Report #: Casa Celeste Jose Dennis 3.419724
((( Job Number -
Job #: SCR15338
Customer Ord.: -

Building name Palace Tower At Silicon Oasis Customer company Premium Community Management Llc
Building addr. SILICON OASIS , DUBAI Customer Nr NA
Building city DUBAI Job completed? Yes
Building # XXX Must produce a quotation? Yes
Extra PPE required (specify which ones) Ergonomic (lifting, position, constrains) Average
Risk Evaluation Fall Average
Confined spaces Average
Cust. ReferenceCHILLER1 .RES.TOWER
CHILLER 2 RES.TOWER - - -
The details of each machine are given in
Unit Model CVHG078TA3 CVHG078TA3 - - -
attachments
Serial number L08C01197 L08C01202 - - -

Technician Dbut
Date Trav. Start Job start Job end Travel end Job & travel Travel mil. Overnight
name Pause
11/1/2017 6:30 7:15 15:30 16:00 9:30 No
- - - - - - - - -
- - - - - - - - -
Casa Celeste
- - - - - - - - -
Jose Dennis
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
Suggested repair / upgrading

L08C01197: NEED TO REPLACE PURGE CONTROL FUSE 1NO.12A CONDENSER TEMP. APPROACH IS HIGH NEED TO DE SCALING AND
SWABIBNG OF CONDENCER TUBE
L08C01202: PURGE CONTROL FUSE IS OPEN AND NEED TO REPLACE 12A.NO

Emergency or Temporary Cooling requirement?

1/11/2017

! "# $% & ! '#


) )* +
,%- ../#'/ 0 ,%- ../#' %
Report #: Casa Celeste Jose Dennis 3.419724
((( Job Number -
Job #: SCR15338
Customer Ord.: -

Building name Palace Tower At Silicon Oasis Customer company Premium Community Management Llc
Building # XXX Customer Nr NA

Serial number L08C01197, Unit Model CVHG078TA3, Cust. Reference CHILLER1 .RES.TOWER
General check installation -
Verify diagnostics -
Oil level check -
Stop the unit -
Control panel settings check -
Condenser flow switch check -
Evaporator flow switch check -
LCWT sensor check -
Refrigerant low temp sensor check -
Electrical service oil pump -
Oil heaters check -
Isolate unit -
Motor insulation check -
Check starter panel -
Restore Unit Power supply -
Leaks search -
-
Warn customer of next operation -
Start the unit -
Unit log -
Clean jobsite -
Fill documentation and get signed -
- -
- -

! "# $% & ! '#


) )* +
,%- ../#'/ 0 ,%- ../#' %
Report #: Casa Celeste Jose Dennis 3.419724
((( Job Number -
Job #: SCR15338
Customer Ord.: -

Building name Palace Tower At Silicon Oasis Customer company Premium Community Management Llc
Building # XXX Customer Nr NA

Serial number L08C01202, Unit Model CVHG078TA3, Cust. Reference CHILLER 2 RES.TOWER
General check installation -
Verify diagnostics -
Oil level check -
Stop the unit -
Control panel settings check -
Condenser flow switch check -
Evaporator flow switch check -
LCWT sensor check -
Refrigerant low temp sensor check -
Electrical service oil pump -
Oil heaters check -
Isolate unit -
Motor insulation check -
Check starter panel -
Restore Unit Power supply -
Leaks search -
-
Warn customer of next operation -
Start the unit -
Unit log -
Clean jobsite -
Fill documentation and get signed -
- -
- -

! "# $% & ! '#


& # / /

) )* +
,%- ../#'/ 0 ,%- ../#' %
Report #: Casa Celeste Jose Dennis 3.419646
((( Job Number -
Job #: SCR15338
Customer Ord.: -

Building name Palace Tower At Silicon Oasis Customer company Premium Community Management Llc
Building # XXX Customer Nr NA

Serial number L08C01202, Unit Model CVHG078TA3, Cust. Reference CHILLER 2 RES.TOWER

CONDUCTED PREVENTIVE MAINTENANCE OF THE CHILLER ( QUARTERLY ) AS PER CHECH LIST ATTACHED

SWITCH OFF THE CHILLER POWER SUPPLY LOCK OUT TAGOUT THE ISOLATOR
CHECKED THE CONTROL PANAEL AND STARTER PANEL
CLEANING THE STARTER RETIGTHEN THE CONTACTOR CONTROL WIRING CONNECTION
CHECKED THE PURGE CONTROL AND OILPUMP MOTOR ELECTRICAL CONNECTION
CHECKED THE INSULATION RESISTANCE OF THE COMPRESSOR MOTOR
CLEANING THE CHILLER , RESTORED THE POWER SUPPLY .
CHECKED THE CONTROL SETTINGS, RESTART THE CHILLER , OBSERVED THE OPERATINGB PARAMETERS AND LOG READING
NOTE CHILLER IS OPERATIONAL . NORMAL
* 2+ ! &
NEED TO REPLACE PURGE CONTROL FUSE 1NO 12A 0*3+ /

BEFORE AND AFTER OF SERVICE

! "# $% & ! '#


& # %-

) )* +
,%- ../#'/ 0 ,%- ../#' %
Report #: Casa Celeste Jose Dennis 3.419724
((( Job Number -
Job #: SCR15338
Customer Ord.: -

Building name Palace Tower At Silicon Oasis Customer company Premium Community Management Llc
Building # XXX Customer Nr NA

Serial number L08C01197, Unit Model CVHG078TA3, Cust. Reference CHILLER1 .RES.TOWER
CONDUCTED PREVENTIVE MAINTENANCE QUARTERLY( QUATERLY ) OF THE CHILLER AS PER CHECK LIST ATTACHED

SHUT OFF THE CHLILER AND LOGOUT BTAG OUT THE ISOLATOR
CLEANINGTHE CONTROL PANEL AND STARTER PANEL
RETIGHTEN THE STARTER / CONTACTORS TERMINAL CONNECTION
APPLY GREASE AT VANE ARM ARM AND LINKAGE ASSEMBLY
CHECKED THE PURGE SYSTEM AND OIL PUMP MOTOR ELECTRICSL WIRING CONNECTION
RESTORED POWER SUPPLY CHECKED THE CONTROL SETTING
RESTART THE CHILLER CHECKEC THE OPERATING PARAMETERS AND LOG READING
.NOTE;CHILLER IS OPERATIONAL

BEFORE

AFTER

BEFORE AFTER

! "# $% & ! '#


4 3 0+ 5 * 6

Serial number L08C01197


JOB SITE AUDIT FORM
Job Site Name: Palace Tower At Silicon Oasis
Date: 1/10/2017
Safety Audit Performed By: 4
Job Number SCR15338 Yes No NA
Is there safe access to the units? X
1
List any possible problems:
In an emergency situation the site is free of specific hazards (exit clear and free, emergency lighting
2 available) X
List any possible problems:

3 Free from slippery floors? X


4 Is there adequate lighting to perform the work? X
Work Area 5 Is adequate space available to conduct the work ? X
6 Will the work area's ambient temperature be acceptable? (i.e.: extreme heat or cold) X
7 Is the working area free from debris or other conditions that may contribute to a slip, trip or fall? X
8 Is the noise level acceptable with appropriate PPE? X
9 Are fire extinguishers readily available/accessible? (Must be within 30m of work area.) X
10 Is the atmosphere (dust/gasses) OK to work in? X
11 In case of vibrations the situation is still acceptable to work in. X
12 Is the equipment able to be locked out? (i.e. De-energized) X
The work area has been checked and is free from any chemical/ explosive hazards such as
corrosives or flammables (Do not include those from TRANE) X
13
If No, list hazards present + examples

The site asbestos register (for certain countries this does not apply), has been checked? X
Materials 14
When you think there is abestos please indicate

Do you have the correct documentation to ensure any waste chemicals can be safely removed from
site: (i.e. refrigerant, oil, lithium bromide etc.)? X
15
If No, list the notifiable responsible parties

Is there a safe area for loading/unloading of service vehicles? X


16
If No, please describe
Handling
The site is free from dangerous material handling issues? X
17
If No, please describe

18 The job can be completed without specific risks for working at heights? X
Height
19 All steps, platforms or scaffolding are safe? X
All site safety specifications (from the customer), have been considered: i.e. permits, training,
induction, etc? X
20
IIf No, list safety specifications needing consideration so
Issues that the clients demands are met.
21 When needed, there was assistance from the technical services of the customer? X
22 Adequate and clean sanitary facilities are available? X
How do you evaluate the total risk for this job site? 1
0= low
Risk 23 1= Average
2= High, needs Customer contact
3= Dangerous, suspend the job, contact Customer & Office
Wednesday, January 11, 2017
11:15:14 AM Arabian Standard ASHRAE Chiller Report
Time


        
Technician: 
Chiller Name:
 
Model Number: CVHG078TA3B0ACX3027
WBE7RFC00000001A0005 0L000003A100A
Serial Number: L08C01197
Job Name:      
Work Order Number:
Location:     
Sales Office Name:
Sales Order Number: 66V702A
Sales Office Address:
Sales Office Phone Number:
Customer Name:
Customer Address:
Customer Phone Number:

Notes:

Chiller Status
Chiller Mode
Active Chilled Water Setpoint 41.0 F Chiller Top Level Mode Running
Active Current Limit Setpoint 80.0%

Evap Entering Water Temp 45.1 F


Evap Leaving Water Temp 41.2 F

Evap Water Flow Status Flow


Cond Leaving Water Temp 83.7 F

Cond Entering Water Temp 80.9 F


Cond Water Flow Status Flow

Circuit Compressor
Evap Sat Rfgt Temp 39.4 F Oil Tank Pressure 8.4 PSIA
Evap Rfgt Pressure 5.7 PSIA Oil Pump Discharge Pressure 25.4 PSIA

ASHRAE Chiller Report Page 1


Evap Approach Temp 1.7 F Oil Differential Pressure 17.00 PSID
Cond Sat Rfgt Temp 91.8 F Oil Tank Temperature 124.1 F

Cond Rfgt Pressure 17.9 PSIA


Cond Approach Temp 8.1 F

Motor Purge
Starter Motor Current L1 % RLA 48.3% Daily Pumpout-24 Hours 00:00 Min:Sec
Starter Motor Current L2 % RLA 52.2% Average Daily Pumpout-7 Days 00:00 Min:Sec

Starter Motor Current L3 % RLA 51.8% Pumpout-Life 14541:30 Min:Sec


Starter Motor Current L1 382.0 A Daily Pumpout Limit 50 Min

Starter Motor Current L2 419.0 A


Starter Motor Current L3 416.0 A

Starter Input Voltage AB 393.0 V


Starter Input Voltage BC 387.0 V

Starter Input Voltage CA 398.0 V

Chiller Setpoints
Compressor Purge
Compressor Starts 382 Purge Top Level Mode Adaptive
Compressor Running Time 16731:15 Hr:Min

Signed:
Date:

Copyright 2016 Trane, Inc. a business of Ingersoll Rand. All rights reserved. TRANE, the TRANE logo and Tracer TU are
either registered trademarks or trademarks of TRANE in the United States and/or other countries.
Protected by U.S. Patents.

ASHRAE Chiller Report Page 2


Wednesday, January 11, 2017
11:55:03 AM Arabian Standard ASHRAE Chiller Report
Time


        
Technician: 
Chiller Name:
 
Model Number: CVHG078TA3B0ACX3027
WBE7RFC00000001A0005 0L000003A100A
Serial Number: L08C01202
Job Name:      
Work Order Number:
Location:     
Sales Office Name:
Sales Order Number: 66V702B
Sales Office Address:
Sales Office Phone Number:
Customer Name:
Customer Address:
Customer Phone Number:

Notes:

Chiller Status
Chiller Mode
Active Chilled Water Setpoint 42.0 F Chiller Top Level Mode Running
Active Current Limit Setpoint 100.0%

Evap Entering Water Temp 45.9 F


Evap Leaving Water Temp 42.1 F

Evap Water Flow Status Flow


Cond Leaving Water Temp 80.3 F

Cond Entering Water Temp 77.2 F


Cond Water Flow Status Flow

Circuit Compressor
Evap Sat Rfgt Temp 42.5 F Oil Tank Pressure 6.7 PSIA
Evap Rfgt Pressure 6.2 PSIA Oil Pump Discharge Pressure 28.1 PSIA

ASHRAE Chiller Report Page 1


Evap Approach Temp -0.4 F Oil Differential Pressure 21.39 PSID
Cond Sat Rfgt Temp 82.8 F Oil Tank Temperature 117.4 F

Cond Rfgt Pressure 15.0 PSIA


Cond Approach Temp 2.6 F

Motor Purge
Starter Current L1 38.8% Daily Pumpout-24 Hours 00:00 Min:Sec
Starter Current L2 38.3% Average Daily Pumpout-7 Days 00:00 Min:Sec

Starter Current L3 40.1% Pumpout-Life 9938:40 Min:Sec


Starter Current L1 312.0 A Daily Pumpout Limit 50 Min

Starter Current L2 310.0 A


Starter Current L3 323.0 A

Starter Voltage Phase AB 399.0 v


Starter Voltage Phase BC 389.0 v

Starter Voltage Phase CA 393.0 v

Chiller Setpoints
Compressor Purge
Compressor Starts 663 Purge Top Level Mode Stop
Compressor Running Time 38416:00 Hr:Min

Signed:
Date:

Copyright 2016 Trane, Inc. a business of Ingersoll Rand. All rights reserved. TRANE, the TRANE logo and Tracer TU are
either registered trademarks or trademarks of TRANE in the United States and/or other countries.
Protected by U.S. Patents.

ASHRAE Chiller Report Page 2