
1.75 in

.35 in
13 in (9 mm)
(330 mm) 9.5 - 197 in
(240 - 5000 mm)