Indoor unit

Cooling Only / R410A


0CIM0-01B (Replace: 0CIM0-01A)
Introduction
Preface
New era brings the more sophisticated and advanced buildings which in turn demands for specialized and optimized direct
expansion air conditioning systems. Also energy efficiency, environment friendly, low noise and low maintenance are the
features which are essential for these systems.

As a part of vertical integration LG makes all the key components in house, which gives us an edge to LG to make better
and latest technology products with best quality in optimized time.

and systems with MPS technology inside are equipped with inverter technology and R410A refriger-
ant which is perfect solution to various installation locations.

This Engineering product data book incorporates information about the product itself, and installation, designing for
and system.

The comprehensive study of this book will improve your knowledge about the system and its application in detail.

LG Electronics Inc.
Air Conditioning & Energy Solution Company
Indoor unit

General information
1. Model line up
2. Nomenclature
3. Appearance
Indoor unit

1. Model line up
Model names
Category Chassis Capacity, kW(kBtu/h)
2.6 3.5 5.3 7.0

General information
(9) (12) (18) (24)
SB AMNC09GDBA2 AMNC12GDBA2
Wall mounted
SC AMNC18GDCA2 AMNC24GDCA2

SB AMNC09GDB*0 AMNC12GDB*0
ART COOL
Mirror
SC AMNC18GDC*0 AMNC24GDC*0

TR AMNC12GTRA2

Ceiling
4-way TQ AMNC18GTQA2
cassette

TP AMNC24GTPA2

High
static BH AMNC18GBHA2 AMNC24GBHA2
pressure
Ceiling
concealed Low B1 AMNC12GB1A2
duct static
pressure
(Slim) B2 AMNC18GB2A2 AMNC24GB2A2

* indicates color of panel (R: Mirror, W: White)

General information _ 1
Indoor unit
2. Nomenclature

AMN C 09 G D B A 2
General information

Serial number
Function
A : Basic
ART COOL Mirror type front panel color
R : Mirror, W : White

Chassis name
Indoor unit type
D : Wall mounted, ART COOL Mirror
T : Ceiling cassette
B : Ceiling concealed duct

Electrical rating
G: 220-240V, 1, 50Hz / 220V, 1, 60Hz
Cooling capacity
Ex) 7,000 Btu/h '07', 18,000 Btu/h '18'
Model type
C : Cooling Only

Indicates that this is multi system indoor unit using R410A

2 _ General information
Indoor unit
3. Appearance
3.1 Indoor units

General information
Wall Mounted ART COOL Mirror
AMNC09GDBA2 AMNC09GDB*0
AMNC12GDBA2 AMNC12GDB*0
AMNC18GDCA2 AMNC18GDC*0
AMNC24GDCA2 AMNC24GDC*0

Ceiling Cassette 4-way Ceiling Concealed Duct High static pressure


AMNC12GTRA2 AMNC18GBHA2
AMNC18GTQA2 AMNC24GBHA2
AMNC24GTPA2

Ceiling Concealed Duct Low Static Pressure (Slim)


AMNC12GB1A2
AMNC18GB2A2
AMNC24GB2A2

* indicates color of panel (R: Mirror, W: White)

3.2 Control system(standard)


These controllers will be provided with the respective indoor units.
But, some models dont provide the controller.
In case the controller is not included, buy the Accessory Part according to List of Function of the Model.

Type Individual controller Applicable model

Ceiling cassette
ART COOL Mirror

Wireless remote
Controller

Wall mounted

General information _ 3
Indoor unit

Product data
Wall mounted
ART COOL Mirror
Ceiling cassette 4-way
Ceiling concealed duct - High static pressure
Ceiling concealed Duct - Low Static Pressure (Slim)
Indoor unit

Wall Mounted
1. List of functions
2. Specifications
3. Dimensions
4. Piping diagrams
5. Wiring Diagrams
6. Air flow and temperature distributions (reference data)
7. Sound levels
8. Controller
9. Installation
Indoor unit
1. List of functions
AMNC09GDBA2, AMNC12GDBA2
Category Functions
AMNC18GDCA2, AMNC24GDCA2
Air supply outlet 1
Airflow direction control (left & right) Manual
Airflow direction control (up & down) Auto
Auto swing (left & right) X
Air flow Auto swing (up & down) O
Airflow steps (fan/cool/heat) 3/4/-
Chaos wind(auto wind) O
Jet cool/heat O
Swirl wind X
Triple filter (Deodorizing) O
Plasma air purifier X
Air purifying
Allergy Safe filter O
Long-life prefilter (washable / anti-fungus) O

Product data_Indoor units


Drain pump X
E.S.P. control X
Installation Electric heater X
High ceiling operation X
Auto Elevation Grille X
Hot start X
Reliability Self diagnosis O
Soft dry operation O
Auto changeover X
Auto cleaning O
Auto operation(artificial intelligence) O
Auto Restart O
Child lock X
Convenience Forced operation O
Group control X
Sleep mode O
Timer(on/off) O
Timer(weekly) X
Two thermistor control X
Wired remote controller PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller X
Individual
Simple wired remote controller X
control
Simple Wired remote controller(for hotel use) X
Wireless remote controller O
General central controller (Non LGAP) X
Network Network Solution(LGAP) O
function Dry contact PQDSA(1)/PQDSB(1) / PQDSBC
PI 485(for Indoor Unit) X
Zone controller X
Special
CTI(Communication transfer interface) X
function kit
Electronic thermostat X
Remote temperature sensor X
Others Group control wrie X
Telecom shelter controller X

Note :
O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Wall mounted _ 1
Indoor unit

2. Specifications
Model Name AMNC09GDBA2 AMNC12GDBA2
230, 1, 50 230, 1, 50
Power Supply V, , Hz
220, 1, 60 220, 1, 60
kW Class 2.6 3.5
Nominal Capacity
Btu/h Class 9,000 12,000
Power Input W x No. - -
Running Current A 0.15 0.15
Casing Color - White White
WxHxD mm 895 289 215 895 289 215
Dimensions Body
WxHxD inch 35-1/4 11-3/8 8-15/32 35-1/4 11-3/8 8-15/32
Net Weight Body kg (lbs) 11.0 (24.3) 11.0 (24.3)
(Row x Column x Fins
- (2 x 16 x 23) x 1 (2 x 16 x 23) x 1
Heat Exchanger per inch) x No.
Product data_Indoor units

Face Area m2 (ft2) 0.22 (2.37) 0.22 (2.37)


Type - Cross Flow Fan Cross Flow Fan
Fan Air Flow H/M/L m3/min 7.0 / 6.5 / 6.0 9.5 / 9.0 / 8.5
Rate H/M/L ft3/min 247 / 230 / 212 336 / 318 / 300
Type - BLDC BLDC
Fan Motor
Output W x No. 14.4 x 1 14.4 x 1
Sound Pressure Level H/M/L dB(A) 33 / 30 / 27 39 / 36 / 31
Sound Power Level H/M/L dB(A) - -
Liquid mm(inch) 6.35 (1/4) 6.35 (1/4)
Piping
Gas mm(inch) 9.52 (3/8) 9.52 (3/8)
Connections
Drain (O.D. / I.D.) mm 21.5 / 16.0 21.5 / 16.0
- Fuse Fuse
Safety Devices
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

2 _ Wall mounted
Indoor unit

2. Specifications
Model Name AMNC18GDCA2 AMNC24GDCA2
230, 1, 50 230, 1, 50
Power Supply V, , Hz
220, 1, 60 220, 1, 60
kW Class 5.3 7.0
Nominal Capacity
Btu/h Class 18,000 24,000
Power Input W x No. - -
Running Current A 0.28 0.28
Casing Color - White White
WxHxD mm 1,030 325 255 1,030 325 255
Dimensions Body
WxHxD inch 40-9/16 12-25/32 10-1/32 40-9/16 12-25/32 10-1/32
Net Weight Body kg (lbs) 13.0 (28.7) 13.0 (28.7)
(Row x Column x Fins
- (3 x 18 x 22) x 1 (3 x 18 x 22) x 1
Heat Exchanger per inch) x No.

Product data_Indoor units


Face Area m2 (ft2) 0.29 (3.07) 0.29 (3.07)
Type - Cross Flow Fan Cross Flow Fan
Fan Air Flow H/M/L m3/min 16.2 / 14.2 / 12.3 20.4 / 17.0 / 13.2
Rate H/M/L ft3/min 572 / 502 / 434 720 / 600 / 466
Type - BLDC BLDC
Fan Motor
Output W x No. 76.0 x 1 76.0 x 1
Sound Pressure Level H/M/L dB(A) 37 / 33 / 28 42 / 39 / 36
Sound Power Level H/M/L dB(A) - -
Liquid mm(inch) 6.35 (1/4) 6.35 (1/4)
Piping
Gas mm(inch) 12.7 (1/2) 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm 21.5 / 16.0 21.5 / 16.0
- Fuse Fuse
Safety Devices
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

Wall mounted _ 3
Product data_Indoor units

SB Chassis
AMNC09GDBA2

4 _ Wall mounted
AMNC12GDBA2
3. Dimensions
Indoor unit
Indoor unit

3. Dimensions

AMNC18GDCA2
AMNC24GDCA2
SC Chassis

Product data_Indoor units

Wall mounted _ 5
Indoor unit

4. Piping diagrams

Evaporator Gas pipe connection port


Heat exchanger
Outlet (flare connection)
Thermistor

Cooling Cross Flow Fan

Thermistor
Indoor Air
M
Thermistor
Evaporator Inlet
Product data_Indoor units

Liquid pipe connection port


(flare connection)

Description PCB Connector


Indoor Air Thermistor
CN-TH1
Evaporator Inlet Thermistor
Evaporator Outlet Thermistor CN-TH2

n Refrigerant pipe connection port diameters [Unit:mm(inch)]

Model Gas Liquid

AMNC09GDBA2
9.52(3/8) 6.35(1/4)
AMNC12GDBA2

AMNC18GDCA2
12.7(1/2) 6.35(1/4)
AMNC24GDCA2

6 _ Wall mounted
Indoor unit
5. Wiring diagrams
Models: AMNC09GDBA2, AMNC12GDBA2

Product data_Indoor units


Models: AMNC18GDCA2, AMNC24GDCA2

Wall mounted _ 7
Indoor unit

6. Air flow and temperature distributions (Reference data)


Model : 9k Btu/h

Discharge angle: 40 Cooling


Air velocity [m/s]
2.7m

2m

1.5

1m

1.0
0.5
0m
5m 4m 3m 2m 1m 0m
Product data_Indoor units

Temperature [C]
2.7m

2m

18

20 1m

24 22
0m
5m 4m 3m 2m 1m 0m

Model : 12k Btu/h

Discharge angle: 40 Cooling


Air velocity [m/s]
2.7m

2m

2.0
1m

1.5
1.0
0.5
0m
5m 4m 3m 2m 1m 0m

Temperature [C]
2.7m

2m

18

1m
20

24 22
0m
5m 4m 3m 2m 1m 0m

8 _ Wall mounted
Indoor unit

6. Air flow and temperature distributions (Reference data)


Model : 18k Btu/h

Discharge angle: 40 Cooling


Air velocity [m/s]
2.7m

2m

2.5 1m

1.0 1.5
0.5
0m
5m 4m 3m 2m 1m 0m

Temperature [C]

Product data_Indoor units


2.7m

2m

18

20 1m

24 22
0m
5m 4m 3m 2m 1m 0m

Model : 24k Btu/h

Discharge angle: 30 Cooling


Air velocity [m/s]
2.7m

2m

3.5

3.0 1m

2.5
2.0
1.0 1.5
0m
5m 4m 3m 2m 1m 0m

Temperature [C]
2.7m

20
2m

16
1m

20
18
18
0m
5m 4m 3m 2m 1m 0m

Wall mounted _ 9
Indoor unit

7. Sound levels
Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
1m - Reference accoustic pressure 0dB=20Pa.
- Sound level will vary depending on a range of factors such as
0.8m the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
Microphone
- The operating conditions are assumed to be standard.

Sound Levels[dB(A)]
Model
H M L
AMNC09GDBA2 33 30 27
AMNC12GDBA2 39 36 31
AMNC18GDCA2 37 33 28
Product data_Indoor units

AMNC24GDCA2 42 39 36

Sound pressure level


AMNC09GDBA2 AMNC12GDBA2 AMNC18GDCA2
80 80 80
Octave Band Sound Pressure Level (0dB = 20Pa)

70
Octave Band Sound Pressure Level (0dB = 20Pa)

Octave Band Sound Pressure Level (0dB = 20Pa)


70 70

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AMNC24GDCA2
80
Octave Band Sound Pressure Level (0dB = 20Pa)

70

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

10 _ Wall mounted
Indoor unit
8. Controller
Wireless remote control

Control Display
Description
panel screen
PLASMA BUTTON*: Used to start or stop the plas-
Display
a # ma-purification.
screen
Sleep mode auto button: Sets the sleep mode
l =
auto operation.

Temperature adjustment buttons: Adjusts the


e y room temperature when cooling and heating.

d - On/Off button: Turns the power on/off.

Product data_Indoor units


Control g 7 v Indoor fan speed button: Adjusts the fan speed.
panel
Operation mode selection button*: Selects the
operation mode.
A C
f Cooling operation (A) / Auto operation or auto
D 4 changeover (C) / Dehumidifying operation (D) /
Air Circulation operation (4)

Jet cooling: Warms up or cools down the indoor


N
temperature within a short period of time.

i jH Air flow direction button*: Adjusts the air flow


I
direction vertically or horizontally.

Temperature display button: Displays the room


k S temperature. Also changes unit from C to F if
pressed for 5 seconds.

m n z Timer button: Sets the current time and the start /


end time.

Navigation and functions button*: Adjusts the


c
J G time and sets the special functions.
b J: Auto clean / G: Operates energy saving cooling

p - Set/clear button: Sets or cancels functions.

r - Reset button: Resets the air conditioner settings.

* Some functions may not be supported, depending on the model.

Wall mounted _ 11
Indoor unit

9. Installation
Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personal only.

Installation plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealant)
Bend the pipe as closely
on the wall as possible,
Product data_Indoor units

but be careful that it


doesn't break.

Vinyl tape (Wide)


Apply after carrying out a
drainage test.
To carry out the drainage
test, remove the air filters
Saddle and pour water into the heat
exchanger.

9.1 Accessories
The following accessories are included with your unit.
1) Standard accessories
Diagram
Name
SB Chassis SC Chassis

Installation Plate

Type A Screws

Type B Screws

Type C Screws

Remote Controller
Holder

h The feature can be changed according a type of model.

12 _ Wall mounted
Indoor unit

9. Installation
2) Installation plates dimensions
Type 1 : SB Chassis

(Unit : mm)

Product data_Indoor units

Wall mounted _ 13
Indoor unit

9. Installation
Type 2 : SC Chassis

(Unit : mm)
Product data_Indoor units

CAUTION

Use only those accessories (Standard or optional) which have designated specilications

14 _ Wall mounted
Indoor unit

9. Installation
9.2 Selection of the best location [SC Chassis]

There should not be any heat or steam near the unit.


Select a place where there are no obstacles around of
the unit. Installation Plate
Make sure that condensation drainage can be conve-
niently routed away.
Do not install near a doorway.
Ensure that the interval between a wall and the left (or
right) of the unit is more than 100mm(3 15/16 inch). The Type "A" Screws
unit should be installed as high as possible on the wall,
allowing a minimum of 200mm(7 7/8 inch) from ceiling.
Use a metal detector to locate studs to prevent unnec- Chassis
essary damage to the wall. Hook

Product data_Indoor units


More than
100 Measure the wall and mark the centerline. It is also
More than 200
important to use caution concerning the location of the
installation plate. Routing of the wiring to power outlets
is through the walls typically. Drilling the hole through
the wall for piping connections must be done safely.
More than
100
More than 2300
9.4 Before piping work
(Unit : mm)

CAUTION
9.3 Fixing installation plate
Installation Information. For right piping. Follow the
The wall you select should be strong and solid enough to instruction given below.
prevent vibration
Mount the installation plate on the wall with
type "A" screws. If mounting the unit on a concrete wall,
use anchor bolts.
Mount the installation plate horizontally by aligning the
centerline using Horizontal meter .

[SB Chassis]

Installation Plate

Type "A" Screws

Chassis
Hook

Wall mounted _ 15
Indoor unit

9. Installation
Good case 9.5 Connecting the piping
Press on the upper side of clamp and unfold the tubing to Pull the screw cap at the bottom of the indoor unit
downward slowly.
Remove the chassis cover from the unit by loosing 3
screws (Be careful not to scratch Horizontal Vane
Main!)

Chassis Cover
Pull back the tubing holder.
Remove pipe port cover and positioning the tubing
Product data_Indoor units

Pipe Port

Left

Tubing holder
Right

Backwards

Wrong method
Following bending type from left to right may cause dam-
age to the tubing. 1) Installation of the Unit
Hook the indoor unit onto the upper portion of the instal-
lation plate.( engage the three hooks at the top of the
indoor unit with the upper edge of the installation plate)
Ensure that the hooks are properly seated on the instal-
lation plate by moving it left and right

2 Installation plate

Unlock the tubing holder from the chassis and mount


between the chassis and installation plate in order to
separate the bottom side of the indoor unit from the wall

Tubing Holder

16 _ Wall mounted
Indoor unit

9. Installation
Piping * Foamed polyethylene or equivalent is recommended.
Insert the connecting cable through the bottom side of <Left side piping>
indoor unit and connect the cable

[SB Chassis]
Tape

Connecting
cable

Drain hose
Connecting pipe
Drain hose

View

Product data_Indoor units


<Right side piping>

Terminal block
Remote controller
cable
Connecting cable
Cable retainer

Tape
[SC Chassis] Connecting
cable

Control Cover Drain hose


Connecting pipe

2) Connecting the installation pipe and


drain hose to the indoor unit.
Align the center of the pipes and sufficiently tighten the
flare nut by hand
Tighten the flare nut with a wrench

Open the Front Grille


Support the Front Grille with supporter
Open the Control Cover
Connect the connecting cable
Indoor unit tubing Flare nut Pipings

CAUTION
Spanner (fixed)
If the drain hose is routed inside the room insulate the Flare nut
hose with an insulation material* so that dripping from Connection pipe
Torque
sweating (condensation) will not damage furniture or wrench
floors.

Wall mounted _ 17
Indoor unit

9. Installation
4) Finishing the indoor unit installation
Outside diameter Torque
mm inch Nm Mount the tubing holder in the original positon.
6.35 1/4 16 2 Ensure that the hooks are properly seated on the instal-
9.52 3/8 38 4 lation plate by moving it left and right.
12.7 1/2 55 6
15.88 5/8 75 7
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their slots
19.05 3/4 110 10
(clicking sound).

When needed to extend the drain hose of indoor unit, Finish the assembly by screwing the unit to the installa-
assembly the drain pipe as shown on the drawing tion plate by using two pieces of type "C" screws. And
assemble a chassis cover.

Drain pipe
Product data_Indoor units

Indoor unit
drain hose Type 'C' screw
Vinyl tape(narrow)
Adhesive

Installation of filters
3) Wrap the insulation material around the Pull out the triple filter and allergy free filter from the sep-
connecting portion. arately packed plastic bag.
Overlap the connection pipe heat insulation and the Insert the triple filter into the left case and insert the aller-
indoor unit pipe heat insulation material. Bind them gy free filter into the right case.
together with vinyl tape so that there may be no gap. Detach two nitto tapes from the plasma filter.
Wrap the area which accommodates the rear piping
housing section with vinyl tape.

Plastic bands
Insulation material

Connection pipe Indoor unit pipe Triple Filter Allergy Free Filter Plasma Filter

Vinyl tape (wide) Wrap with vinyl tape

Pipe
Vinyl tape(narrow)

Bundle the piping and drain hose together by wrapping


them with cloth tape over the range within which they fit
into the rear piping housing section.

Wrap with vinyl tape

Pipe

Vinyl tape(wide)
Drain hose

18 _ Wall mounted
Indoor unit

9. Installation
9.6 Checking the Drainage 2) Drain piping
1) To check the drainage. The drain hose should point downward for easy drain
flow.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the
Downward slope
indoor unit without any leakage and goes out the drain
exit.

Connecting area
drain hose

Do not make drain piping like the following.


Leakage Accumulated

Product data_Indoor units


checking Do not raise
drain water
Air

Drain Pan Water Water


Waving
leakage leakage
Leakage
Checking
Drain
Hose

Tip of drain hose Less than


dipped in water 50mm gap

Water
leakage Ditch

Wall mounted _ 19
Indoor unit

ARTCOOL Mirror
1. List of functions
2. Specifications
3. Dimensions
4. Piping diagrams
5. Wiring Diagrams
6. Air flow and temperature distributions (Reference data)
7. Sound levels
8. Controller
9. Installation
Indoor unit
1. List of functions
AMNC09GDB*0 AMNC12GDB*0
Category Functions
AMNC18GDC*0 AMNC24GDC*0
Air supply outlet 1
Airflow direction control (left & right) Auto
Airflow direction control (up & down) Auto
Auto swing (left & right) O
Air flow Auto swing (up & down) O
Airflow steps (fan/cool/heat) 5/6/-
Chaos wind(auto wind) O
Jet cool/heat O/X
Swirl wind X
Triple filter (Deodorizing) O
Plasma air purifier O
Air purifying
Allergy Safe filter O
Long-life prefilter (washable / anti-fungus) O
Drain pump X

Product data_Indoor units


E.S.P. control X
Installation Electric heater X
High ceiling operation X
Auto Elevation Grille X
Hot start X
Reliability Self diagnosis O
Soft dry operation O
Auto changeover X
Auto cleaning O
Auto operation(artificial intelligence) O
Auto Restart O
Child lock X
Convenience Forced operation O
Group control X
Sleep mode O
Timer(on/off) O
Timer(weekly) X
Two thermistor control X
Wired remote controller PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller X
Individual
Simple wired remote controller X
control
Simple Wired remote controller(for hotel use) X
Wireless remote controller O
General central controller (Non LGAP) X
Network Network Solution(LGAP) O
function Dry contact PQDSA(1)/PQDSB(1) / PQDSBC
PI 485(for Indoor Unit) X
Special Zone controller X
CTI(Communication transfer interface) X
function kit
Electronic thermostat X
Remote temperature sensor X
Others Group control wire X
Telecom shelter controller X

Note :
O : Applied X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

ART COOL Mirror _ 1


Indoor unit
2. Specifications
Model Name AMNC09GDB*0 AMNC12GDB*0
230, 1, 50 230, 1, 50
Power Supply V, , Hz
220, 1, 60 220, 1, 60
kW Class 2.6 3.5
Nominal Capacity
Btu/h Class 9,000 12,000
Power Input W x No. - -
Running Current A 0.15 0.15
Casing Color - Grace Dark Gray Grace Dark Gray
WxHxD mm 895 289 205 895 289 205
Dimensions Body
WxHxD inch 35-1/4 x 11-3/8 x 8-1/16 35-1/4 x 11-3/8 x 8-1/16
Net Weight Body kg (lbs) 11.0 (24.3) 11.0 (24.3)
(Row x Column x Fins
- (2 x 16 x 23) x 1 (2 x 16 x 23) x 1
Heat Exchanger per inch) x No.
Product data_Indoor units

Face Area m2 (ft2) 0.67 (7.23) 0.67 (7.23)


Type - Cross Flow Fan Cross Flow Fan
Fan Air Flow H/M/L m3/min 7.0 / 6.5 / 6.0 9.5 / 9.0 / 8.5
Rate H/M/L ft3/min 247 / 229 / 212 336 / 318 / 300
Type - BLDC BLDC
Fan Motor
Output W x No. 14.4 x 1 14.4 x 1
Sound Pressure Level H/M/L dB(A) 33 / 30 / 27 39 / 36 / 31
Sound Power Level H/M/L dB(A) - -
Liquid mm(inch) 6.35 (1/4) 6.35 (1/4)
Piping
Gas mm(inch) 9.52 (3/8) 9.52 (3/8)
Connections
Drain (O.D. / I.D.) mm 21.5 / 16.0 21.5 / 16.0
- Fuse Fuse
Safety Devices
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

2 _ ART COOL Mirror


Indoor unit
2. Specifications
Model Name AMNC18GDC*0 AMNC24GDC*0
230, 1, 50 230, 1, 50
Power Supply V, , Hz
220, 1, 60 220, 1, 60
kW Class 5.3 6.7
Nominal Capacity
Btu/h Class 18,000 23,000
Power Input W x No. - -
Running Current A 0.28 0.28
Casing Color - White White
WxHxD mm 1,030 325 245 1,030 325 245
Dimensions Body
WxHxD inch 40-9/16 x 12-25/32 x 9-21/32 40-9/16 x 12-25/32 x 9-21/32
Net Weight Body kg (lbs) 15.5 (34.2) 15.5 (34.2)
(Row x Column x Fins
- (3 x 18 x 22) x 1 (3 x 18 x 22) x 1
Heat Exchanger per inch) x No.

Product data_Indoor units


Face Area m2 (ft2) 1.13 (12.2) 1.13 (12.2)
Type - Cross Flow Fan Cross Flow Fan
Fan Air Flow H/M/L m3/min 12.0 / 10.0 / 8.2 14.2 / 12.0 / 10.2
Rate H/M/L ft3/min 424 / 353 / 289 501 / 424 / 360
Type - BLDC BLDC
Fan Motor
Output W x No. 76 x 1 76 x 1
Sound Pressure Level H/M/L dB(A) 37 / 33 / 28 42 / 39 / 36
Sound Power Level H/M/L dB(A) - -
Liquid mm(inch) 6.35 (1/4) 6.35 (1/4)
Piping 12.7 (1/2) 12.7 (1/2)
Gas mm(inch)
Connections
Drain (O.D. / I.D.) mm 21.5 / 16.0 21.5 / 16.0
- Fuse Fuse
Safety Devices
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

ART COOL Mirror _ 3


Product data_Indoor units

SB Chassis
AMNC09GDB*0
AMNC12GDB*0

4 _ ART COOL Mirror


3. Dimensions
Indoor unit
Indoor unit
3. Dimensions

AMNC18GDC*0
AMNC24GDC*0
SC Chassis

Product data_Indoor units

ART COOL Mirror _ 5


Indoor unit
4. Piping diagrams

Evaporator Gas pipe connection port


Heat exchanger
Outlet (flare connection)
Thermistor

Cooling Cross Flow Fan

Thermistor
Indoor Air
M
Thermistor
Evaporator Inlet

Liquid pipe connection port


Product data_Indoor units

(flare connection)

Description PCB Connector


Indoor Air Thermistor
CN-TH1
Evaporator Inlet Thermistor
Evaporator Outlet Thermistor CN-TH2

n Refrigerant pipe connection port diameters


[Unit:mm(inch)]
Model Gas Liquid
AMNC09GDB*0
9.52(3/8)
AMNC12GDB*0
6.35(1/4)
AMNC18GDC*0
12.7(1/2)
AMNC24GDC*0

6 _ ART COOL Mirror


Indoor unit
5. Wiring diagrams
Models: AMNC09GDB*0 / AMNC12GDB*0

Product data_Indoor units


Models: AMNC18GDC*0 / AMNC24GDC*0

ART COOL Mirror _ 7


Indoor unit
6. Air flow and temperature distributions (Reference data)

Model : 9k Btu/h

Discharge angle: 40 Cooling


Air velocity [m/s]
2.7m

2m

1.5

1m

1.0
0.5
0m
5m 4m 3m 2m 1m 0m
Product data_Indoor units

Temperature [C]
2.7m

2m

18

20 1m

24 22
0m
5m 4m 3m 2m 1m 0m

Model : 12k Btu/h

Discharge angle: 40 Cooling


Air velocity [m/s]
2.7m

2m

2.0
1m

1.5
1.0
0.5
0m
5m 4m 3m 2m 1m 0m

Temperature [C]
2.7m

2m

18

1m
20

24 22
0m
5m 4m 3m 2m 1m 0m

8 _ ART COOL Mirror


Indoor unit
6. Air flow and temperature distributions (Reference data)

Model : 18k Btu/h

Discharge angle: 40 Cooling


Air velocity [m/s]
2.7m

2m

2.5 1m

1.0 1.5
0.5
0m
5m 4m 3m 2m 1m 0m

Product data_Indoor units


Temperature [C]
2.7m

2m

18

20 1m

24 22
0m
5m 4m 3m 2m 1m 0m

Model : 24k Btu/h

Discharge angle: 30 Cooling


Air velocity [m/s]
2.7m

2m

3.5

3.0 1m

2.5
2.0
1.0 1.5
0m
5m 4m 3m 2m 1m 0m

Temperature [C]
2.7m

20
2m

16
1m

20
18
18
0m
5m 4m 3m 2m 1m 0m

ART COOL Mirror _ 9


Indoor unit
7. Sound levels
Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
1m - Reference accoustic pressure 0dB=20Pa.
- Sound level will vary depending on a range of factors such as
0.8m the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
Microphone
- The operating conditions are assumed to be standard.
50Hz, 220-240V
Model Sound pressure Levels [dB(A)]
H M L
AMNC09GDB*0 33 30 27
AMNC12GDB*0 39 36 31
AMNC18GDC*0 37 33 28
AMNC24GDC*0 42 39 36
Product data_Indoor units

Sound pressure level


AMNC09GDB*0 AMNC12GDB*0 AMNC18GDC*0
80 80 80

70 70 70
Sound Pressure Level (0dB = 20Pa)
Sound Pressure Level (0dB = 20Pa)

Sound Pressure Level (0dB = 20Pa)


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30

NC-30 NC-30 NC-30

20 NC-25 20 NC-25 20 NC-25

Approximate Approximate Approximate


NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AMNC24GDC*0
80

70
Sound Pressure Level (0dB = 20Pa)

NC-65
60
NC-60

NC-55
50

NC-50

NC-45
40

NC-40

NC-35
30

NC-30

20 NC-25

Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

10 _ ART COOL Mirror


Indoor unit
8. Controller
Wireless remote control

The controls will look like the following.


ON/OFF BUTTON
Signal transmitter Used to turn off/on the unit.

OPERATION MODE SELECTION BUTTON


Used to select the operation mode.

ROOM TEMPERATURE SETTING BUTTONS


Used to select the room temperature.

INDOOR FAN SPEED SELECTION BUTTON


Used to select fan speed in six steps low, medium-low,
medium, medium-high, high and natural wind.

Product data_Indoor units


PLASMA BUTTON
Used to start or stop the plasma-purification.

SLEEP MODE AUTO BUTTON


Used to set sleep mode auto operation.
SLEEP

TIME ADJUSTING BUTTONS


Used to adjust the time.

TIMER SET/CLEAR BUTTON(after adjusting)


Used to set and to cancel the timer operation.

RESET BUTTON
Used prior to resetting time.

LED LUMINOSITY BUTTON


Used to adjust LED luminosity.

JET COOL BUTTON


Used to start or stop the speed cooling.
The Jet Cool operates fan in super high speed
in cooling mode.

HORIZONTAL VANE CONTROL BUTTON


Used to set the desired vertical airflow direction.

VERTICAL LOUVER CONTROL BUTTON


Operation Mode Used to set the desired horizontal airflow direction.

Cooling Operation AUTO CLEAN BUTTON


Used to set auto clean.

Auto Operation or Auto Changeover ENERGY SAVING COOLING BUTTON


Used to save Energy.

Healthy Dehumidification Operation


ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
Air Circulation
TIMER BUTTON(before adjusting)
Used to set the current time and the time of starting / stopping.

ART COOL Mirror _ 11


Indoor unit
9. Installation
Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personal only.

Installation plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealant)
Bend the pipe as closely
on the wall as possible,
Product data_Indoor units

but be careful that it


doesn't break.

Vinyl tape (Wide)


Apply after carrying out a
drainage test.
To carry out the drainage
test, remove the air filters
Saddle and pour water into the heat
exchanger.

9.1 Accessories
The following accessories are included with your unit.

1) Standard accessories

1. Type "A" screw 3. Type "B" screw


2. Installation plate 4. Remote control holder

Name Installation panel Securing screws


(Other)
Type "A" screw Type "B" screw

Shape
Owner's manual
Installation manual
M4 x 12L
The feature can be changed
according a type or model.

12 _ ART COOL Mirror


Indoor unit
9. Installation
2) Installation plates dimensions

Type 1: SB Chassis

(Unit : mm)

Product data_Indoor units

ART COOL Mirror _ 13


Indoor unit
9. Installation
Type 2: SC Chassis

(Unit : mm)
Product data_Indoor units

CAUTION

Use only those accessories (Standard or optional) which have designated specilications

14 _ ART COOL Mirror


Indoor unit
9. Installation
9.2 Selection of the best location Measure the wall and mark the centerline. It is also
important to use caution concerning the location of the
There should not be any heat or steam near the unit. installation plate. Routing of the wiring to power outlets
Select a place where there are no obstacles around of is through the walls typically. Drilling the hole through
the unit. the wall for piping connections must be done safely.
Make sure that condensation drainage can be conve-
niently routed away. Place a level on raised tab
Unit Outline
Do not install near a doorway.
Ensure that the interval between a wall and the left (or
right) of the unit is more than 100mm(3 15/16 inch). The
unit should be installed as high as possible on the wall,
70
allowing a minimum of 200mm(7 7/8 inch) from ceiling. (2 3/4) 70
Use a metal detector to locate studs to prevent unnec- (2 3/4)

Right rear piping


Left rear piping
Installation Plate
essary damage to the wall.
More than 95(3 3/4)

Product data_Indoor units


133(5 1/4)
100(3 15/16) 175(6 7/8) 217(8 17/32)
More than 200(7 7/8)
Unit : mm(inch)

More than 9.4 Before piping work


100(3 15/16)
More than
2300(90 9/16) CAUTION

Unit : mm(inch) Installation Information. For right piping. Follow the


instruction given below.

9.3 Fixing installation plate


The wall you select should be strong and solid enough to Good case
prevent vibration Press on the upper side of clamp and unfold the tubing to
Mount the installation plate on the wall with downward slowly.
type "A" screws. If mounting the unit on a concrete wall,
use anchor bolts.
Mount the installation plate horizontally by aligning the
centerline using Horizontal meter .

Installation Plate

Type "A" Screws

Chassis
Hook

ART COOL Mirror _ 15


Indoor unit
9. Installation
Wrong method 1) Installation of Indoor Unit
Following bending type from left to right may cause dam- Hook the indoor unit onto the upper portion of the instal-
age to the tubing. lation plate.( engage the three hooks at the top of the
indoor unit with the upper edge of the installation plate)
Ensure that the hooks are properly seated on the instal-
lation plate by moving it left and right

2 Installation plate
Product data_Indoor units

Unlock the tubing holder from the chassis and mount


between the chassis and installation plate in order to
separate the bottom side of the indoor unit from the wall

Tubing Holder

Piping
9.5 Connecting the piping Insert the connecting cable through the bottom side of
Pull the screw cap at the bottom of the indoor unit indoor unit and connect the cable (You can see detail
Remove the chassis cover from the unit by loosing 2 contents in 'Connecting the cables' section)
screws
<Left side piping>

Chassis cover

Pull back the tubing holder.


View
Remove pipe port cover and positioning the tubing

Indoor unit back side view Tubing holder

Terminal block
Connecting cable

Cable retainer

Right Left
Backwards
Downwards

16 _ ART COOL Mirror


Indoor unit
9. Installation
<Right side piping> <Right side piping>

Tape
Connecting
pipe
View

Drain hose

Terminal block
Connecting cable
3) Connecting the installation pipe and

Product data_Indoor units


Cable retainer drain hose to the indoor unit.
Align the center of the pipes and sufficiently tighten the
flare nut by hand
Tighten the flare nut with a wrench
Secure the cable onto the control board with the cable
retainer.
Tape the tubing pipe, drain hose. Be sure that the drain
hose is located at the lowest side of the bundle. Locating
at the upper side can cause overflow from the drain pan
Indoor unit tubing Flare nut Pipings
through the inside of the unit.

CAUTION Spanner (fixed)

If the drain hose is routed inside the room insulate the Flare nut
hose with an insulation material* so that dripping from Torque Connection pipe
sweating (condensation) will not damage furniture or wrench
floors.
Outside diameter Torque
* Foamed polyethylene or equivalent is recommended. mm inch kgf.m
<Left side piping> 6.35 1/4 1.8~2.5
9.52 3/8 3.4~4.2
12.7 1/2 5.5~6.5
15.88 5/8 6.3~8.2
19.05 3/4 9.9~12.1

Tape When needed to extend the drain hose of indoor unit,


Connecting assembly the drain pipe as shown on the drawing
pipe

Drain hose
Drain hose
Drain pipe

Indoor unit
drain hose
Vinyl tape(narrow)
Adhesive

ART COOL Mirror _ 17


Indoor unit
9. Installation
4) Wrap the insulation material around the 5) Finishing the indoor unit installation
connecting portion. Mount the tubing holder in the original positon.
Overlap the connection pipe heat insulation and the Ensure that the hooks are properly seated on the instal-
indoor unit pipe heat insulation material. Bind them lation plate by moving it left and right.
together with vinyl tape so that there may be no gap. Press the lower left and right sides of the unit against the
Wrap the area which accommodates the rear piping installation plate until the hooks engage into their slots
housing section with vinyl tape. (clicking sound).
Finish the assembly by screwing the unit to the installa-
Plastic bands tion plate by using two pieces of type "C" screws. And
Insulation material
assemble a chassis cover.
Product data_Indoor units

Connection pipe Indoor unit pipe


Vinyl tape (wide) Wrap with vinyl tape Type 'C' screw

Installation of filters
Pipe
Premium type
Vinyl tape(narrow)
Pull out the [Allergy free filter + Triple Filter] from the
separately packed plastic bag.
Detach the two nitto tapes from the filter.
Bundle the piping and drain hose together by wrapping Insert the filter into the filter case.
them with cloth tape over the range within which they fit Detach two nitto tapes from the plasma filter.
into the rear piping housing section.

Wrap with vinyl tape

Pipe

Vinyl tape(wide)
Drain hose

Allergy Free Filter + Triple Filter Plasma Filter

Rational type
Pull out the triple filter and allergy free filter from the sep-
arately packed plastic bag.
Insert the triple filter into the left case and insert the aller-
gy free filter into the right case.
Detach two nitto tapes from the plasma filter.

Triple Filter Allergy Free Filter Plasma Filter

18 _ ART COOL Mirror


Indoor unit
9. Installation
9.6 Checking the Drainage 2) Drain piping

1) To check the drainage. The drain hose should point downward for easy drain
flow.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain Downward slope
exit.

Connecting area
drain hose

Leakage
checking
Do not make drain piping like the following.

Product data_Indoor units


Drain pan
Accumulated
Do not raise
drain water
Air
Drain
hose
Leakage
checking
Water Water
Waving
leakage leakage

Tip of drain hose Less than


dipped in water 50mm gap

Water
leakage Ditch

ART COOL Mirror _ 19


Indoor unit

Ceiling cassette 4-way


1. List of functions
2. Specifications
3. Dimensions
4. Piping diagrams
5. Wiring Diagrams
6. Air flow and temperature distributions (Reference data)
7. Sound levels
8. Controller
9. Installation
Indoor unit
1. List of functions
AMNC12GTRA2
Category Functions AMNC24GTPA2
AMNC18GTQA2
Air supply outlet 4 4
Airflow direction control (left & right) X X
Airflow direction control (up & down) Auto Auto
Auto swing (left & right) X X
Air flow Auto swing (up & down) O O
Airflow steps (fan/cool/heat) 4/5/- 4/5/-
Chaos wind(auto wind) O O
Jet cool/heat O/X O/X
Swirl wind O O
Triple filter (Deodorizing) X X
Plasma air purifier PTPKQ0 PTPKM0
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump O O

Product data_Indoor units


E.S.P. control* X X
Installation Electric heater X X
High ceiling operation* O O
Auto Elevation Grille* X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) O O
Auto Restart O O
Child lock* O O
Convenience Forced operation O O
Group control* O O
Sleep mode O O
Timer(on/off) O O
Timer(weekly)* O O
Two thermistor control* O O
Wired remote controller PQRCVSL0 / PQRCVSL0QW PQRCVSL0 / PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 PQRCUDS0
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q PQRCHCA0Q
Wireless remote controller O O
General central controller (Non LGAP) X X
Network Network Solution(LGAP) O O
function Dry contact PQDSA(1) / PQDSB(1) / PQDSBCPQDSA(1) / PQDSB(1) / PQDSBC
PI 485(for Indoor Unit) X X
Zone controller X X
Special
CTI(Communication transfer interface) X X
function kit
Electronic thermostat X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others Group control wire PZCWRCG3 PZCWRCG3
Telecom shelter controller X X

Note
1. * : These functions need to connect the wired remote controller.
O : Applied X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied
with separate package.

Ceiling cassette 4-way _ 1


Indoor unit
2. Specifications
Model Name AMNC12GTRA2 AMNC18GTQA2

230, 1, 50 230, 1, 50
Power Supply V, , Hz
220, 1, 60 220, 1, 60
kW Class 3.5 5.3
Nominal Capacity
Btu/h Class 12,000 18,000
Power Input W x No. - -
Running Current A 0.35 0.43
WxHxD mm 570 214 570 570 256 570
Dimensions Body
WxHxD inch 22-7/16 x 8-7/16 x 22-7/16 22-7/16 x 10-3/32 x 22-7/16
Net Weight Body kg (lbs) 14.0 (30.9) 15.0 (33.1)
(Row x Column x Fins
- (2 x 8 x 18) x 1 (2 x 8 x 19) x 1
Heat Exchanger per inch) x No.
Product data_Indoor units

Face Area m2 (ft2) 0.34 (3.61) 0.34 (3.61)


Type - Cross Flow Fan Cross Flow Fan
Fan Air Flow H/M/L m3/min 9.5 / 8.0 / 6.5 13.0 / 12.0 / 10.0
Rate H/M/L ft3/min 336 / 283 / 230 459 / 424 / 353
Type - BLDC BLDC
Fan Motor
Output W x No. 43 x 1 43 x 1
Sound Pressure Level H/M/L dB(A) 35 / 31 / 27 40 / 37 / 34
Sound Power Level H/M/L dB(A) - -
Liquid mm(inch) 6.35 (1/4) 6.35 (1/4)
Piping
Gas mm(inch) 9.52 (3/8) 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm 32.0 / 25.0 32.0 / 25.0
- Fuse Fuse
Safety Devices
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UQC PT-UQC

Decoration Casing Color - Morning Fog Morning Fog


Panel WxHxD mm 700 x 22 x 700 700 x 22 x 700
Dimensions
WxHxD inch 27-9/16 x 7/8 x 27-9/16 27-9/16 x 7/8 x 27-9/16
Net weight kg (lbs) 3.0 (6.6) 3.0 (6.6)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

2 _ Ceiling cassette 4-way


Indoor unit
2. Specifications
Model Name AMNC24GTPA2

230, 1, 50
Power Supply V, , Hz
220, 1, 60
kW Class 7.0
Nominal Capacity
Btu/h Class 24,000
Power Input W x No. -
Running Current A 0.60
WxHxD mm 840 204 840
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16
Net Weight Body kg (lbs) 21.0 (46.3)
(Row x Column x Fins
- (3 x 18 x 22) x 1
Heat Exchanger per inch) x No.

Product data_Indoor units


Face Area m2 (ft2) 1.134 (12.2)
Type - Cross Flow Fan
Fan Air Flow H/M/L m3/min 17.0 / 15.0 / 13.0
Rate H/M/L ft3/min 600 / 530 / 459
Type - BLDC
Fan Motor
Output W x No. 60 x 1
Sound Pressure Level H/M/L dB(A) 39 / 37 / 34
Sound Power Level H/M/L dB(A) -
Liquid mm(inch) 6.35 (1/4)
Piping
Gas mm(inch) 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm 32.0 / 25.0
- Fuse
Safety Devices
- Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18)
Model Name - PT-UMC
Decoration Casing Color - Morning Fog
Panel WxHxD mm 950 x 25 x 950
Dimensions
WxHxD inch 37-13/32 x 1 x 37-13/32
Net weight kg (lbs) 5.0 (11.0)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

Ceiling cassette 4-way _ 3


Indoor unit
3. Dimensions

AMNC12GTRA2
TR Chassis
Product data_Indoor units

4 _ Ceiling cassette 4-way


Indoor unit
3. Dimensions

AMNC18GTQA2
TQ Chassis

Product data_Indoor units

Ceiling cassette 4-way _ 5


Indoor unit
3. Dimensions

AMNC24GTPA2
TP Chassis
Product data_Indoor units

6 _ Ceiling cassette 4-way


Indoor unit
4. Piping diagrams

Evaporator Gas pipe connection port


Heat exchanger
Outlet (flare connection)
Thermistor

Cooling Turbo fan

Thermistor
Indoor Air
M
Thermistor
Evaporator Inlet

Liquid pipe connection port

Product data_Indoor units


(flare connection)

Description PCB Connector


Indoor Air Thermistor CN-ROOM
Evaporator Inlet Thermistor CN-PIPE/IN
Evaporator Outlet Thermistor CN-PIPE/OUT

n Refrigerant pipe connection port diameters [Unit:mm(inch)]


Model Gas Liquid
AMNC12GTRA2 9.52(3/8)
AMNC18GTQA2 6.35(1/4)
12.7(1/2)
AMNC24GTPA2

Ceiling cassette 4-way _ 7


Indoor unit
5. Wiring diagrams
Models: TR/TQ/TP
Product data_Indoor units

8 _ Ceiling cassette 4-way


Indoor unit
6. Air flow and temperature distributions (Reference data)
Model : 12k Btu/h
Cooling
Discharge angle: 40

Air velocity [m/s]

2.7m
2.0 2.0
2m
1.5 1.5

1.0 1.0
1m

0.5 0.5

0m
2.5m 1.5m 0m 1.5m 2.5m

Temperature [C]

Product data_Indoor units


2.7m
18 18
2m
20 20

22 22

1m

24 24
0m
2.5m 1.5m 0m 1.5m 2.5m

Model : 18k Btu/h


Cooling
Discharge angle: 40

Air velocity [m/s]

2.7m
2.0 2.0
2m
1.5 1.5

1m
1.0 1.0
0.5 0.5
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Temperature [C]

2.7m
18 18
20 20 2m

22 22
1m

24 24
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Ceiling cassette 4-way _ 9


Indoor unit
6. Air flow and temperature distributions (Reference data)
Model : 24k Btu/h

Discharge angle: 40
Cooling
Air velocity [m/s]

2.7m
2.0 2.0
2m

1m
1.5 1.5

1.0 1.0
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Temperature [C]
Product data_Indoor units

2.7m
18 18
20 20
2m
22 22

1m
23 23
24 24
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

10 _ Ceiling cassette 4-way


Indoor unit
7. Sound levels
Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
Ceiling - Reference accoustic pressure 0dB=20Pa.
1.5m - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard.
Sound Levels[dB(A)]
Model
H M L
AMNC12GTRA2 35 31 27
AMNC18GTQA2 40 37 34
AMNC24GTPA2 39 37 34

Product data_Indoor units


Sound pressure level
AMNC12GTRA2 AMNC18GTQA2 AMNC24GTPA2
80 80 80

70 70 70
Octave Band Sound Pressure Level (0dB = 20Pa)

Octave Band Sound Pressure Level (0dB = 20Pa)


Octave Band Sound Pressure Level (0dB = 20Pa)

NC-65 NC-65
NC-65
60 60 60
NC-60 NC-60
NC-60

NC-55 NC-55
NC-55
50 50 50
NC-50 NC-50
NC-50

NC-45 NC-45
40 NC-45
40 40
NC-40 NC-40
NC-40

NC-35 NC-35
30 NC-35
30 30

NC-30 NC-30
NC-30

20 NC-25 20 NC-25
20 NC-25

Approximate Approximate Approximate


NC-20 NC-20
Hearing NC-20 Hearing
Hearing
Threshold Threshold Threshold
NC-15 NC-15
10 NC-15 10
10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

Ceiling cassette 4-way _ 11


Indoor unit
8. Controller
Wireless Remote Controller
1 PLASMA Button (OPTIONAL)
Used to start or stop the plasma-purification function.
2 JET COOL Button
Speed cooling operates super high fan speed.
3 OPERATION MODE SELECTION Button
Used to select the operation mode.
4 FUNCTION SETTING Button
8
Used to set or clear Auto Clean, Smart Clean, Electric
1 9 heater or Individual vane angle control
5 LCD LUMINOSITY Button (OPTIONAL)
Product data_Indoor units

2 10
Used to adjust LCD luminosity
11 6 SMART CLEAN Button (OPTIONAL)
3 12 Used to start or stop Smart Clean.
4 13 7 CLEAR ALL Button
14
5 Used to clear all timer.
6 15 8 ROOM TEMPERATURE SETTING Button
7
Used to select the room temperature.
16 9 ON/OFF Button
Used to turn on/off the unit.
10 INDOOR FAN SPEED SELECTION Button
Used to select fan speed in four steps low, medium,
Operation Mode high and chaos.
11 UP/DOWN AIRFLOW Button
Cooling Mode
Used to stop or start louver movement and set the
desired up/down airflow direction.
Auto Mode or Auto Changeover
12 LEFT/RIGHT AIRFLOW Button (OPTIONAL)
Dehumidification mode Used to set the desired left/right(horizontal) airflow
direction.
Heating Mode 13 TIMER AND TIME SETTING Button
Used to set the time of starting or stopping and sleep-
Fan Mode ing operation.
Cooling Model( ), Heat Pump Model( ) 14 ROOM TEMPERATURE CHECKING Button
Used to check the room temperature.
15 C/F SWITCH Button
Used to switch temperature reading from Celsius to
Fahrenheit.
16 RESET Button
Used to reset the remote controller.

12 _ Ceiling cassette 4-way


Indoor unit
9. Installation
Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Long life filter

Product data_Indoor units


Air
return
Remote
Air supply Controller

9.1 Accessories
Check whether the following accessories are included with your unit.

1) Standard accessories

Washer for Insulation for


Name Drain hose Clamp metal Clamp (Other)
hanging backet fitting

Quantity 1 EA 1 EA 8 EA 8 EA 1 SET

Paper pattern for


installation
Owner's manual
Installation manual
Shape for gas pipe

for liquid pipe

Ceiling cassette 4-way _ 13


Indoor unit
9. Installation
9.2 Selection of the best location 9.3 Precautions regarding cassette
There should not be any heat source or steam near the unit. indoor unit installation
There should not be any obstacles to the air circulation.
There should be provision of easy condensate drain.
1) Main points about the indoor installation
Taking into accounting the noise prevention criteria, spot - In case of high height ceiling
the installation location. In general commercial places and offices though the
Do not install the unit near the door way. height of the ceiling is 2.7 m, the ceiling height can be 3
Keep proper distances, of the unit, from ceiling, fence, m. In such cases because of the temperature difference
floor, walls and other obstacles as shown in figure. with the floor the heating effect can fall down.
The indoor unit must have the maintenance space.

Discharge
Suction
Ceiling 20 or more
Product data_Indoor units

High elevation Hot air


False ceiling
of the ceiling
False ceiling Outdoor
Cold air
side (Entering of air by
frequent opening
or more

1500 or 1500 or and closing of door)


1500

more more
H
- Countermeasure method
Unit:mm
Air conditioner must be able to operate in high ceiling
Floor conditioner.
Plan to install the circulator.
NOTE The air discharge port is made to give more airflow to the
Above figure means minimum value. Please keep these down wood directions.
value at least. The gate or exit of the building is protected by dual door
system.
High Ceiling mode selection 2) In case the floor or surfaces of the place
Capacity 9.0 kW >9.0kW Mode Selection to be air conditioned is in direct contact
H 2.3m H 2.7m Low Ceiling
with the outdoor air
Ceiling 2.3m < H 2.7m 2.7m < H 3.2m Standard
Height 2.7m < H 3.1m 3.2m < H 3.6m High Ceiling - The floor of the heating room indirect contact with
3.1m < H 3.6m 3.6m < H 4.2m Super High Ceiling the storeroom, garage or the outside air receives
the cold air at the floor and the floor temperature
[Unit : mm] decrease will feel cold at the feet.

Indoor

1500 or more
Low temperature
1500 or more

of the floor

Outdoor side (50~100mm


Insulation required)
Outdoor side Garage
1500 or more

Outdoor side

1500 or more In such places where the feet comes in direct contact
with floors will give a cold feeling to th floor.

14 _ Ceiling cassette 4-way


Indoor unit
9. Installation
- Countermeasure: Refrigerant piping: Increase the piping insulation
Use the carpet on the floor (compared to the tiles the thickness with thickness above 20 mm.
carpet over it will have a 3 degree rise in temperature) Refrigerant piping
Insulating the floor.
Floor heating

CAUTION

Case of cold air intake:


The duct surface will have the dew drops so a insulation
Others: Inside the ceiling near th air tight seal places
on the duct is a must.(Insulation material: a glass wool of
(To escape of the humidity inside false ceiling)
thickness 25 mm will be appropriate.)

Product data_Indoor units


3) In case of high temperature or high
humidity between the false ceiling and
ceiling slab(near by the sea, river, lake,
spa)
- In case of temperature of 30 degree and humidity
above 80%, the units body as well as the piping
insulation should be strengthened.
Grill for ventilation
Refer to the picture given below.

Psychrometric chart Enhance additional 4) In case of multiple indoor cassette units


insulation required area
(recommended)

Indoor unit Indoor unit


Ventilator

Lighting

Relative humidity 30C


1500mm or more

2000mm or more
3000mm or more
- Places having the temperature and humidity of the
surrounding water sources(sea, river etc.)
In case the steam is generated between the false ceiling
and the ceiling slab
Due to some nearby by steam source.
Indoor unit: Insulate the unit body with some insulation
like glass wool at least 10 mm in thickness.

Additional insulation required

Ceiling cassette 4-way _ 15


Indoor unit
9. Installation
9.4 Ceiling opening dimensions and 1) Install the suspension bolts.
hanging bolt location (Use either a W3/8 or M10 size bolt) Use a hole-in anchor
for existing ceilings, and a sunken insert, sunken anchor or
The dimensions of the paper pattern for installation are other field supplied parts for new ceilings to reinforce the
the same as those of the ceiling opening dimensions. ceiling to bear the weight of the unit. Adjust clearance from
Select and mark the position for fixing bolts and piping the ceiling before proceeding further.
hole.
Decide the position for fixing bolts slightly tilted to the
Ceiling
drain direction after considering the direction of drain
hose. Anchor
Long nut or turn-buckle
Drill the hole for anchor bolt on the wall.
Suspension bolt

TP Chassis False ceiling


Product data_Indoor units

875
NOTE
787

All the above parts are field suppiled.


840

9.5 Indoor unit installation


671

684

875

840
Installing of the accessories (except for the decoration
panel) before installing the indoor unit is easier.
1) Install the indoor unit.
Unit: mm Attach the hanger bracket to the suspension bolt. Be sure
to fix it securely by using a nut and washer from the upper
TQ/TR Chassis and lower sides of the hanger bracket.
585~660 (Ceiling Opening)
Hanging bolt
517 (W3/8 or M10)
Nut
Flat washer for M10
(W3/8 or M10)
(accessory)
585~660 (Ceiling Opening)

Spring washer
(M10)
319 570 Unit
Size
523

517

Flat washer for M10


570 Unit (accessory)
Size Nut
(W3/8 or M10)

Unit: mm
180mm(TR,Q Chassis)

461 Ceiling
150mm(TP Chassis)

Keep the length of the bolt


from the bracket to 40mm

Air Conditioner body


Ceiling board Ceiling board

Keep the length of 31~34mm


(TR,Q Chassis) or 15~18mm
(TP Chassis) between the air
conditioner bottom surface and the
ceiling surface
Set screw of
paper model (4 pieces)
Paper model
for installation
Open the ceiling board
along the outer edge of the
paper model

16 _ Ceiling cassette 4-way


Indoor unit
9. Installation
The following parts are local purchasing. 9.6 Connecting pipes to the indoor
- Hanging Bolt - W 3/8 or M10 unit
- Nut - W 3/8 or M10
1) Refrigerant piping work
- Spring Washer - M10
please refer REFRIGERANT PIPING WORK.
- Plate Washer - M10
2) Piping insulation
Perform heat insulation work completely on both gas and
2) For new ceilings the liquid pipe. Because improper insulation will result
Refer to the paper pattern for ceiling opening condensate formation over pipe.
dimension. Use the heat insulation material for the refrigerant piping
The center of the ceiling opening is indicated on the which has an excellent heat resistance (over 120C).
paper pattern for installation.
The center of the unit is indicated on the label attached Precautions in high humidity circumstance:
to the unit and on the paper pattern for installation. Refer to insulation work

Product data_Indoor units


First remove paper packaging material from the
4 corners of the paper pattern for installation , fix the
paper pattern to the unit with screws. CAUTION

Ceiling height is shown on the side of the paper pattern Make sure to insulate any field piping all the way to the
for installation. Adjust the height of the unit according to piping connection inside the unit. Any exposed piping
this indication. may cause condensation or burns if touched.

<Ceiling work>
Adjust the unit to the right position for installa- 3) Indoor unit drain piping
tion.
Drain piping must have downward (1/50 to 1/100): be sure
Assure that the unit is horizontal. not to provide up-and-down slope to prevent reverse flow.
The indoor unit is equipped with a built-in drain pump During drain piping connection, be careful not to exert
and float switch. At each of the unit's 3 corners, verify extra force on the drain port on the indoor unit.
that it is level by using awater-level or a water-filled
vinyl tube. (Otherwise it will result in the malfunctioning The outside diameter of the drain connection on the inddor
of unit and cause water to drip.) unit is 32mm.

Remove the washer fixing plate used for


preventing the washer from falling and tighten the
upper nut. Piping material: Polyvinyl chloride pipe 25mm and pipe
fittings
5) Remove the paper pattern for installation
p

2) For existing ceilings Upward


routing
Adjust the height and position of the unit. 1/50~ not allowed
Perform steps 3 and 4 in "5.1 For new ceilings". 1/100
Max. 800mm
(18k : Max. 700mm)

Ceiling cassette 4-way _ 17


Indoor unit
9. Installation
4) Drain test 9.7 Installation of decoration panel

CAUTION
Feed water Flexible drain hose
(Accessory) Properly install decoration panel because any slit or gap
Main between unit and decoration panel will result cool air
drain pipe leakage which may responsible for water driblling.

Drain
Drain pump port Glue the joint Air conditioner
unit
Drain hose connection
use the clip (Accessory)
False
ceiling
Decoration panel
Product data_Indoor units

Drain pan Fit the insulation (this part) and


be careful for cool air leakage

Air conditioner unit

Air
Cool air leakage(no good)

Flexible drain hose False


ceiling
Decoration panel

The decorative panel has its installation direction.


Before installing the decorative panel, always
remove the paper template.

n TP Chassis
1. Remove the packing and take out air inlet grille
from front panel.

Front grille

2. Remove the Corner covers of the panel.

Coner cover

18 _ Ceiling cassette 4-way


Indoor unit
9. Installation
3. Fit the panel on the unit by inserting hooks as 6. Open two screws of control panel cover.
shown in picture.

Hook clip
Screw
Hook
7. Connect one display connector and two vane
control connectors of front panel to indoor unit
PCB.
The position marking on PCB is as:
4. Insert two screws on diagonal corners of panel. Display connector : CN-DISP
Do not tighten the bolts completely. (The fixing Vane control connector: CN-VANE 1,2
screws are included in the indoor unit box.)

Product data_Indoor units


Check the alignment of panel with the ceiling.
Height can be adjusted using hanging bolts as
shown in picture. Insert the other two screws
and tighten all screws completely.

CN VANE 1,2 CN DISP

8. Close the cover for control box.

9. Fit the link on the panel as shown in picture.


(The link is included in the front panel unit box.)

Link

5. Fit the corner covers.


10. Attach the other side of link on the filter guide
of inlet grille. Install the air inlet grille and filter
on the panel.

Link

Filter
guide

Ceiling cassette 4-way _ 19


Indoor unit
9. Installation
n TQ/TR Chassis
1. Remove the packing and take out air inlet grille 5. Fit the corner covers.
from front panel.

Front grille

6. Open two screws of control panel cover.

2. Remove the Corner covers of the panel.


Product data_Indoor units

Screw

Coner cover
7. Connect one display connector and two vane con-
trol connectors of front panel to indoor unit PCB.
The position marking on PCB is as:
Display connector : CN-DISPLAY
3. Fit the panel on the unit by inserting hooks as Vane control connector: CN-VANE 1,2
shown in picture.

Hook clip

Hook

CN VANE 1,2 CN DISPLAY

8. Close the cover for control box.

4. Insert two screws on diagonal corners of panel.


Do not tighten the bolts completely. (The fixing
screws are included in the indoor unit box.)
Check the alignment of panel with the ceiling.
Insert the other two screws and tighten all
screws completely.
9. Install the air inlet grille and Filter on the panel.

20 _ Ceiling cassette 4-way


Indoor unit
9. Installation
9.8 Electric wiring work Make sure to attach the sealing material (field supplied)
to hole of wiring to prevent the infiltration of foreign parti-
1) General instructions cle from outside. Otherwise a short-circuit may occur
All field supplied parts and materials, electric works must inside the electric parts box
conform to local codes. When clamping the wires, be sure no pressure is applied
Use copper wire only. to the wire connections by using the included clamping
Follow the "WIRING DIAGRAM attached to the unit body to material to make appropriate clamps. Also, when wiring,
wire the outdoor unit, indoor units and the remote controller. make sure the cover on the electric parts box fits snugly
All wiring must be performed by an authorized electrician. by arranging the wires neatly and attaching the electric
This system consists of multiple indoor units. Mark each parts box cover firmly. When attaching the electric parts
indoor unit as unit A, unit B..., and make sure the termi- box cover, make sure no wires get caught in the edges.
nal board wiring to the outdoor unit and indoor units are Pass wiring through the holes to prevent damage.
properly matched. If wiring and piping between the out- Make sure the remote controller wiring, the wiring
door unit and an indoor units are mismatched, the sys- between the units, and other electrical wiring do not pass
tem may a malfunction. through the same locations outside the unit, separating

Product data_Indoor units


A circuit breaker capable of shutting down the power them properly, otherwise electrical noise (external static)
supply to the entire system must be installed. could cause product malfunction.

2) Wiring Connection WARNING

Open the control box cover and connect the Remote con- Make sure that the screws of the terminal are not loose.
troller cord and Indoor power wires.

NOTE

1. Use round crimp-style terminals for connecting


wires to the power supply terminal block. If
unavailable, observe the following points when
Connecting
Remote Controller
Cable
Cable wiring.
12k/18k Btu/h(1) Do not connect wires of different gauge to the same
Terminal Block of Outdoor Unit Terminal Block of Indoor Unit
power supply terminal. (Loose connection may cause
L N 1(L) 2(N) 3 4 5 1(L) 2(N) 3 4 overheating.)
POWER INPUT Use the specified electric wire. Connect the wire
securely to the terminal. Lock the wire down without
Connecting
applying excessive force to the terminal.
Remote Controller
Cable Cable

Attach insulation sleeve

Round crimp-style terminal

Electricwire

24k Btu/h(1)
Terminal Block of Outdoor Unit Terminal Block of Indoor Unit
1(L) 2(N) 1(L) 2(N) 3 1(L) 2(N) 3

POWER INPUT

Connect wires of the same gauge to both sides

Ceiling cassette 4-way _ 21


Indoor unit
9. Installation
2. Tightening torque for the terminal screws.
Use the correct screwdriver for tightening the terminal
screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw
will not be properly tightened.
If the terminal screws are tightened too hard, screws
might be damaged.
3. Do not connect wires of different gauge to the
same grounding terminal. Loose connection may
deteriorate protection.
4. At the unit, keep proper distance between trans-
misson and power supply wiring.
The equipment may malfunction if subjected to
electrical (external) noise.
Product data_Indoor units

5. Never connect power supply wiring to the terminal


block for remote controller wiring. A mistake of
this sort could damage the entire system.
6. Use only specified wire and tightly connect wires
to terminals. Be careful that wires should not
place external stress on terminals. Keep wiring in
neat order and so as not to obstruct other equip-
ment such as popping open the electric parts box
cover. Make sure the cover closes tight.
Incomplete connections could result in overheat-
ing, and in worst case, electric shock or fire.

22 _ Ceiling cassette 4-way


Indoor unit

Ceiling concealed duct - High static pressure


1. List of functions
2. Specifications
3. Dimensions
4. Piping diagrams
5. Wiring Diagrams
6. External pressure setting for Tuning
7. Sound levels
8. Controller
9. Installation
Indoor unit
1. List of functions
AMNC18GBHA2
Category Functions
AMNC24GBHA2
Air supply outlet 2
Airflow direction control (left & right) X
Airflow direction control (up & down) X
Auto swing (left & right) X
Air flow Auto swing (up & down) X
Airflow steps (fan/cool/heat) 3/3/-
Chaos wind(auto wind) X
Jet cool/heat X
Swirl wind X
Triple filter (Deodorizing) X
Plasma air purifier X
Air purifying
Allergy Safe filter X
Long-life prefilter (washable / anti-fungus) O
Drain pump ABDPG

Product data_Indoor units


E.S.P. control* O
Installation Electric heater X
High ceiling operation* X
Auto Elevation Grille* X
Hot start X
Reliability Self diagnosis O
Soft dry operation O
Auto changeover X
Auto cleaning X
Auto operation(artificial intelligence) O
Auto Restart O
Child lock* O
Convenience Forced operation X
Group control* O
Sleep mode X
Timer(on/off) O
Timer(weekly)* O
Two thermistor control* O
Wired remote controller PQRCVSL0 / PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) X
Wireless remote controller PQWRCDF0
General central controller (Non LGAP) X
Network Solution(LGAP) O
CAC network
Dry contact PQDSA(1)/PQDSB(1) / PQDSBC
function
PI 485(for Indoor Unit) X
Zone controller ABZCA
CTI(Communication transfer interface) X
Special
Electronic thermostat X
function kit
Remote temperature sensor PQRSTA0
Group control wire PZCWRCG3
Others
Telecom shelter controller X

Note
1. * : These functions need to connect the wired remote controller.
O : Applied X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied
with separate package.

Ceiling concealed duct - high static pressure _ 1


Indoor unit
2. Specifications

Model Name AMNC18GBHA2 AMNC24GBHA2


230, 1, 50 230, 1, 50
Power Supply V, , Hz
220, 1, 60 220, 1, 60
kW Class 5.3 7.0
Nominal Capacity
Btu/h Class 18,000 24,000
Power Input W x No. - -
Running Current A 1.0 1.1
WxHxD mm 882 260 450 882 260 450
Dimensions Body
WxHxD inch 34-23/32 10-1/4 17-23/32 34-23/32 10-1/4 17-23/32
Net Weight Body kg (lbs) 26.0 (57.3) 26.0 (57.3)
Heat (Row x Column x Fins per inch) x No. - (3 x 10 x 21) x 1 (3 x 10 x 21) x 1
Exchanger Face Area m2 (ft2) 0.15 (1.63) 0.15 (1.63)
Product data_Indoor units

Type - Sirocco Fan Sirocco Fan


H/M/L m3/min 16.5/.14.5/13.0 18.0 / 16.5 / 14.0
Fan High-static H /M/L ft3/min 583/512/459 636 / 583 / 494
Air Flow
Mode (Factory
Rate External Static
Set) Pa (mmAq) 78 (8) 78 (8)
Pressure
Type - BLDC BLDC
Fan Motor
Output W x No. 154 x 1 154 x 1
Sound Pressure Level H/M/L dB(A) 36 / 34 / 32 38 / 36 / 34
Sound Power Level H/M/L dB(A) - -
Liquid mm(inch) 6.35 (1/4) 6.35 (1/4)
Piping
Gas mm(inch) 12.7 (1/2) 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm 32.0 / 25.0 32.0 / 25.0
- Fuse Fuse
Safety Devices
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

2 _ Ceiling concealed duct - high static pressure


Indoor unit
3. Dimensions

AMNC18GBHA2
AMNC24GBHA2
BH Chassis

Product data_Indoor units

Ceiling concealed duct - high static pressure _ 3


Indoor unit
4. Piping diagrams

Evaporator Gas pipe connection port


Heat exchanger
Outlet (flare connection)
Thermistor

Cooling Sirocco Fan

Thermistor
Indoor Air
M
Thermistor
Evaporator Inlet
Product data_Indoor units

Liquid pipe connection port


(flare connection)

Description PCB Connector


Indoor Air Thermistor CN-ROOM
Evaporator Inlet Thermistor CN-PIPE/IN
Evaporator Outlet Thermistor CN-PIPE/OUT

n Refrigerant pipe connection port diameters [Unit:mm(inch)]


Model Gas Liquid
AMNC18GBHA2
12.7(1/2) 6.35(1/4)
AMNC24GBHA2

4 _ Ceiling concealed duct - high static pressure


Indoor unit
5. Wiring diagrams
Models : AMNC-BH model

Product data_Indoor units

Ceiling concealed duct - high static pressure _ 5


Indoor unit
6. External pressure setting for
How to Set E.S.P. on the remote controller?

CAUTION:
If you set ESP incorrectly, the air conditioner may malfunction.
This setting must be carried out by a certificated-technician.

1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
Product data_Indoor units

2 If entering into ESP setup mode by using


button, it indicates as the picture
below.

ESP step
Function Code ESP value

Function code,
ESP code 3 Select ESP fan step by pressing
button. (01: very low, 02: low,
03: medium, 04: high, 05: power)
ESP value

4 Movebutton.
to ESP value setting by pressing

(It is 000 when delivering


from the warehouse.)

5 Press button to setup ESP value.

(It is possible to setup ESP


value from 1 to 255, and 1 is
the smallest and 255 is the
biggest.)

j When setting ESP value on the product without very weak wind or power wind function, it may not work.

6 _ Ceiling concealed duct - high static pressure


Indoor unit
6. External pressure setting for
Table 1

AMNC18GBHA2
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
2.5(25) 4(39) 6(59) 8(78)
100 12.8 - - -
105 13.9 - - -
110 15.2 12.7 - -
115 16.5 14.0 - -
120 17.8 15.3 12.7 -
125 - 16.5 14.0 -
130 - 17.8 15.3 12.6
135 - - 16.5 13.5
140 - - 17.5 14.5

Product data_Indoor units


145 - - - 16.5

AMNC24GBHA2
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
2.5(25) 4(39) 6(59) 8(78)
105 13.9 - - -
110 15.2 12.7 - -
115 16.5 14.0 - -
120 17.8 15.3 12.7 -
125 - 16.5 14.0 -
130 - 17.8 15.3 12.6
135 - - 16.5 13.5
140 - - 17.6 14.5
145 - - - 16.5
150 - - - 18.0

Table 2

Lower Limit of Upper Limit of


Standard External Static External Static
Model Mode Set value CMM
ESP(mmAq(Pa)) Pressure Pressure
(mmAq(Pa)) (mmAq(Pa))
Hl 145 16.5
High
AMNC18GBHA2 Mid 140 8(78) 14.5 2.5(25) 8(78)
(factory set)
Low 134 13.0
Hl 150 18.0
High
AMNC24GBHA2 Mid 145 8(78) 16.5 2.5(25) 8(78)
(factory set)
Low 136 14.0

Ceiling concealed duct - high static pressure _ 7


Indoor unit
7. Sound levels
Overall
Notes:
DISCHARGE SUCTION - Data is valid at nominal operation condition
- Reference accoustic pressure 0dB = 20Pa
DUCT DUCT - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
2m 1.5m
1m - The operating conditions are assumed to be standard.
1m

Sound Levels[dB(A)]
Model
H M L
AMNC18GBHA2 36 34 32
AMNC24GBHA2 38 36 34
Product data_Indoor units

Sound pressure level


AMNC18GBHA2 AMNC24GBHA2
80 80

70 70
Sound pressure level (0dB = 20Pa)

Sound pressure level (0dB = 20Pa)

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50

NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

20 NC-25 20 NC-25

Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz) Octave band center frequency (Hz)

8 _ Ceiling concealed duct - high static pressure


Indoor unit
8. Controller
Wired remote controller (ACCESSORY)
1 OPERATION INDICATION SCREEN
2 SET TEMPERATURE BUTTON
1 3 FAN SPEED BUTTON
10 4 ON/OFF BUTTON
9 5 OPRATION MODE SELECTION BUTTON
8 2
6 WIRELESS REMOTE CONTROLLER
3
7 RECEIVER
4
11 Some products don't receive the wireless
12 5 signals.

Product data_Indoor units


13 6 7 AIR FLOW BUTTON
14 8 SUBFUNCTION BUTTON
15 9 FUNCTION SETTING BUTTON
10 VENTILATION BUTTON
11 RESERVATION
12 UP,DOWN,LEFT,RIGHT BUTTON
To check the indoor temperature, press
button.
Please attach the inform label inside of the door. 13 ROOM TEMPERATURE BUTTON
Please choose proper language depend on your
country. 14 SETTING/CANCEL BUTTON
15 EXIT BUTTON

Note
h Some functions may not be operated and displayed depending on the product type.
h Display temperature can be different from actual room temperature if the remote controller is installed at the place where sun-rays are
falling directly or the place nearby heat source.
h The actual product can be different from above contents depending upon model type.

Ceiling concealed duct - high static pressure _ 9


Indoor unit
9. Installation
Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air outlet vents Air filters


(Optional)
Air intake vents
Wired Remote Controller
Product data_Indoor units

(Accessory)

Air Supply Air filter


Can be installed
inside return grill.
Air return

Wired Remote Controller


(Accessory)

9.1 Accessories
Check whether the following accessories are included with your unit.
1) Standard accessories

Insulation for Screws for


Name Clamp metal Drain hose Clamp (Other)
fitting duct flanges

Quantity 1 EA 1 EA 1 set 6 EA 1 set

Owner's manual
Installation manual
Washers(8 pcs.)
Shape for gas pipe

for liquid pipe

10 _ Ceiling concealed duct - high static pressure


Indoor unit
9. Installation

9.2 Selection of the best location


Install the air conditioner in the location that satisfies the fol- 30mm or more
lowing conditions.
The place shall easily bear a load of the indoor unit.
The place should have enough area for inspection as 30mm or more
shown in figure.
The place where the unit shall be leveled.
The place shall allow easy water drainage.(Suitable [Unit : mm]
dimension H is necessary to get a slope to drain as fig- Capacity(Btu/h) a
a
ure.) 18k/24k 900
The place shall easily connect with the outdoor unit.
Min. 460
The place where the unit is not affected by an electrical (Service space)
noise.

Product data_Indoor units


The place where air circulation in the room will be good . NOTE
There should not be any heat source or steam near the If the service panel is at the top of the unit, then provide
unit. sufficient service clearance as per convenience.

2) Relative positions of indoor unit, suspension bolt


9.3 Ceiling dimension, also hanging and inspection hatch size

bolt location and service space 932


[Unit : mm]
882
1) Select an installation site where the following con-
ditions are fulfilled and also that meets with your
customer's approval.
If supporting structural members are not strong enough

740
to take the units weight, the unit could fall out of place
and cause serious injury.
Where sufficient clearance of maintenance and service
can be ensured. 120
Where optimum air distribution can be ensured. Inspection
hatch 600 x 600
Where nothing blocks the air passage.
Where condensate can be properly drained.
Where piping between indoor and outdoor units is pos- 3) Install a canvass duct to the air discharge outlet
sible within the allowable limit (Refer to the installation and air inlet so that vibration from the machine
manual of the outdoor unit.) body is not transmitted to the duct or ceiling. You
Keep the indoor and outdoor units, power cable and should also apply acoustic (insulation material) to
transmission wiring, at least 1 m from TVs and radios, the inside of the duct, and vibration insulation
to prevent distorted pictures and static.(Depending on rubber to the suspension bolts.
the type and source of the electrical waves, static may 4) Install suspension bolts.
be heard even when more than 1 m away.) (Use bolts of 10 mm diameter.)
Install the equipment where supporting structures are
A C
strong enough to bear the equipment's weight. Use
embedded inserts or anchor bolts with new buildings
and hole-in-anchors with old buildings.
B

[Unit : mm]
Capacity(Btu/h) A B C
18k/24k 882 260 450

Ceiling concealed duct - high static pressure _ 11


Indoor unit
9. Installation
9.4 Position of suspension bolt Insert the set anchor and washer on the suspension bolts
for locking the suspension bolts on the ceiling.
Install the unit leaning to a drainage hole side as given in
the figure above for easy water drainage. Mount the suspension bolts to the set anchor firmly.

A place where the unit will be leveled and that can sup- Secure the installation plates on the suspension bolts
port the weight of the unit. (adjust level roughly) using nuts, washers and spring
washers.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
Old building New building

M10 Nut x4
(Local
M10 SP. washer x 4 supply)
M10 washer x4
1 Set anchor
Product data_Indoor units

2 Plate washer
M10 washer x4 3 Spring washer
(Local 4 Nut
M10 SP. washer x 4 supply)
M10 Nut x4 5 Suspension
bolts

Select and mark the position for fixing bolts.


Drill the hole for set anchor on the face of ceiling.

CAUTION

Tighten the nut and bolt to prevent unit from


falling.

12 _ Ceiling concealed duct - high static pressure


Indoor unit
9. Installation
9.5 Connection pipes to the indoor unit 3) Indoor unit drain piping
1) Refrigerant piping work During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
please refer REFRIGERANT PIPING WORK.
The outside diameter of the drain connection on the
2) Piping insulation indoor unit is 32mm.
Perform heat insulation work completely on both gas and Piping material: Polyvinyl chloride pipe inner diameter
the liquid pipe. Because improper insulation will result 25mm and pipe fitting
due condensate formation over pipe.
Use the heat insulation material for the refrigerant piping CAUTION
which has an excellent heat resistance (over 120C).
1. Decline Installation of indoor unit is very important for
Precautions in high humidity circumstance.
the drain of the duct type air conditioner.
Refer to the insulation works. 2. Minimum thickness of the insulation for the connecting
pipe should be 5mm.

Product data_Indoor units


4) Caution for gradient of unit and drain
Liquid pipe piping
Refrigerant pipe and thermal - Without drain pump
insulation(Local supply)
Always lay the drain with downward inclination (1/50 to
1/100).
Clamp for insulation Prevent any upward flow or reverse flow in any part.
(Local supply)
10mm or thicker formed thermal insulation shall always
Insulation be provided for the drain pipe.
(Local supply)
Union for gas pipe

Attached drain hose


Downward 1/50~1/100 or more
Bottom of unit
Thermal insulation for refrigerant pipe

or more or more
50mm 50mm
(Local supply) Thermal insulation for Approx 2~3mm
piping(Local supply)

Overlap with
insulation

h U-trap is not required for low static model in which the


Make sure that there is no clearance here.
external static pressure is below 50 pa(5mm Aq)

CAUTION

Make sure to insulate any field piping all the way to the
piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.

Ceiling concealed duct - high static pressure _ 13


Indoor unit
9. Installation
- With drain pump Check the drain.
Possible drain head is upto 700mm. Poor eough water on the drain pan.
Keep the drain pipe downward stope upto 1/50~1/100. Ensure that water flows through the drain pipe from indoor
Prevent any upward flow or reverse flow in any part. unit without any leakage.
10mm or thicker insulation should be provided for the
drain pipe.

1/50~1/100

Drain Pipe

MAX 700mm
Product data_Indoor units

Drain Pump
9.6 Electric wiring work
Thermal insulattion 1) General instructions
(Local supply)
All field supplied parts and materials, electric works must
Drain pipe
Unit (Local supply)
conform to local codes.
Use copper wire only.
Follow the "WIRING DIAGRAM attached to the unit
body to wire the outdoor unit, indoor units and the remote
Elbow controller.
All wiring must be performed by an authorized electri-
Drain pump cian.
This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B..., and be sure the terminal
5) Checking the drain board wiring to the outdoor unit and indoor unit are prop-
erly matched. If wiring and piping between the outdoor
Remove the air filter. unit and an indoor unit are mismatched, the system may
cause a malfunction.
A circuit breaker capable of shutting down the power
supply to the entire system must be installed.

14 _ Ceiling concealed duct - high static pressure


Indoor unit
9. Installation
2) Wiring connection NOTE
Connect the wires to the terminals on the control board indi-
vidually according to the outdoor unit connection. 1. Use round crimp-style terminals for connecting
wires to the power supply terminal block. If
Ensure that the color of the wires of outdoor unit and the unavailable, observe the following points when
terminal No. are the same as those of indoor unit respec- wiring.
tively 24/30/36 kBtu/h
Do not connect wires of different gauge to the same
power supply terminal.
Terminal block of Indoor Unit
Use the specified electric wire. Connect the wire securely
1(L) 2(N) 3 to the terminal. Lock the wire down without applying
excessive force to the terminal.

Attach insulation sleeve


Connected to outdoor Unit (or BD unit) Round crimp-style terminal

Product data_Indoor units


If the supply cord is damaged, it must be replaced by a
special cord or assembly availible from the manufacturer Electric wire
of its service agent.

WARNING

Make sure that the screws of the terminal are fixed tightly.
Connect wires of the same gauge to both sides

2 Tightening torque for the terminal screws.


CAUTION
Use the correct screwdriver for tightening the terminal
Make sure to attach the sealing material or (field sup- screws. If the blade of screwdriver is too small, the head
plied) to hole of wiring to prevent the infiltration of foreign of the screw might be damaged, and the screw will not
particle from outside. Otherwise a short-circuit may be properly tightened.
occur inside the electric parts box If the terminal screws are tightened too hard, screws
When clamping the wires, be sure no pressure is applied might be damaged.
to the wire connections by using the included clamping 3. Do not connect wires of different gauge to the
material to make appropriate clamps. Also, when wiring, same grounding terminal. Loose connection may
make sure the cover on the electric parts box fits snugly deteriorate protection.
by arranging the wires neatly and attaching the electric
parts box cover firmly. When attaching the electric parts 4. Outside of the unit, keep proper separation
box cover, make sure no wires get caught in the edges. between transmission and power supply wiring.
Pass wiring through the holes to prevent damage to The equipment may malfunction if subjected to
them. electrical (external) noise.

Make sure the remote controller wiring, the wiring 5. Never connect power supply wiring to the terminal
between the units, and other electrical wiring do not pass block for remote controller wiring. A mistake of
through the same locations outside of the unit, separat- the sort could damage the entire system.
ing them properly, otherwise electrical noise (external 6. Use only specified wire and tightly connect wires
static) could cause product malfunction. to terminals. Be careful wires do not place exter-
nal stress on terminals. Keep wiring in neat order
and so as not to obstruct other equipment such as
popping open the electric parts box cover. Make
sure the cover closes tight. Incomplete connec-
tions could result in overheating, and in worse
case, electric shock or fire.

Ceiling concealed duct - high static pressure _ 15


Indoor unit

Ceiling concealed duct - low static pressure(Slim)


1. List of functions
2. Specifications
3. Dimensions
4. Piping diagrams
5. Wiring Diagrams
6. External pressure setting for Tuning
7. Sound levels
8. Controller
9. Installation
Indoor unit
1. List of functions
AMNC12GB1A2
Category Functions AMNC18GB2A2
AMNC24GB2A2
Air supply outlet 1
Airflow direction control (left & right) X
Airflow direction control (up & down) X
Auto swing (left & right) X
Air flow Auto swing (up & down) X
Airflow steps (fan/cool/heat) 3/3/-
Chaos wind(auto wind) X
Jet cool/heat X
Swirl wind X
Triple filter (Deodorizing) X
Plasma air purifier X
Air purifying
Allergy Safe filter X
Long-life prefilter (washable / anti-fungus) O

Product data_Indoor units


Drain pump O
E.S.P. control* O
Installation Electric heater X
High ceiling operation* X
Auto Elevation Grille* X
Hot start X
Reliability Self diagnosis O
Soft dry operation O
Auto changeover X
Auto cleaning X
Auto operation(artificial intelligence) O
Auto Restart O
Child lock* O
Convenience Forced operation X
Group control* O
Sleep mode X
Timer(on/off) O
Timer(weekly)* O
Two thermistor control* O
Wired remote controller PQRCVSL0 / PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) X
Wireless remote controller PQWRCDF0
General central controller (Non LGAP) X
Network Network Solution(LGAP) O
function Dry contact PQDSA(1)/PQDSB(1) / PQDSBC
PI 485(for Indoor Unit) X
Zone controller ABZCA
Special
CTI(Communication transfer interface) X
function kit
Electronic thermostat X
Remote temperature sensor PQRSTA0
Others Group control wire PZCWRCG3
Telecom shelter controller X

Note
1. * : These functions need to connect the wired remote controller.
O : Applied X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with sepa-
rate package.

Ceiling Concealed Duct Low static pressure(Slim) _ 1


Indoor unit
2. Specifications
Model Name AMNC12GB1A2 AMNC18GB2A2
230, 1, 50 230, 1, 50
Power Supply V, , Hz
220, 1, 60 220, 1, 60
kW Class 3.5 5.3
Nominal Capacity
Btu/h Class 12,000 18,000
Power Input W x No. - -
Running Current A 1.00 1.60
WxHxD mm 820 190 575 1,100 190 575
Dimensions Body
WxHxD inch 32-9/32 x 7-15/32 x 22-5/8 43-5/16 x 7-15/32 x 22-5/8
Net Weight Body kg (lbs) 20.5 (45.2) 25.0 (55.1)
Heat (Row x Column x Fins per inch) x No. - (2 x 12 x 21) x 1 (2 x 11 x 21) x 1
Exchanger Face Area m2 (ft2) 0.16 (1.68) 0.21 (2.31)
Product data_Indoor units

Type - Sirocco fan Sirocco fan


H/M/L m /min
3
9.5 / 8.5 / 7.5 15.0 / 13.5 / 11.5
High-static
Fan Air Flow Mode H / M / L ft3/min 336 / 300 / 265 530 / 477 / 406
Rate (Factory External Static
Set) Pa (mmAq) 39 (4) 39 (4)
Pressure
Type - BLDC BLDC
Fan Motor
Output W x No. (5 x 1) + (19 x 1) 19 x 2
Sound Pressure Level H/M/L dB(A) 33 / 31 / 26 34 / 31 / 29
Sound Power Level H/M/L dB(A) - -
Liquid mm(inch) 6.35 (1/4) 6.35 (1/4)
Piping
Gas mm(inch) 9.52 (3/8) 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm 32.0 / 25.0 32.0 / 25.0
- Fuse Fuse
Safety Devices
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

2 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
2. Specifications
Model Name AMNC24GB2A2
230, 1, 50
Power Supply V, , Hz
220, 1, 60
kW Class 7.0
Nominal Capacity
Btu/h Class 24,000
Power Input W x No. -
Running Current A 1.60
WxHxD mm 1,100 190 575
Dimensions Body
WxHxD inch 43-5/16 x 7-15/32 x 22-5/8
Net Weight Body kg (lbs) 25.0 (55.1)
Heat (Row x Column x Fins per inch) x No. - (3 x 10 x 18) x 1
Exchanger Face Area m2 (ft2) 0.19 (2.10)

Product data_Indoor units


Type - Sirocco fan
H/M/L m /min
3
17.0 / 15.0 / 13.5
High-static
Fan Air Flow Mode H / M / L ft3/min 600 / 530 / 477
Rate (Factory External Static
Set) Pa (mmAq) 39 (4)
Pressure
Type - BLDC
Fan Motor
Output W x No. 19 x 2
Sound Pressure Level H/M/L dB(A) 36 / 34 / 32
Sound Power Level H/M/L dB(A) -
Liquid mm(inch) 6.35 (1/4)
Piping
Gas mm(inch) 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm 32.0 / 25.0
- Fuse
Safety Devices
- Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18)

Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.

Ceiling Concealed Duct Low static pressure(Slim) _ 3


Indoor unit
3. Dimensions

AMNC12GB1A2
B1 Chassis
Product data_Indoor units

4 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
3. Dimensions

AMNC18GB2A2
AMNC24GB2A2
B2 Chassis

Product data_Indoor units

Ceiling Concealed Duct Low static pressure(Slim) _ 5


Indoor unit
4. Piping diagrams
Models : AMNC-B1 model

Evaporator Gas pipe connection port


Heat exchanger
Outlet (flare connection)
Heating Thermistor

Cooling
Sirocco Fan

Thermistor
Indoor Air
M M
Thermistor
Evaporator Inlet
Product data_Indoor units

Liquid pipe connection port


(flare connection)

Description PCB Connector


Indoor Air Thermistor CN-ROOM
Evaporator Inlet Thermistor CN-PIPE/IN
Evaporator Outlet Thermistor CN-PIPE/OUT

n Refrigerant pipe connection port diameters


[Unit:mm(inch)]
Model Gas Liquid
AMNC12GB1A2 9.52(3/8) 6.35(1/4)

6 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
4. Piping diagrams
Models : AMNC-B2 model

Evaporator Gas pipe connection port


Heat exchanger
Outlet (flare connection)
Heating Thermistor

Cooling
Sirocco Fan

Thermistor
Indoor Air
M M
Thermistor
Evaporator Inlet

Product data_Indoor units


Liquid pipe connection port
(flare connection)

Description PCB Connector


Indoor Air Thermistor CN-ROOM
Evaporator Inlet Thermistor CN-PIPE/IN
Evaporator Outlet Thermistor CN-PIPE/OUT

n Refrigerant pipe connection port diameters


[Unit:mm(inch)]
Model Gas Liquid
AMNC18GB2A2
12.7(1/2) 6.35(1/4)
AMNC24GB2A2

Ceiling Concealed Duct Low static pressure(Slim) _ 7


Indoor unit
5. Wiring diagrams
Product data_Indoor units

8 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
6. External pressure setting for
How to Set E.S.P. on the remote controller?

CAUTION:
If you set ESP incorrectly, the air conditioner may malfunction.
This setting must be carried out by a certificated-technician.

1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press

Product data_Indoor units


more than 3 seconds for sure.

2 If entering into ESP setup mode by using


button, it indicates as the picture
below.

ESP step
Function Code ESP value

Function code,
ESP code 3 Select ESP fan step by pressing
button. (01: very low, 02: low,
03: medium, 04: high, 05: power)
ESP value

4 Movebutton.
to ESP value setting by pressing

(It is 000 when delivering


from the warehouse.)

5 Press button to setup ESP value.

(It is possible to setup ESP


value from 1 to 255, and 1 is
the smallest and 255 is the
biggest.)

h When setting ESP value on the product without very weak wind or power wind function, it may not work.

Ceiling Concealed Duct Low static pressure(Slim) _ 9


Indoor unit
6. External pressure setting for
Static Pressure (mmAq) 0 1 2 3 4
Model name Step CMM(CFM) Setting value
High 9.5(336) 82 90 99 109 118
AMNC12GB1A2
Mid 8.5(300) 75 84 94 104 114
Low 7.5(265) 69 77 88 99 110
High 15.0(530) 90 97 105 114 122
AMNC18GB2A2 Mid 13.5(477) 82 90 99 109 119
Low 11.5(406) 75 84 93 103 114
High 17.0(600) 110 117 125 129 -
AMNC24GB2A2 Mid 15.0(530) 100 107 115 121 127
Low 13.5(477) 90 97 105 114 122
Product data_Indoor units

[ Notes ]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.

10 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
7. Sound levels
Overall
Notes:
- Data is valid at nominal operation condition
- Reference accoustic pressure 0dB = 20Pa
- Sound level will vary depending on a range of factors such as
Ceiling the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

1.5m
2.0m - The operating conditions are assumed to be standard.

Microphone

50Hz 230V
Model Sound pressure Levels [dB(A)]
H M L

Product data_Indoor units


AMNC12GB1A2 33 31 26
AMNC18GB2A2 34 31 29
AMNC24GB2A2 36 34 32

Sound Pressure Level


AMNC12GB1A2 AMNC18GB2A2 AMNC24GB2A2
80 80 80

70 70 70
Octave Band Sound Pressure Level (0dB = 20Pa)

Octave Band Sound Pressure Level (0dB = 20Pa)

Octave Band Sound Pressure Level (0dB = 20Pa)

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

Ceiling Concealed Duct Low static pressure(Slim) _ 11


Indoor unit
8. Controller
Wired remote control(Accessory)
1 OPERATION INDICATION SCREEN
2 SET TEMPERATURE BUTTON
1 3 FAN SPEED BUTTON
10 4 ON/OFF BUTTON
9 5 OPRATION MODE SELECTION BUTTON
8 2
6 WIRELESS REMOTE CONTROLLER
3
7 RECEIVER
4
11 Some products don't receive the wireless
12 5 signals.
13 7 AIR FLOW BUTTON
Product data_Indoor units

6
14 8 SUBFUNCTION BUTTON
15 9 FUNCTION SETTING BUTTON
10 VENTILATION BUTTON
11 RESERVATION
12 UP,DOWN,LEFT,RIGHT BUTTON
To check the indoor temperature, press
button.
Please attach the inform label inside of the door. 13 ROOM TEMPERATURE BUTTON
Please choose proper language depend on your
country. 14 SETTING/CANCEL BUTTON
15 EXIT BUTTON

Note
h Some functions may not be operated and displayed depending on the product type.
h Display temperature can be different from actual room temperature if the remote controller is installed at the place where sun-rays are
falling directly or the place nearby heat source.
h The actual product can be different from above contents depending upon model type.

12 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
9. Installation
Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards.

Air outlet vents

Product data_Indoor units


Air filters

Remote Controller
(Accessory)

9.1 Accessories
Check the following accessories are included with your unit.

1) Standard accessories

Insulation for Screws for


Name Clamp metal Clamp (Other)
fitting duct flanges

Quantity 1 EA 1 set 1 set 8 EA

Owner's manual
Installation manual

Diagram for gas pipe

for liquid pipe

Ceiling Concealed Duct Low static pressure(Slim) _ 13


Indoor unit
9. Installation
9.2 Selection of the best location B1/B2 Chassis
A
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
The place shall easily bear a load exceeding four times the
indoor units weight.

B
The place shall be able to inspect the unit as the figure.
The place where the unit shall be leveled.
The place shall allow easy water drainage.(Suitable
dimension H is necessary to get a slope to drain as fig-
ure.) Unit:mm(inch)

The place shall easily connect with the outdoor unit. Dimension
A B
Capacity
The place where the unit is not affected by an electrical 850 383
12kBtu/h Class
noise. (33 15/32) (15 3/32)
Product data_Indoor units

1,130 383
The place where air circulation in the room will be good . 18/24kBtu/h Class (15 3/32) (15 3/32)
There should not be any heat source or steam near the
unit.
2) Relative positions of indoor unit, suspen-
sion bolt and inspection hatch size
B1/B2 Chassis
Top view

9.3 Ceiling dimension and hanging


bolt location and service space
1) Select an installation site where the fol-
lowing conditions are fulfilled and that
1,000(39 3/8)

meets with your customer's approval. 600(23 19/32) 600(23 19/32)


If supporting structural members are not strong enough to Front
take the units weight, the unit could fall out of place and Unit:mm(inch)
cause serious injury. Front view
Where sufficient clearance of maintenance and service
can be ensured.
Where optimum air distribution can be ensured. 7 5/16
Where nothing blocks the air passage.
H=13/16 or more
Where condensate can be properly drained.
Where piping between indoor and outdoor units is possible
within the allowable limit (Refer to the installation manual
of the outdoor unit.)
Keep the indoor and outdoor units, power cable and trans- A
mission wiring, at least 3.3ft from TVs and radios, to pre-
vent distorted pictures and static.(Depending on the type
and source of the electrical waves, static may be heard B
even when more than 3.3ft away.) Unit:mm(inch)
Capacity(Btu/h Class) A B
12k 600(23 5/8) 900(35 15/32)
18/24k 600(23 5/8) 1,100(43 5/16)

14 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
9. Installation
Low static duct type in case of suction from back side. 9.4 Position of suspension bolt
Air Filter A place where the unit will be leveled and that can sup-
port the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

Air outlet M10 Nut x4


Panel Rear (Local
M10 SP. washer x 4 supply)
M10 washer x4

Low static duct type in case of suction from bottom side

Product data_Indoor units


Panel Rear M10 washer x4
(Local
M10 SP. washer x 4 supply)
M10 Nut x4

Air outlet
Air Filter

3) Install a canvass duct to the air discharge outlet and air


inlet so that vibration from the machine body is not
transmitted to the duct or ceiling. You should also apply Select and mark the position for fixing bolts.
acoustic (insulation material) to the inside of the duct, Drill the hole for set anchor on the face of ceiling.
and vibration insulation rubber to the suspension bolts.
4) Install suspension bolts. (Use bolts of 13/32 inch diame-
ter.)
Install the equipment where supporting structures are strong
enough to bear the equipment's weight. Use embedded inserts
or anchor bolts with new buildings and hole-in-anchors with old
buildings.

CAUTION

Tighten the nut and bolt to prevent the unit falling.

Ceiling Concealed Duct Low static pressure(Slim) _ 15


Indoor unit
9. Installation
Insert the set anchor and washer onto the suspension
bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set anchor firmly. Liquid pipe
Secure the installation plates onto the suspension bolts
Refrigerant pipe and thermal
(adjust level roughly) using nuts, washers and spring insulation(Local supply)
washers.

Clamp for insulation


Old building New building (Local supply)
Insulation
(Local supply)
Union for gas pipe

1 Set anchor
2 Plate washer
Product data_Indoor units

3 Spring washer
Thermal insulation for refrigerant pipe
4 Nut (Local supply) Thermal insulation for
al
5 Suspension piping(Local supply)
bolts

Overlap with
9.5 Connecting pipes to the indoor insulation
unit
Make sure that there is no clearance here.
1) Refrigerant piping work
please refer REFRIGERANT PIPING WORK.
2) Piping insulation CAUTION
Perform heat insulation work completely on both gas and Make sure to insulate any field piping all the way to the
the liquid pipe. Because improper insulation will result piping connection inside the unit. Any exposed piping
condensate formation over pipe. may cause condensation or burns if touched.
Use the heat insulation material for the refrigerant piping
which has an excellent heat resistance (over 248F).
Precautions in high humidity circumstance: This air con-
ditioner has been tested according to the "KS
Conditions" and confirmed that there is not any default.
However, if it is operated for a long time in high humid
atmosphere (dew point temperature: more than 73F),
water drops are liable to fall. In this case, add heat
insulation material according to the following procedure:
Heat insulation material : Adiabatic glass wool with thick-
ness 13/32 to 13/16 inch.
Stick glass wool on all air conditioners that are located in
ceiling atmosphere.

16 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
9. Installation
3) Indoor unit drain piping Lay the drain hose with a downware inclination so water
will drain out.
Drain piping must have down-slope (1/50 to 1/100): be
sure not to provide up-and-down slope to prevent rever- Thermal insulator
sal flow. (Local supply)
During drain piping connection, be careful not to exert Drainage pipe
extra force on the drain port on the indoor unit. (Local supply)
Unit
The outside diameter of the drain connection on the
indoor unit is 1 1/4 inch.
Piping material: Polyvinyl chloride pipe inner diameter Make sure to be closed. Drainage hole
1 inch and pipe fittings

CAUTION

1. Decline Installation of indoor unit is very important for Wrong method

Product data_Indoor units


the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting
pipe should be 7/32 inch.

4) Caution for gradient of unit and drain


piping
- Without drain pump:
Always lay the drain with downward inclination (1/50 to
1/100).
Prevent any upward flow or reverse flow in any part.
7/32 inch or thicker formed thermal insulation shall always
be provided for the drain pipe.

Correct method

Attached drain hose


Downward
1/50~1/100 or more

Approx 3/32~5/32 inch

U-trap is not required for low static model in which the


external static pressure is below 50 pa(5mm Aq)

Ceiling Concealed Duct Low static pressure(Slim) _ 17


Indoor unit
9. Installation
- With drain pump Check the drainage
Possible drain head height is upto 27 6/19 inch. So the Spray one or two glasses of water on the evaporator.
drain head should be below 27 6/19 inch. Ensure that water flows through the drain hose from indoor
Keep the drain hose downward upto 1/50~1/100 inclina- unit without any leakage.
tion.
Prevent any upward flow or reverse flow in any part.
7/32 inch or thicker insulation should be provided for the
drain pipe.

1/50~1/100

Drain Pipe

MAX 27 9/16 inch


Product data_Indoor units

9.6 Electric wiring work


Drain Pump
1) General instructions
All field supplied parts and materials, electric works must
Thermal insulation conform to local codes.
(Local supply) Use copper wire only.
Drain pipe Follow the "WIRING DIAGRAM attached to the unit
Unit (Local supply)
body to wire the outdoor unit, indoor units and the remote
controller.
All wiring must be performed by an authorized electri-
Elbow cian.
This system consists of multiple indoor units. Mark each
Drain pump indoor unit as unit A, unit B..., and be sure the terminal
board wiring to the outdoor unit and ID unit are properly
matched. If wiring and piping between the outdoor unit
5) Checking the drainage and an indoor unit are mismatched, the system may
cause a malfunction.
Remove the air filter.
A circuit breaker capable of shutting down the power
supply to the entire system must be installed.

2) Wiring connection
Connect the wires to the terminals on the control board ind
vidually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the
terminal No. are the same as those of indoor unit respec-
tively

Terminal block in indoor

1(L) 2(N) 3

Connected to outdoor unit(or BD Unit)

18 _ Ceiling Concealed Duct Low static pressure(Slim)


Indoor unit
9. Installation
Clamping of cables NOTE
Arrange 2 power cables on the control panel.
First, fasten the steel clamp with a screw to the inner 1. Use round crimp-style terminals for connecting
boss of control panel. wires to the power supply terminal block. If
For the cooling model, fix the other side of the clamp with unavailable, observe the following points when
a screw strongly. For the heat pump model, put the wiring.
0.75mm2 cable (thinner cable) on the clamp and tighten it
with a plastic clamp to the other boss of the control Do not connect wires of different gauge to the same power
panel. supply terminal.
In Australia, the length of power supply cord measured Use the specified electric wire. Connect the wire securely
from the entry of the power supply cord to the middle of to the terminal. Lock the wire down without applying
live pin on the power plug should be over 5.9ft. excessive force to the terminal.

CAUTION Attach insulation sleeve


Make sure that the screws of the terminal are fixed

Product data_Indoor units


Round crimp-style terminal
tightly.

Electric wire

CAUTION

Make sure to attach the sealing material or (field sup-


plied) to hole of wiring to prevent the infiltration of foreign
particle from outside. Otherwise a short-circuit may
occur inside the electric parts box
When clamping the wires, be sure no pressure is applied Connect wires of the same gauge to both sides
to the wire connections by using the included clamping
material to make appropriate clamps. Also, when wiring, 2. Tightening torque for the terminal screws.
make sure the cover on the electric parts box fits snugly Use the correct screwdriver for tightening the terminal
by arranging the wires neatly and attaching the electric screws. If the blade of screwdriver is too small, the
parts box cover firmly. When attaching the electric parts head of the screw might be damaged, and the screw
box cover, make sure no wires get caught in the edges. will not be properly tightened.
Pass wiring through the wiring through holes to prevent
damage to them. If the terminal screws are tightened too hard, screws
might be damaged.
Make sure the remote controller wiring, the wiring
between the units, and other electrical wiring do not 3. Do not connect wires of different gauge to the
pass through the same locations outside of the unit, sep- same grounding terminal. Loose connection may
arating them properly, otherwise electrical noise (exter- deteriorate protection.
nal static) could cause product malfunction. 4. Outside of the unit, keep proper separation
between transmission and power supply wiring.
The equipment may malfunction if subjected to
electrical (external) noise.
5. Never connect power supply wiring to the terminal
block for remote controller wiring. A mistake of
the sort could damage the entire system.
6. Use only specified wire and tightly connect wires
to terminals. Be careful wires do not place
external stress on terminals. Keep wiring in neat
order and so as not to obstruct other equipment
such as popping open the electric parts box
cover. Make sure the cover closes tight.
Incomplete connections could result in overheat-
ing, and in worse case, electric shock or fire.

Ceiling Concealed Duct Low static pressure(Slim) _ 19


P/No.: MFL67502503

Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.