You are on page 1of 116

Breakers and Switches

Switch fuses
OS and OSM
Switch fuses
OS and OSM 20...1250

Product overview, features


Product overview 4
Features 6

Technical data 7

Type designation key 17

Ordering information, manual operation, DIN type 19


Front operated 19
Side operated 24
Special connected 26

Ordering information, manual operation, BS type 28


Front operated 28
Side operated 34
Special connected 36

Ordering information, manual operation, NFC type 38


Front operated 38
Side operated 39

Ordering information, manual operation, CC, J and L types 40


Front operated 40
Side operated 42

Ordering information, motorized operation 43


Motorized switch fuses OSM, DIN-, BS- and NFC -types 43

Ordering information, accessories 45


Selection overview 45
Optional handles 47
Extended shafts and shaft accessories 51
Auxiliary contacts 54
Fourth poles and neutral links 57
Solid links, handle/fuse storage and phase barriers 59
Terminal shrouds and terminal angles 60
Terminal clamps 62
Conversion kits 65
Blown fuse indicators 68
Locking and mounting accessories 69

Dimension drawings 71

Contact functions 105

Index 107

Switch fuses OS and OSM | Contents 3


Switch fuses 20...1250 Amperes

Manual operation

Switch size [A] 20 25 30 32 35 40 32 50 60 63 100 125 160 100 200 250


DIN - OS40FD OS32GD OS125GD OS200D
- OS63GD OS160GD OS250D
BS OS20FB OS32GB OS100GB OS200B
OS32FB OS63GB OS125GB OS250B
OS160GB
NFC OS25FF OS50GF OS125GF
OS32FF
UL98 File # E101914 OS30FACC OS60GJ OS100GJ
OS30FAJ
AC23/400 V [kW] 11 15 15 18.5 15 22 30 55 75 110 140
AC23/415 V [kW] 7.5 15 15 30 55 55 75 110 145
480 V [HP] 15 30 60
600 V [HP] 20 50 75

Switch size [A] 200 315 400 600 630 800 1200 1250
DIN OS400D OS630D OS1250D
OS800D
BS OS315B OS630B OS1250B
OS400B OS800B
UL98 File # E101914 OS200J OS400J OS600J OS1200L
OS800L
AC23/400 V [kW] 230 355 450 560
AC23/415 V [kW] 180 230 355 450 560
480 V [HP] 150 250 400 500 -
600 V [HP] 200 250 500 600 -

4 Product overview | Switch fuses OS and OSM


Switch fuses 20...1250 Amperes

Motor operation

Switch size [A] 32 50 63 100 125 160 200 250


DIN OSM32GD OSM125GD OSM200D

OSM63GD OSM160GD OSM250D


BS OSM32GB OSM100GB OSM200B
OSM63GB OSM125GB OSM250B
OSM160GB

Switch size [A] 315 400 630 800 1250


DIN OSM400D OSM630D OSM1250D
OSM800D
BS OSM315B OSM630B OSM1250B
OSM400B OSM800B

Switch fuses OS and OSM | Product overview 5


Switch fuses
Designed for extreme conditions

Reduced testing and design costs Save money and installation space
Tested type 2 co-ordination tables for motor protection are OS switch fuses are compact, allowing installation in smaller
available. This enables a fast and easy selection of motor enclosures. Lighweight structure saves money by reducing
control devices. installation time.
(http://applications.it.abb.com/SOC/Page/Selection.aspx)
High protection and reliability
Easy installation and design of panels Contact design enables rapid fault clearance and maintains
Thanks to a modular structure the mechanism and poles can protection level even after fault occurs.
be placed according to installation requirements. The shaft is
adjustable for a range of installation depths.

6 Features | Switch fuses OS and OSM


Technical data, IEC
Switch fuses OS20...40 and OS32G

Technical data according to IEC 60947-3 OS (Mini) OS (Mini) OS (Mini) OS (Mini) OS_
Switch size
A 20 25 32 40 32G
Rated insulation voltage Pollution degree 3 V 1 000 1 000 1 000 1 000 1 000
Dielectric strength 50 Hz 1min. kV 10 10 10 10 10
Rated impulse withstand voltage kV 12 12 12 12 12
Rated thermal current in ambient In open air A/W 20/3.5 25/3.5 32/3.5 40/4.5 32/7.5
35 C and temporarily 40 C 4) / In enclosure2) A/W 20/3.5 25/3.5 32/3.5 40/4.5 32/7.5
max. fuse power dissipation 1) In enclosure with solid links A 32 32 32 40
...with minimum cable cross section Cu mm 2 2.5 4 6 10 6
Rated operational voltage AC-20 and DC-20 V 1 000 1 000 1 000 1 000 1 000
Rated operational current, AC-21A up to 500 V A 20 25 32 40 32
690 V A 20 25 32 40 32
Rated operational current, AC-22A up to 500 V A 20 25 32 40 32
690 V A 20 25 32 40 32
Rated operational current, AC-23A up to 500 V A 20 25 32 40 32
690 V A 20 25 32 40 32
Rated operational current / poles in series DC-21A 48 V A 20/2 25/2 32/2 32/2 32/2
110-220 V A 20/2 25/2 32/2 32/2 32/2*
440 V A 20/4 25/4 25/4 32/4 32/4*
Rated operational current / poles in series DC-22A 48 V A 20/2 25/2 32/2 32/2 32/2
110-220 V A 20/2 25/2 32/2 32/2 32/2*
440 V A 20/4 25/4 32/4 32/4
Rated operational current / poles in series DC-23A 48 V A 20/2 25/2 32/2 32/2 32/2
110-220 V A 20/2 25/2 32/2 32/2 32/2*
440 V A 20/4 25/4 32/4 32/4
Rated operational power, AC-23 3) The kW-ratings are accurate for 230 V kW 5.5 5.5 7.5 11 7.5
three-phase 1500 R.P.M. 400 V kW 7.5 11 15 18.5 15
standard asynchronous motors. 415 V kW 7.5 11 15 18.5 15
500 V kW 11 15 18.5 22 18.5
690 V kW 15 22 22 30 22
Rated breaking capacity in category AC-23 690 V A 256 256 256 320 504
Rated breaking capacity / poles in series up to 220 V A 128/2 128/2 128/2 128/2 252/2
in category DC-23 440 V A 128/4 128/4 128/4 128/4
Rated conditional short-circuit current at prospective SC-current 80 kA, 415 V kA 9 9 9 9 13.5
I p (r.m.s.) and corresponding max. Max. OFA_ fuse size gG / aM A 80/63
allowed cut-off current c at prospective SC-current 100 kA, 500 V kA 8 8 8 8 12.5
Max. OFA_ fuse size gG / aM A 63/50
The cut-off current c refers to values at prospective SC-current 50 kA, 690 V kA 7 7 7 7 9.5
listed by fuse manufacturers Max. OFA_ fuse size gG / aM A 63/50
(single phase test acc. to IEC60269). at prospective SC-current 80 kA, 690 V kA 7.5 7.5 7.5 7.5 11.5
Max. OFA_ fuse size gG / aM A 50/50
Rated short-time withstand current, 1 s. r.m.s. -value kA 1 1 1 1 2.5
Rated capacitor power The capacitor rating of the 400 V kVAr 10 12.5 15 15 15
when no initial charge on the capacitor switch-fuse is limited by 415 V kVAr 10 12 15 15 15
the fuse link. 690 V kVAr 15 20 25 25 25
Power loss / pole With rated current, without fuse W 1.3 1.3 2 3.5 1
Mechanical endurance Divide by two for operation cycles Oper. 20 000 20 000 20 000 20 000 20 000
Fuse types, IEC 60269-2-1 DIN 43620 000 000
NFC 63210, 63211 10x38 14x51
BS 88-2, -6 -size / A1 A1, A2 A2-A3 5)
distance of fuse-link bolts mm M4/44.5 M4/44.5 (A1) M5/73
mm M4/73 (A2)
Cable size Cu mm 2 0.75...10 0.75...10 0.75...10 0.75...10 2.5...25
Terminal tightening torque Counter torque required Nm 2 2 2 2 3/4 6)
Fuse-links bolts tightening torque Nm 2 2 3.5
Operating torque Typical for 3-pole switch fuses Nm 3 3 3 3 5
* = Utilization category B
1)
Ambient temperature 60C: derating 20%. Mounting on "ceiling": derating 10%
2)
OS160G: Mounting on wall, horizontal fuses: derating 5%
3)
Some fuse links limit these figures further. Starting current characteristics must be considered separately
4)
Acc. to IEC 60947-1, 6.1.1. Minimum ambient temperature -5C. Category B: -5C...-35C
5)
Max. fuse body diam. 22 mm
6)
3 Nm with cable sizes 2.5...6 mm2,
4 Nm with cable sizes 10...25 mm2

Switch fuses OS and OSM | Technical data 7


Technical data, IEC
Switch fuses OS50...160G

Technical data according to IEC 60947-3 OS_ OS_ OS_ OS_ OS_
Switch size A 50G 63G 100G 125G 160G
Rated insulation voltage Pollution degree 3 V 1 000 1 000 1 000 1 000 1 000
Dielectric strength 50 Hz 1min. kV 10 10 10 10 10
Rated impulse withstand voltage kV 12 12 8 8 8
Rated thermal current in ambient In open air A/W 50/7.5 63/7.5 100/12 125/12 160/12
35 C and temporarily 40 C 5) / In enclosure2) A/W 50/7.5 63/7.5 100/12 125/12 160/12
max. fuse power dissipation 1)
...with minimum cable cross section Cu mm2 10 16 50 50 70
Rated operational voltage AC-20 and DC-20 V 1 000 1 000 1 000 1 000 1 000
Rated operational current, AC-21A up to 500 V A 50 63 100 125 160
690 V A 50 63 100 125 160
Rated operational current, AC-22A up to 500 V A 50 63 100 125 160
690 V A 50 63 100 125 160
Rated operational current, AC-23A up to 500 V A 50 63 100 125 160
690 V A 50 63 100 125 160
Rated operational current / poles in series DC-21A 48 V A 50/2 63/2 100/2 125/2 160/2
110-220 V A 50/2* 63/2* 100/2* 125/2* 125/2*
440 V A 50/4* 50/4* 100/4* 125/4* 125/4*
Rated operational current / poles in series DC-22A 48 V A 50/2 63/2 100/2 125/2 160/2
110-220 V A 50/2* 63/2* 100/2* 125/2* 125/2*
Rated operational current / poles in series DC-23A 48 V A 50/2 63/2 100/2 125/2 160/2
110-220 V A 50/2* 63/2* 100/2* 125/2* 125/2*
Rated operational power, AC-23 4) The kW-ratings are accurate for 230 V kW 11 18.5 30 37 45
three-phase 1500 R.P.M. 400 V kW 22 30 55 55 75
standard asynchronous motors. 415 V kW 22 30 55 55 75
500 V kW 30 37 55 75 90
690 V kW 37 55 90 110 132
Rated breaking capacity in category AC-23 690 V A 504 504 1280 1280 1280
Rated breaking capacity / poles in series up to 220 V A 252/2 252/2 640/2 640/2 640/2
in category DC-23
Rated conditional short-circuit current at prospective SC-current 80 kA, 415 V kA 13.5 13.5 23.5 23.5 23.5
I p (r.m.s.) and corresponding max. Max. OFA_ fuse size gG / aM A 80/63 80/63 160/160 160/160 160/160
allowed cut-off current c at prospective SC-current 100 kA, 500 V kA 12.5 12.5 25.5 25.5 25.5
Max. OFA_ fuse size gG / aM A 63/50 63/50 160/160 160/160 160/160
The cut-off current c refers to values at prospective SC-current 50 kA, 690 V kA 9.5 9.5 17.5 17.5 17.5
listed by fuse manufacturers Max. OFA_ fuse size gG / aM A 63/50 63/50 125/160 125/160 125/160
(single phase test acc. to IEC60269). at prospective SC-current 80 kA, 690 V kA 11.5 11.5 20.5 20.5 20.5
Max. OFA_ fuse size gG / aM A 50/50 50/50 125/160 125/160 125/160
Rated short-time withstand current, 1 s. r.m.s. -value kA 2.5 2.5 5 5 5
Rated capacitor power The capacitor rating of the 400 V kVAr 20 25 40 50 60
when no initial charge on the capacitor switch-fuse is limited by 415 V kVAr 25 32 42 55 65
the fuse link. 690 V kVAr 42 50 75 90 100
Power loss / pole With rated current, without fuse W 2.5 4 4 5 9
Mechanical endurance Divide by two for operation cycles Oper. 20 000 20 000 20 000 16 000 16 000
Fuse types, IEC 60269-2-1 DIN 43620 000 000, 00 000, 00
NFC 63210, 63211 14x51 22x58
BS 88-2, -6 -size / A2-A3 6) A2-A43) A2-A43) A2-A43)
distance of fuse-link bolts mm M5/73 M5/73, M8/94 M5/73, M8/94 M5/73, M8/94
mm
Cable size Cu mm 2 2.5...25 2.5...25
Terminal tightening torque Counter torque required Nm 3/47) 3/47) 15-22 15-22 15-22
Fuse-links bolts tightening torque Nm 3.5 M5:3.5 M8:5 M5:3.5 M8:5 M5:3.5 M8:5
Operating torque Typical for 3-pole switch fuses Nm 5 5 7 7 7
* = Utilization category B
1)
Ambient temperature 60C: derating 20%. Mounting on "ceiling": derating 10%
2)
OS160G: Mounting on wall, horizontal fuses: derating 5%
3)
Max. fuse body diam. 32 mm
4)
Some fuse links limit these figures further. Starting current characteristics must be considered separately
5)
Acc. to IEC 60947-1, 6.1.1. Minimum ambient temperature -5C. Category B: -5C...-35C
6)
Max. fuse body diam. 22 mm
7)
3 Nm with cable sizes 2.5...6 mm2,
4 Nm with cable sizes 10...25 mm2

8 Technical data | Switch fuses OS and OSM


Technical data, IEC
Switch fuses OS/OSM200...1250

Technical data according to IEC 60947-3 OS_ OS_ OS_ OS_ OS_
Switch size A 200GB 200_ 250_ 315_ 400_
Rated insulation voltage and rated operational
voltage AC-20 and DC-20 Pollution degree 3 V 1 000 1000 1 000 1 000 1 000
Dielectric strength 50 Hz 1min. kV 10 10 10 10 10
Rated impulse withstand voltage kV 8 12 12 12 12
Rated thermal current in ambient
35 C and temporarily 40 C5) / In open air A/W 200/14 200/17 250/23 315/32 400/45
max. fuse power dissipation In enclosure A/W 200/14 200/15 250/20 315/32 400/30
...with minimum cable cross section Cu mm2 70 95 120 185 240
Derating, mounting on In open air or ventilated enclosure % 0 0 0 0 4
wall horizontal fuses Totally enclosed % 5 5 5 5 8
Derating, mounting on ceiling % 10 10 10 10 10
Derating at 60 C In open air / in enclosure % 20/20 20/20 20/20 20/20 20/20
Rated operational current AC-22B 415 V A 200
Rated operational current AC-21A 500 V A 160 200 250 315 400
690 V A 160 200 250 315 400
Rated operational current AC-22A 415 V A 160 200 250 315 400
500 V A 160 200 250 315 400
690 V A 160 200 250 315 400
Rated operational current AC-23A 415 V A 160 200 250 315 400
500 V A 160 200 250 315 400
690 V A 160 200 250 315 400
Rated operational current / 220 V A 125/26) 200/1 250/1 315/2 400/2
poles in series DC-21A, DC-22A and DC-23A 440 V A 125/46) 200/2 250/2 315/34) 400/34)
660 V A 200/3 250/3 315/44) 400/44)
750 V A 180/4 230/4 315/44) 400/44)
880 V A 180/4 230/4
Rated operational power AC-231) 230 V kW 45 60 75 100 132
400 V kW 75 110 140 160 220
415 V kW 75 110 145 180 230
500 V kW 90 132 170 220 280
690 V kW 132 200 250 315 400
Rated breaking capacity AC-23 690 V A 1280 1600 2000 3200 3200
Rated conditional short-circuit at prospective SC-current 80 kA, 415 V kA 23.5 35 40.5 59
current Ip (r.m.s.) Max. OFA_ fuse size gG/aM A 160/160 250/200 355/315 500/500
and corresponding max. at prospective SC-current 100 kA, 500 V kA 25.5 37.5 37.5 63.5
allowed cut-off current c Max. OFA_ fuse size gG/aM A 160/160 250/200 250/250 500/500
at prospective SC-current 80 kA, 690 V kA 20.5 25 32.5 46
Max. OFA_ fuse size gG/aM A 125/160 160/ 200/250 315/400
The cut-off current c refers at prospective SC-current 50 kA, 415 V kA 17.5 28 28 44 44
to values listed by fuse Max. BS fuse size gG/gM A 125/160 200/200M315 250/200M315 400/400M500 400/400M500
manufacturers (single phase at prospective SC-current 80 kA, 690 V kA 20.5 28 28 48 48
test acc. to IEC60269). Max. BS fuse size gG/gM A 125/160 200/200M250 250/200M250 400/400M450 400/400M450
Rated short-time withstand current, 1s. r.m.s. -value kA 5 8 8 14 14
Max. distance from switch frame mm 150 150 150 150 150
to nearest busbar/cable support
Rated capacitor power The capacitor ratings of the switch-fuses 400 V kVAr 60 90 105 145 180
when no initial charge of the capacitor are limited by the fuse links 415 V kVAr 65 100 115 160 200
500 V kVAr 120 135 175 215
690 V kVAr 100 160 190 250 325
Power loss / pole With rated current, without fuse W 9 8 13 19 30
Mechanical endurance Divide by two for operation cycles Oper. 16 000 20 000 20 000 16 000 16 000
Fuse types, IEC 60269-2 Sec. I, DIN 43620 0 0-1 0-2
Sec. IA, NFC 0-3 Ref.A, 4a Ref.B 1 1 2
Sec. II, BS 88 A2-A4 B1-B2 B1-B32) B1-B43) B1-B43)
Size / distance of fuse-link bolts mm M5/73, M8/94 M6/111 M8/111 M8/111 M8/111
Terminal tightening torque Counter torque required Nm 15-22 15-22 30-44 30-44 30-44
Fuse-links bolts tightening torque Nm M5:3.5 M8:5 4 5 20 20
Operating torque Typical for 3-pole switch fuses Nm 7 7 7 19 19
1)
These values are given for guidance and may vary acc. to the motor manufacturer
2)
Max fuse body dia 52 mm
3)
Max fuse body dia 62 mm
4)
Category B
5)
Acc. to IEC 60957-2, IEC 60947-1, 6.1.1. Minimum ambient temperature -5C. Category B: -5C...-35C
6)
Utilization category DC21-B

Switch fuses OS and OSM | Technical data 9


Technical data, IEC
Switch fuses OS/OSM200...1250

Technical data according to IEC 60947-3 OS_ OS_ OS_


Switch size A 630_ 800_ 1250_
Rated insulation voltage and rated operational
voltage AC-20 and DC-20 Pollution degree 3 V 1000 1000 1000
Dielectric strength 50 Hz 1min. kV 10 10 10
Rated impulse withstand voltage kV 12 12 12
Rated thermal current in
ambient 35 C and temporarily in 40 C3) / In open air A/W 630/60 800/65 1250/110
max. fuse power dissipation In enclosure A/W 570/50 720/55 1000/85
...with minimum cable cross section Cu mm2 2 x 185 2 x 240 2 x 400
Derating, mounting on In open air or ventilated enclosure % 0 4 4
wall horizontal fuses Totally enclosed % 5 8 8
Derating, mounting on 'ceiling' % 10 10 10
Derating at 60 C In open air / in enclosure % 20/20 20/20 20/20
Rated operational current AC-21A 500 V A 630 800 12504)
690 V A 630 800 12504)
Rated operational current AC-22A 415 V A 630 800 1250
500 V A 630 800 12504)
690 V A 630 800 12504)
Rated operational current AC-23A 415 V A 6302) 800 1000
500 V A 6302) 800 1000 4)
690 V A 6302) 800 1000 4)
Rated operational current / 220 V A 630/12) 800/12)
poles in series DC-21A, DC-22A and DC-23A 440 V A 630/22) 800/22)
660 V A 630/32) 720/32)
750 V A 630/42) 720/42)
880 V A 630/42) 720/42)
Rated operational power AC-231) 230 V kW 200 250 315
400 V kW 355 450 560
415 V kW 355 450 560
500 V kW 450 560 710
690 V kW 630 710 1000
Rated breaking capacity AC-23 690 V A 6400 6400 8000
Rated conditional short circuit current at prospective SC-current 80 kA, 415 V kA 77 77 89
Ip (r.m.s.) and corresponding max. Max. OFA_ fuse size gG/aM A 800/800 800/800 1250/1250
allowed cut-off current c at prospective SC-current 100 kA, 500 V kA 83 83 105
Max. OFA_ fuse size gG/aM A 800/800 800/800 1250/-
The cut-off current c refers to values at prospective SC-current 80 kA, 690 V kA 55 55 88
listed by fuse manufacturers Max. OFA_ fuse size gG/aM A 500/630 500/630 1000/1000
(single phase at prospective SC-current 50 kA, 415 V kA 67 67 90
test acc. to IEC60269) Max. BS fuse size gG/gM A
Rated short-time withstand current, 1s. r.m.s. -value kA 18 18 40
Max. distance from switch frame mm 150 150 150
to nearest busbar/cable support
Rated capacitor power The capacitor ratings of the 400 V kVAr 250 310 440
when no initial charge of the capacitor switch-fuses are limited by 415 V kVAr 270 340 460
the fuse links 500 V kVAr 300 375 550
690 V kVAr 450 550 750
Power loss / pole With rated current, without fuse W 46 75 75
Mechanical endurance Divide by two for operation cycles Oper. 10 000 6000 6000
Fuse types, IEC 60269-2 Sec. I, DIN 43620 3 3 4, 4 a
Sec. IA, NFC 0-3 Ref.A, 4a Ref.B 3 3 4a
Sec. II, BS 88 C1-C2 C1-C3 D1
Size / distance of fuse-link bolts mm M10/133, 184 M10/133, 184 2xM12/149
Terminal tightening torque Counter torque required Nm 50-75 50-75 50-75
Fuse-links bolts tightening torque Nm M10:30 M12:40 M10:30 M12:40 M12:40
Operating torque Typical for 3-pole switch fuses Nm 38 38 65
1)
These values are given for guidance and may vary acc. to the motor manufacturer
2)
Category B with 4-pole
3)
Acc. to IEC 60957-2, IEC 60947-1, 6.1.1. Minimum ambient temperature -5C. Category B: -5C...-35C

10 Technical data | Switch fuses OS and OSM


Technical data, IEC
Special connected switch fuses OS125...200

Technical data according to IEC 60947-3 OS OS OS


Switch size A 125G 160G 200
Rated insulation voltage and rated operational voltage AC-20 and DC-20 Pollution degree 3 V 1000 1000 1000
Dielectric strength 50 Hz 1min. kV 10 10 10
Rated impulse withstand voltage kV 8 8 12
Rated thermal current in ambient 35 C A/W 125/12 160/12 200/17
and temporarily 40 C10)/max. fuse power dissipation1)
...with minimum cable or bar cross section Cu mm 50 70 95
Rated operational current, AC-21A, AC-22A, AC-23A up to 690 V A 125 160 200
Rated operational current/poles in series 48 V A 125/2 160/2 200/1
DC-21A, DC-22A and DC23-A 110-220 V A 125/2 125/2* 200/1
440 V A 125/4*(DC-21A) 125/4*(DC-21A) 200/2
660 V A 200/3
750 V A 180/4
880 V A 180/4
Rated operational power, AC-232) The kW-ratings are accurate for 230 V kW 37 45 60
three-phase 1500 R.P.M. standard 400 V/415 V kW 55/55 75/75 100/110
asynchronous motors. 500 V/690 V kW 75/110 90/132 140/180
Rated breaking capacity in category AC-23 up to 690 V A 1280 1280 1600
Rated breaking capacity/poles in series in category DC-23 up to 220 V A 640/2 640/2
Rated conditional short-circuit current Ip (r.m.s.) at prospective SC-current 80 kA, 415 V kA 23.5 23.5
and corresponding max. allowed cut-off current c Max. OFA_ fuse size gG/aM A 160/160 160/160
The cut-off currents c refer to values listed by at prospective SC-current 100 kA, 500 V kA 25.5 25.5 30
fuse manufacturers7) Max. OFA_ fuse size gG/aM A 160/160 160/160 200/2008)
(single phase test acc. to IEC60269) at prospective SC-current 50 kA, 690 V kA 17.5 17.5 20
Max. OFA_ fuse size gG/aM A 125/160 125/160 160/-
at prospective SC-current 80 kA, 690 V kA 20.5 20.5 25
Max. OFA_ fuse size gG/aM A 125/160 125/160 160/- 8)
Rated short-time withstand current, 1s. r.m.s. -value kA 5 5 8
Max. distance from switch frame mm 150
to nearest busbar/cable support
Rated capacitor power The capacitor rating of the switch- 400 V/415 V kVAr 50/55 60/65
when there is no initial charge on the capacitor fuse is limited by the fuse link 690 V kVAr 90 100
Power loss/pole With rated current, without fuse BB, BD, UB W 5 9 8
P_, L_, _R, _L, LR W 11
Mechanical endurance Divide by two for operation cycles Oper. 20 000 20 000 20 000
Fuse types, IEC 60269-2 DIN 43620 BB, BD, UB 000, 00 000, 00 0
P_, L_, _R, _L, LR 000, 00 000, 00
BS 88 BB, BD, UB A2-A49) A2-A49) B1 - B24)
-size/distance of fuse-link bolts BB, BD, UB mm M5/73, M8/94 M5/73, M8/94 M6/111
BS 88 P_, L_, _R, _L, LR A2-A49) A2-A49) B1 - B34)
-size/distance of fuse-link bolts P_, L_, _R, _L, LR mm M5/73, M8/94 M5/73, M8/94 M8/111
Terminal tightening torque Counter torque required Nm 15-22 15-22 M8:15-225),M10:30-44
Fuse-links bolts tightening torque BB, BD, UB Nm M5:3.5 M8:5 M5:3.5 M8:5 4
P_, L_, _R, _L, LR Nm 5
Operating torque Typical for 3 and 4-pole switches Nm 7 7 7
* B category. 5)
BS fuse manufacturers covered by this table ABB, MEM, Bussmann, GEC.
1)
Ambient temperature 60 C: derating 20%; mounting on ceiling: derating 10%; mounting on wall, horizontal fuses: derating 8%. 6)
3-pole types only.
OS160G: Mounting on wall, horizontal fuses: derating 5%. 7)
Max fuse body dia 32 mm.
2)
Some fuse links limit these figures further. Starting current characteristics must be considered separately. 8)
Acc. to IEC 60947-1, 6.1.1. Minimum ambient temperature -5C.Category B: -5C...-35C.
3)
Max fuse body dia 52 mm.
4)
Side terminals tightening torque max 15 Nm.

Switch fuses OS and OSM | Technical data 11


Technical data, IEC
Special connected switch fuses OS250...400

Technical data according to IEC 60947-3 OS OS OS


Switch size A 250 315 400
Rated insulation voltage and rated operational voltage AC-20 and DC-20 Pollution degree 3 V 1 000 1 000 1 000
Dielectric strength 50 Hz 1min. kV 10 10 10
Rated impulse withstand voltage kV 12 12 12
Rated thermal current in ambient 35C and temporarily 40C9)/max. fuse power dissipation1) A/W 250/23 315/32 400/45
...with minimum cable or bar cross section Cu mm 120 185 240
Rated operational current, AC-21A, AC-22A, AC-23A up to 690 V A 250 315 400
Rated operational current/poles in series 48 V A 250/1 315/2 400/2
DC-21A, DC-22A and DC23-A 110-220 V A 250/1 315/2 400/2
440 V A 250/2 315/3* 400/3*
660 V A 250/3 315/4* 400/4*
750 V A 230/4 315/4* 400/4*
880 V A 230/4
Rated operational power, AC-232) The kW-ratings are accurate for 230 V kW 75 100 110
three-phase 1500 R.P.M. standard 400 V/415 V kW 132/140 170/180 220/230
asynchronous motors. 500 V/690 V kW 170/240 220/295 280/355
Rated breaking capacity in category AC-23 up to 690 V A 2000 3200 3200
Rated conditional short-circuit current Ip (r.m.s.) at prospective SC-current 65 kA, 500 V kA 32,5 40.5
and corresponding max. allowed Max. OFA_ fuse size gG/aM A 250/- 400/-
cut-off current c

The cut-off currents c refer to values listed by at prospective SC-current 100 kA, 500 V kA 37,5 63.5
fuse manufacturers7) Max. OFA_ fuse size gG/aM A 250 /2508) 500/5008)
(single phase test acc. to IEC60269) at prospective SC-current 50 kA, 690 V kA 29,5 32
Max. OFA_ fuse size gG/aM A 250/- 355/-
at prospective SC-current 80 kA, 690 V kA 32,5 38
Max. OFA_ fuse size gG/aM A 200/2508) 355/4008)
at prospective SC-current 50 kA, 415 V kA 26 28 34
Max. BS fuse size gG/gM A 250/- 315/- 400/-
at prospective SC-current 80 kA, 415 V kA 30 50 50
Max. BS fuse size gG/gM A 250/200M2508) 400/400M5008) 400/400M5008)
at prospective SC-current 50 kA, 690 V kA 28 30 38
Max. BS fuse size gG/gM A 250/- 315/- 400/-
at prospective SC-current 80 kA, 690 V kA 28 48 48
Max. BS fuse size gG/gM A 250/200M2508) 400/400M4508) 400/400M4508)
Rated short-time withstand current, 1s. r.m.s. -value kA 8 14 14
Max. distance from switch frame mm 150 150 150
to nearest busbar/cable support
Rated capacitor power The capacitor rating of the switch- 400 V/415 V kVAr
when there is no initial charge on the capacitor fuse is limited by the fuse link 690 V kVAr
Power loss/pole With rated current, without fuse BB, BD, UB W 13 19 30
P_, L_, _R, _L, LR W 17 25 40
Mechanical endurance Divide by two for operation cycles Oper. 20 000 16 000 16 000
Fuse types, IEC 60269-2 DIN 43620 BB, BD, UB 0-1 0-2
P_, L_, _R, _L, LR 0-1 0-2
BS 88 BB, BD, UB B1 - B34) B1 - B46) B1 - B46)
-size/distance of fuse-link bolts BB, BD, UB mm M8/111 M8/111 M8/111
BS 88 P_, L_, _R, _L, LR B1 - B34) B1 - B46) B1 - B46)
-size/distance of fuse-link bolts P_, L_, _R, _L, LR mm M8/111 M8/111 M8/111
Terminal tightening torque Counter torque required Nm M8:15-225),M10:30-44 M8:15-22 5),M10:30-44 M8:15-225),M10:30-44
Fuse-links bolts tightening torque BB, BD, UB Nm 5 20 20
P_, L_, _R, _L, LR Nm 5 20 20
Operating torque Typical for 3 and 4-pole switches Nm 7 19 19
*) B category.
1)
Ambient temperature 60 C: derating 20%; mounting on ceiling: derating 10%; mounting on wall, horizontal fuses: derating 8%. OS160G: Mounting on wall, horizontal fuses: derating 5%.
2)
Some fuse links limit these figures further. Starting current characteristics must be considered separately.
3)
Plug in types: fuse size gG/aM:400/400.
4)
Max fuse body dia 52 mm.
5)
Side terminals tightening torque max 15 Nm.
6)
Max fuse body dia 62 mm.
7)
BS fuse manufacturers covered by this table ABB, MEM, Bussmann, GEC.
8)
3-pole types only.
9)
Acc. to IEC 60947-1, 6.1.1. Minimum ambient temperature -5C.Category B: -5C...-35C.

12 Technical data | Switch fuses OS and OSM


Technical data, UL/CSA
Fusible disconnect switches OS30...200

OS Mini OS OS OS
Switch size A 30 60G 100G 200
Approvals* ) 2 pole - UL98, IEC UL98, IEC UL98, IEC
3 pole UL98, IEC UL98, IEC UL98, IEC UL98, IEC
4 pole UL98, IEC UL98, IEC UL98, IEC UL98, IEC

Technical data according to UL/CSA


General purpose amp rating pf= 0.7...0.8 up to 40 C A 30 60 100 200
Max. oprerating voltage VAC 600 600 600 600
VDC 250 250 250
Max. horsepower rating / motor FLA current pf= 0.4...0.5 Three phase 240 V HP/A 7.5/22.0 15/42.0 30/80.0 60/154.0
480 V HP/A 15/21.0 30/40.0 60/77.0 125/156.0
600 V HP/A 20/22.0 50/52.0 75/77.0 150/144.0
Single phase 120 V HP/A 2/24.0
240 V HP/A 3/17.0
Short circuit rating with fuse, 3 and4-pole types kA 200 200 200 200
UL/CSA fuse size A 30 60 100 200
UL/CSA fuse type J/CC J J J
Min. electrical endurance pf= 0.75...0.8 operation cycles 6000 6000 6000 6000
Terminal lug kits Integral Integral OZXA-24 OZXA-200
Wire range AWG #18-8 #14-4 #14-2/0 #4-300MCM
Torque Wire tightening lb.in 17 30/35 4) 120 275
Lug mounting lb.in N/A N/A 50 72

Technical data according to IEC 60947-3


Rated insulation voltage Pollution degree 3 V 1 000 1 000 1 000 1 000
Dielectric strength 50 Hz 1min. kV 10 10 10 10
Rated impulse withstand voltage kV 12 12
Rated thermal current in ambient 40 C/ In open air A/W 32/3.5 63/7.5 160/12 200/17
max. fuse power dissipation 1) In enclosure2) A/W 32/3.5 63/7.5 160/10,135/12 200/15
...with minimum cable cross section Cu mm 2 6 16 70 95
Rated operational current, AC-23A up to 500 V A 32 63 160 200
690 V A 32 63 160 200
Rated operational power, AC-23 3) The kW-ratings are accurate for 230 V kW 7.5 18.5 45 60
three-phase 1500 R.P.M. 400 V kW 15 30 75 110
standard asynchronous motors. 415 V kW 15 30 75 110
500 V kW 18.5 37 90 132
690 V kW 22 55 132 200
Rated breaking capacity in category AC-23 up to 500 V A 256 504 1280 1600
690 V A 256 504 1280 1600
Rated short-time withstand current, 1 s r.m.s. -value kA 1 2.5 5 8
Power loss / pole With rated current, without fuse W 2 4 9 8
Built-in terminal size Cu mm 2 0.75...10 2.5...25
Fuse-links bolts tightening torque Nm 4 4
*) UL listed disconnects are also listed under CSA requirements
1)
Ambient temperature 60 C: derating 20%
2)
Mounting on "ceiling": derating 10%. Mounting on wall, horizontal fuses: derating 8%.
3)
Some fuse links limit these figures further. Starting current characteristics must be considered separately.
4)
30 lb.in with cable size #14-10, 35 lb.in with cable size #8-4

Switch fuses OS and OSM | Technical data 13


Technical data, UL/CSA
Fusible disconnect switches OS400...1200

OS OS OS OS
Switch size A 400 600 800 1200
Approvals *) 2 pole UL98, IEC UL98, IEC UL98, IEC UL98, IEC
3 pole UL98, IEC UL98, IEC UL98, IEC UL98, IEC
4 pole UL98, IEC UL98, IEC UL98, IEC UL98, IEC

Technical data according to UL/CSA


General purpose amp rating pf= 0.7...0.8 up to 40 C A 400 600 800 1200
Max. oprerating voltage VAC 600 600 600 600
VDC 250 250 250 250
Max. horsepower rating / motor FLA current pf= 0.4...0.5 Three phase 240 V HP/A 125.0/312.0 200/480.0 250/602.0
480 V HP/A 250.0/302.0 400/477.0 500/590.0
600 V HP/A 350.0/336.0 500/472.0 500/472.0
Single phase 120 V HP/A
240 V HP/A
Short circuit r ating with fuse, 3 and4-pole types kA 200 200 200 200
UL/CSA fuse size A 400 600 800 1200
UL/CSA fuse type J J L L
Min. electrical endurance pf= 0.75...0.8 operation cycles 1000 1000 500 500
Terminal lug kits OZXA-400 OZXA-800 OZXA-800 OZXA-1200
Wire range AWG #2-600MCM (2)#2-600MCM (2)#2-600MCM (4)#2-600MCM
Torque Wire tightening lb.in 375 500 500 500
Lug mounting lb.in 240 480 480 480

Technical data according to IEC 60947-3


Rated insulation voltage Pollution degree 3 V 1 000 1 000 1 000 1000
Dielectric strength 50 Hz 1min. kV 10 10 10 10
Rated impulse withstand voltage kV 12 12 12 12
Rated thermal current in ambient 40 C/ In open air A/W 400/45 630/60 800/65 1250/110
max. fuse power dissipation1) In enclosure2) A/W 400/30 570/50 720/55 1000/85
...with minimum cable cross section Cu mm2 240 2x185 2x240 2x400
Rated operational current, AC-23A up to 500 V A 400 630 800 10004)
690 V A 400 630 800 10004)
Rated operational power, AC-233) The kW-ratings are accurate for 230 V kW 132 200 250 3154)
three-phase 1500 R.P.M. 400 V kW 220 355 450 5604)
standard asynchronous motors. 415 V kW 230 355 450 5604)
500 V kW 280 450 560 7104)
690 V kW 400 630 710 10004)
Rated breaking capacity in category AC-23 up to 500 V A 3200 6400 6400 8000
690 V A 3200 6400 6400 8000
Rated short-time withstand current, 1 s r.m.s. -value kA 14 20 20
Power loss / pole With rated current, without fuse W 30 46 75 75
Built-in terminal size Cu mm2
Fuse-links bolts tightening torque Nm 20 40 40 40
1)
Ambient temperature 60 C: derating 20%
2)
Mounting on "ceiling": derating 10%. Mounting on wall, horizontal fuses: derating 8%.
3)
Some fuse links limit these figures further. Starting current characteristics must be considered separately.
4)
= Utilization category B
* UL listed disconnects are also listed under CSA requirements
)

14 Technical data | Switch fuses OS and OSM


Technical data, motor operators, IEC
Motorized switch fuses OSM32...250

Data for motor operator OSM according to IEC 60947 Switch size A 3263 100160 200250
Rated operational voltage Ue Pollution degree 3
50/60 Hz V AC 220 - 240 220 - 240
Operating voltage range 0.85 - 1.1 x U e 0.85 - 1.1 x Ue 0.85 - 1.1 x Ue
Operating time1) 90 I - 0, 0 - I 220-240VAC s 0.5 - 1.0 0.5 - 1.0 0.5 - 1.0
Nominal current In1) 220-240VAC A 0.3 0.3 0.3
Current Inrush1) 220-240VAC A 1.5 1.5 1.5
Overload fuse Type / In / Capacity 220-240VAC mA T / 315 / H T / 315 / H T / 315 / H
Size mm 5x20 5x20 5x20
Operating rate Cycle 0 - I - 0
Max. continuous 220-240VAC cycles / min 1 1 1
Max. short-time 10 cycles 220-240VAC cycles / min 10 10 10
Overvoltage category III III III
Rated impulse withstand voltage Uimp kV 4 4 4
Dielectric strength 50 Hz 1 min. kV 1.5 1.5 1.5
Impulse command Min. impulse
duration ms 100 100
Terminals
Voltage supply wiring for Ue PE - N - L PE - N - L PE - N - L PE - N - L
Cross section solid/stranded mm2 1.5 - 2.5 1.5 - 2.5 1.5 - 2.5
Short-circuit protection device max.fuse size A 16 16 16
Push-button control C- I-O no SELV no SELV no SELV
Cross section solid/stranded mm2 1.5 - 2.5 1.5 - 2.5 1.5 - 2.5
Maximum cable length m 100 100 100
State information of locking no SELV no SELV no SELV
Handle attached or motor operator locked 11-12-14 (C/O) cos=1 5A/250V 5A/250V 5A/250V
Locking motor operator 23-24 (NO) cos=1 5A/250V 5A/250V 5A/250V
Short-circuit protection device MCB type and size C/2A C/2A C/2A
Protection degree IP20 IP20 IP20
Operating temperature C -25+55 -25+55 -25+55
Transportation and storage temperature C -40+70 -40+70 -40+70
Max. altitude m 2000 2000 2000
1)
Under nominal conditions

Switch fuses OS and OSM | Technical data 15


Technical data, motor operators, IEC
Motorized switch fuses OSM315...1250

Data for motor operator OSM according to IEC 60947 Switch size A 315...400 630800 1250
Rated operational voltage Ue Pollution degree 3
50/60 Hz V AC 220 - 240 220 - 240 220 - 240
Operating voltage range 0.85 - 1.1 x U e 0.85 - 1.1 x Ue 0.85 - 1.1 x Ue
Operating time1) 90 I - 0, 0 - I 220-240VAC s 0.5 - 1.2 0.5 - 1.5 0.8 - 2.0
Nominal current In1) 220-240VAC A 0.5 0.9 1.4
Current Inrush1) 220-240VAC A 2.5 4 10
Overload fuse Type / In / Capacity 220-240VAC mA T / 500 / H T / 1000 / H T / 2000 / H
Size mm 5x20 5x20 5x20
Operating rate Cycle 0 - I - 0
Max. continuous 220-240VAC cycles / min 1 1 0.5
Max. short-time 10 cycles 220-240VAC cycles / min 10 10 5
Overvoltage category III III
Rated impulse withstand voltage Uimp kV 4 4
Dielectric strength 50 Hz 1 min. kV 1.5 1.5
Impulse command Min. impulse
duration ms 100 100
Terminals
Voltage supply wiring for Ue PE - N - L PE - N - L PE - N - L
Cross section solid/stranded mm2 1.5 - 2.5 1.5 - 2.5 1.5 - 2.5
Short-circuit protection device max.fuse size A 16 16 16
Push-button control C- I-O no SELV no SELV no SELV
Cross section solid/stranded mm2 1.5 - 2.5 1.5 - 2.5 1.5 - 2.5
Maximum cable length m 100 100 100
State information of locking no SELV no SELV no SELV
Handle attached or motor operator locked 11-12-14 (C/O) cos=1 5A/250V 5A/250V 5A/250V
Locking motor operator 23-24 (NO) cos=1 5A/250V 5A/250V 5A/250V
Short-circuit protection device MCB type and size C/2A C/2A C/2A
Protection degree IP20 IP20 IP20
Operating temperature C -25+55 -25+55 -25+55
Transportation and storage temperature C -40+70 -40+70 -40+70
Max. altitude m 2000 2000 2000
1)
Under nominal conditions

16 Technical data | Switch fuses OS and OSM


Type designation key

Explanation of the types OS2040

OS 25F F _ 22 10 N1 -2
1 2 3 4 5 6 7 8

1 - Brand 5 - Number of poles and placing of the operating mechanism


OS ABB switch fuse/fusible switch 12 3 poles, operating mechanism between the poles
2- Switch size/ Ampere rating 22 4 poles, operating mechanism between the poles
20...40F Mini, 2040 A 30 3 poles, operating mechanism at the right end of the switch
3- Fuse type 6- Fuse size
D DIN A1, A2 BS88, A1, A2
B BS 000 DIN 000
F NFC 10, 14 NFC 10x38, 14x51
AJ J 7- Fourth pole/neutral terminal
ACC CC N1 Non-fused switched neutral on the left side
4- Switch operation F Fused switched neutral
Blank Front operation Blank Terminal not included
S Side operation 8 - Included handle
Blank Pistol handle and shaft included
-2 No handle included

Explanation of the types OS321250 A

OS 125G D _ 04 N2 _ P
1 2 3 4 5 6 7 8

1 - Brand 12: 3 poles, operating mechanism between the poles


OS ABB switch fuse/fusible switch 22: 4 poles, operating mechanism between the poles
2- Switch size/ Ampere rating 30: 3 poles, operating mechanism at the right end of the switch
32G200G Gamma, 32A200A 40: 4 poles, operating mechanism at the right end of the switch
2001250 200A1250 A 6- Fourth pole/neutral terminal
3- Fuse type Blank Neutral terminal not included
D DIN N1 Non-fused switched neutral on the left side
B BS N2 Non-fused switched neutral on the right side
F NFC N3 Includes a detachable neutral link integrated into the mechanism
J J F Fused switch neutral
L L 7 - Terminals for special connection (only IEC)
4- Switch operation Blank No special connection
Blank: Front operation BB Back in, back out
S Side operation LR Left in, right out
5 - Number of poles and placing of the operating mechanism 8 - Included handle
03 3 poles, operating mechanism at the left end of the switch Blank No handle included
04 4 poles, operating mechanism at the left end of the switch P Pistol handle and shaft
K Direct mount handle

Switch fuses OS and OSM | Type designation key 17


Type designation key

Explanation of the types OSM1250 A (IEC only)

OSM 125G B 4 N1 M230C


1 2 3 4 5 6

1 - Brand 4: 4 poles, motor operator at the left end of the switch


OSM ABB motorized switch fuse 5- Fourth pole/neutral terminal
2- Switch size/ Ampere rating N1 Non-fused switched neutral on the left side
32G200G Gamma, 32A200A N2 Non-fused switched neutral on the right side
2001250 200A1250 A N3 Includes a detachable neutral link integrated into the mechanism
3- Fuse type Blank Neutral terminal not included
B BS 6- Motor operator voltage
D DIN 230C 230 V AC
4 - Number of poles
3: 3 poles, motor operator at the left end of the switch

Placing options of the operating mechanism

At the end of Between Side operated


the switch fuse the poles types
N OS_03 or 04 N OS_12 or 22 N OS_30 or 40
OS_03 or 04

N N N

N N

BB-types LR-types

18 Type designation key | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, DIN-type

OS32...63GD02P Front operated switch fuses


Including terminal bolt set in OS125G...160G, a black ON-OFF plastic handle and shaft
as standard. The handle is IP65 protected, padlockable in the OFF-position and with door
interlock in the ON-position. The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS32...63GD04N2P Mechanism at the end of the switch fuse
Protected tunnel terminals, IP20
32 000 2 OS32GD02P 1SCA116714R1001 1.0
32 000 3 OS32GD03P 1SCA115189R1001 1.3
32 000 4 OS32GD04N2P 1SCA115193R1001 1.6
32 000 4 OS32GD04FP 1SCA115196R1001 1.6
63 000 2 OS63GD02P 1SCA116715R1001 1.0
63 000 3 OS63GD03P 1SCA115207R1001 1.3
63 000 4 OS63GD04N2P 1SCA115209R1001 1.6
OS32...63GD04FP 63 000 4 OS63GD04FP 1SCA115228R1001 1.6
Including terminal bolt set
125 000, 00 2 OS125GD02P 1SCA116716R1001 1.2
125 000, 00 3 OS125GD03P 1SCA115639R1001 1.5
125 000, 00 4 OS125GD04N2P 1SCA115877R1001 1.8
125 000, 00 4 OS125GD04FP 1SCA115686R1001 1.8
160 000, 00 2 OS160GD02P 1SCA116717R1001 1.2
160 000, 00 3 OS160GD03P 1SCA115399R1001 1.5
160 000, 00 4 OS160GD04N2P 1SCA115882R1001 1.8
160 000, 00 4 OS160GD04FP 1SCA115402R1001 1.8
OS125...160GD03P F = Fused switched neutral
N2 = Non-fused switched neutral on the right side

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS32G...63G_P OXP6X161 OHB45J6 -
OS125G...160G_P OXP6X161 OHB65J6 M8X25

Switch fuses OS and OSM | Ordering information 19


Ordering information, IEC
Switch fuses, DIN-type

OS200DZ04N2P Front operated switch fuses


Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle
is IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position.
The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS200...250D03N3P Mechanism at the end of the switch fuse
200 00 3 OS200DZ03P 1SCA022797R3440 3.3
200 00 4 OS200DZ04N2P 1SCA022820R9230 4.2
200 0 2 OS200D02P 1SCA022759R9220 2.4
200 0 3 OS200D03P 1SCA022709R9500 3.3
200 0 3+N OS200D03N3P 1SCA022749R8710 3.4
200 0 4 OS200D04N2P 1SCA022709R9680 4.2
200 0 4 OS200D04FP 1SCA022725R4750 4.2
250 0-1 2 OS250D02P 1SCA022760R0170 3.5
250 0-1 3 OS250D03P 1SCA022719R0090 4.3
OS200...250D02P 250 0-1 3+N OS250D03N3P 1SCA022749R9430 4.4
250 0-1 4 OS250D04N2P 1SCA022719R2380 5.1
250 0-1 4 OS250D04FP 1SCA022726R8620 5.1
400 0-2 2 OS400D02P 1SCA022811R2740 5.4
400 0-2 3 OS400D03P 1SCA022719R0250 7.1
400 0-2 3+N OS400D03N3P 1SCA022753R9320 7.5
400 0-2 4 OS400D04N2P 1SCA022719R2460 9.1
400 0-2 4 OS400D04FP 1SCA022753R7110 9.1
F = Fused switched neutral, N2 = Non-fused switched neutral on the right side
N3 = Include a detachable neutral link integrated into the mechanism
OS400D04FP
Shafts and handles included as standard
Suitable for switches Included shaft Included handle Incl. terminal bolts
OS200_P OXP6X210 OHB65J6 M8X25
OS250_P OXP6X210 OHB65J6 M10X30
OS400_P OXP12X250 OHB95J12 M10X30

20 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, DIN-type

OS630...800D02P Front operated switch fuses


Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle
is IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position.
The shaft is adjustable for a range of installation depths. OS1250DA_: a fuse replacement tool
is integrated in the fuse cover.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS630...800D04FP Mechanism at the end of the switch fuse
630 3 2 OS630D02P 1SCA107745R1001 10.3
630 3 3 OS630D03P 1SCA022825R2830 13.6
630 3 3+N OS630D03N3P 1SCA100858R1001 14.5
630 3 4 OS630D04N2P 1SCA022825R4290 16.9
630 3 4 OS630D04FP 1SCA022825R4610 16.9
800 3 2 OS800D02P 1SCA022837R2650 10.3
800 3 3 OS800D03P 1SCA022825R4880 13.6
800 3 3+N OS800D03N3P 1SCA100859R1001 14.5
800 3 4 OS800D04N2P 1SCA022825R5180 16.9
800 3 4 OS800D04FP 1SCA022825R5000 16.9
12501) 4 2 OS1250D02P 1SCA114051R1001 37
OS1250D03P 12501) 4 3 OS1250D03P 1SCA105475R1001 46
1250 1)
4 3+N OS1250D03N3P 1SCA107932R1001 47
12501) 4 4 OS1250D04N2P 1SCA105248R1001 55
12501) 4 4 OS1250D04FP 1SCA105473R1001 55
12501) 4a 2 OS1250DA02P 1SCA114059R1001 37
12501) 4a 3 OS1250DA03P 1SCA105238R1001 46
12501) 4a 3+N OS1250DA03N3P 1SCA107934R1001 47
12501) 4a 4 OS1250DA04N2P 1SCA105243R1001 55
12501) 4a 4 OS1250DA04FP 1SCA105240R1001 55
F = Fused switched neutral, N2 = Non-fused switched neutral on the right side
N3 = Include a detachable neutral link integrated into the mechanism
OS1250D04P 1)
1250A / AC-21...22A, 1000A / AC-23A

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS630...800_P OXP12X280 OHB145J12 M12X40
OS1250_P OXP12X395 OHB274J12 M12x50

Switch fuses OS and OSM | Ordering information 21


Ordering information, IEC
Switch fuses, DIN-type

OS32...63GD03K Front operated switch fuses with direct mount handle


Including terminal bolt set in OS125G...160G, a black Test-OFF-ON plastic handle and shaft
as standard. The handle is padlockable in the OFF-position. Types OS1250DA_: a fuse
replacement tool is integrated in the fuse cover.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS32...63GD04N2K Mechanism at the end of the switch fuse
Protected tunnel terminals, IP20
32 000 3 OS32GD03K 1SCA116733R1001 1.3
32 000 4 OS32GD04N2K 1SCA116734R1001 1.6
32 000 4 OS32GD04FK 1SCA116737R1001 1.6
63 000 3 OS63GD03K 1SCA116738R1001 1.3
63 000 4 OS63GD04N2K 1SCA116876R1001 1.6
63 000 4 OS63GD04FK 1SCA116739R1001 1.6
Including terminal bolt set
125 000, 00 3 OS125GD03K 1SCA116878R1001 1.5
OS125...160GD03K 125 000, 00 4 OS125GD04N2K 1SCA116740R1001 1.8
125 000, 00 4 OS125GD04FK 1SCA116741R1001 1.8
160 000, 00 3 OS160GD03K 1SCA116742R1001 1.5
160 000, 00 4 OS160GD04N2K 1SCA116743R1001 1.8
160 000, 00 4 OS160GD04FK 1SCA116880R1001 1.8
F = Fused fourth pole
N2 = Non-fused switched neutral on the right side

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS125...160GD04FK OS32G...63G_K - OSV200BK -
OS125G...160G_K - OSV200BK M8X25

22 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, DIN-type

OS200...250D03K Front operated switch fuses with direct mount handle


Including terminal bolt set, a black Test-OFF-ON plastic handle and shaft as standard. The
handle is padlockable in the OFF-position. Types OS1250DA_: a fuse replacement tool is
integrated in the fuse cover.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS400D03K Mechanism at the end of the switch fuse
Including terminal bolt set
200 0 3 OS200D03K 1SCA022764R7130 3.3
200 0 4 OS200D04N2K 1SCA022768R7430 4.2
250 0-1 3 OS250D03K 1SCA022763R6360 4.3
250 0-1 4 OS250D04N2K 1SCA022763R6440 5.1
400 0-2 3 OS400D03K 1SCA022779R5410 7.0
400 0-2 4 OS400D04N2K 1SCA022763R7250 9.0
630 3 3 OS630D03K 1SCA108704R1001 13
630 3 4 OS630D04N2K 1SCA108705R1001 16
OS630...800D03K 800 3 3 OS800D03K 1SCA108725R1001 13
800 3 4 OS800D04N2K 1SCA108722R1001 16
12501) 4 3 OS1250D03K 1SCA108718R1001 45
1250 1) 4 4 OS1250D04N2K 1SCA108719R1001 54
1250 1)
4a 3 OS1250DA03K 1SCA108720R1001 45
1250 1) 4a 4 OS1250DA04N2K 1SCA108721R1001 54
N2 = Non-fused switched neutral on the right side
1)
1250A / AC-20...22A, 1000A / AC-23A

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS200_K - OSV250DK M8X25
OS250_K - OSV250DK M10X30
OS400_K - OSV400DK M10X30
OS630...800_K - OSV800DK M12X40
OS1250_K - OSV1250DK M12x50

Switch fuses OS and OSM | Ordering information 23


Ordering information, IEC
Switch fuses, DIN-type

OS32...63GDS30K Side operated switch fuses with pistol handle


Including a black ON-OFF plastic handle and shaft as standard. The handle is IP65 protected,
padlockable in the OFF-position and with door interlock in the ON-position. The shaft is
adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
OS32...63GDS40N2K [A] size poles Type Order number [kg]
Shaft mounting depths measured from the left side of the switch, 3-pole: H=157164 mm and 4-pole:
H= 193200 mm. Protected tunnel terminals, IP20.
40 000 3 OS40FDS30000 1SCA108942R1001 0.9
40 000 3 OS40FDS30000-2 1SCA108945R1001 0.7

Side operated switch fuses with direct mount handle


Including terminal bolt set in OS125G...160G, a black Test-ON-OFF plastic handle and shaft as
standard. The handle is padlockable in the OFF-position.

OS125...160GDS40N2K Rated op.


current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Protected tunnel terminals, IP20.
32 000 3 OS32GDS30K 1SCA115929R1001 1.3
32 000 4 OS32GDS40N2K 1SCA116402R1001 1.6
63 000 3 OS63GDS30K 1SCA115931R1001 1.3
63 000 4 OS63GDS40N2K 1SCA116403R1001 1.6
Including terminal bolt set
125 000, 00 3 OS125GDS30K 1SCA115933R1001 1.5
125 000, 00 4 OS125GDS40N2K 1SCA115934R1001 1.8
160 000, 00 3 OS160GDS30K 1SCA115935R1001 1.5
160 000, 00 4 OS160GDS40N2K 1SCA115939R1001 1.8
N2 = Non-fused switched neutral on the right side

Shafts and handles incl. as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS40FDS_ (OS Mini) OPX6X150 OHB65J6 -
OS32G...63_K OXP6X42-TO OHB65D6 -
OS125G...160G_K OXP6X42-TO OHB65D6 M8X25

24 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, DIN-type

Side operated switch fuses with direct mount handle


OS200...250DS40FK Including terminal bolt set, a black Test-ON-OFF plastic handle and shaft as standard.
The handle is padlockable in the OFF-position.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Including terminal bolt set
OS630...800DS04FK 200 0 3 OS200DS30K 1SCA022871R1450 3.6
200 0 4 OS200DS40FK 1SCA022871R1610 4.5
250 0-1 3 OS250DS30K 1SCA022871R2260 4.6
250 0-1 4 OS250DS40FK 1SCA022871R2420 5.4
400 0-2 3 OS400DS30K 1SCA022871R2930 7.5
400 0-2 4 OS400DS40FK 1SCA022871R3150 9.5
630 3 3 OS630DS30K 1SCA108136R1001 14.1
630 3 4 OS630DS40FK 1SCA108138R1001 17
800 3 3 OS800DS30K 1SCA108099R1001 14.1
800 3 4 OS800DS40FK 1SCA108101R1001 17
F = Fused switched neutral

Shafts and handles included as standard:


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS200_K OXP6X42-TO OHB65D6 M8x25
OS250_K OXP6X42-TO OHB65D6 M10x30
OS315...400_K OXP12X47-TO OHB95D12 M10x30
OS630800_K OXP12X59-TO OHB145D12 M12x40

Switch fuses OS and OSM | Ordering information 25


Ordering information, IEC
Switch fuses, DIN-type

OS250D03BBP Special connected switch fuses, back in, back out connection (BB)
Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle
is IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position.
The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse*) of unit
OS250D04BBN2P [A] size poles Type Order number [kg]
Mechanism at the end of the switch fuse
125 000, 00 3 OS125GD03BBP 1SCA120802R1001 2.3
125 000, 00 4 OS125GD04BBN2P 1SCA120806R1001 2.7
160 000, 00 3 OS160GD03BBP 1SCA120655R1001 2.3
160 000, 00 4 OS160GD04BBN2P 1SCA120661R1001 2.7
200 0 3 OS200D03BBP 1SCA102150R1001 3.3
200 0 4 OS200D04BBN2P 1SCA102139R1001 4.2
250 0...1 3 OS250D03BBP 1SCA102190R1001 4.3
250 0...1 4 OS250D04BBN2P 1SCA102205R1001 5.1
400 02 3 OS400D03BBP 1SCA102260R1001 7.1
400 02 4 OS400D04BBN2P 1SCA102289R1001 9.1
N2 = Non-fused switched neutral on the right side

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS125G_...160G_P OXP6X161 OHB65J6 M8x25
OS200_P OXP6X210 OHB65J6 M8x25
OS250_P OXP6X210 OHB65J6 M10x30
OS400_P OXP12X250 OHB95J12 M10x30

26 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, DIN-type

OS125...160GD12LRP Special connected switch fuses, left in, right out connection (LR)
Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle
is IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position.
The shaft is adjustable for a range of installation depths. Terminal angles for side terminals are
accessories and are not included in standard delivery.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse*) of unit
OS200...250D22LR [A] size poles Type Order number [kg]
Mechanism between the poles
125 000, 00 3 OS125GD12LRP 1SCA120062R1001 2.9
125 000, 00 3 OS125GD21LRP 1SCA120255R1001 2.9
125 000, 00 4 OS125GD22LRP 1SCA120263R1001 3.7
160 000, 00 3 OS160GD12LRP 1SCA120267R1001 2.9
160 000, 00 3 OS160GD21LRP 1SCA120294R1001 2.9
160 000, 00 4 OS160GD22LRP 1SCA120275R1001 3.7
250 0...1 3 OS250D12LRP 1SCA022852R8410 6.2
250 0...1 3 OS250D21LRP 1SCA022852R8500 6.2
OS400D12LRP 250 0...1 4 OS250D22LRP 1SCA022853R0310 9.1
400 02 3 OS400D12LRP 1SCA022853R2280 9.6
400 02 3 OS400D21LRP 1SCA022853R2360 9.6
400 02 4 OS400D22LRP 1SCA022853R4140 12.8
Fuse standards DIN 43620, IEC 60269-2 sec. I

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS125G_...160G_P OXP6X161 OHB65J6 M8x25
OS250_P OXP6X210 OHB65J6 M8x16
OS400_P OXP12X250 OHB95J12 M8x16

Switch fuses OS and OSM | Ordering information 27


Ordering information, IEC
Switch fuses, BS-type

OS32...63GB02P Front operated switch fuses


Including terminal bolt set in OS100G...160G, a black ON-OFF plastic handle and shaft
as standard. The handle is IP65 protected, padlockable in the OFF-position and with door
interlock in the ON-position. The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS32...63GB04N1P Protected tunnel terminals IP20, mechanism at the end of the switch
32 A2, A3 2 OS32GB02P 1SCA116721R1001 1.0
32 A2, A3 3 OS32GB03P 1SCA115259R1001 1.3
32 A2, A3 4 OS32GB04N1P 1SCA114610R1001 1.6
63 A2, A3 2 OS63GB02P 1SCA116854R1001 1.0
63 A2, A3 3 OS63GB03P 1SCA115235R1001 1.3
63 A2, A3 4 OS63GB04N1P 1SCA115238R1001 1.6
Including terminal bolt set, mechanism at the end of the switch
100 A2-A41) 3 OS100GB03P 1SCA114613R1001 1.8
100 A2-A41) 3+N OS100GB03N3P 1SCA125531R1001 2.1
OS100...160GB03P 100 A2-A41) 4 OS100GB04N1P 1SCA114614R1001 2.5
125 A2-A41) 3 OS125GB03P 1SCA115634R1001 1.7
125 A2-A41) 3+N OS125GB03N3P 1SCA122008R1001 2.1
125 A2-A41) 4 OS125GB04N1P 1SCA115901R1001 2.7
160 A2-A4 1)
3 OS160GB03P 1SCA115413R1001 1.8
160 A2-A41) 3+N OS160GB03N3P 1SCA122010R1001 2.1
160 A2-A41) 4 OS160GB04N1P 1SCA115896R1001 2.5
N1 = Non-fused switched neutral on the left side
N3=Detachable neutral link integrated into the mechanism
1)
Max. fuse diameter 32 mm

Shafts and handles included as standard


OS100...160GB03N3P Suitable for switches Included shaft Included handle Incl. terminal bolts
OS32G...63G_P OXP6X161 OHB45J6 -
OS100G...160G_P OXP6X161 OHB65J6 M8X25

28 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, BS-type

OS200...250B02P Front operated switch fuses


Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle is
IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position. The
shaft can be adjusted to different installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS200...250B03N3P Mechanism at the end of the switch fuse
200 B1-B2 2 OS200B02P 1SCA022769R7820 2.4
200 B1-B2 3 OS200B03P 1SCA022709R9330 3.3
200 B1-B2 3+N OS200B03N3P 1SCA022750R0620 3.4
250 B1-B3 2 OS250B02P 1SCA022769R9440 3.5
250 B1-B3 3 OS250B03P 1SCA022750R6660 4.3
250 B1-B3 3+N OS250B03N3P 1SCA022750R8010 4.4
315 B1-B4 2 OS315B02P 1SCA022817R3450 5.4
315 B1-B4 3 OS315B03P 1SCA022719R0680 7.1
315 B1-B4 3+N OS315B03N3P 1SCA022753R8940 7.5
OS315...400B03P 400 B1-B4 2 OS400B02P 1SCA022813R7220 5.4
400 B1-B4 3 OS400B03P 1SCA022719R0840 7.1
400 B1-B4 3+N OS400B03N3P 1SCA022753R9160 7.5
N3 = Include a detachable neutral link integrated into the mechanism.

OS200GB_P are optimal for electrical distribution applications and are compact in size.

Rated op.
current
AC-20...22B No. Weight/
415V Fuse of unit
[A] size poles Type Order number [kg]
Mechanism at the end of the switch fuse
200 A2-A41) 3 OS200GB03P 1SCA125468R1001 2.3
200 A2-A41) 3+N OS200GB03N3P 1SCA126216R1001 2.3
200 A2-A41) 4 OS200GB04N1P 1SCA125493R1001 2.7
N1 = Non-neutral on the right side
N3 = Include a detachable neutral link integrated into the mechanism.

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS200_GB_P OXP6X161 OHB65J6 M8X25
OS200_P OXP6X210 OHB65J6 M8X25
OS250_P OXP6X210 OHB65J6 M10X30
OS315400_P OXP12X250 OHB95J12 M10X30

Switch fuses OS and OSM | Ordering information 29


Ordering information, IEC
Switch fuses, BS-type

OS630...800B02P Front operated switch fuses


Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle
is IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position.
The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Mechanism at the end of the switch fuse
630 C1-C2 2 OS630B02P 1SCA113529R1001 10.3
OS630...800B03N3P 630 C1-C2 3 OS630B03P 1SCA022825R5850 13.6
630 C1-C2 3+N OS630B03N3P 1SCA100860R1001 14.5
800 C1-C3 2 OS800B02P 1SCA022837R6480 10.3
800 C1-C3 3 OS800B03P 1SCA022825R7550 13.6
800 C1-C3 3+N OS800B03N3P 1SCA100861R1001 14.5
12501) D1 2 OS1250B02P 1SCA114070R1001 37
1250 1) D1 3 OS1250B03P 1SCA105250R1001 46
1250 1) D1 3+N OS1250B03N3P 1SCA107936R1001 47
N3 = Include a detachable neutral link integrated into the mechanism.
1)
1250A / AC-20...22A, 1000A / AC-23A

Shafts and handles included as standard


OS1250D03P Suitable for switches Included shaft Included handle Incl. terminal bolts
OS630...800_P OXP12X280 OHB145J12 M12X40
OS1250_P OXP12X395 OHB274J12 M12X50

30 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, BS-type

Terminals with Front operated switch fuses


integrated nuts These types (-42) have nuts integrated on the back of the terminals, for easy installation.
A black ON-OFF plastic handle and shaft included as standard. The handle is IP 54 protected,
padlockable in OFF position and has door interlock in the ON-position and when padlocked.
The shaft can be adjusted to different installation depth.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
OS100...200GB03P-42 [A] size poles Type Order number [kg]
Mechanism Mechanism between the poles
100 A2-A41) 3+N OS100GB12N3P-42 1SCA129910R1001 2.7
125 A2-A41) 3+N OS125GB12N3P-42 1SCA129914R1001 2.7
160 A2-A41) 3+N OS160GB12N3P-42 1SCA129919R1001 2.7
Mechanism at the end of the switch fuse
100 A2-A41) 3 OS100GB03P-42 1SCA128217R1001 1.7
100 A2-A41) 3+N OS100GB03N3P-42 1SCA129907R1001 2.7
125 A2-A41) 4 OS125GB03P-42 1SCA128215R1001 2.3
125 A2-A41) 3+N OS125GB03N3P-42 1SCA129912R1001 2.7
OS100...160GB12P-42 160 A2-A41) 3 OS160GB03P-42 1SCA128213R1001 2.3
160 A2-A41) 3+N OS160GB03N3P-42 1SCA129916R1001 2.7
N3 = Include a detachable neutral link integrated into the mechanism
1)
Max. fuse diameter 32 mm

Rated op
current
AC20B-AC22B No. Weight/
415V Fuse of unit
[A] size poles Type Order number [kg]
OS100...200GB03N3P-42 Mechanism at the end of the switch fuse
200 A2-A41) 3 OS200GB03P-42 1SCA128211R1001 2.3
200 A2-A4 1)
3+N OS200GB03N3P-42 1SCA129922R1001 2.7
N3 = Include a detachable neutral link integrated into the mechanism
1)
Max. fuse diameter 32 mm

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS100...125GB_P-42 OXP6X161 OHB65J6 M8x25

Switch fuses OS and OSM | Ordering information 31


Ordering information, IEC
Switch fuses, BS-type

OS32G...63GB03K Front operated switch fuses with direct mount handle


Including terminal bolt set in OS100G...160G, a black Test-OFF-ON plastic handle and shaft as
standard. The handle is padlockable in the OFF-position.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Mechanism at the end of the switch fuse
OS32G...63GB04N1K Protected tunnel terminals, IP20
32 A2, A3 3 OS32GB03K 1SCA116744R1001 1.3
32 A2, A3 4 OS32GB04N1K 1SCA116856R1001 1.6
63 A2, A3 3 OS63GB03K 1SCA116745R1001 1.3
63 A2, A3 4 OS63GB04N1K 1SCA116746R1001 1.6
Including terminal bolt set
100 A2-A41) 3 OS100GB03K 1SCA116747R1001 1.5
100 A2-A41) 4 OS100GB04N1K 1SCA116748R1001 1.8
125 A2-A41) 3 OS125GB03K 1SCA116751R1001 1.5
125 A2-A41) 4 OS125GB04N1K 1SCA116752R1001 1.8
OS100G...160GB03K 160 A2-A41) 3 OS160GB03K 1SCA116753R1001 1.5
160 A2-A41) 4 OS160GB04N1K 1SCA116754R1001 1.8
N1 = Non-fused switched neutral on the left side
1)
Max. fuse diameter 32 mm

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS32G...63G_K - OSV200BK -
OS100G...160G_K - OSV200BK M8X25

OS100G...160GB04N1K

32 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, BS-type

OS630B03K Front operated switch fuses with direct mount handle


Including terminal bolt set, a black Test-OFF-ON plastic handle and shaft as standard. The
handle is padlockable in the OFF-position.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Mechanism at the end of the switch fuse
Including terminal bolt set
200 B1-B2 3 OS200B03K 1SCA022763R6950 3.3
250 B1-B3 3 OS250B03K 1SCA022763R6010 4.3
315 B1-B4 3 OS315B03K 1SCA022763R6520 7.0
400 B1-B4 3 OS400B03K 1SCA022763R6790 7.0
630 C1-C2 3 OS630B03K 1SCA108708R1001 13
800 C1-C3 3 OS800B03K 1SCA108713R1001 13
1250A1) D1 3 OS1250B03K 1SCA108715R1001 45
1)
1250A / AC-2022A, 1000A / AC-23A

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS200_K - OSV200BK M8X25
OS250_K - OSV250DK M10X30
OS315400_K - OSV400BK M10X30
OS630...800_K - OSV800DK M12X40
OS1250_K - OSV1250DK M12x50

Switch fuses OS and OSM | Ordering information 33


Ordering information
Switch fuses, BS-type

OS32GBS30K Side operated switch fuses with direct mount handle


Including terminal bolt set (OS125G...160G), a black Test-ON-OFF plastic handle and shaft as
standard. The handle is padlockable in the OFF-position.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Protected tunnel terminals, IP20.
OS32GBS40N1K 32 A2, A3 3 OS32GBS30K 1SCA115918R1001 1.3
32 A2, A3 4 OS32GBS40N1K 1SCA115923R1001 1.6
63 A2, A3 3 OS63GBS30K 1SCA115924R1001 1.3
63 A2, A3 4 OS63GBS40N1K 1SCA115979R1001 1.6
Including terminal bolt set
125 A2-A41) 3 OS125GBS30K 1SCA116400R1001 1.5
125 A2-A41) 4 OS125GBS40N1K 1SCA115926R1001 1.8
160 A2-A41) 3 OS160GBS30K 1SCA115927R1001 1.5
160 A2-A41) 4 OS160GBS40N1K 1SCA115928R1001 1.8
N1 = Non-fused switched neutral on the left side
1)
Max. diameter 32 mm
OS125GBS30K

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS20F...32F_ (OS Mini) OXP6X70-V0 OHB65J6 -
OS32G...63G_K OXP6X42-TO OHB65D6 -
OS125G...160G_K OXP6X42-TO OHB65D6 M8X25

OS125GBS40N1K

34 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, BS-type

OS200...250BS30K Side operated switch fuses with direct mount handle


Including terminal bolt set, a black Test-ON-OFF plastic handle and shaft as standard. The
handle is padlockable in the OFF-position.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
200 B1-B2 3 OS200BS30K 1SCA022870R7850 3.6
OS200...250BS40N2K 200 B1-B2 4 OS200BS40N2K 1SCA022870R8230 4.5
250 B1-B3 3 OS250BS30K 1SCA022870R8660 4.6
250 B1-B3 4 OS250BS40N2K 1SCA022870R9040 5.4
315 B1-B4 3 OS315BS30K 1SCA022870R9470 7.5
315 B1-B4 4 OS315BS40N2K 1SCA022870R9800 9.5
400 B1-B4 3 OS400BS30K 1SCA022871R0210 7.5
400 B1-B4 4 OS400BS40N2K 1SCA022871R0640 9.5
630 C1-C2 3 OS630BS30K 1SCA108148R1001 14.1
630 C1-C2 4 OS630BS40N2K 1SCA108151R1001 17
800 C1-C3 3 OS800BS30K 1SCA108084R1001 14.1
800 C1-C3 4 OS800BS40N2K 1SCA108087R1001 17
N2 = Non-fused switched neutral on the right side

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS200_K OXP6X42-TO OHB65D6 M8x25
OS250_K OXP6X42-TO OHB65D6 M10x30
OS315...400_K OXP12X47-TO OHB95D12 M10x30
OS630800_K OXP12X59-TO OHB145D12 M12x40

Switch fuses OS and OSM | Ordering information 35


Ordering information, IEC
Switch fuses, BS-type

OS125...160GB03BBP Special connected switch fuses, back in, back out connection (BB)
Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle
is IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position.
The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS200...400B03BBP Mechanism at the end of the switch fuse
125 A2A4 1) 3 OS125GB03BBP 1SCA120783R1001 2.3
125 A2A4 1) 4 OS125GB04BBN1P 1SCA122597R1001 2.7
160 A2A4 1) 3 OS160GB03BBP 1SCA120657R1001 2.3
160 A2A4 1) 4 OS160GB04BBN1P 1SCA122598R1001 2.7
200 B1B2 2)
3 OS200B03BBP 1SCA102082R1001 3.3
200 B1B2 2) 4 OS200B04BBN2P 1SCA102123R1001 4.2
250 B1B3 2) 3 OS250B03BBP 1SCA102168R1001 4.3
250 B1B3 2) 4 OS250B04BBN2P 1SCA102164R1001 5.1
315 B1B4 3) 3 OS315B03BBP 1SCA102222R1001 7.1
OS250...400B04BBN2P 315 B1B4 3) 4 OS315B04BBN2P 1SCA102225R1001 9.1
400 B1B4 3) 3 OS400B03BBP 1SCA102252R1001 7.1
400 B1B4 3) 4 OS400B04BBN2P 1SCA102248R1001 9.1
1)
Max fuse body dia 32 mm
2)
Max fuse body dia 52 mm
3)
Max fuse body dia 62 mm
N1 = Non-fused switched neutral on the left side
N2 = Non-fused switched neutral on the right side

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS125G...160G_P OXP6X161 OHB65J6 M8x25
OS200_P OXP6X210 OHB65J6 M8x25
OS250_P OXP6X210 OHB65J6 M10x30
OS315...400_P OXP12X250 OHB95J12 M10x30

36 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, BS-type

Special connected switch fuses, left in, right out connection (LR)
OS125G...160GB12LRP Including terminal bolt set, a black ON-OFF plastic handle and shaft as standard. The handle
is IP65 protected, padlockable in the OFF-position and with door interlock in the ON-position.
The shaft is adjustable for a range of installation depths. Terminal angles for side terminals are
accessories and are not included in standard delivery.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS200...250B12LRP Mechanism between the poles
125 A2A41) 3 OS125GB12LRP 1SCA120258R1001 2.9
125 A2A41) 3 OS125GB21LRP 1SCA120261R1001 2.9
125 A2A41) 4 OS125GB22LRP 1SCA120265R1001 3.7
160 A2A41) 3 OS160GB12LRP 1SCA120271R1001 2.9
160 A2A4 1)
3 OS160GB21LRP 1SCA120273R1001 2.9
160 A2A41) 4 OS160GB22LRP 1SCA120277R1001 3.7
200 B1B22) 3 OS200B12LRP 1SCA022854R2910 6.2
200 B1B22) 3 OS200B21LRP 1SCA022854R3050 6.2
200 B1B22) 4 OS200B22LRP 1SCA022854R4290 9.1
OS125GB21LRP 250 B1B32) 3 OS250B12LRP 1SCA022854R5690 6.2
250 B1B32) 3 OS250B21LRP 1SCA022854R5850 6.2
250 B1B32) 4 OS250B22LRP 1SCA022854R7210 9.1
315 B1B43) 3 OS315B12LRP 1SCA022854R8790 9.6
315 B1B4 3)
3 OS315B21LRP 1SCA022854R8870 9.6
315 B1B43) 4 OS315B22LRP 1SCA022855R0000 12.8
400 B1B43) 3 OS400B12LRP 1SCA022855R1400 9.6
400 B1B43) 3 OS400B21LRP 1SCA022855R1580 9.6
400 B1B43) 4 OS400B22LRP 1SCA022855R2710 12.8
1)
Max fuse body dia 32 mm
2)
Max fuse body dia 52 mm
OS125GB22LRP 3)
Max fuse body dia 62 mm

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS125G...160G_P OXP6X161 OHB65J6 M8x25
OS200...250_P OXP6X210 OHB65J6 M8x16
OS315...400_P OXP12X250 OHB95J12 M8x16

Switch fuses OS and OSM | Ordering information 37


Ordering information, IEC
Switch fuses, NFC-type

OS50GF04FP Front operated switch fuses


Including terminal bolt set in OS125G, a black ON-OFF plastic handle and shaft as standard.
The handle is IP65 protected, padlockable in the OFF-position and with door interlock in the
ON-position. The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Mechanism at the end of the switch fuse
Protected tunnel terminals, IP20
50 14x51 2 OS50GF02P 1SCA118345R1001 1.0
50 14x51 3 OS50GF03P 1SCA115492R1001 1.3
50 14x51 4 OS50GF04N1P 1SCA115495R1001 1.6
50 14x51 4 OS50GF04FP 1SCA115498R1001 1.6
Including terminal bolt set
125 22x58 2 OS125GF02P 1SCA116727R1001 1.2
125 22x58 3 OS125GF03P 1SCA115602R1001 1.5
125 22x58 4 OS125GF04N1P 1SCA115888R1001 1.8
125 22x58 4 OS125GF04FP 1SCA115606R1001 1.8
F = Fused switched neutral
N1 = Non-fused switched neutral on the left side

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS25FF32FF_ (OS Mini) OXP6X150 OHB65J6 -
OS50G_P OXP6X161 OHB45J6 -
OS125G_P OXP6X161 OHB65J6 M8X25

38 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Switch fuses, NFC-type

OS50GFS40FK Side operated switch fuses with pistol handle


Including a black ON-OFF plastic handle and shaft as standard. The handle is IP65 protected,
Nema type 1, 3R, 12, padlockable in the OFF-position and with door interlock in the ON-
position. The shaft is adjustable for a range of installation depths.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
OS125GFS40FK Shaft mounting depths measured from the left side of the switch, 3-pole: H=154166 mm
and 4 pole: H=189201 mm. Protected tunnel terminals, IP20.
25 10x38 3 OS25FFS3010 1SCA108639R1001 0.7
25 10x38 3 OS25FFS3010-2 1SCA108808R1001 0.7
F = Fused switched neutral

Side operated switch fuses with direct mount handle


Including terminal bolt set (OS125G), a black Test-ON-OFF plastic handle and shaft as
standard. The handle is padlockable in the OFF-position.

Rated op.
current
AC-20...23A No. Weight/
690V Fuse of unit
[A] size poles Type Order number [kg]
Protected tunnel terminals, IP20.
50 14x51 3 OS50GFS30K 1SCA116404R1001 1.3
50 14x51 4 OS50GFS40N1K 1SCA116013R1001 1.6
50 14x51 4 OS50GFS40FK 1SCA116425R1001 1.6
Including terminal bolt set
125 22x58 3 OS125GFS30K 1SCA115944R1001 1.5
125 22x58 4 OS125GFS40N1K 1SCA115945R1001 1.8
125 22x58 4 OS125GFS40FK 1SCA115946R1001 1.8
F = Fused switched neutral
N1 = Non-fused switched neutral on the left side

Shafts and handles included as standard


Suitable for switches Included shaft Included handle Incl. terminal bolts
OS50G_K OXP6X42-TO OHB65D6 -
OS125G_K OXP6X42-TO OHB65D6 M8X25

Switch fuses OS and OSM | Ordering information 39


Ordering information, UL/CSA
Switch fuses, CC and J types

OS60GJ12 Front operated fusible disconnect switches

Ampere No. Weight/


rating Fuse of unit
[A] size poles Type Order number [kg]
Mechanism between the poles
Protected tunnel terminals, IP20, cable size 0.510 mm2, (AWG 18 - 8).
30 CC, 30A 3 OS30FACC12 1SCA108813R1001 0.7
OS100GJ12 30 CC, 30A 4 OS30FACC22F 1SCA108819R1001 0.9
30 J, 30A 3 OS30FAJ12 1SCA108824R1001 0.7
30 J, 30A 4 OS30FAJ22F 1SCA108829R1001 0.8
Protected tunnel terminals, IP20, cable size 2.525 mm2 (AWG 14 - 4).
60 J, 60A 3 OS60GJ12 1SCA122981R1001 1.3
60 J, 60A 4 OS60GJ22F 1SCA115468R1001 1.6
Including terminal bolt set
100 J, 100A 3 OS100GJ12 1SCA115665R1001 2.2
100 J, 100A 4 OS100GJ22F 1SCA115668R1001 2.5
Mechanism at the end of the switch fuse
Protected tunnel terminals, IP20, cable size 2.525 mm2 (AWG 14 - 4).
OS60GJ22F 60 J, 60A 3 OS60GJ03 1SCA115866R1001 1.3
60 J, 60A 4 OS60GJ04F 1SCA115445R1001 1.6
Including terminal bolt set
100 J, 100A 3 OS100GJ03 1SCA115436R1001 2.2
100 J, 100A 4 OS100GJ04F 1SCA115438R1001 2.5
F = Fused switched neutral

Recommended shafts and handles


Suitable for switches Shaft Handle Terminal bolts
OS30FA (OS Mini) OXP6X150 OHB65J6 -
OS100GJ22F OS60G OXP6X161 OHB45J6 -
OS100G OXP6X161 OHB65J6 M8X25

OS100GJ03

40 Ordering information | Switch fuses OS and OSM


Ordering information, UL/CSA
Switch fuses, J and L types

OS200J02 Front operated fusible disconnect switches


Including terminal bolt set.

Ampere No. Weight/


rating Fuse of unit
[A] size poles Type Order number [kg]
Mechanism at the end of the switch fuse
OS400J03 Including terminal bolt set
200 J/200A 2 OS200J02 1SCA107591R1001 2.1
200 J/200A 3 OS200J03 1SCA022733R6130 3.1
200 J/200A 4 OS200J04F 1SCA022758R9340 4.0
400 J/400A 2 OS400J02 1SCA107592R1001 5.0
400 J/400A 3 OS400J03 1SCA022755R0810 6.8
400 J/400A 4 OS400J04F 1SCA022755R3660 8.6
600 J/600A 2 OS600J02 1SCA107593R1001 10.0
600 J/600A 3 OS600J03 1SCA022825R8610 13.0
OS400J04F 600 J/600A 4 OS600J04F 1SCA022839R3900 15.9
800 L/800A 2 OS800L02 1SCA116920R1001 9.8
800 L/800A 3 OS800L03 1SCA022825R9760 13.0
800 L/800A 4 OS800L04F 1SCA022839R5350 15.9
1200 L/1200A 2 OS1200L02 1SCA116924R1001 37
1200 L/1200A 3 OS1200L03 1SCA105467R1001 45
1200 L/1200A 4 OS1200L04F 1SCA105465R1001 54
F = Fused switched neutral

OS600J02 Recommended shafts and handles


Suitable for switches Shaft Handle Terminal bolts
OS200 OXP6X210 OHB65J6 M8X25
OS400 OXP12X250 OHB95J12 M10X30
OS600...800 OXP12X280 OHB145J12 M12X40
OS1200 OXP12X395 OHB274J12 M12X50

OS800L04F

Switch fuses OS and OSM | Ordering information 41


Ordering information, UL/CSA
Switch fuses, CC and J types

OS60GJS40F Side operated fusible disconnect switches

Ampere No. Weight/


rating Fuse of unit
[A] size poles Type Order number [kg]
Protected tunnel terminals, IP20.
30 CC, 30A 3 OS30FACCS30 1SCA108822R1001 0.7
30 J, 30A 3 OS30FAJS30 1SCA108834R1001 0.8
60 J, 60A 3 OS60GJS30 1SCA116051R1001 1.3
OS100GJS30 60 J, 60A 4 OS60GJS40F 1SCA115970R1001 1.7
Including terminal bolt set
100 J, 100A 3 OS100GJS30 1SCA115971R1001 2.3
100 J, 100A 4 OS100GJS40F 1SCA115972R1001 2.7
F = Fused switched neutral

Recommended shafts and handles


Suitable for switches Shaft Handle Terminal bolts
OS30FA (OS Mini) OXP6X70 OHB65J6 -
OS60GJS OXP6X42-TO OHB65D6 -
OS100GJS OXP6X42-TO OHB65D6 M8X25

42 Ordering information | Switch fuses OS and OSM


Ordering information, IEC
Motorized switch fuses OSM, DIN-type

OSM63GD3M230C Motorized switch fuses OSM


Including a handle for manual operation, bolt kit with nut and washers for all terminals
(100A1250A), male connectors for control circuit and a handle and spare fuse storage clip.
Type codes for motor voltage Ue = 220-240 VAC

Rated current No. Weight/


AC-20...23 Fuse of unit
OSM160GD3M230C 690V size poles Type Order number [kg]
32 000 3 OSM32GD3M230C 1SCA116664R1001 7.0
32 000 4 OSM32GD4N2M230C 1SCA118822R1001 7.3
63 000 3 OSM63GD3M230C 1SCA116660R1001 7.0
63 000 4 OSM63GD4N2M230C 1SCA118865R1001 7.3
125 000,00 3 OSM125GD3M230C 1SCA116674R1001 7.6
125 000,00 4 OSM125GD4N2M230C 1SCA118828R1001 7.9
OSM200D4N2M230C 160 000,00 3 OSM160GD3M230C 1SCA116673R1001 7.6
160 000,00 4 OSM160GD4N2M230C 1SCA118831R1001 7.9
200 0 3 OSM200D3M230C 1SCA104284R1001 9.6
200 0 3+N OSM200D3N3M230C 1SCA104282R1001 9.8
200 0 4 OSM200D4N2M230C 1SCA118836R1001 10.7
250 0-1 3 OSM250D3M230C 1SCA104295R1001 10.4
250 0-1 3+N OSM250D3N3M230C 1SCA104297R1001 10.5
250 0-1 4 OSM250D4N2M230C 1SCA118838R1001 11.2
OSM400D3M230C 400 0-2 3 OSM400D3M230C 1SCA104315R1001 14.8
400 0-2 3+N OSM400D3N3M230C 1SCA104317R1001 15.1
400 0-2 4 OSM400D4N2M230C 1SCA118842R1001 16.7
630 3 3 OSM630D3M230C 1SCA104518R1001 34
630 3 3+N OSM630D3N3M230C 1SCA104533R1001 35
630 3 4 OSM630D4N2M230C 1SCA118846R1001 38
800 3 3 OSM800D3M230C 1SCA104522R1001 34
800 3 3+N OSM800D3N3M230C 1SCA104534R1001 35
800 3 4 OSM800D4N2M230C 1SCA118847R1001 38
OSM800D3M230C 1250 4 3 OSM1250D3M230C 1SCA112549R1001 55
1250 4 3+N OSM1250D3N3M230C 1SCA112547R1001 56
1250 4 4 OSM1250D4N2M230C 1SCA118850R1001 65
1250 4a 3 OSM1250DA3M230C 1SCA112546R1001 55
1250 4a 3+N OSM1250DA3N3M230C 1SCA112544R1001 56
1250 4a 4 OSM1250DA4N2M230C 1SCA118851R1001 65
Number of poles: 3+N / Type: _N3_ = Include a detachable neutral link integrated into the mechanism
N2 = Non-fused switched neutral on the right side
Available on request: F = Fused switched neutral

Handles and bolt kits included as standard


OSM1250D3M230C Suitable for switch fuses Handle+shaft kit Bolt kit
OSM3263 OTV250EMK -
OSM100200 OTV250EMK M8x25
OSM250 OTV250EMK M10X30
OSM400 OTV400EMK M10X30
OSM630800 OTV800EMK M12X40
OSM1250 OTV1000EMK M12X50

Switch fuses OS and OSM | Ordering information 43


Ordering information, IEC
Motorized switch fuses OSM, BS-type

OSM100GB3M230C Motorized switch fuses OSM


Including a handle for manual operation, bolt kit with nut and washers for all terminals
(100A1250A), male connectors for control circuit and a handle and spare fuse storage clip.
Type codes for motor voltage Ue = 220-240 VAC.

Rated current No. Weight/


AC-20...23 Fuse of unit
690V size poles Type Order number [kg]
OSM250B3N3M230C 32 A2-A3 3 OSM32GB3M230C 1SCA116662R1001 7.0
32 A2-A3 4 OSM32GB4N1M230C 1SCA118775R1001 7.3
63 A2-A3 3 OSM63GB3M230C 1SCA116657R1001 7.0
63 A2-A3 4 OSM63GB4N1M230C 1SCA118776R1001 7.3
100 A2-A4 3 OSM100GB3M230C 1SCA116679R1001 7.6
100 A2-A4 4 OSM100GB4N1M230C 1SCA118779R1001 7.9
125 A2-A4 3 OSM125GB3M230C 1SCA116677R1001 7.6
125 A2-A4 4 OSM125GB4N1M230C 1SCA118780R1001 7.9
OSM250B4N1M230C 160 A2-A4 3 OSM160GB3M230C 1SCA116670R1001 7.6
160 A2-A4 4 OSM160GB4N1M230C 1SCA118781R1001 7.9
200 B1-B2 3 OSM200B3M230C 1SCA104272R1001 9.6
200 B1-B2 3+N OSM200B3N3M230C 1SCA104323R1001 9.8
200 B1-B2 4 OSM200B4N1M230C 1SCA118784R1001 10.7
250 B1-B3 3 OSM250B3M230C 1SCA104287R1001 10.4
250 B1-B3 3+N OSM250B3N3M230C 1SCA104290R1001 10.5
250 B1-B3 4 OSM250B4N1M230C 1SCA118785R1001 11.2
OSM315B3N3M230C 315 B1-B4 3 OSM315B3M230C 1SCA104303R1001 14.8
315 B1-B4 3+N OSM315B3N3M230C 1SCA104306R1001 15.1
315 B1-B4 4 OSM315B4N1M230C 1SCA118788R1001 16.7
400 B1-B4 3 OSM400B3M230C 1SCA104310R1001 14.8
400 B1-B4 3+N OSM400B3N3M230C 1SCA104312R1001 15.1
400 B1-B4 4 OSM400B4N1M230C 1SCA118789R1001 16.7
630 C1-C2 3 OSM630B3M230C 1SCA104516R1001 34
630 C1-C2 3+N OSM630B3N3M230C 1SCA104535R1001 35
630 C1-C2 4 OSM630B4N1M230C 1SCA118791R1001 38
800 C1-C3 3 OSM800B3M230C 1SCA104520R1001 34
800 C1-C3 3+N OSM800B3N3M230C 1SCA104536R1001 35
800 C1-C3 4 OSM800B4N1M230C 1SCA118792R1001 38
1250 D1 3 OSM1250B3M230C 1SCA112552R1001 55
1250 D1 3+N OSM1250B3N3M230C 1SCA112550R1001 56
1250 D1 4 OSM1250B4N1M230C 1SCA118795R1001 65
Number of poles: 3+N / Type: _N3_ = Include a detachable neutral link integrated into the mechanism
N1 = Non-fused switched neutral on the left side
Available on request: F = Fused switched neutral, N2 = Non-fused switched neutral on the right side

Handle and bolt kits included as standard


Suitable for switch fuses Handle+shaft kit Bolt kit
OSM3263 OTV250EMK -
OSM100200 OTV250EMK M8x25
OSM250 OTV250EMK M10X30
OSM315400 OTV400EMK M10X30
OSM630800 OTV800EMK M12X40
OSM1250 OTV1000EMK M12X50

44 Ordering information | Switch fuses OS and OSM


Accessories
Selection overview

OS16...OS40 (OS Mini)

3
1
3
4
5
6 4

2
S07019

7 8
9

10

1 Switch fuse | 2 Extended shaft | 3 Mounting frame for auxiliary contact | 4 Auxiliary contact | 5 Fuse monitor | 6 Detachable neutral link |
7 Handle knob | 8 Pistol type handle | 9 Blown fuse indicator | 10 Conversion kit: 6/8-pole, C/O, mech. interlock

OS32G...OS63G

11

1
3
12

4
2

6 7
S04135

10 9

1 Switch fuse | 2 Extended shaft | 3 Module for auxiliary contacts | 4 Auxiliary contact | 5 Fuse monitor | 6 Pistol type handle | 7 Direct mounted
handle | 8 Blown fuse indicator | 9 Interlocks, mechanical & electrical | 10 Detachable neutral link | 11 Conversion kit: 6/8-pole, C/O, bypass,
mech. interlock | 12 DIN rail mounting kit

Switch fuses OS and OSM | Accessories, selection overview 45


OS100G...OS1250_

5 14

3
1 4
15 6

7
2

9
10

12
S04134

11

13

1 Switch fuse | 2 Extended shaft | 3 Terminal clamp | 4 Fourth pole | 5 Terminal shroud | 6 Module for auxiliary contacts | 7 Auxiliary contact |
8 Fuse monitor | 9 Pistol type handle | 10 Direct mounted handle | 11 Detachable neutral link | 12 Interlocks, mechanical & electrical | 13 Blown
fuse indicator | 14 Conversion kit: 6/8-pole, C/O, bypass, mech. interlock | 15 DIN rail mounting kit (only for OS100G...160G_)

OSM32G...OSM1250
3

2
4

8
S07018

1 Motor operator | 2 Terminal clamp | 3 Terminal shroud | 4 Auxiliary contact | 5 Fuse monitor | 6 Detachable neutral link | 7 Blown fuse indicator
| 8 Storage for handle and fuses

46 Accessories, selection overview | Switch fuses OS and OSM


Ordering information
Accessories

OHB65J6 Pistol handles for front operated switch fuses

Plastic pistol handles, IP 65, Nema type 1, 3R, 12


Padlockable with 3 padlocks in the OFF-position, door interlock in the ON-position. Screw fixingfrom
the back side of the handle ensures double insulation.

OHY65J6 Handle Weight/


length unit
Colour [mm] Type Order number [kg]
For shaft diameter 6 mm (for OSMini and OS32...250)
Black and red-yellow: I-O/ON-OFF, grey: I-O.
Black 45 OHB45J6 1SCA022380R8770 0.12
OHG65J6 Red-yellow 45 OHY45J6 1SCA022380R8930 0.12
Grey 45 OHG45J6 1SCA022380R8850 0.12
Black 65 OHB65J6 1SCA022380R9660 0.12
Red-yellow 65 OHY65J6 1SCA022380R9820 0.12
Grey 65 OHG65J6 1SCA022380R9740 0.12
Black 80 OHB80J6 1SCA022381R0240 0.14
OHB95J12 Black and red-yellow: Test/I-O/ON-OFF, grey: Test/I-O.
Black 45 OHB45J6T 1SCA109870R1001 0.12
Black 65 OHB65J6T 1SCA022399R8110 0.12
Red-yellow 65 OHY65J6T 1SCA022456R9540 0.12
Grey 65 OHG65J6T 1SCA022456R9620 0.12
Black 80 OHB80J6T 1SCA022399R8290 0.14
For shaft diameter 12 mm (for OS315...400)
OHY95J12T Black and red-yellow: I-O/ON-OFF, grey: I-O.
Black 95 OHB95J12 1SCA022381R0830 0.16
Red-yellow 95 OHY95J12 1SCA022381R1050 0.16
Grey 95 OHG95J12 1SCA022381R0910 0.16
Indication: Test-OFF-ON/Test-O-I
Black 95 OHB95J12T 1SCA022736R1750 0.16
Red-yellow 95 OHY95J12T 1SCA022736R1910 0.16
OHB125J12 For shaft diameter 12 mm (for OS630...800)
Black and red-yellow: I-O/ON-OFF, grey: I-O.
Black 125 OHB125J12 1SCA022381R1560 0.16
Red-yellow 125 OHY125J12 1SCA022381R1720 0.16
Grey 125 OHG125J12 1SCA022381R1640 0.16
Black 145 OHB145J12 1SCA022381R2110 0.17
Red-yellow 145 OHY145J12 1SCA022381R2370 0.17
Grey 145 OHG145J12 1SCA022381R2290 0.17
Black 175 OHB175J12 1SCA022381R2450 0.18
Red-yellow 175 OHY175J12 1SCA022381R2700 0.18
Grey 175 OHG175J12 1SCA022381R2610 0.18
Indication: Test-OFF-ON/Test-O-I
Black 125 OHB125J12T 1SCA022652R2220 0.16
Red-yellow 125 OHY125J12T 1SCA022652R2310 0.16
Black 145 OHB145J12T 1SCA022652R2570 0.17
Red-yellow 145 OHY145J12T 1SCA022652R2650 0.17
Black 175 OHB175J12T 1SCA022708R0740 0.18
- Door interlocking in the ON-position means that the door cannot be opened, when the handle is in the ON-position.
This can be defeated to allow authorized personnel access for inspection.
- Handles padlockable in all positions and NEMA4/4X handles are available on request.

Switch fuses OS and OSM | Ordering information 47


Ordering information
Accessories

OHB274/330J12 Optional handles for front operated switch fuses

Plastic pistol handles, IP 65, Nema type 1, 3R, 12


Padlockable with 3 padlocks in the OFF-position, door interlock in the ON-position. Screw
fixing from the back side of the handle ensures double insulation.

OHY274J12 Handle Weight/


length unit
Colour [mm] Type Order number [kg]
For shaft diameter 12 mm (for OS1200...1250)
Black and red-yellow: I-O/ON-OFF.
Black 274 OHB274J12 1SCA115920R1001 0.54
OHM_ Red-yellow 274 OHY274J12 1SCA115919R1001 0.54
Black 330 OHB330J12 1SCA115922R1001 0.58
Red-yellow 330 OHY330J12 1SCA115921R1001 0.58
Black 2x150 OHB150J12P 1SCA022865R9430 0.17
Red-yellow 2x150 OHY150J12P 1SCA101586R1001 0.17
Black 2x200 OHB200J12P 1SCA022865R9510 0.40
YASDA_ Red-yellow 2x200 OHY200J12P 1SCA101587R1001 0.40
Indication: Test-OFF-ON/Test-O-I
Black 274 OHB274J12T 1SCA120250R1001 0.54
Black 330 OHB330J12T 1SCA120252R1001 0.58
Black 2x200 OHB200J12PT 1SCA106510R1001 0.40
Red-yellow 2x200 OHY200J12PT 1SCA111512R1001 0.40
- Door interlocking in the ON-position means that the door cannot be opened, when the handle is in the ON-position.
This can be defeated to allow authorized personnel access for inspection.
- Handles padlockable in all positions and NEMA4/4X handles are available on request.

Stainless steel pistol handles, IP66, NEMA 4X


Padlockable with 3 padlocks in the OFF-position, door interlock in the ON-position, indication:
I-O/ON-OFF

Handle Weight/
length unit
Colour [mm] Type Order number [kg]
For shaft diameter 6 mm (for OSMini and OS32...250)
Metallic 65 OHM65L6 1SCA022739R1070 0.73
For shaft diameter 12 mm
Metallic 125 OHM125L12 1SCA022739R1150 0.76
Metallic 175 OHM175L12 1SCA022739R1230 0.83
Metallic 275 OHM275L12 1SCA022832R4840 0.96

Metallic pistol handles


Padlockable with 3 padlocks in OFF-position, door interlock in the ON-position.

For shaft diameter 12 mm


Black 1-0 220 YASDA 7 1SCA022071R3010 0.70
Black ON-OFF 220 YASDA 8 1SCA022071R3270 0.70
Black I-0 320 YASDA35 1SCA104400R1001 0.80

48 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OHB65J6E00S Pistol handles for side operated switch fuses

Plastic pistol handles, IP 65, Nema type 1, 3R, 12


For mounting on the side of the enclosure. Padlockable with three padlocks in the OFF-
position, door interlock in the ON-position, IP 65. The position indications are rotated 90.
If the handle is mounted on the front of the door, a standard handle can be used as well.

Handle Weight/
OHY65J6E00S length unit
Colour [mm] Type Order number [kg]
For shaft diameter 6 mm
Plastic handles, black and red-yellow: I-O/ON-OFF, grey: I-O.
Black 65 OHB65J6E00S 1SCA022382R9850 0.12
Red-yellow 65 OHY65J6E00S 1SCA022382R9930 0.12
Grey 65 OHG65J6E00S 1SCA022383R4510 0.12
Plastic handles, black and red-yellow: Test/I-O/ON-OFF, grey: Test/I-O.
OHZX14 Black 65 OHB65J6TE00S 1SCA109016R1001 0.12
Red-yellow 65 OHY65J6TE00S 1SCA022688R0140 0.12
Grey 65 OHG65J6TE00S 1SCA109014R1001 0.12
For shaft diameter 12 mm
Plastic handles, indication I-O/ON-OFF
Black 145 OHB145J12E00S 1SCA022679R9700 0.17
- Door interlocking in the ON-position means that the door cannot be opened, when the handle is in the ON-position.
This can be defeated to allow authorized personnel access for inspection.
- Handles padlockable in all positions are available on request.

Extension ring for pistol handles

Suitable Weight
for unit
handles Colour Type Order number [kg]
OHB_ Black OHZX14 1SCA022851R6590 0.06

Switch fuses OS and OSM | Ordering information 49


Ordering information
Accessories

OSV250DK Direct mount handles for front operated switch fuses


Panel board handle, can be padlocked in the OFF-position. Includes a special shaft.
The handle can also be used with a standard shaft as padlocking device.

Suitable Weight/
for unit
switches Colour Type Order number [kg]
Suitable for OS Mini
Indication: I-O/ON-OFF/TEST Padlockable with 2 padlocks in the OFF- and Test-positions when the door is open. Max. bail dia 8 mm.
OS20F40F_ Black OHBS5 1SCA109015R1001 0.05
Suitable for OS 32G...1250
Indication: Test OFF-ON/Test O-I indication Padlockable with three padlocks in the OFF-position, optionally also in the ON-position.
OSV400DK Includes shaft and mechanism cover.
OS32G...160G, OS200J Black OSV200BK 1SCA022779R7530 0.14
OS200B/J_K Red-yellow OSVY200BK 1SCA022779R7700 0.14
OS200D250D/B_K Black OSV250DK 1SCA022763R3510 0.16
OS200D250D/B_K Red-yellow OSVY250DK 1SCA022778R6500 0.16
OS400D_K Black OSV400DK 1SCA022763R4230 0.34
OS400D_K Red-yellow OSVY400DK 1SCA022779R5590 0.34
OS315400B/J_K Black OSV400BK 1SCA022763R3930 0.33
OS315400B/J_K Red-yellow OSVY400BK 1SCA022779R5830 0.33
OSV1250DK OS600800_K Black OSV800DK 1SCA107794R1001 1.1
OS600800_K Red-yellow OSVY800DK 1SCA108703R1001 1.1
OS1200...OS1250_K Black OSV1250DK 1SCA107797R1001 1.5
OS1200...OS1250_K Red-yellow OSVY1250DK 1SCA108702R1001 1.5

Direct mount handles for side operated switch fuses


Panel board handle, can be padlocked in the OFF-position. Includes a special shaft.
The handle can also be used with a standard shaft as padlocking device.

Suitable Weight/
for unit
switches Colour Type Order number [kg]
Suitable for OS Mini
OHB4 Padlockable with three padlocks in the OFF- position when the door is open. Max. bail dia 6 mm.
OS20F40F_ Black OHB4 1SCA022439R4050 0.05

Fuse replacement handles

OFAE506 For Weights/


DIN-fuse unit
sizes Type Order number [kg]
000,00,1,2,3 OFAE506 1SCA128175R1001 0.2

50 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OXP6X_ Extended shafts

Shaft Front Side Weight/


length operated operated unit
[mm] H [mm] H [mm] Type Order number [kg]
OXP_X_-45 For OS 16...35 (Mini)2), shaft diameter 6 mm
150 135...210 154...166 OXP6X150 5) 1SCA022295R5600 0.05
170 155...230 174...186 OXP6X170 1SCA108224R1001 0.05
265 250...325 269...281 OXP6X265 1SCA108225R1001 0.08
400 385...460 404...416 OXP6X400 1SCA108226R1001 0.12
150 135...210 154...166 OXP6X150-45 1) 1SCA022294R4400 0.05
170 155...230 174...186 OXP6X170-45 1) 1SCA108227R1001 0.05
265 380...460 269...281 OXP6X265-45 1)
1SCA108228R1001 0.08
400 380...460 404...416 OXP6X400-45 1) 1SCA108229R1001 0.12
For OS 40 (Mini) 2), shaft diameter 6 mm
150 135...210 235...243 OXP6X150 5) 1SCA022295R5600 0.05
170 155...230 255...363 OXP6X170 1SCA108224R1001 0.05
265 250...325 352...360 OXP6X265 1SCA108225R1001 0.08
400 385...460 487...495 OXP6X400 1SCA108226R1001 0.12
150 135...210 235...243 OXP6X150-45 1) 1SCA022294R4400 0.05
170 155...230 255...363 OXP6X170-45 1) 1SCA108227R1001 0.05
265 250...325 352...360 OXP6X265-45 1)
1SCA108228R1001 0.08
400 385...460 487...495 OXP6X400-45 1) 1SCA108229R1001 0.12
For OS 32G...63G 4) , shaft diameter 6 mm
63 161167 OXP6X63 1SCA111010R1001 0.02
90 188194 OXP6X90 1SCA022064R1180 0.03
130 127174 6) 228234 OXP6X130 1SCA022057R0570 0.04
161 138205 OXP6X161 3) 1SCA022067R1760 0.05
210 187254 OXP6X210 1SCA022295R6080 0.06
290 267334 OXP6X290 1SCA022042R6370 0.08
360 337404 OXP6X360 1SCA022042R6530 0.10
430 407474 OXP6X430 1SCA022056R6030 0.12
210 187254 OXP6X210-45 1) 1SCA022294R4230 0.06
290 267334 OXP6X290-45 1) 1SCA022304R4290 0.08
360 337404 OXP6X360-45 1) 1SCA022341R4640 0.10
1)
The shaft position is rotated 45 degrees
2)
Side operated, 4-pole: add 36 mm
3)
Included as standard in P-types
4)
Side operated 3-pole OS60GJ: add 33mm, 4-pole types: OS3263GD/GB: add 23.5 mm, OS60GJ: add 68mm
5)
Included as standard in front operated types
6)
OS3263GB/GF: 115174

Switch fuses OS and OSM | Ordering information 51


Ordering information
Accessories

OHP6X_ Extended shafts

Shaft Front Side Weight/


length operated operated unit
[mm] H [mm] H [mm] Type Order number [kg]
OHP_X_-45 For OS100G...160G 2), shaft diameter 6 mm
63 196202 OXP6X63 1SCA111010R1001 0.02
90 223229 OXP6X90 1SCA022064R1180 0.03
130 1371744) 263269 OXP6X130 1SCA022057R0570 0.04
161 138205 OXP6X1613) 1SCA022067R1760 0.05
210 187254 OXP6X210 1SCA022295R6080 0.06
290 267334 OXP6X290 1SCA022042R6370 0.08
OHP12X_ 360 337404 OXP6X360 1SCA022042R6530 0.10
430 407474 OXP6X430 1SCA022056R6030 0.12
210 187254 OXP6X210-45 1) 1SCA022294R4230 0.06
290 267334 OXP6X290-45 1) 1SCA022304R4290 0.08
360 337404 OXP6X360-45 1) 1SCA022341R4640 0.10
For OS 200...250 DIN-type, shaft diameter 6 mm
161 160...205 OXP6X161 1SCA022067R1760 0.05
210 189...254 OXP6X210 3) 1SCA022295R6080 0.06
290 269...334 OXP6X290 1SCA022042R6370 0.08
For OS 200...250 BS-type, shaft diameter 6 mm
161 140205 OXP6X161 1SCA022067R1760 0.05
210 189254 OXP6X210 3) 1SCA022295R6080 0.06
290 269334 OXP6X290 1SCA022042R6370 0.08
For OS 315...400, shaft diameter 12 mm
250 230325 OXP12X250 3) 1SCA022325R6980 0.30
280 260355 OXP12X280 1SCA022137R5140 0.30
325 305400 OXP12X325 1SCA022042R5810 0.36
395 375470 OXP12X395 1SCA022042R5990 0.43
465 445540 OXP12X465 1SCA022042R6020 0.51
535 515610 OXP12X535 1SCA022042R6110 0.59
1)
The shaft position is rotated 45 degrees
2)
Side operated 4-pole types: add 35mm
3)
Included as standard in P-types
4)
OS100GJ: 113174, OS100GB160GB: 121174

52 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OXP12X_ Extended shafts

Shaft Front Weight/


length operated unit
OXP12X250-45 [mm] H [mm] H [mm] Type Order number [kg]
For OS 630...800, shaft diameter 12 mm
280 258...382 OXP12X280 2) 1SCA022137R5140 0.30
325 303...427 OXP12X325 1SCA022042R5810 0.40
395 373...497 OXP12X395 1SCA022042R5990 0.50
465 443...567 OXP12X465 1SCA022042R6020 0.60
535 513...637 OXP12X535 1SCA022042R6110 0.70
OETLZX95 280 258...382 OXP12X280-45 1) 1SCA022382R0800 0.30
325 303...427 OXP12X325-45 1)
1SCA022304R4450 0.40
For OS 1200...1250, shaft diameter 12 mm
395 366495 3) 371...5004) OXP12X3952) 1SCA022042R5990 0.43
465 436565 3)
441...570 4)
OXP12X465 1SCA022042R6020 0.51
535 5066353) 441...5714) OXP12X535 1SCA022042R6110 0.59
1)
The shaft position is rotated 45 degrees
2)
Included as standard in front operated P-types
3)
H with handle OH_274/330J12
4)
H with handle OHB150/200J12P

Shaft extension socket


For extending the shaft of combination attachment.

Suitable for Weight/


shaft with diameter unit
[mm] Type Order number [kg]
12 OETLZX95 1SCA022083R5620 0.04

Adapters for extension socket


Adapters to place inside of OETLZX 95 to connect shafts of different sizes.

Suitable for Weight/


shaft with diameter unit
[mm] Type Order number [kg]
6/6, 6/12 OETLZK19 1SCA022093R1850 0.02

Switch fuses OS and OSM | Ordering information 53


Ordering information
Accessories

OA4B10 Auxiliary contacts for OS20F_40F_ (OS Mini)


Units/type = 1 piece

Weight/
unit
Description Type Order number [kg]

Mounting to the switch mechanism


Change over contacts
Auxiliary/test contacts. Max. two change over contacts.
OA3G01 See function chart below OA4B1C 1SCA022193R0150 0.03
Single pole contacts
> 3 mm contact gap.
1 NO OA4B10 1SCA022276R9050 0.03
1 NC OA4B01 1SCA022276R9210 0.03

Mounting on the side of the switch


Mounting on the side of the switch with aux.contact frame OESAZX 169
1NO MCB-10 1SCA022150R5110 0.03
1NC MCB-01 1SCA022150R5370 0.03
OESAZX169 Snap-on mounting on the switch, by using a frame OSZ4, IP20
NO contacts are provided with a positive opening feature.
Types _AU have gold plated contacts for harsh environments and low operating voltages.
1 NO OA1G10 1SCA022353R4970 0.03
1 NC OA3G01 1SCA022456R7410 0.03
1 NO OA1G10AU 1SCA022436R7910 0.03
1 NC OA3G01AU 1SCA022819R5260 0.03

Mounting frames for auxiliary contacts of OS20F_40F_ (OS Mini)

Amount of Weight/
auxiliary contacts unit
Description [pcs] Type Order number [kg]
Frame for auxiliary contacts OA1G10 and OA3G01 and for fuse monitor
Mounting on the left side max. 6 OSZ4 1SCA022530R0200 0.06
of the switch
Frame for MCB-_ auxiliary contacts. Not suitable for side operated switches
Mounting on the right side max. 6 OESAZX169 1SCA022196R9360 0.06
of the switch

Function chart, change over contacts OA4B1C / OS Mini


Handle position Main contacts Aux./Test contacts N.O.
Test open closed
0 open open
I closed closed

54 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OA3G01 Auxiliary contacts for OS/OSM32G...1250


Types _AU have gold plated contacts for harsh environments and low operating voltages.

Suitable Weight/
for Protection unit
switches Description degree Type Order number [kg]
OA3G01AU OS/OSM32G...1250 1NO IP20 OA1G10 1SCA022353R4970 0.03
OS/OSM32G...1250 1NC IP20 OA3G01 1SCA022456R7410 0.03
OS/OSM32G...1250 1NO IP20 OA1G10AU 1SCA022436R7910 0.03
OS/OSM32G...1250 1NC IP20 OA3G01AU 1SCA022819R5260 0.03

Mounting under the mechanism cover


The test contacts operate in ON- and OFF-positions as well as when the handle is turned to
TEST-position = 45 degrees over the OFF-position. The test tindication contacts operate only
when the handle is turned to TEST-position. See the function table below. The OA1G10 (N.O.)
or OA3G01 (N.C.) auxiliary contact blocks can be used as standard auxiliary contacts, test or
test indication contacts. The desired functions are achieved when an auxiliary contact block
is installed in a specific place shown in the mounting instruction. In order to activate the test
and test indication features, a handle with test function is required. See the optional handles,
pages 60...48.

Function table of OS/OSM32G1250 auxiliary contacts


Handle position Main contacts Aux./Test contacts N.O. Test indication contacts N.O
Test open closed closed
0 open open open
I closed closed open

Maximum number of contact blocks, Aux./test contacts and test indication contacts, see
the table below. Standard versions include all except for N3-types, which are equipped with
integrated neutral through the mechanism.

Maximum number of auxiliary contacts under the mechanism cover


OS/OSM32G250 OS/OSM315800 OS/OSM12001250
Pole version Standard N3 Standard N3 Standard N3
Maximum number of contact blocks 4 0 8 4 12 8
Aux./Test contacts 4 0 4 2 81) 62)
Test indication contacts 2 0 4 2 4 2
For contact timing, see pages 106 and 107.
1)
6 aux/test contacts and 2 early operation aux./test contacts
2)
4 aux/test contacts and 2 early operation aux./test contacts

Mounting on the left side of the OS switch fuse:


Maximum 8 auxiliary contact blocks (N.O. or N.C.) with the OEA28 module.
Side operated types: OS_S30..._S40 types only.
Mounting on the right side of the OSM motorized switch fuse:
Maximum 4 auxiliary contact blocks (N.O. or N.C.), snap-on mounting.

Switch fuses OS and OSM | Ordering information 55


Ordering information
Accessories

OEA28 Module for auxiliary contacts for OS32...1250

Weight/
unit
Description Type Order number [kg]
Screw mounting to the left side of the switch OEA28 1SCA022714R8810 0.04

Performance data for auxiliary contacts according to IEC 60947-5-1


OA1G_, OA3G_
U i/[V] 690
Uimp/[kV] 4
Pollution degree 3
Ith/[A] 16
Cable size 12 x 0,752,5 mm2
Maximum fuse 16 A/gG
NEMA A600, R300
Wire size 18 - 14AWG, 1 (2)
OA1G_, OA3G_
AC15 DC12 DC13
Ue /[V] Ie/[A] Ue/[V] Ie/[A] P/[W] Ie/[A] P/[W]
230 6 24 10 240 2 48
400 4 72 4 288 0.8 58
690 2 125 2 250 0.55 69
250 0.55 138 0.27 68
440 0.1 44
OA4_
EN61058-1
Ui /[V] 400
Ith /[A] 10
Ie 400V AC
10 (4) A, 10E3
6 (2,5) A, 50E3
NEMA 10 A, 125-250V AC, 1/4 HP
M3 Screw connection
MCB_
IEC60947-5-1
Ui /[V] 690
Ith /[A] 10
AC12 AC15 DC13
I e /[A] 24V 10 8 5
110V 10 8 1.1
220/240V 10 6 0.55
250V 4 0.55
380/415V 4
660/690V 2
NEMA A600, 10A, 600VAC

56 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OSP200-400D Mounting plate for auxiliary contacts


Mount on the switch mechanism, max. 3 auxiliary contacts.

Suitable
for
switches Type Order number
R: Mounting on the right side of the switch L: mounting on the left side of the switch
OS100G_...200G_ OEA30R 1SCA131817R1001
OS100G_...200G_ OEA30L 1SCA131816R1001

OSP160GN Fourth poles


Snap-on mounting to the side of the switch (not suitable for OSM-types).

Suitable for Weight/


3-pole Mounting unit
switches side Type Order number [kg]
Fusible 4. poles
OS100GB...160GB Left/right OSP160GB 1SCA114769R1001 0.45
OS125GD...160GD Left/right OSP160GD 1SCA114768R1001 0.45
OS200B Left/right OSP200B 1SCA022735R9180 1.20
OSP250N OS200D Left/right OSP200D 1SCA022735R8960 1.20
OS250B Left/right OSP250B 1SCA022770R4030 1.20
OS250D Left/right OSP250D 1SCA022735R9340 1.20
OS315B400B Left/right OSP400B 1SCA022770R3140 2.00
OS400D Left/right OSP400D 1SCA022770R3220 2.00
OS630...800D Left/right OSP800D 1SCA100433R1001 4.20
OS630...800B Left/right OSP800B 1SCA100434R1001 4.20
OS1250D Left/right OSP1250D 1SCA107946R1001 7.20
OS1250DA Left/right OSP1250DA 1SCA112402R1001 7.20
OS1250B Left/right OSP1250B 1SCA107950R1001 7.20
OSP800N Switched 4. poles
OS100G...160G Left/right OSP160GN 1SCA114770R1001 0.45
OS200_ Left/right OSP200N 1SCA022735R8700 1.20
OS250_ Left/right OSP250N 1SCA022735R9260 1.20
OS400_ Left/right OSP400N 1SCA022770R3490 1.20
OS630...800 Left/right OSP800N 1SCA100432R1001 4.40
OS1200...1250 Left/right OSP1250N 1SCA107943R1001 7.20

Switch fuses OS and OSM | Ordering information 57


Ordering information
Accessories

OSZ1 Neutral links

Weight/
H/W/D Mounting unit
Max. wire [mm] holes Type Order number [kg]

For OS/OSM 32G...160G


Detachable, mounting onto the base plate or DIN-rail.

16 mm2 Cu 39/41/40 4.2, distance 32 OSZ1 1SCA022481R3710 0.06


OXN250 35 mm2 Cu 39/44/45 4.2, distance 35 OSZ2 1SCA022481R3800 0.07

For OS/OSM 100G...1250


Mounting with screws (included) onto either side of the switch (OXN250 to OS200...250) or on
the base plate (OXN250...1250) according the table below.

Detachable, mounting on the switch


OS200...250 OXN250 1SCA022752R9950 0.40
Detachable, mounting on the base plate
OS/OSM32G...250 OXN250 1SCA022752R9950 0.40
OXN400 OS/OSM315400 OXN400 1SCA022770R3060 0.70
OS/OSM630800 OXN800S 1SCA022831R4880 1.20
OS/OSM1250 OXN1250S 1SCA104163R1001 2.50

OXN800S

58 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OTVS1 Solid links

Weight/
unit
Suitable for Type Order number [kg]
OS32GD...OS160GD OFAW00 1SCA022003R9680 0.08
OS200250B, J OEZNL1 1SCA022723R7400 0.19
OS600J, 8001200L OEZNL8 1SCA113998R1001 0.58
OS1250B OEZNL10 1SCA116437R1001 0.60
OS250 D OFAW1 1SCA022003R9760 0.15
OTVS2 OS400 D OFAW2 1SCA022003R9840 0.24
OS630/800 D OFAW3 1SCA022003R9920 0.28

Handle and spare fuse storage clip for OSM


Handle and two spare fuses (for motor operator) can be stored on the OTVS_. OTVS_ can
be installed on the left side of the motorized switch-fuse OSM_. Snap-on mounting, no tools
required. On OSM1250, the size of the handle prevents the installation onto the switch frame.
However, the handle clip can be separately installed on the panel frame and the fuse holder
clip onto the switch frame.

Weight/
unit
Suitable for Type Order number [kg]
OSM32G...250 OTVS1 1SCA111413R1001 0.02
OSM315...1250 OTVS2 1SCA111414R1001 0.04

Phase barriers
The phase barriers designed for ABB Tmax T4-T5 MCCBs can also be used for OS200400
switch fuses. 3-pole switch fuses need 4 barriers and 4-pole switch fuses need 6 barriers for
full protection. Cutting width of the phase barrier 55mm.

Suitable No. Height Units/


for of h type
switches poles [mm] Type Order number [pcs]
OS100GOS200G 3 - OSB160/4 1SCA131820R1001 4
OS100GOS200G 3 - OSB160/6 1SCA131821R1001 6
OS250 3 - OSB250/4 1SCA131822R1001 4
OS250 4 - OSB250/6 1SCA131823R1001 6
OS315, OS400 3 200 PB200 high 1SDA054972R1 4
OS315, OS400 4 200 PB200 high 1SDA054973R1 6

Switch fuses OS and OSM | Ordering information 59


Ordering information
Accessories

OSS200G1L Terminal shrouds

Units/ Weight/
Suitable for type unit
switches Description Type Order number [pcs] [kg]
Pack of single pole terminal shrouds
Snap-on mounting, grey plastic, IP 3X from front. Transparent shrouds available on request.
OSS200G1S OS/OSM100G160G Long type OSS160GG1L/3 1SCA114764R1001 3 0.08
OS/OSM100G160G Short type OSS160GG1S/3 1SCA114766R1001 3 0.05
OS/OSM100G160G Long type OSS160GG1L/4 1SCA114765R1001 4 0.11
OS/OSM100G160G Short type OSS160GG1S/4 1SCA114767R1001 4 0.07
OS/OSM200 Long type OSS200G1L/3 1SCA022731R8910 3 0.09
OS/OSM200 Short type OSS200G1S/3 1SCA022732R0130 3 0.06
OS/OSM200 Long type OSS200G1L/4 1SCA022731R9040 4 0.12
OSS250G1L OS/OSM200 Short type OSS200G1S/4 1SCA022732R0050 4 0.08
OS/OSM250 Long type OSS250G1L/3 1SCA022731R9390 3 0.09
OS/OSM250 Short type OSS250G1S/3 1SCA022731R9550 3 0.06
OS/OSM250 Long type OSS250G1L/4 1SCA022731R9470 4 0.12
OS/OSM250 Short type OSS250G1S/4 1SCA022731R9630 4 0.08
OS/OSM315...400 Long type OSS400G1L/3 1SCA022776R6650 3 0.18
OS/OSM315...400 Short type OSS400G1S/3 1SCA022776R6900 3 0.10
OS/OSM315...400 Long type OSS400G1L/4 1SCA022776R6730 4 0.25
OS/OSM315...400 Short type OSS400G1S/4 1SCA022776R7030 4 0.15
OSS800G1L OS/OSM600...800 Long type OSS800G1L/3 1SCA022776R7200 3 0.53
OS/OSM600...800 Short type OSS800G1S/3 1SCA022776R7540 3 0.21
OS/OSM600...800 Long type OSS800G1L/4 1SCA022776R7380 4 0.70
OS/OSM600...800 Short type OSS800G1S/4 1SCA022776R7460 4 0.28
OS1200...1250/ OSM1250 Long type OSS1250G1L/3 1SCA107938R1001 3 0.76
OS1200...1250/ OSM1250 Short type OSS1250G1S/3 1SCA107939R1001 3 0.40
OS1200...1250/ OSM1250 Long type OSS1250G1L/4 1SCA107940R1001 4 1.00
OS1200...1250/ OSM1250 Short type OSS1250G1S/4 1SCA107941R1001 4 0.52
Terminal shrouds suitable for mechanisms with detachable integrated neutral (N3 versions)
OSS800G1S OS/OSM100G250_N3_ Long type OTS250G1L 1SCA022715R5340 1 0.03
OS/OSM100G250_N3_ Short type OTS250G1S 1SCA022715R5260 1 0.02
OS/OSM315400_N3_ Long type OSS250G1L 1SCA022727R5080 1 0.03
OS/OSM315400_N3_ Short type OSS250G1S 1SCA022727R4940 1 0.02
OS/OSM630800_N3_ Long type OTS800G1L 1SCA022776R7710 1 0.10
OS/OSM630800_N3_ Short type OTS800G1S 1SCA022776R8010 1 0.06
OS1200...1250/OSM1250_N3_ Long type OTS1600G1L 1SCA106134R1001 1 0.20
OS1200...1250/OSM1250_N3_ Short type OTS1600G1S 1SCA102667R1001 1 0.12
OSS250G1SH Single pole terminal shroud for the fourth pole side terminals (LR-types)
IP20, snap-on mounting, grey plastic.
OS250_LR Short type OSS250G1SH/1 1SCA103500R1001 1 0.003
OS400_LR Short type OSS400G1SH/1 1SCA103503R1001 1 0.003
Please consult us when using OS600J...OS800L with OZXA-800 lugs

60 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OSS160GG3LS Terminal shrouds

Three and four pole terminal shrouds for side terminals (LR types)
IP20. Snap-on mounting, grey plastic.

No. Units/ Weight/


Suitable for of type unit
switches poles Remarks Type Order number [pcs] [kg]
OS100G...160G_LR 3 Long type OSS160GG3LS 1SCA121570R1001 1 0.01
OS100G...160G_LR 4 Long type OSS160GG4LS 1SCA121571R1001 1 0.01
OSS400G3LS OS200400_ 3 Short type OSS400G3SS 1SCA100390R1001 1 0.01
OS200400_ 3 Long type OSS400G3LS 1SCA100396R1001 1 0.01
OS200400_ 4 Left side, short OSS400G4SSL 1SCA100392R1001 1 0.01
OS200400_ 4 Left side, long OSS400G4LSL 1SCA100398R1001 1 0.01
OS200400_ 4 Right side, short OSS400G4SSR 1SCA100394R1001 1 0.01
OS200400_ 4 Right side, long OSS400G4LSR 1SCA100400R1001 1 0.01

Single pole shroud for terminal clamps


Snap-on mounting, transparent plastic, IP 2X.

OEZXU14 Suitable for Units/ Weight/


terminal type unit
clamps Type Order number [pcs] [kg]
OZXB2, 2L OZXB2K 1SCA022264R0010 3 0.06
OZXB3, 4 OZXB3K 1SCA022264R0440 3 0.18
OZXB5, 6 OZXB4K 1SCA022199R2850 3 0.24
OZXB7, 7L OZXB5K 1SCA022283R8040 3 0.15

Terminal angle for side terminals (LR types)


Terminal angle extension bar for cable connections in upper or lower position.
Including terminal bolts M10x30.

Units/ Weight/
Suitable for type unit
switches Type Order number [pcs] [kg]
OS100G...160G_LR, 3-pole OEZXU68/3 1SCA121380R1001 3
OS100G...160G_LR, 4-pole OEZXU68/4 1SCA121379R1001 4
OS200400_LR OEZXU14/3 1SCA100361R1001 3 0.24
OS200400_LR OEZXU14/4 1SCA101082R1001 4 0.32

Switch fuses OS and OSM | Ordering information 61


Ordering information
Accessories

OZXT1 Terminal clamp sets for Al- and Cu-cables

Cable cross Units/ Weight/


Suitable section type unit
for switches [mm2] Type Order number [pcs] [kg]

Insulated versions
OS/OSM32G63G 1650 Al, 2.550 Cu OZXT1 1SCA022469R6310 3 0.05

OZXB-type Al/Cu connectors made of stainless steel


OZXB8
Cable cross Units/ Weight/
Suitable section Suitable type unit
for switches [mm2] shroud Type Order number [pcs] [kg]
OS/OSM100G160G1) 10...70 OSS160G_ OZXB1L 1SCA022169R2030 3 0.15
OS/OSM100G160G 1)
95...185 OSS160G_ OZXB8 1SCA022744R1510 3 0.50
OS/OSM200 10...70 OSS200_L OZXB1L 1SCA022169R2030 3 0.15
OS/OSM200 25...120 OZXB2K OZXB2 1SCA022119R7610 3 0.34
OS/OSM2002) 25...120 OZXB2K OZXB2L 1SCA022158R7750 3 0.42
OS/OSM200 95...185 OSS200_L OZXB8 1SCA022744R1510 3 0.50
OZXB2L OS200 95...240 OSS200_L OZXB9 1SCA022750R3210 3 0.50
OSM250 10...70 OSS200_L OZXB1L 1SCA022169R2030 3 0.15
OS/OSM2502) 25...120 OZXB2K OZXB2L 1SCA022158R7750 3 0.42
OS/OSM2502) 95185 OZXB3K OZXB3 1SCA022136R8100 3 1.30
OS/OSM250 2)
2x(95185) OZXB3K OZXB4 1SCA022137R4760 3 1.70
OS/OSM2502) 120...300 OZXB4K OZXB5 1SCA022137R2470 3 2.30
OS/OSM2502) 120...240 OZXB5K OZXB7L 1SCA022185R7130 3 1.20
OS/OSM2502) 95...185 OSS250_L OZXB8 1SCA022744R1510 3 0.50
OS2502) 95...240 OSS250_L OZXB9 1SCA022750R3210 3 0.50
OS200400_LR_ 95240 OSS400G4LSL OZXB17 1SCA022859R3230 3 0.53
OZXB17 1)
Suitable for OS125G...160G_LR -types only with terminal angle OEZXU68
2)
Suitable for OS250_BB -types, OS200B_LR, for OS250_LR types suitable only with terminal angle OEZXU14

62 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OZXB2L Terminal clamp sets for Al- and Cu-cables

Cable cross Units/ Weight/


Suitable section Suitable type unit
for switches [mm2] shroud Type Order number [pcs] [kg]

OZXB-type Al/Cu connectors made of stainless steel


OS/OSM3154001) 25120 OSS400_L OZXB2L 1SCA022158R7750 3 0.42
OS/OSM3154001) 95185 OZXB3K OZXB3 1SCA022136R8100 3 1.30
OS/OSM3154001) 2x(95185) OZXB3K OZXB4 1SCA022137R4760 3 1.70
OZXB8 OS315...4001) 120300 OZXB4K OZXB5 1SCA022137R2470 3 2.30
OS315...4001) 2x(120300) OZXB4K OZXB6 1SCA022137R4920 3 3.03
OS/OSM315...4001) 120240 OZXB5K OZXB7 1SCA022185R0040 3 1.00
OS/OSM3154001) 95185 OSS400_L OZXB8 1SCA022744R1510 3 0.50
OS/OSM3154001) 95240 OSS400_L OZXB9 1SCA022750R3210 3 0.50
OS/OSM630...800 95185 OSS800_L OZXB3 1SCA022136R8100 3 1.30
OS/OSM630...800 2x(95185) OSS800_L OZXB4 1SCA022137R4760 3 1.70
OS/OSM630...800 120300 OSS800_L OZXB5 1SCA022137R2470 3 2.30
OS/OSM630...800 2x(120300) OSS800_L OZXB6 1SCA022137R4920 3 3.03
OS/OSM630...800 120240 OSS800_L OZXB7L 1SCA022185R7130 3 1.20
OS/OSM630...800 95185 OSS800_L OZXB8 1SCA022744R1510 3 0.50
OS/OSM630...800 95240 OSS800_L OZXB9 1SCA022750R3210 3 0.50
1)
Suitable for OS315...400_BB_-types, for OS315...400_LR_-types suitable only with terminal angle OEZXU14

Switch fuses OS and OSM | Ordering information 63


Ordering information
Accessories

OZXB8 Terminal clamp sets for Al- and Cu-cables

Cable cross Units/ Weight/


Suitable section Suitable type unit
for switches [mm2] shroud Type Order number [pcs] [kg]

OZXB-type Al/Cu connectors made of stainless steel


OS/OSM1250 95185 OTS1600_L OZXB3 1SCA022136R8100 3 1.30
OZXR95 OS/OSM1250 2x(95185) OTS1600_L OZXB4 1SCA022137R4760 3 1.70
OS/OSM1250 120300 OTS1600_L OZXB5 1SCA022137R2470 3 2.30
OS/OSM1250 2x(120300) OTS1600_L OZXB6 1SCA022137R4920 3 3.03
OS/OSM1250 120240 OTS1600_L OZXB7L 1SCA022185R7130 3 1.20
OS/OSM1250 95185 OTS1600_L OZXB8 1SCA022744R1510 3 0.50
OS/OSM1250 95240 OTS1600_L OZXB9 1SCA022750R3210 3 0.50

OZXR185 OZXR type Al/Cu connectors made of stainless steel and copper2)
OS100G160G1) 670 OSS160G_L OZXR70 1SCA115529R1001 3 0.15
OS100G160G1) 2595 OSS160G_L OZXR95 1SCA115530R1001 3 0.21
OS200 2595 OSS200_L OZXR95 1SCA115530R1001 3 0.21
OS200 95185 OSS200_L OZXR185 1SCA115531R1001 3 0.45
OS200 2x(95185) - OZXR2X185 1SCA115534R1001 3 0.66
OS250 95185 OSS250_L OZXR185 1SCA115531R1001 3 0.45
OS250 2x(95185) - OZXR2X185 1SCA115534R1001 3 0.66
OZXR240 OS315400 95240 OSS400_L OZXR240 1SCA115532R1001 3 0.42
OS315400 2x(95185) - OZXR2X185 1SCA115534R1001 3 0.66
OS315400 185300 - OZXR300 1SCA115533R1001 3 0.87
OS630800 2x(185300) OSS800_L OZXR2X300 1SCA115535R1001 3 1.59

OZXP type Al/Cu connectors made of tin plated aluminium profile2)


OS100G160G1) 695 OSS160G_L OZXP95 1SCA115539R1001 3 0.09
OS200 695 OSS200_L OZXP95 1SCA115539R1001 3 0.09
OS200 16120 OSS200_L OZXP120 1SCA115540R1001 3 0.15
OZXR300 OS200 25150 - OZXP150 1SCA115541R1001 3 0.18
OS200 35240 - OZXP240 1SCA115542R1001 3 0.27
OS250 35240 - OZXP240 1SCA115542R1001 3 0.27
OS315400 35240 - OZXP240 1SCA115542R1001 3 0.27
OS315400 95300 - OZXP300 1SCA115543R1001 3 0.42
OS315400 2x(70240) - OZXP2X240 1SCA115544R1001 3 1.38
OS630800 2x(70240) OSS800_L OZXP2X240 1SCA115544R1001 3 1.38
1)
For _LR-types, suitable only with terminal angle OEZXU68
2)
Suitable also for OS200...400_BB_, for OS200...400_LR_-types suitable only with terminal angle OEZXU14

64 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OESAZW2 Conversion kits for front operated combination switches

Suitable Switches Shaft Units/ Weight/


for needed distance type unit
switches [pcs] [mm] Type Order number [pcs] [kg]

6 and 8-pole switch mechanism


Parallel attachment for connecting 3- and 4-pole switches. The switches work simultaneously.

6-pole switches, OS Mini


OTZW25 OS Mini Two 3-pole OWP6DS1 1SCA105255R1001 1 0.69
8-pole switches, OS Mini
OS Mini Two 4-pole OWP6DS2 1SCA105256R1001 1 0.69
6 and 8-pole switches, OS32G...400
The attachment levers are provided with holes, enabling different shaft distances.
The combination switches can be mounted either horizontally or vertically.
OS32G...250 Two 3- or 4-pole 45+(0-13)x15 OESAZW2 1SCA022078R1600 1 0.37
OS315...400 Two 3- or 4-pole 60+(0-19)x20 OETLZW9 1SCA022061R3300 1 1.1

Change-over switch mechanism


OTZW26 Two switches connected with a mechanism operating into I-O-II positions.

OS Mini Two 3-pole - OWC6DSH1 1SCA105251R1001 1 1.0


OS Mini Two 4-pole - OWC6DSH2 1SCA105252R1001 1 1.0
OS32G...250 Two 3- or 4-pole 210+(0 - 18)x20 OTZW25 1SCA022778R6920 1 2.8
OS315...400 Two 3- or 4-pole 210+(0 - 11)x20 OETLZW11 1SCA022078R0030 1 3.0
OS315...400 Two 3- or 4-pole 210+(0 - 20)x20 OETLZW12 1SCA022078R0200 1 4.6

Bypass switch mechanism


A combination of two switches in parallel with a third switch for change-over operation to
bypass, for example, a breaker for maintenance. The bypass attachment can be used together
with another combination attachment.

OS32G...250 Three 3- or 4-pole OTZW26 1SCA022778R7060 1 3.3


Between 1 and 2: 210+(0 - 9)x20
OETLZW3 Between 1 and 3: 250+(0 - 9)x20
OS315...400 Three 3- or 4-pole OETLZW13 1SCA022078R0460 1 4.0
Between 1 and 2: 210+(0 - 18)x20
Between 1 and 3: 250+(0 - 18)x20

Mechanical interlock mechanism


Prevents one switch from closing to ON -position, if the other is not in OFF - position.
OTZW/OETLZW-types: When mounted upside down, prevents one switch from opening to
OFF-position, if the other is not in the ON-position. (UPS-usage, make-before-break)

OS Mini Two 3-pole - OWM6DS1 1SCA105253R1001 1 0.30


OS Mini Two 4-pole - OWM6DS2 1SCA105254R1001 - 0.30
OS32G...250 Two 3- or 4-pole 190 OTZW10 1SCA022431R5280 1 0.40
OS315...800 Two 3- or 4-pole 250 OETLZW14 1SCA022077R3410 1 0.70
OS315...800 Two 3- or 4-pole 300 OETLZW3 1SCA022049R0380 1 0.80
OS315...1250 Two 3- or 4-pole 500 OETLZW15 1SCA022081R9340 1 1.24

Switch fuses OS and OSM | Ordering information 65


Ordering information
Accessories
I II

II I

Change-over switches Shafts and handles for conversion kits


I II
I II The standard
II I
To be Included in the handle or shaft of
II I
ordered conversion kit one of the combined
II ConversionI separately delivery switches can be used
kit type Shaft Handle Shaft Handle Shaft Handle

I 6 and 8-pole
II switches
OWP6DS1 x - - - - x
OWP6DS2 x - - - - x
OESAZW2 - - x (2 pcs) OHB145J12 - -
II I
II I OETLZW9 - - - - x x

I II Change-over switches
I II OWC6DSH1 x (length min. 170mm) - - OHB65J6E011 - -
OWC6DSH2 IIx (length min. 170mm) - - OHB65J6E011 - -
OTZW25 - - x (2 pcs) OHB95J12E011 - -
OETLZW11 - - x (2 pcs) OHB145J12E011 - -
I
Change-over and bypass OETLZW12 - - x (2 pcs) YASDA21 - -
switches
III
Bypass switches
II OTZW26 - - x (3 pcs) OHB95J12E011 - -
II OETLZW13 - - x (3 pcs) YASDA 6 - -

I Mechanical interlock
I
OWM6DS1 x (2 pcs, length min. 170mm) x (2 pcs) - - - -
III OWM6DS2 x (2 pcs, length min. 170mm) x (2 pcs) - - - -
III
OTZW10 - - - - x x
OETLZW14 - - - - x x
OETLZW3 - - - - x x
OETLZW15 - - - - x x

Mechanical interlock Change-over switches Bypass switches

I II II I III

II ON II ON

Change-over switches Bypass switches


Change-over switches O
Bypass switches O
OFF OFF
I II II I III
I II II I III
II ON II ON
II ON II ON
I ON I ON

O O
O
OFF O
OFF
OFF OFF

I ON I ON
I ON I ON
66 Ordering information | Switch fuses OS and OSM
Ordering information
Accessories

OFM260 Electronic fuse monitor


Includes the auxiliary contacts 1NO + 1NC. More information, see brochure OFM_OFS20GB.

Rated Weight/
voltage unit
[V] Type Order number [kg]

OS Mini
Mounting onto the left side of OS Mini (with a frame OSZ4) or on mounting plate.

OFS260 120...240/AC OFM240 1SCA022579R1340 0.2


120...260/AC OFM260 1SCA022459R8560 0.14
380...600/AC OFM600 1SCA022579R1260 0.2
380...690/AC OFM690 1SCA022459R8480 0.14

OS/OSM32G1250
Mounting onto the left side of OS32G-1250 switch fuse (right side of OSM motorized switch
fuses) or on DIN-rail or on mounting plate.

100260/AC OFS260 1SCA022716R0180 0.16


OFD500EA 380690/AC OFS690 1SCA022715R9920 0.16
48...110/DC OFD110EA 1SCA121775R1001 0.155
110...500/DC OFD500EA 1SCA121776R1001 0.155

Mounting accessories for fuse monitor

Suitable Flat terminal Units/ Weight


for size type /unit
switches [mm] Type Order number [pcs] [kg]
Crimp terminals
OFMZX2 OS_ 2.8 - 0.8 OFMZX2 1SCA022475R9910 6 0.01
Mounting frame for OS Mini
Mounting on the left side of the switch OSZ4 1SCA022530R0200 1 0.60

OSZ4

Switch fuses OS and OSM | Ordering information 67


Ordering information
Accessories

OSD25P3 Blown fuse indicators (DPMM)


Striker type fuse is needed. See the dimensions in IEC60269-2-1, Section 1A.

Suitable Weight/
for unit
switches Type Order number [kg]

OS Mini
Auxiliary contact (1x C/O) included. See the ratings on page 63, type OA4

OSGD50P4 for 3-pole switches OSD25P3 1SCA022192R9060 0.10


for 4-pole switches, fused neutral OSD25P4 1SCA022196R9520 0.10

OS/OSM50GF_
Auxiliary contacts (3 x C/O in 3-pole, 4 x C/O in 4-pole) included. Ratings: Ith: 5A, AC15:
0.15A/250VAC. NEMA 5A, 125-250 VAC, 1/10 HP

for 3-pole switches OSGD50P3 1SCA116401R1001 0.015


for 4-pole switches, fused neutral OSGD50P4 1SCA115689R1001 0.020

OSGD125P3 OS/OSM125GF_
Auxiliary contacts (3 x C/O in 3-pole, 4 x C/O in 4-pole) included. Ratings: Ith: 5A, AC15:
0.15A/250VAC. NEMA 5A, 125-250 VAC, 1/10 HP

for 3-pole switches OSGD125P3 1SCA115690R1001 0.025


for 4-pole switches, fused neutral OSGD125P4 1SCA115692R1001 0.035

OS/OSM250D...800D
Auxiliary contacts (3xNO + 3xNC in 3-pole and 4xNO + 4xNC in 4-pole) included. See the
ratings on page 63, type OA1G_, OA3G_
OSZX3
for 3-pole switches OSZX3 1SCA101224R1001 0.15
for 4-pole switches, fused neutral OSZX4 1SCA101225R1001 0.20

68 Ordering information | Switch fuses OS and OSM


Ordering information
Accessories

OSZT1A Cam attachment


For Castell, Lowe & Fletcher and Ronis interlock. Cam attachment for adapting the switches to
the interlock system. The interlock is not included.

Suitable Weight
for /unit
switches Type Order number [kg]
OS16...250 OETLZW16 1SCA022095R2070 0.17
OS315...1250 OETLZW5 1SCA022052R3900 0.14

OSZT2A Mechanism interlock kits and Electrical interlocks


OS32G1250 switch fuses can be interlocked in the OFF position using padlocks and by
using a mechanical interlock kit mounted on the mechanism. The diameter of the lock bail can
be max 8 mm.
Note: The shaft must go through the interlock into the switch mechanism.

Suitable Weight
for /unit
switches Type Order number [kg]
Interlocking in the OFF position
OS32G...160G OTZT1A 1SCA106522R1001 0.21
OS200 250_ OSZT1A 1SCA106532R1001 0.32
OS315 400_ OSZT2A 1SCA106534R1001 0.75
OS600 800_ OSZT3A 1SCA106535R1001 1.20
OS1200 1250_ OSZT4A 1SCA106536R1001 2.00
Interlocking in the OFF & ON positions
OS32G...160G OTZT1L 1SCA106527R1001 0.21
OS200 250_ OSZT1L 1SCA106538R1001 0.32
OS315 400_ OSZT2L 1SCA106539R1001 0.75
OS600 800_ OSZT3L 1SCA106540R1001 1.20
OS1200 1250_ OSZT4L 1SCA106541R1001 2.00

Switch fuses OS and OSM | Ordering information 69


Ordering information
Accessories

PDAL2-230AC50Hz Coils
By installing a coil inside the housing of the interlock kit the switch can be interlocked
electrically in the OFF position or both in the OFF and ON positions. The electrical interlock
works using the closed circuit principle, meaning that when the control voltage is not
connected to the coil, the switches provided with A-type interlocks cannot be turned to the
ON position and switches with L-type interlocks cannot be turned to the ON or OFF positions.

Suitable Weight
for Order /unit
switches Type number [kg]
OSGZD1 AC coils
24 VAC, 60 Hz PDAL2/24AC60Hz 1SCA111350R1001 0.15
110 VAC, 50Hz PDAL2/110AC50Hz 1SCA106543R1001 0.15
110 VAC, 60Hz PDAL2/110AC60Hz 1SCA107100R1001 0.15
120 VAC, 60 Hz PDAL2/120AC60Hz 1SCA111353R1001 0.15
208 VAC, 60Hz PDAL2/208AC60Hz 1SCA107101R1001 0.15
230 VAC, 50Hz PDAL2/230AC50Hz 1SCA107102R1001 0.15
240 VAC, 60 Hz PDAL2/240AC60Hz 1SCA111356R1001 0.15
DC coils
24 VDC PDAL2/24DC 1SCA106542R1001 0.15
48 VDC PDAL2/48DC 1SCA107103R1001 0.15
60 VDC PDAL2/60DC 1SCA107104R1001 0.15
110 VDC PDAL2/110DC 1SCA107105R1001 0.15
125 VDC PDAL2/125DC 1SCA111338R1001 0.15
220 VDC PDAL2/220DC 1SCA112503R1001 0.15

Technical data for the coil

Operating voltage U=0.7...1.1 x Un


Operating ambient temperature -40C...+65C
Power consumption with AC 6.5 W
with DC 9 VA

Mounting accessories

DIN-rail mounting kit


For mounting a switch fuse into 35 mm DIN-rail

Suitable for switches Weight


/unit
Type Order number [kg]
OS32G160G, 1 - 4 -pole OSGZD1 1SCA115688R1001 0.20

70 Ordering information | Switch fuses OS and OSM


Dimension drawings, IEC and UL/CSA
Front operated switch fuses

OS Mini

OS16...35FD12_ OS16...35FD22_
OS20...32FB12_ OS20...32FB22_
OS25...32FF12_ OS25...32FF22_

EN 50022 * OS30FA_12_ * OS30FA_12_


14...85 OA 3G01 OA 3G01
30 OA 1G10 OSZ 4 OA4B1C OA 1G10 OSZ 4 OA4B1C
max 3+3 max 1+1 max 3+3 max 1+1
6 38 74
*
* *

I I
66 35 75...80 75...80
97 O Test O Test
85

65 * *
*
4,5
93 9 4,5 9 35,6
95 14,3 30,8 27,6 14,3 30,8 27,6
S00579C

105 33 106 33 142


36 45 135...210

41 41
A
M00224/OS16-35F_

IEC 60269-2-1 BS88-2 BS88-6 IEC 60269-2-1 BS88-2 BS88-6


IEC 60260-3-1 IEC 60269-2-1 IEC 60269-2-1 IEC 60269-3-1 IEC 60269-2-1 IEC 60269-2-1
UL 198C OS20FB12A1 OS32FB12F1 OS20FB22A1N1 NFC63210,-63211 OS20FB22A1
CSA C22.2 No.106 OS32FB22F1
OS32FB12A1 OS32FB22A1N1 UL 198C OS32FB22A1
NFC63210,-63211 OS32FB12A2 OS20FB22A1F OS32FB22A2N1 OS32FB22A2
OS25FF1210 OS32FB22A1F OS32FB22F1N1
OS32FF1214 OS25FF2210F OS25FF2210N1
OS30FA12J OS32FF2214F OS32FF2214N1
OS30FA12CC OS16FD2201F OS16FD2201N1
OS16FD1201 OS35FD2202F OS35FD2202N1
OS35FD1202 OS30FAJ22F
OS30FACC22F

OS40 Mini
OS 40 FD12000 OS 40 FD22000_

EN 50022
14...133 OA 3G01 OA 3G01
30 OA 1G10 OSZ 4 OA4B1C OA 1G10 OSZ 4 OA4B1C
max 3+3 max 1+1 max 3+3 max 1+1
6 38 74

I I
66 75...80 75...80
35
97 O Test O Test
85

65
4,5
95 9 4,5 9
121 14,3 30,8 27,6 14,3 30,8 27,6
133 33 106 33 142
36 45 135...210

41 41
M00223/OS40F_ A

DIN 000 DIN 000


OS40FD12000 OS40FD22000N1

Switch fuses OS and OSM | Dimension drawings 71


Dimension drawings, IEC
Front operated switch fuses

OS32...63G_P
Mechanism at the end of the switch fuse
mm 47,5
in 1,87
mm 17,5 47,5
E 138...205 (OXP 6x161)
in 0,69 1,87 45
5,43...8,07 1,77 10
17,5 E 138...205 (OXP 6x161) 45 0,39
0,69 25
5,43...8,07 1,77 10 0,98
0,39 25
57/2,24 0,98
6 100/3,94 114 84
ON ON

0,24
ON

57/2,24

OFF

OFF
4,49 O

3,31
O

112/4,41
OFF

6 100/3,94
T T

O
114 ON

84
ON

0,24
T ON

OFF

OFF
100/3,94 4,49 O

3,31
O

112/4,41
OFF

45/1,77
T T

O
T

100/3,94 45/1,77 A1 B1

A1 B1
M5 D C 14 min
3/16 0,55
M5 D A C 14 min
3/16 0,55 B
8A B
0,31
8
29 0,31
1,14
29
1,147
0,28
7
0,28

OS32-63GD OS32-63GB/F OS60GJ


[mm] D01 D02 D03 D04 [mm] B/F01 B/F02 B/F03 B/F04 [mm/in] J01 J02 J03 J04
OS32-63GD OS32-63GB/F OS60GJ
M00287/OS32-63G_01-04 B

A 64,5 88 111,5 135,5 A 64,5 88 111,5 135,5 A 74,5/2,93 109,5/4,31 144,5/5,69 179,5/7,07
[mm] D01 D02 D03 D04 [mm] B/F01 B/F02 B/F03 B/F04 [mm/in] J01 J02 J03 J04
B 120,5 120,5 120,5 120,5 B 108,5 108,5 108,5 108,5 B 118/4,65 118/4,65 118/4,65 118/4,65
M00287/OS32-63G_01-04 B

A 64,5 88 111,5 135,5 A 64,5 88 111,5 135,5 A 74,5/2,93 109,5/4,31 144,5/5,69 179,5/7,07
C - 23,5 23,5 23,5 C - 23,5 23,5 23,5 C - 35/1,38 35/1,38 35/1,38
B 120,5 120,5 120,5 120,5 B 108,5 108,5 108,5 108,5 B 118/4,65 118/4,65 118/4,65 118/4,65
D 40 40 40 40 D 40 40 40 40 D 45,5/1,79 45,5/1,79 45,5/1,79 45,5/1,79
C - 23,5 23,5 23,5 C - 23,5 23,5 23,5 C - 35/1,38 35/1,38 35/1,38
E 30 30 30 30 E 30 30 30 30 E 36/1,41 36/1,41 36/1,41 36/1,41
D 40 40 40 40 D 40 40 40 40 D 45,5/1,79 45,5/1,79 45,5/1,79 45,5/1,79
A1 45 68,5 92 111,5 A1 45 68,5 92 111,5 A1 51/2,01 86/3,39 121/4,76 156/6,14
E 30 30 30 30 E 30 30 30 30 E 36/1,41 36/1,41 36/1,41 36/1,41
B1 75 98,5 122 145,5 B1 75 98,5 122 145,5 B1 81/3,19 116/4,57 151/5,94 186/7,32
A1 45 68,5 92 111,5 A1 45 68,5 92 111,5 A1 51/2,01 86/3,39 121/4,76 156/6,14
B1 75 98,5 122 145,5 B1 75 98,5 122 145,5 B1 81/3,19 116/4,57 151/5,94 186/7,32
mm G 138...205 (OXP 6x161)
in 45
F E 5,43...8,07 1,77
Mechanism between the poles A2 B2

mm G 138...205 (OXP 6x161)


in 45 100/3,94
F E 5,43...8,07 1,77
ON
I 112 ON
I

84
ON
I

114
OFF

OFF
OFF

4,41
O O

O
T
T
A2 T

B2
45/1,77
100/3,94 A1
ON
112 ON B1 ON

84
I I I

114
OFF

OFF
OFF

4,41
O O

D 14 min
O T T

M5 H C 0,35
3/16 45/1,77
A B
A1 B1
8
0,31 D 14 min
29 M5 H C 0,35
1,14 3/16 A B
7 8
0,28 0,31
29
1,14

7
0,28

OS32-63GD OS32-63GB/F OS60GJ


[mm] D11 D12 D13 D22 [mm] B/F11 B/F12 B/F13 B/F22 [mm/in] J11 J12 J13 J22
A 91 114,5 138 138 A 91 114,5 138 138 A 112,5/4,43 148/5,82 182,5/7,19 182,5/7,19
B 120,5 120,5 120,5 120,5 B 108,5 108,5 108,5 108,5 B 118/4,65 118/4,65 118/4,65 118/4,65
C OS32-63GD
- 23,5 23,5 23,5 C OS32-63GB/F
- 23,5 23,5 23,5 C OS60GJ - 35/1,38 35/1,38 35/1,38
D [mm] 60 D11 60 D12 60 D13 60 D22 D [mm] 60B/F11 B/F12
60 B/F13
60 B/F22 D
60 [mm/in]
71,5/2,81 J11 71,5/2,81 J12 71,5/2,81 J13 71,5/2,81 J22
A 30 91 30114,5 30 138 30 138 E A 30 91 30114,5 30 138 30 138 E A 36/1,41
112,5/4,43 36/1,41
148/5,82 36/1,41
182,5/7,19 36/1,41
182,5/7,19
B

E
B 44120,5 44120,5 44120,5 67,5120,5 F B 44108,5 44108,5 44108,5 67,5108,5 F B55,5/2,19
118/4,65 55,5/2,19
118/4,65 55,5/2,19
118/4,65 90,5/3,56
118/4,65
M00288/OS32-63G_11-22

F
G C 74 - 74 23,5 74 23,5 97,5 23,5 G C 74 - 74 23,5 74 23,5 97,5 23,5 G C 91,5/3,6 - 91,5/3,6
35/1,38 91,5/3,6
35/1,38126,5/4,98
35/1,38
A1 D 70 60 93,5 60 117 60 117 60 A1 D 70 60 93,5 60 117 60 117 60 A1 D81,5/3,21
71,5/2,81116,5/4,59
71,5/2,81151,5/5,96
71,5/2,81151,5/5,96
71,5/2,81
B

A2 E 35 30 35 30 35 30 58,5 30 A2 E 35 30 35 30 35 30 58,5 30 A2 E40,5/1,59


36/1,41 40,5/1,59
36/1,41 40,5/1,59
36/1,41 75,5/2,97
36/1,41
M00288/OS32-63G_11-22

B1 F 100 44 123,5 44 147 44 147 67,5 B1 F 100 44 123,5 44 147 44 147 67,5 B1 111,5/4,39
F 55,5/2,19146,5/5,77
55,5/2,19181,5/7,15
55,5/2,19181,5/7,15
90,5/3,56
B2 G 50 74 50 74 50 74 73,5 97,5 B2 G 50 74 50 74 50 74 73,5 97,5 B2 G 56/2,20
91,5/3,6 56/2,20
91,5/3,6 56/2,20
91,5/3,6 90,5/3,56
126,5/4,98
A1 70 93,5 117 117 A1 70 93,5 117 117 A1 81,5/3,21 116,5/4,59 151,5/5,96 151,5/5,96
A2 35 35 35 58,5 A2 35 35 35 58,5 A2 40,5/1,59 40,5/1,59 40,5/1,59 75,5/2,97
B1 100 123,5 147 147 B1 100 123,5 147 147 B1 111,5/4,39 146,5/5,77 181,5/7,15 181,5/7,15
72 Dimension drawings | Switch fuses OS and OSM
B2 50 50 50 73,5 B2 50 50 50 73,5 B2 56/2,20 56/2,20 56/2,20 90,5/3,56
Dimension drawings, IEC
Front operated switch fuses

138...205 (OXP 6x161)

OS100...160G_P 33,4 81
95,5 53,3 at the end20
Mechanism of the switch fuse 45
17,5 8,5 7,2 38
5,5 2,5
138...205 (OXP 6x161)
43
10 17,5 25
33,4 2,5 24 81
95,5 53,3 20 45 C
ON 6
17,5 7,2
8,5 114,5 38
ON ON ON

Back 46 114 110 84


OFF

OFF
OFF

OFF
5,5 2,5
O O O
O T T T

T
connection
43
types:
140 65 10 17,5 25
M5 2,5 24
9 A1 B1 C1
ON 6 C
10
114,5 14 min
ON ON ON

Back 46 114 110 84


OFF

46 35

OFF
OFF

OFF
O O O
O T T T

T
connection
A 20
types:
140 B 65
M5
9 A1 B1 C1

46 35 10 14 min

A 20
B

OS100-160G_ OS100-200G_
M00289/OS100-160G_01-04 C

[mm] D/F01 D/F02 D/F03 D/F04 [mm] B01 B02 B03 B04
A 76,5 111,5 146,5 181,5 A 76,5 111,5 146,5 181,5
B 130 130 130 130 B 114,5 114,5 114,5 114,5
C 100 100 100 100 C 118 118 118 118
A1 55 90 125 160 A1 55 90 125 160
B1 OS100-160G_
70 105 140 175 B1 OS100-200G_
70 105 140 175
M00289/OS100-160G_01-04 C

C1 [mm] D/F01
85 D/F02
120 D/F03
155 D/F04
190 C1 [mm] B01
85 B02
120 B03
155 B04
190
A 76,5 111,5 146,5 181,5 A 76,5 111,5 146,5 181,5
B 130 130 130 130 B 114,5 114,5 114,5 114,5
C 100 100 100 100 C 118 118 118 118
A1 55 90 125 160 A1 55 90 125 160
B1 70 105 140 175 B1 70 105 140 175
C1 85 120 155 190 C1 85 120 155 190

33,4 138...205 (OXP 6x161)


Mechanism between the poles
95,5 81
36 2033,4 138...205 (OXP 6x161) 45
8,5 5,5 38 2,5
43 81
95,5 36 20 A2 B2 C2
20 2,5 24 45
7,2
8,5 5,5 140 38 2,5 6
43
ON ON ON

114,5
ON
114 110
OFF

OFF
OFF

84
C
O O O

Back
20 A2
OFF

B2
46 C2
T T T

O
connection
2,5 24
T

7,2 types:
140 65
M5 6 A1 ON B1 ON C1 ON

114,5 9Back
ON
114 110
OFF

OFF
OFF

84
C
O O O
OFF

46
T T T

O
T connection 14 min
10 types:
71,5 35 65
20 B A1 B1 C1
M5 D 9
A 14 min
10
71,5 35 20 B
D
A

OS100-160GD/F OS100-160GB
[mm] D/F11 D/F12 D/F13 D/F22 [mm] B11 B12 B13 B22
A 113 148 183 183 A 113 148 183 183
B 130 130 130 130 B 114,5 114,5 114,5 114,5
C OS100-160GD/F
100 100 100 100 C OS100-160GB
118 118 118 118
M00290/OS100-160G_11-22 B

D [mm] D/F11
81 D/F12
81 D/F13
81 D/F22
116 D [mm] 81B11 81B12 81B13 116B22
A1 A 90113 125148 160183 160183 A1 A 90113 125148 160183 160183
A2 B 45130 45130 45130 80130 A2 B 114,5
45 114,5
45 114,5
45 114,5
80
B1 C 105100 140100 175100 175100 B1 C 105118 140118 175118 175118
M00290/OS100-160G_11-22 B

B2 D 52,5 81 52,5 81 52,5 81 87,5116 B2 D 52,5 81 52,5 81 52,5 81 87,5116


C1 A1 120 90 155125 190160 190160 C1 A1 120 90 155125 190160 190160
C2 A2 60 45 60 45 60 45 95 80 C2 A2 60 45 60 45 60 45 95 80
B1 105 140 175 175 B1 105 140 175 175
B2 52,5 52,5 52,5 87,5 B2 52,5 52,5 52,5 87,5
C1 120 155 190 190 C1 120 155 190 190
C2 60 60 60 95 C2 60 60 60 95
Switch fuses OS and OSM | Dimension drawings 73
Dimension drawings, IEC
Front operated switch fuses

OS 200: 43 75
OS 250: 53
20 I
OS 200:110/46 40,5
10,5 20 K OS 250:116/46 3
L 6
8,4 J
33,5 8,6 D
*) 8,5
45 18 26,5
72 5,5
0,22
OS200_P
126 and OS250_P E
144 138,5 108
M C
Mechanism at the end of the switch fuse
65
OS 200: 43 75
OS 250: 53 A1 B1 C1
20
*) I
M5 OS 200:110/46 40,5
10,5 20 K OS 250:116/46 3 14 min
H 6
8,4 F J G L B
*) OS_N3
33,5 8,6 A 189...254
D
*) (OXP 6X210)
8,5 18 26,5
45
72 5,5
0,22
126 E
M C 144 138,5 108

65
A1 B1 C1
*)
M5 14 min
G H B
F 189...254
*) OS_N3 A
(OXP 6X210)
OS200 OS250
[mm] D01 B01 D02 B02 D03 B03 D04 B04 [mm] D01/B01 D02/B02 D03/B03 D04/B04
A 89,5 89,5 133 133 176,5 176,5 220 220 A 99,5 153,5 207,5 261,5
B 149 130 149 130 149 130 149 130 B 154 154 154 154
C 198,5 198,5 198,5 198,5 198,5 198,5 198,5 198,5 C 193 193 193 193
D 36,5 36,5 36,5 36,5 36,5 36,5 36,5 36,5 D 33,5 33,5 33,5 33,5
E 144,5 144,5 144,5 144,5 144,5 144,5 144,5 144,5 E 148,5 148,5 148,5 148,5
F 48,5 48,5 48,5 48,5 48,5 48,5 48,5 48,5 F 53,5 53,5 53,5 53,5
G - - 43,5 43,5 43,5 43,5 43,5 43,5 G - 54 54 54
H 20 20 20 20 20 20 20 20 H 25 25 25 25
I 20
40 40 40 40 40 40 40 40 I 45 45 45 45
I G K
M00008/OS200_250_01_04 H

M5 J OS200 10 10 10 10 10 10 10 10 J OS250 11 11 11 11
L
K [mm] J
8,4D01 8,4B01 8,4D02 8,4B02 8,4D03 8,4B03 8,4D04 8,4B04 K [mm] D01/B01
11,5 11,5
D02/B02 11,5
D03/B03 11,5
D04/B04
33,5
L A 89,5
8,6
) 89,5
8,6 8,6133 8,6133 176,5
8,6 176,5
8,6 8,6220 8,6220 L A 99,5
4 153,5
4 207,5
4 261,5
4
* A2130 B2
M B 164,5149 164,5130 164,5149 164,5130 164,5149 164,5 164,5149 164,5130 M B 162C2
154 162154 162154 162154
72A1 C 198,5
60,5 198,5
60,5 198,5
104 198,5
104 198,5
147,5 198,5
147,5 198,5
191 198,5
191 A1 C 70,5193 124,5193 178,5193 232,5193
B1 D 36,5
79,5 36,5
79,5 36,5
123 36,5
123 36,5
166,5 36,5
166,5 36,5
210 36,5
210 B1 D 33,5
89,5 33,5
143,5 33,5
197,5 33,5
251,5
144 M
C1 E 144,5
96,5 144,5
96,5 144,5
140 144,5
140 144,5
183,5 144,5
183,5 144,5
227 144,5
227 C1 E 148,5
106,5
108 148,5
160,5 148,5
214,5 148,5
268,5
144 138,5
F 48,5 48,5 48,5 48,5 48,5 48,5 48,5 48,5 F 53,5 53,5 53,5 53,5
G - - 43,5 43,5 43,5 43,5 43,5 43,5 G - 54 54 54
H
Mechanism
10,5
* ) 20 between
20 the poles
20 20 20 20
A1
20
B1
20 H 25
C1
25 25 25
I 8,6
40 40 40 40 40 40 40 40 I 45 45 45 45
8,4
20
M00008/OS200_250_01_04 H

J
G N 10 I F 10
K
10 10 10 10 10 10 J 11 11 11 11
K
M5 E 8,4 8,4 8,4 8,4 8,4 8,4 8,4 8,4 K 11,5 11,5 11,5 11,5
L
L H J
8,6 8,6 *) OS_N3: 8,6 8,6 8,6 8,6 8,6 8,6 L 4 4 4 4
33,5
M 164,5* ) 164,5 164,5 164,5 164,5 164,5 164,5
A2 B2 164,5 M 162 162 162 162
A1 60,5 60,5 104 104 147,5 147,5 191 191 A1 C270,5 124,5 178,5 232,5
72
B1 79,5 79,5 123 123 166,5 166,5 210 210 B1 89,5 143,5 197,5 251,5

144 C1 96,5 96,5 M 140 140 183,5 183,5 227 227 C1 106,5 160,5 214,5 268,5
144 138,5 108

10,5
*) A1 B1 C1
8,6
8,4
N F
E
H *) OS_N3:

OS200 OS250
[mm] D11 B11 D12 B12 D13 B13 D22 B22 [mm] D11 D12 D13 D22
A 149 130 149 130 141 130 149 130 A 154 154 154 154
B 199 199 199 199 199 199 199 199 B 193 193 193 193
C 36,5 36,5 36,3 36,5 36,5 36,5 36,5 36,5 C 33,5 33,5 33,5 33,5
D 144,5 144,5 144,5 144,5 144,5 144,5 144,5 144,5 D 148,5 148,5 148,5 148,5
E 92 92 92 92 92 92 135,5 135,5 E 112,5 112,5 112,5 161
F 43,5 43,5 43,5 43,5 43,5 43,5 43,5 43,5 F 54 54 54 54
G 20 20 20 20 20 20 20 20 G 25 25 25 25
H 132 132 175,5 175,5 219 219 219 219 H 152 206 260 260
I 40 40 40 40 40 40 40 40 I 45 45 45 45
J OS200 10 10 10 10 10 10 10 10 OS250
J 11 11 11 11
K [mm] 8,4 D11 8,4B11 8,4D12 B12
8,4 D13
8,4 B13
8,4 D22
8,4 B22
8,4 [mm]
K D11
11,5 D12
11,5 D13
11,5 D22
11,5
A 149 130 149 130 141 130 149 130 A 154 154 154 154
L 8,6 8,6 8,6 8,6 8,6 8,6 8,6 8,6 L 4 4 4 4
M00014/OS200_250_11_22 K

B 199 199 199 199 199 199 199 199 B 193 193 193 193
M 165 165 165 165 165 165 165 165 M 162 162 162 162
C 36,5 36,5 36,3 36,5 36,5 36,5 36,5 36,5 C 33,5 33,5 33,5 33,5
N 80 80 80 80 80 80 80 80 N 90 90 90 90
D 144,5 144,5 144,5 144,5 144,5 144,5 144,5 144,5 D 148,5 148,5 148,5 148,5
A1 104 104 147,5 147,5 191 191 191 191 A1 124 178 232 232
E 92 92 92 92 92 92 135,5 135,5 E 112,5 112,5 112,5 161
A2 52 52 52 52 52 52 95,5 95,5 A2 62 62 62 116
F 43,5 43,5 43,5 43,5 43,5 43,5 43,5 43,5 F 54 54 54 54
B1 123 123 166,5 166,5 210 210 210 210 B1 143 197 251 251
G 20 20 20 20 20 20 20 20 G 25 25 25 25
B2 61,5 61,5 61,5 61,5 61,5 61,5 105 105 B2 71,5 71,5 71,5 125,5
H 132 132 175,5 175,5 219 219 219 219 H 152 206 260 260
C1 I 140 40 140 40 183,5 40 183,5 40 22740 227
40 227
40 227
40 IC1 160
45 214
45 268
45 45268
C2 J 70 10 70 10 70 10 70 10 7010 70
10 113,5
10 113,5
10 JC2 80
11 1180 11 80 11134
K 8,4 8,4 8,4 8,4 8,4 8,4 8,4 8,4 K 11,5 11,5 11,5 11,5
L 8,6 8,6 8,6 8,6 8,6 8,6 8,6 8,6 L 4 4 4 4
0_250_11_22 K

74 MDimension
165 165
drawings 165
| Switch 165
fuses OS 165 165
and OSM 165 165 M 162 162 162 162
N 80 80 80 80 80 80 80 80 N 90 90 90 90
A1 104 104 147,5 147,5 191 191 191 191 A1 124 178 232 232
A2 52 52 52 52 52 52 95,5 95,5 A2 62 62 62 116
Dimension drawings, IEC
Front operated switch fuses

OS315_P and OS400_P


Mechanism at the end of the switch fuse
64 81

28 58,5
50,3/125,4 43,5 5
11,5 7,5 10,8 64 81
M5 12 45
28 58,5 40
3/16 50,3/125,4 43,5 5
11,5 7,5 10,8
17 26 35
M5 12 45
82 40
3/16
193 C
140 164 17 159 26 35
230 128
82
193 95 C
140 164 159
230 A1 B1 128 C1

min 20 95
75,5 64 25
B
A A1 B1 C1
230...325 (OXP 12 x 250)
min 20
75,5 64 25
B
A 230...325 (OXP 12 x 250)

OS315 OS400
[mm] B01 B02 B03 B04 [mm] B01 B02 B03 B04 D01 D02 D03 D04
A

A 127 191 255 319 A 127 191 255 319 127 191 255 319
C000014 /OS315_400_001_04

B OS315176 176 176 176 B OS400176 176 176 176 193 193 193 193
C [mm] 194 B01 194 B02 194 B03 194 B04 C [mm] 194 B01 194 B02 194 B03 194 B04 166 D01 166 D02 166 D03 166 D04
A

A 127 191 255 319 A 127 191 255 319 127 191 255 319
C000014 /OS315_400_001_04

B
OS315 176 176 176 176 OS400
B 176 176 176 176 193 193 193 193
[mm]C B01 194 B02 194 B03 194 B04 194 [mm]CB01/D01 194 B02/D02 194 B03/D03 194 B04/D04 194 166 166 166 166
A1 98,5 162,5 226,5 290,5 A1 98,5 162,5 226,5 290,5
B1 OS315
116,5 180,5 244,5 308,5 B1 OS400
116,5 180,5 244,5 308,5
C1 [mm]134,5 B01 198,5 B02 262,5 B03 326,5 B04 C1 [mm]134,5
B01/D01 198,5
B02/D02 262,5
B03/D03 326,5
B04/D04
A1 98,5 162,5 226,5 290,5 A1 98,5 162,5 226,5 290,5
B1 116,5 180,5 244,5 308,5 B1 116,5 180,5 244,5 308,5
C1 134,5 198,5 262,5 326,5 C1 134,5 198,5 262,5 326,5

64
58,5
Mechanism between
2,30 the2,52
poles
43,5 5
25 0,20
7,5 64
10,8 55,8/130,9 1,71
0,98 58,5
0,30 2,52 2,20/5,15
0,43 12 45
M5 2,30 40
3/16 43,5 5 0,47 1,77
25 1,57
7,5 55,8/130,9 1,71 0,20
0,98 *0,30
) 10,8
0,43 2,20/5,15 A2 B2 C2
M5 12 45
40
5 0,47 1,77
3/16 1,57 B
0,20
*) 193 164 A2 159 B2 128 C2
7,60 6,46 6,26 5,04
230 5
9,06 0,20 95 B
3,74
193 164 159 128
7,60 A1 B1 C1
6,46 6,26 5,04
* )
230
95
11,5 9,06 min 20
0,45 0,79 3,74
117 64 A C1
A1 B1
4,61 2,52
*C) 230...325
11,5 D *) OS_N3 min 12x250)
9,06...12,80 (OXP 20
0,45 0,79
117 64 A
4,61 2,52 230...325
C *)
D OS_N3 9,06...12,80 (OXP 12x250)

OS315-400 OS400
[mm] B11 B12 B13 B21 B22 [mm] D11 D12 D13 D21 D22
A 176 176 176 176 176 A 193 193 193 193 193
B
OS315-400194 194 194 194 194 B
OS400 166 166 166 166 166
C
[mm] 140
B11 140
B12 140
B13 204
B21 204
B22 C
[mm] 140
D11 140
D12 140
D13 204
D21 204
D22
AD 190
176 254
176 318
176 254
176 318
176 AD 190
193 254
193 318
193 254
193 318
193
B

B 194 194 194 194 194 B 166 166 166 166 166
C000011/OS315-400_11_22

OS315
C 140 140 140 204 204 OS400
C 140 140 140 204 204
[mm]
D B11
190 B12
254 B21
318 B22
254 B13
318 [mm]
D B11/D11
190 B12/D12
254 B21/D21
318 254B22/D22 318B13/D13
B

A1 163 227 227 291 291 A1 163 227 227 291 291
C000011/OS315-400_11_22

A2
OS315 81,5 81,5 145,5 145,5 81,5 A2
OS400 81,5 81,5 145,5 145,5 81,5
B1
[mm] 181
B11 245
B12 245
B21 309
B22 309
B13 B1
[mm] 181
B11/D11 245
B12/D12 245
B21/D21 309
B22/D22 309
B13/D13
B2
A1 90,5
163 90,5
227 154,5
227 154,5
291 90,5
291 B2
A1 90,5
163 90,5
227 154,5
227 154,5
291 90,5
291
C1
A2 199
81,5 263
81,5 263
145,5 327
145,5 327
81,5 C1
A2 199
81,5 263
81,5 263
145,5 327
145,5 327
81,5
C2
B1 99,5
181 99,5
245 163,5
245 163,5
309 99,5
309 C2
B1 99,5
181 99,5
245 163,5
245 163,5
309 99,5
309
B2 90,5 90,5 154,5 154,5 90,5 B2 90,5 90,5 154,5 154,5 90,5
C1 199 263 263 327 327 C1 199 263 263 327 327
C2 99,5 99,5 163,5 163,5 99,5 C2 99,5 99,5 163,5 163,5 Switch
99,5 fuses OS and OSM | Dimension drawings 75
Dimension drawings, IEC
Front operated switch fuses

OS 630_P
39 and
13.5 OS 800_P
39 142/67 6
Mechanism
OS_N3 at the end of the switch fuse
6
M8 20 48.4
50
36.5 12
39 13.5 39 5 142/67 6 45 36
OS_N3
6
M8
ON
20 48.4
230 254 266 306 50
232 223.3 176
ON ON

ON

OFF
OFF OFF

T OFF T T

12
T

36.5
5 min 20 45 36
145
ON
B C D
230 254 266 306 13 232 223.3 176
ON ON

ON

OFF
OFF OFF

T OFF T T

77.5 88 233
min 20
256...379 145
95 (OXP 12X280)
A B C D
13
77.5 88 233
256...379
95 (OXP 12X280)
M00097/OS600-800_01-04 A / KE00041

OS630-800
M00097/OS600-800_01-04 A / KE00041

[mm] D/B01 D/B02 D/B03 D/B04


A 167 255 343 431
B 120 208 296 384
C 150 238 326 414
OS630-800
D 176 264 352 440
[mm] D/B01 D/B02 D/B03 D/B04
A 167 255 343 431
B 120 208 296 384
C 150 238 326 414
D 176 264 352 440

Mechanism
OS_N3
between
39
the poles
39 142/67 6
13.5 20
6
M8 48.4
OS_N3 39 39 142/67 50
6
13.5 20 12
6
M8 5 48.4 45 36
50
ON 12
230 254 266 5306 45 36 232 223.3 176
ON ON
ON

OFF OFF OFF


OFF T T

T T

ON
min 20
230 254 266 306 145 232 ON

223.3
ON

176
ON

C D
OFF

B
OFF OFF
OFF T T

T T

13 min 20
233 145
77.5 77.5 88 53 B C D
256...379
102.5 (OXP
13 12X280)
A 233
77.5 77.5 88 53
256...379
102.5 (OXP 12X280)
A

A
KE00042 / M00100/OS600-800_11-22
KE00042 / M00100/OS600-800_11-22 A

OS630-800
[mm] D/B11 D/B12 D/B13 D/B22
A 253 341 429 429
OS630-800
B 205 293 381 381
[mm] D/B11 D/B12 D/B13 D/B22
C 235 323 411 411
A 253 341 429 429
D 261 349 437 437
B 205 293 381 381
C 235 323 411 411
D 261 349 437 437

76 Dimension drawings | Switch fuses OS and OSM


Dimension drawings, IEC 164,5
Front operated switch fuses
mm 6,48
in 42
1,65
110 108
4,25
4,33
53 50 175
1,97
M8 2,01 6,89 93
5/16 *) 3,66 58
2,28
28 43 56
6 1,10 1,69 2,20
346 0,24 12
13,62 0,47
240 287 266 257,5 210
9,45 11,30 10,47 10,14 8,27
min 40
0,79
OS1200...1250_P 274
10,79 A1 B1 C1
45 6
Mechanism *)at the end of the switch fuse 1,77 0,24
13,5
0,53 12
22,5 0,47 54
0,89 98,5 110 50 132 2,13
mm11 3,88 4,33 1,97 164,5
5,20 14
in 0,43 42 126,5 6,48 0,55 70
294
1,65 4,98 11,57 2,76 13,5
110 108 0,53
A 4,25 366...475 80
4,33
50 *) N3- types 14,41...18,70(OXP 12 X 395) 3,15
53 1,97 175
M8 2,01 6,89 93

OS1250D/B_
5/16 *) 3,66 58
2,28
28 356 43 56
6 1,10 1,69 2,20
346 0,24 12 14,02
13,62 0,47
240 287 266 257,5 210
9,45 11,30 10,47 10,14 8,27
min 40
0,79
11
22,5 0,43
274 0,89 A1 B1 C1
45 10,79
*) 1,77 6
13,5 0,24
0,53 12
22,5 0,47 54
0,89 98,5 110 50 132 2,13
11 3,88 4,33 1,97 5,20 14
0,43 126,5 294 0,55 70
4,98 11,57 2,76 13,5
A 80
0,53
366...475
mm
*) N3- types 164,514,41...18,70(OXP 12 X 395) 3,15
in 6,48
OS1250D/B_
M00207/OS1200-1250_01-04 C

13,5 50 110
20 1,97 22,5 50 12
0,54
OS1200/1250 1,97 4,33 0,47
0,79 0,89 6 45
[mm] 13,5
D/B01 D/B02 0,24
D/B03 1,77
175 D/B04
0,53 6,89 356
A 209 319 429 539
93 14,02
A1 *) 166 276 386 3,66
496 58
M8 2,28
5/16
B1 196 306
11
416 526
C1 222 332 0,43
442 552 138 153 166
12 5,44 6,03 6,54
0,47 11
346 287 22,5 0,43
13,62 11,30 0,89
min 40
0,79 266 257,5 210
10,47 10,14 8,27

274
10,79
6
*) 37,5 0,24
A1 B1 C1
1,48 54
39,5 98,5 110 132
Mechanism
1,56 between
3,88 the 4,33
poles 5,20 14
0,55
2,13
197 294
7,76 70
11,57
M00207/OS1200-1250_01-04 C

A 164,5 2,76 *) N3- types


mm 6,48
371...480 80
in
OS1200/1250
14,61...18,91 (OXP 12 X 395) 3,15 13,5
[mm] 13,5 50
D/B01 D/B0250 D/B03 110
D/B04
20 0,54 1,97 22,5 4,33 12 0,53
A 0,79 209 0,89 3191,97 6 429 45
539 0,47
13,5 0,24 175 496 1,77
A1 0,53166 276 386 6,89
OS1250D/B_

B1 196 306 416 93


526
*) 3,66 58
C1
M8 222 332 442 552 2,28
5/16 11
0,43 138 356
153
14,02 166
12 5,44 6,03 6,54
0,47
346 287
13,62 11,30
min 40
0,79 266 257,5 210
10,47 10,14 8,27
22,5 11
274 0,89 0,43
10,79
6
*) 37,5 0,24
A1 B1 C1
1,48 54
39,5 98,5 110 132
1,56 3,88 4,33 5,20 14 2,13
197 0,55
7,76 294 70
11,57
A 2,76 *) N3- types
371...480 80
14,61...18,91 (OXP 12 X 395) 3,15 13,5
0,53
M00208/OS1200-1250_11-22 C

OS1250D/B_

OS1200/1250
[mm] D/B11 D/B12 D/B13 D/B22
A 322 432 542 542
A1 276 386 496 496 356
B1 306 416 526 526 14,02
C1 322 442 552 552

22,5 11
0,89 0,43

Switch fuses OS and OSM | Dimension drawings 77


Dimension drawings, UL/CSA
Front operated switch fuses

OS60...100GJ_
mm 138...205 (OXP 6x161)
in Mechanism 33,4 of the switch fuse 45
53,3/2,10at the end1,31 5,35...8,07 1,77
17,5 81/3,19
0,69 20
mm 138...205 (OXP 6x161)
in 53,3/2,10 8,5 33,40,79 69/2,725,35...8,07
45
95,5 0,33 1,31 60/2,36 1,77
11
3,76 17,5 0,43 81/3,19 2,5
0,69 20 0,10
46 8,5 0,79
1,81 0,33 60/2,36 69/2,72
95,5 11
3,76 0,43 6
2,5 10 A1 17,5 B1 25 C1
220 36 0,24
0,10 0,39 0,69 0,98
8,66 1,42 125,5
46 4,94
1,81 ON
OFF

172 138,5 10 A1 B1 C1
6 114 17,5
110 8425
O
T

6,77
ON ON ON

220 0,24 5,45 0,39


4,49 0,69
4,33 0,98

OFF

OFF

OFF
36 3,31
O O O

65 125,5
T T T

8,66 1,42
ON 2,56 4,94
OFF

O
17238 138,5 114 110 84
M5
T

6,77
ON ON ON

1,50 5,45 4,49 4,33

OFF

OFF

OFF
3,31
O O O
T T T

min 14 65
0,55 2,56
46 35 38
M5 1,50
1,81 1,38 104,5/4,11 min 14
A
0,55
46 35
1,81 1,38 104,5/4,11
A
B

OS60GJ OS100GJ
M00291/OS100GJ01-04

[mm/in] J01 J02 J03 J04 [mm/in] J01 J02 J03 J04
A 74,5/2,93 109,5/4,31 144,5/5,69 179,5/7,07 A 76,5/3,01 111,5/4,39 146,5/5,77 181,5/7,15
B

B OS60GJ
118/4,65 118/4,65 118/4,65 A1 OS100GJ
55/2,17
118/4,65 90/3,54 125/4,92 160/6,30
M00291/OS100GJ01-04

C [mm/in] -J01 35/1,38J02 35/1,38J03 35/1,38J04 B1 [mm/in]


70/2,76J01 105/4,13J02 140/5,51J03 175/6,89J04
D A 45,5/1,79
74,5/2,93 45,5/1,79
109,5/4,31 45,5/1,79 179,5/7,07 C1 A 85/3,35
144,5/5,69 45,5/1,79 76,5/3,01 120/4,72
111,5/4,39 155/6,10
146,5/5,77 190/7,48
181,5/7,15
E B 36/1,41
118/4,65 36/1,41
118/4,65 36/1,41
118/4,65 36/1,41
118/4,65 A1 55/2,17 90/3,54 125/4,92 160/6,30
A1 C 51/2,01 - 86/3,39
35/1,38 121/4,76
35/1,38 156/6,14
35/1,38 B1 70/2,76 105/4,13 140/5,51 175/6,89
B1 D 81/3,19
45,5/1,79 116/4,57
45,5/1,79 151/5,94
45,5/1,79 186/7,32
45,5/1,79 C1 85/3,35 120/4,72 155/6,10 190/7,48
E 36/1,41 36/1,41 36/1,41 36/1,41
A1 51/2,01 86/3,39 121/4,76 156/6,14
B1 81/3,19 116/4,57 151/5,94 186/7,32
mm 138...205 (OXP 6x161)
in 5,35...8,07
33,4
Mechanism between the 1,31poles 81/3,19
8,5 20 60 69/2,72
36 0,79
95,5
mm 0,33 1,42 2,36 138...205 (OXP 6x161)
in
3,76 11 2,5
5,35...8,07
33,4
0,43 0,10
1,31 81/3,19
46 38
4,81 8,5 20 60 1,50
69/2,72
36 0,79 A2 B2 C2
95,5 0,33 1,42 220 2,36
3,76 6
11 8,66 36 2,5
0,24
1,42 0,10 125,5
0,43 4,94
46
ON

172 38 114 110 84


OFF

ON ON ON

4,81 1,50 138,5


OFF

OFF

OFF

6,77 4,49 3,31


O

4,33
O O

A2 B2 C2
T T T
T

5,45
220 6 65
8,66 36 0,24 2,56 125,5
1,42
4,94
ON

172 114 A1 B1 84 C1
M5 110
OFF

ON ON ON

138,5
OFF

OFF

OFF

6,77 4,49 3,31


O

4,33
O O
T T T
T

71,5 min 14 5,45


2,81 0,55 65
2,56
B 35 104,5/4,11
A
1,38 A1 B1 C1
M5
71,5 min 14
2,81 0,55
B 35 104,5/4,11
1,38
A

OS60GJ OS100GJ
[mm/in] J11 J12 J13 J22 [mm/in] J11 J12 J13 J22
A 112,5/4,43 148/5,82 182,5/7,19 182,5/7,19 A 113/4,45 148/5,83 183/7,20 183/7,20
B 118/4,65 118/4,65 118/4,65 118/4,65 B 81/3,19 81/3,19 81/3,19 116/4,57
C OS60GJ - 35/1,38 35/1,38 35/1,38 A1 OS100GJ
90/3,54 125/4,92 160/6,30 160/6,30
D [mm/in]
71,5/2,81J11 71,5/2,81J12 71,5/2,81J13 71,5/2,81J22 A2 [mm/in]
45/1,77J11 45/1,77J12 45/1,77J13 80/3,15J22
E A 112,5/4,43
36/1,41 36/1,41
148/5,82 36/1,41
182,5/7,19 36/1,41
182,5/7,19 B1 A 105/4,13
113/4,45 140/5,51
148/5,83 175/6,89
183/7,20 175/6,89
183/7,20
B

F B 55,5/2,19
118/4,65 55,5/2,19
118/4,65 55,5/2,19
118/4,65 90,5/3,56
118/4,65 B2 B 52,5/2,07
81/3,19 52,5/2,07
81/3,19 52,5/2,07
81/3,19 160/3,44
116/4,57
M00292/OS100GJ11-22

G C 91,5/3,6 - 91,5/3,6
35/1,38 91,5/3,6
35/1,38 126,5/4,98
35/1,38 C1 A1120/4,72
90/3,54 155/6,10
125/4,92 190/7,48
160/6,30 190/7,48
160/6,30
A1 D 81,5/3,21
71,5/2,81 116,5/4,59
71,5/2,81 151,5/5,96
71,5/2,81 151,5/5,96
71,5/2,81 C2 A2 60/2,36
45/1,77 60/2,36
45/1,77 60/2,36
45/1,77 95/3,74
80/3,15
A2 E 40,5/1,59
36/1,41 40,5/1,59
36/1,41 40,5/1,59
36/1,41 75,5/2,97
36/1,41 B1 105/4,13 140/5,51 175/6,89 175/6,89
B

B1 F111,5/4,39
55,5/2,19 146,5/5,77
55,5/2,19 181,5/7,15
55,5/2,19 181,5/7,15
90,5/3,56 B2 52,5/2,07 52,5/2,07 52,5/2,07 160/3,44
M00292/OS100GJ11-22

B2 G 56/2,20
91,5/3,6 56/2,20
91,5/3,6 56/2,20
91,5/3,6 90,5/3,56
126,5/4,98 C1 120/4,72 155/6,10 190/7,48 190/7,48
A1 81,5/3,21 116,5/4,59 151,5/5,96 151,5/5,96 C2 60/2,36 60/2,36 60/2,36 95/3,74
A2 40,5/1,59 40,5/1,59 40,5/1,59 75,5/2,97
B1 111,5/4,39 146,5/5,77 181,5/7,15 181,5/7,15
78 B2Dimension
56/2,20 drawings
56/2,20 | Switch fuses90,5/3,56
56/2,20 OS and OSM
Dimension drawings, UL/CSA
Front operated switch fuses

OS200J 75
2,95
20 40
Mechanism at the end of the switch fuse 0,79 1,57
110/46
8,6 40,5 3
M5 20 0,34 8,4 4,33/1,81
1,59 0,12
3/16 0,79 0,33
75 6 45
10,5 36,5 2,95 0,24 1,77
0,43 20 40 1,44
)
*0,79 1,57 8,5 18 26,5
8,6 110/46
M5 8,4 4,33/1,81 40,5 3 0,34 0,71 1,04
20 0,34 5,5 1,59 0,12
72 3/16 0,79 0,33
2,83 0,22 6 45
0,24 1,77 159 144
126 10,5 164,5 36,5 6,26 138,5 108
4,96 0,43 6,48 198,5 1,44 5,67 4,25
5,45 18
*) 218 7,82
65
8,5 26,5
8,59 2,56 0,34 0,71 1,04
72 5,5
2,83 0,22
159 144 A1 B1 C1
126
8,4/0,33 164,5 138,5 108
33,5/1,32 4,96
*) 6,48 198,5
6,26
5,67 4,25
218 7,82 14 min 5,45
10 65
8,6/0,34 0,40 8,59 0,55
48,5 46 20 2,56
132
1,91 1,81 0,79 5,20
8,4/0,33 A *) OS_N3: A1 B1 C1
33,5/1,32
*) 189...254
7,44...10 (OXP 6X210)
14 min
10
8,6/0,34 0,40 0,55
48,5 46 20
132
1,91 1,81 0,79 5,20
A *) OS_N3: 189...254
7,44...10 (OXP 6X210)

OS200
M00001/OS200J01_04 H

[mm/in] J01 J02 J03 J04


A 89,5 / 3,52 135,5/5,34 181,5/7,15 227,5/8,96
A1 60,5 / 2,38 106,5/4,19 152,5/6,00 198,5/7,82
B1 OS200
79,5 / 3,13 125,5/4,94
217,5/8,56 171,5/6,75
M00001/OS200J01_04 H

C1 [mm/in]
96,5 / 3,80 J01
142,5 / 5,61 J02 188,5/7,42 J03234,5/9,23 J04
A 89,5 / 3,52 135,5/5,34 181,5/7,15 227,5/8,96
A1 60,5 / 2,38 106,5/4,19 152,5/6,00 198,5/7,82
B1 79,5 / 3,13 125,5/4,94 171,5/6,75 217,5/8,56
C1 96,5 / 3,80 142,5 / 5,61 188,5/7,42 234,5/9,23

81
OS400J 3,19
28 58,5
Mechanism
1,10 2,30
at the end
10,8 of the switch fuse 43,5
5
55,8/130,9
0,43 1,71 0,20
81
11,5 2,20/5,15
7,5
M5 0,45 0,30 3,19 12 45
58,5 40
3/16 28 0,47 1,77
1,10 2,30 10,8 43,5 1,565
55,8/130,9 26
*) 11,5 0,43 1,71 0,20 17 35
2,20/5,15 1,02
7,5 0,67 1,38
M5
82 5 12 45
0,45 0,30 40
3,23
3/16 0,20 0,47 1,77
1,56 C
193
17 159 26 128 35
140 *) 7,60 230 164
5,51 9,06 5 6,46 0,67 6,26 1,02 5,04 1,38
82
3,23 0,20 95
3,74 C
193
140 7,60 230 164 159 128
5,51 *) A1 6,26 B1 5,04 C1
9,06 min 20 6,46
0,79 95
3,74
B
75,5 64 25
*)
2,97 2,52 0,98 230...325 (OXP 12x250) A1 B1 C1
min 20
9,06...12,80
A *) OS_N3 0,79
B
75,5 64 25
2,97 2,52 0,98 230...325 (OXP 12x250)
9,06...12,80
A *) OS_N3
B
C000012 /OS315_400_01_04

OS400
B

[mm/in] J01 J02 J03 J04


C000012 /OS315_400_01_04

A 127/5,00 191/7,52 255/10,04 319/12,56


B 176/6,93 176/6,93 176/6,93 176/6,93
OS400
C 194/7,64 194/7,64 194/7,64 194/7,64
[mm/in] J01 J02 J03 J04
A 127/5,00 191/7,52 255/10,04 319/12,56
B 176/6,93 176/6,93 176/6,93 176/6,93
C 194/7,64 194/7,64 194/7,64 194/7,64

Switch fuses OS and OSM | Dimension drawings 79


Dimension drawings, UL/CSA
Front operated switch fuses

OS600J and OS800L


13,5 142/67
Mechanism
39
6
at the end of
0,53 39 the switch fuse
5,60/2,64
6
0,24
1,54 0,24 1,54
OS_N3 20
M8 0,79 48,4 50
5/16 1,91 1,97
39 13,5 142/67 6 12
36,5 39
1,44 6
1,54 0,24 0,53
1,54 55,60/2,64 0,24 0,47
45 36
OS_N3 20 0,20
M8 230 48,4 50 1,77 1,42
0,79 9,06
5/16 306 1,91 1,97
254 12,05
10 12
36,5 0,47
1,44 266 5 45 36
10,47 0,20 232 223,3 176
230 min 20 1,77 1,42
9,06 306 0,79 145 9,13 8,80 6,93
5,71
254 12,05
10
266 13
10,47 0,51 232 B 223,3 C 176 D
233 min 20
77,5 88 9,17 0,79 145 9,13 8,80 6,93
3,05 3,46 256...379 5,71
95 10,08...14,92 (OXP 12X280)
3,74 A 13
0,51 B C D
233
77,5 88 9,17
3,05 3,46 256...379
95 10,08...14,92 (OXP 12X280)
3,74 A
M00097 / OS 600-800_01-04 B

OS600-800
[mm/in] J/L01 J/L02 J/L03 J/L04
A 167/6,57 255/10,04 343/13,50 431/16,97
M00097 / OS 600-800_01-04 B

B 120/4,72 208/8,19 296/11,65 384/15,12


OS600-800
C 150/5,91 238/9,37 326/12,83 414/16,30
[mm/in] J/L01 J/L02 J/L03 J/L04
D 176/6,93 264/10,39 352/13,86 440/17,32
A 167/6,57 255/10,04 343/13,50 431/16,97
B 120/4,72 208/8,19 296/11,65 384/15,12
C 150/5,91 238/9,37 326/12,83 414/16,30
D 176/6,93 264/10,39 352/13,86 440/17,32 164,5
42 6,48
1,65
110 108
4,25
4,33
53 50 175
1,97
M8 2,01 6,89 93
5/16 *) 3,66 58
2,28
28 43 56
6 1,10 1,69 2,20
346 0,24 12
13,62 0,47
240 287 266 257,5 210
11,30
OS1200L
9,45
min 40
10,47 10,14 8,27

0,79
164,5
42 6,48 274 A1 B1 C1
45 10,79
1,65 1,77 6
*)
110 108
0,24
13,5 4,25
0,53 12
4,33
22,5 0,47 54
0,89 53 50
98,5 110 50 175
1,97
3,88 132 2,13
13,5
4,33 1,97
M811 2,01 6,89 93
5,20 14
0,55 70 0,53
0,43
5/16 126,5
*) 3,66 294 58
4,98 11,57
2,28 2,76
A 366...475 80
28 43 56
*) N3- types 6 14,41...18,70(OXP 12 X 395) 3,15 1,10 1,69 2,20
346 0,24 12
OS1200L_

13,62 0,47
240 287 266 257,5 210
9,45 11,30 10,47 10,14 8,27
min 40
0,79 426
16,77
274 A1 B1 C1
45 10,79
*) 1,77 6
13,5 0,24
0,53 12 37,5
22,5 0,47 54
0,89 98,5 110 50 1,48
3,88 4,33 1,97
132
14
2,13
13,5 11
0,53 0,43
11 5,20
0,43 126,5 294 0,55 70 20
4,98 11,57 2,76 0,79
A 80
6
366...475 0,24
*) N3- types 14,41...18,70(OXP 12 X 395) 3,15
OS1200L_

426
16,77
M00207/OS1200-1250_01-04 C

OS1200/1250
[mm/in] L01 L02 L03 L04 37,5
1,48
A 209/8,23 319/12,56 429/16,89 539/21,22 11
A1 166/6,54 276/10,87 386/15,20 496/19,53 0,43
20
B1 196/7,72 306/12,05 416/16,38 526/20,71 0,79
C1 222/8,74 332/13,07 442/17,40 552/21,73
6
0,24

80 Dimension drawings | Switch fuses OS and OSM


04 C
Dimension drawings, IEC
Front operated switch fuses with direct mount handles

OS32G_K...OS63G_K
47,5
E
47,5 37
17,5
10
E 37
17,5
25
57 10
100
ON
ON 25 ON

57 114 84
112
OFF

OFF

OFF
O O
O

100
T T

100 ON

114
ON

84
ON

112
OFF

OFF

OFF
65
O O
O T T

100 A1 B1
65
M5 C B A1 B1
165
M5 C A B 165
A

OS32-63G_K OS32-63G_K
M00389/OS32-63G_01-04K A

[mm] D01 D02 D03 D04 [mm] B/F01 B/F02 B/F03 B/F04
A OS32-63G_K
64,5 88 111,5 135,5 A OS32-63G_K
64,5 88 111,5 135,5
M00389/OS32-63G_01-04K A

B [mm] 40D01 40D02 40D03 40D04 B [mm] B/F01


40 B/F02
40 B/F03
40 B/F04
40
C A 64,5
- 23,5 88 111,5
23,5 135,5 C A
23,5 64,5
- 23,5 88 111,5
23,5 135,5
23,5
E B 30 40 30 40 30 40 30 40 E B 30 40 30 40 30 40 30 40
A1 C 45 - 23,5
68,5 23,5
92 23,5 A1 C
111,5 45 - 23,5
68,5 23,5
92 23,5
111,5
B1 E 75 30 98,5 30 122 30 145,5 30 B1 E 75 30 98,5 30 122 30 145,5 30
A1 45 68,5 92 111,5 A1 45 68,5 92 111,5
B1 75 98,5 122 145,5 B1 75 98,5 122 145,5

OS100G_K...OS160G_K
33,4 81
95,5 53,3 20
17,5 8,5 7,2 38 37
33,4 5,5 2,5
81
43
95,5 53,3 20 10 17,5 25
17,5 8,5 7,2 38 37
5,5 2,5
43 B
ON
10 17,5 25
114,5
ON ON ON

114 110 84
OFF

OFF
OFF

OFF

O O O O
T T T
T

ON
140 65 B
M5 114,5 114
ON

110
ON

84
ON
OFF

OFF
OFF

OFF

O O O O
T T T
T
A1 B1 C1
140 65
M5 46 35
165
A1 B1 C1
A
46 35
165
A
A
M00390/OS100-160G_01-04K

OS100-160G_K OS100-160G_K
[mm] D/F01 D/F02 D/F03 D/F04 [mm] B01 B02 B03 B04
A 76,5 111,5 146,5 181,5 A 76,5 111,5 146,5 181,5
A

B OS100-160G_K
100 100 100 100 B OS100-160G_K
118 118 118 118
M00390/OS100-160G_01-04K

A1 [mm] 55
D/F01 90
D/F02 125
D/F03 160
D/F04 A1 [mm] 55B01 90B02 125B03 160B04
B1 A 7076,5 105
111,5 140
146,5 175
181,5 B1 A 7076,5 105
111,5 140
146,5 175
181,5
C1 B 85100 120100 155100 190100 C1 B 85118 120118 155118 190118
A1 55 90 125 160 A1 55 90 125 160
B1 70 105 140 175 B1 70 105 140 175
C1 85 120 155 190 C1 85 120 155 190

Switch fuses OS and OSM | Dimension drawings 81


Dimension drawings, IEC
Front operated switch fuses with direct mount handles

OS200_K and OS250_K


75 8,5
OS200K
20 K D 3 [mm] D01/B01 D02/B02 D03/B03 D04/B04
A1
M A1 144 144 144 144
N E A2 60,5 104 147,5 191
L
B1 138,5 138,5 138,5 138,5
A2
B2 79,5 123 166,5 210
C1 108 108 108 108 18
72 F
C2 96,5 140 183,5 227
126 C
O
65 OS250K B1
[mm] D01 D02 D03 D04
A1 144 144 144 144
A2 70,5 124,5 178,5 232,5 B2

A B1 138,5 138,5 138,5 138,5 26,5


G H I B B2 89,5 143,5 197,5 251,5
J
C1 108 108 108 108
C2 106,5 106,5 214,5 268,5 C1

OS200_K OS250_K C2
[mm] D01 B01 D02 B02 D03 B03 D04 B04 [mm] D01/B01 D02/B02 D03/B03 D04/B04
A 154 130 154 130 154 130 154 130 A 154 154 154 154
B 191 167 191 167 191 167 191 167 B 191 191 191 191
C 198,5 198,5 198,5 198,5 198,5 198,5 198,5 198,5 C 193 193 193 193
D 40,5 40,5 40,5 40,5 40,5 40,5 40,5 40,5 D 40,5 40,5 40,5 40,5
E 36,5 36,5 36,5 36,5 36,5 36,5 36,5 36,5 E 33,5 33,5 33,5 33,5
F 144,5 144,5 144,5 144,5 144,5 144,5 144,5 144,5 F 148,5 148,5 148,5 148,5
G 48,5 48,5 48,5 48,5 48,5 48,5 48,5 48,5 G 53,5 53,5 53,5 53,5
H - - 43,5 43,5 43,5 43,5 43,5 43,5 H - 54 54 54
M00080/OS 200_250_01_04K C

I 20 20 20 20 20 20 20 20 I 25 25 25 25
J 89,5 89,5 133 133 176,5 176,5 220 220 J 99,5 153,5 207,5 261,5
K 40 40 40 40 40 40 40 40 K 45 45 45 45
L 10 10 10 10 10 10 10 10 L 11 11 11 11
M 8,5 8,5 8,5 8,5 8,5 8,5 8,5 8,5 M 11,5 11,5 11,5 11,5
N 8,5 8,5 8,5 8,5 8,5 8,5 8,5 8,5 N 4 4 4 4
O 164,5 164,5 164,5 164,5 164,5 164,5 164,5 164,5 O 162 162 162 162

OS315_K and OS400_K

OS315,OS400 OS400
[mm] B01K
OS315,OS400 B02K B03K B04K [mm]
OS400 D01K D02K D03K D04K
B

A 127 191 255 319 A 127 191 255 319


315-400_01_04K

[mm] B01K B02K B03K B04K [mm] D01K D02K D03K D04K
B

B
A 176
127 176
191 176
255 176
319 B
A 193
127 193
191 193
255 193
319
315-400_01_04K

C
B 194
176 194
176 194
176 194
176 C
B 166
193 166
193 166
193 166
193
D
C 219
194 219
194 219
194 219
194 D
C 236
166 236
166 236
166 236
166
A1
D 98,5
219 162,5
219 226,5
219 290,5
219 A1
D 98,5
236 162,5
236 226,5
236 290,5
236
M00081/OS

B1
A1 116,5
98,5 180,5
162,5 244,5
226,5 308,5
290,5 B1
A1 116,5
98,5 180,5
162,5 244,5
226,5 308,5
290,5
M00081/OS

C1
B1 134,5
116,5 198,5
180,5 262,5
244,5 326,5
308,5 C1
B1 134,5
116,5 198,5
180,5 262,5
244,5 326,5
308,5
C1 134,5 198,5 262,5 326,5 C1 134,5 198,5 262,5 326,5

82 Dimension drawings | Switch fuses OS and OSM


Dimension drawings, IEC
Front operated switch fuses with direct mount handles

OS 630_K and OS 800_K


A
M00229/OS600-800_01-04K
A

OS600-800
M00229/OS600-800_01-04K

[mm/in] D/B01 D/B02 D/B03 D/B04


OS600-800
A 167/6,57 255/10,04 343/13,50 431/16,97
[mm/in] D/B01 D/B02 D/B03 D/B04
B 120/4,72 208/8,19 296/11,65 384/15,12
A 167/6,57 255/10,04 343/13,50 431/16,97
C mm 150/5,91 238/9,37 326/12,83 414/16,30 164,5
B 120/4,72 208/8,19 296/11,65 384/15,12 6,48
D in 42 176/6,93 264/10,39 352/13,86 440/17,32
C 1,65 150/5,91 238/9,37 326/12,83 414/16,30
110 108
D 176/6,93 264/10,39 352/13,86 440/17,32 4,25
4,33 106
53 50 175
1,97
M8 2,01 6,89 93
5/16 *) 3,66 58
2,28
28 43 56
6 1,10 1,69 2,20
346 0,24
13,62
240 287 400 266 257,5 210
9,45 11,30 10,47 10,14 8,27

A1 B1 C1
45 6
*) 1,77 0,24
13,5
0,53 12
OS22,5
1200_K98,5
0,89 110 50
0,47 294
11,57
13,5
0,53
11 3,88 4,33 1,97 13,5
0,43 126,5 0,53
mm 4,98 164,5
in 42 A *) N3- types 6,48
1,65
110 108
4,25
4,33 106
53 50 175 426
2,01 1,97 356 16,77
M8 6,89 93 14,02
5/16 *) 3,66 58
2,28
28 43 56
6 1,10 1,69 37,5 2,20
346 0,24 1,48
13,62 11 11
22,5 0,43 0,43
240 287 400 266
0,89 257,5 210
11,30 10,47 10,14 20 8,27
9,45 0,79
OS1250D/B_ 6
0,24
B1
OS1200L_ C1
A1
45 6
*) 1,77 0,24
13,5
0,53 12
22,5 0,47 294 13,5
0,89 98,5 110 50 11,57 0,53
11 3,88 4,33 1,97 13,5
0,43 126,5 0,53
4,98
A *) N3- types
M00231 / OS1200-1250_01-04K A

OS1200/1250
356 426
[mm/in] L01 L02 L03 L04 14,02 16,77
A 209 / 8,23 319 / 12,56 429 / 16,89 539 / 21,22
A1 166 / 6,54 276 / 10,87 386 / 15,20 496 / 19,53
B1 196 / 7,72 306 / 12,05 416 / 16,38 526 / 20,71 37,5
C1 222 / 8,74 332 / 13,07 442 / 17,40 552 / 21,73 11 1,48
22,5 11
0,43 0,43
0,89 20
OS1250D/B_ 0,79
6
0,24
OS1200L_

Switch fuses OS and OSM | Dimension drawings 83


A
Dimension drawings, IEC and UL/CSA
Side operated switch fuses

OS Mini
OS 16...35FDS30_ OS 16...35FDS40_
OS 20...32FBS30_ OS 20...32FBS40_
OS 25...32FFS30_ OS 25...32FFS40_
EN 50022 * OS 30FA_S30_ * OS 30FA_S40_
OA 3G01 OA 3G01
45 OA 1G10 OSZ 4 OA4B1C OA 1G10 OSZ 4 OA4B1C
max 3+3 max 1+1 6 max 3+3 max 1+1 6
38 74
14...23 75...80
* 75...80
* *
I I
ON ON

O O
35 OFF 66 OFF 66
97
85
Test Test

* 65 * 65
*
4,5
31 9 4,5 35,6
9
108 14,3 30,8 27,6 14,3 30,8 27,6
110 33 106 33 142
120 129 164
154...166 45 189...201 45

55 55
A
M00222/OS16-35F_S

IEC 60269-2-1 BS88-2 BS88-6 OS20FBS40A1F OS20FBS40A1N1 IEC 60269-2-1 BS88-2 BS88-6
IEC 60269-3-1 IEC 60269-2-1 IEC 60269-2-1 OS32FBS40A1F OS32FBS40A1N1 IEC 60269-3-1 IEC 60269-2-1 IEC 60269-2-1
UL 198C OS20FBS30A1 OS32FBS30F1 OS25FFS4010F OS32FBS40F1N1 NFC63210,-63211 OS20FBS40A1 OS32FBS40F1
CSA C22.2 No.106 OS32FBS30A1 OS32FFS4014F OS25FFS4010N1 UL 198C OS32FBS40A1
NFC63210,-63211 OS32FBS30A2 OS16FDS4001F OS32FFS4014N1 OS32FBS40A2
OS25FFS3010 OS35FDS4002F OS16FDS4001N1
OS32FFS3014 OS30FAJS40F OS35FDS4002N1
OS30FAS30J OS30FACCS40F OS30FAJS40N1
OS30FAS30CC OS30FACCS40N1
OS16FDS3001
OS35FDS3002

OS 40 Mini

OS 40FDS30000 OS40FDS40000
EN 50022 OA 1G10
OA 3G01
OA 3G01 max 2+2+2+2 OA 3G01
50 OA 1G10 OSZ 4 OA4B1C OA 1G10 OSZ 4 OA4B1C 6
max 3+3 max 1+1 max 3+3 max 1+1
38 75...80 6 74 75...80
14...19 14...19

N N
I 66 66
35
O Test 97
85
N N

65 65
4,5
56 9 4,5 9 35,6
105 14,3 30,8 27,6 14,3 30,8 27,6
33 115 33 151
141
126 162
157...164 45 36 193...200 45 36

61 61
A
M00221/OS40FDS_

DIN 000 OS40FDS40000N1 DIN 000


OS40FDS30000

84 Dimension drawings | Switch fuses OS and OSM


Dimension drawings, IEC and UL/CSA
Side operated switch fuses

OS32G...63G_S_ E
mm M5 53
in 3/16 2,08
mm M5 53 E
2,08 26,5 41,5
in 3/16 1,04 1,63
57 26,5 41,5
2,24 1,04 1,63
100 57 112 100 84
2,24 4,41 3,94 114 3,31
3,94 4,49
100 112 100 84
Shaft 4,41 3,94 114 3,31
3,94 depth 4,49
Min 23/0,91
Max 27/1,06
Shaft depth A1 B1
Min 23/0,91
Max 27/1,06 A1 B1
D C 36,5 65
1,44 2,56
A (OS30-63G_S_)
D C 36,5 65
F (OS30_63G_S_K) 1,44 B 2,56
A (OS30-63G_S_)
F (OS30_63G_S_K)
8 B
0,31
8
0,31 41
1,61
741
1,61
0,28
7
0,28

OS32-63G_ OS60G_
[mm] DS01 DS02 DS03 DS04 B/FS01 B/FS02 B/FS03 B/FS04 [mm/in] JS01 JS02 JS03 JS04
A OS32-63G_
99,5 123 146,5 170 99,5 123 146,5 170 A OS60G_
109,5/4,31 144,5/5,69 179,5/7,07 214,5/8,44
M00296/OS30_63G_01_04S A

B [mm] 132,5
DS01 DS02
132,5 DS03
132,5 DS04
132,5 B/FS01
120,5 B/FS02
120,5 B/FS03
120,5 B/FS04 B
120,5 [mm/in]
130/5,12JS01 130/5,12JS02 130/5,12JS03 130/5,12JS04
C A 99,5
- 23,5123 146,5
23,5 23,5 170 -99,5 23,5 123 146,5
23,5 23,5 170 C A 109,5/4,31
- 144,5/5,69
35/1,38 179,5/7,07
35/1,38 214,5/8,44
35/1,38
M00296/OS30_63G_01_04S A

D B 132,5
56,5 132,5
56,5 132,5
56,5 132,5
56,5 120,5
56,5 120,5
56,5 120,5
56,5 120,5 D
56,5 B 62/2,44
130/5,12 130/5,12
62/2,44 130/5,12 62/2,44
62/2,44 130/5,12
E C 30 - 3023,5 3023,5 3023,5 30 - 3023,5 3023,5 3023,5 E C 36/1,41 - 35/1,38
36/1,41 35/1,38 36/1,41
36/1,41 35/1,38
F D 116,556,5 14056,5 163,556,5 18756,5 116,556,5 14056,5 163,556,5 18756,5 F D 62/2,44161,5/6,36
126,5/4,98 62/2,44196,5/7,74
62/2,44 62/2,44
231,5/9,11
A1 E 61,5 30 85 30 108,5 30 132 30 61,5 30 85 30 108,5 30 132 30 A1 E67,5/2,66
36/1,41102,5/4,04
36/1,41137,5/5,41
36/1,41 36/1,41
172,5/6,79
B1 F 116,5
91,5 115140 163,5
138,5 162,5 187 116,5
91,5 115 140 163,5
138,5 162,5 187 B1 F37,5/1,48
126,5/4,98 72,5/2,85
161,5/6,36107,5/4,23
196,5/7,74 231,5/9,11
142,5/5,61
A1 61,5 85 108,5 33,4 132 61,5 85 108,5 132 A1 67,5/2,66 102,5/4,04 137,5/5,41 172,5/6,79
B1 91,5 115 138,5 162,5 91,5 115 138,5 162,5 B1 37,5/1,48 72,5/2,85 107,5/4,23 142,5/5,61
93
95,5
OS100G...160G_S_
88,5 20

8,5 33,4 50 2,5


43 53
5,5
93
95,5
20 26,5 34 41,5
57 88,5

8,5 140 50 2,5


53 114,5 C
43
5,5 114 110 84
Shaft depth 34
Min 26,5 41,5
57 23
Max 27
M5 A1 B1 C1
140 C
114,5
62,5 35
B 84
114 110
A (OS100-160G_S_)
Shaft depth
Min 23 D (OS100-160G_S_K)
Max 27
M5 A1 B1 C1

62,5 35
B
A (OS100-160G_S_)

D (OS100-160G_S_K)
A

OS100-160G
M00298/OS100_160G_S01_04

[mm] D/F01 D/F02 D/F03 D/F04 B01 B02 B03 B04


A 111,5 146,5 181,5 216,5 111,5 146,5 181,5 216,5
B 142 142 142 142 126,5 126,5 126,5 126,5
C 100 100 100 100 118 118 118 118
A

D 128,5
OS100-160G 163,5 198,5 233,5 128,5 163,5 198,5 233,5
M00298/OS100_160G_S01_04

A1
[mm] 71,5
D/F01 106,5
D/F02 141,5
D/F03 176,5
D/F04 71,5
B01 106,5
B02 141,5
B03 176,5
B04
B1
A 86,5
111,5 121,5
146,5 156,5
181,5 191,5
216,5 86,5
111,5 121,5
146,5 156,5
181,5 191,5
216,5
C1
B 101,5
142 136,5
142 171,5
142 206,5
142 101,5
126,5 136,5
126,5 171,5
126,5 206,5
126,5
C 100 100 100 100 118 118 118 118
D 128,5 163,5 198,5 233,5 128,5 163,5 198,5 233,5
A1 71,5 106,5 141,5 176,5 71,5 106,5 141,5 176,5
B1 86,5 121,5 156,5 191,5 86,5 121,5 156,5 191,5
C1 101,5 136,5 171,5 206,5 101,5 136,5 171,5 206,5

Switch fuses OS and OSM | Dimension drawings 85


Dimension drawings, IEC and UL/CSA
Side operated switch fuses

OS100GJS
mm 33,4 93
in
mm 33,4
1,31 3,66
93
in 1,31 3,66
20 50 2,5
95,5 88,5 20 1,97
50 0,10
2,5
0,79 0,10
3,76
95,5 88,5
3,48 0,79 1,97
3,76 3,48
53 11
43 53
2,08 11
0,43
1,69
43
1,69
2,08 0,43 26,5 34 41,5
1,04
26,5 1,34
34 1,63
41,5
57 220 1,04 1,34 1,63
2,24
57 150 8,66
220
100 2,24 125,5
3,94 150
5,91 8,66 4,94
125,5
100
5,91 114 110 84
3,94 172 4,94 3,31
84
6,77 138,5 4,49
114 4,33
110
Shaft depth 172 5,45
138,5 4,49 4,33 3,31
Min
Shaft23/0,91
depth 6,77 5,45
Max 27/1,06
Min 23/0,91
Max 27/1,06

M5 A1 B1 C1
M5
3/16
A1 B1 C1
8,5
3/16 8,5
0,33
62,5 35 0,33
2,46
62,5 1,38
35 116,5
2,46 1,38
A (OS100GJS_) 4,59
116,5
A (OS100GJS_) 4,59
B (OS100GJS_K )
B (OS100GJS_K )
A A

OS100G_
M00296/OS30_63G_01_04S

OS100G_
M00296/OS30_63G_01_04S

[mm/in] JS01 JS02 JS03 JS04


[mm/in] JS01 JS02 JS03 JS04
A 111,5/4,39 146,5/5,77 181,5/7,15 216,5/8,52
A 111,5/4,39 146,5/5,77 181,5/7,15 216,5/8,52
B 128,5/5,06 163,5/6,44 198,5/7,91 233,5/9,19
B 128,5/5,06 163,5/6,44 198,5/7,91 233,5/9,19
A1 71,5/2,81 106,5/4,19 141,5/5,57 176,5/6,95
A1 71,5/2,81 106,5/4,19 141,5/5,57 176,5/6,95
B1 86,5/3,41 121,5/4,78 156,5/6,16 191,5/7,54
B1 86,5/3,41 121,5/4,78 156,5/6,16 191,5/7,54
C1 101,5/4,00 136,5/5,37 171,5/6,75 206,5/8,13
C1 101,5/4,00 136,5/5,37 171,5/6,75 206,5/8,13

75
OS 200: 43 / 1,69 2,95
OS 250: 53 / 2,09
OS 200:110/46
OS200...250_S_
70 K (IEC only) 4,33/1,81
OS 250:116/46
53,5
2,11
3
0,12
D M
2,76 4,57/1,81 75
L OS 200: 43 / 1,69 2,95
OS 250: 53 / 2,09 E
OS 200:110/46
4,33/1,81 53,5 3
70 K OS 250:116/46
72 D M 5,5 2,11 0,12 17,5
2,83 2,76 4,57/1,81 8,5
0,22 0,33 0,69 26,5
126 L F 1,04
4,96 E
B C
139
144 5,47 108
5,67 4,25
72 5,5 17,5
2,83 8,5
0,22 0,33 0,69 26,5
126 F 1,04
4,96
B C B1
A1 139 C1
144 5,47 108
5,67 4,25
G H I 39,5 65
1,56 2,56
N (OS200/250_)
A
J (OS200/250_K)
A1 B1
C1

G H I 39,5 65
1,56 2,56
N (OS200/250_)
A
J (OS200/250_K)

OS200_, OS200_K OS250_, OS250_K


[mm/in] DS01 BS01 DS02 BS02 DS03 BS03 DS04 BS04 [mm/in] DS01 BS01 DS02 BS02
A 162,0/6,38 143,0/5,63 162,0/6,38 143,0/5,12 162,0/6,38 143,0/5,63 162,0/6,38 143,0/5,63 A 154,0/6,06 154,0/6,06 154,0/6,06 154,0/6,06
B 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 B 162,0/6,38 162,0/6,38 162,0/6,38 162,0/6,38
C 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 C 193,0/7,60 193,0/7,60 193,0/7,60 193,0/7,60
OS200_, OS200_K OS250_, OS250_K
D 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 D 4,0/0,16 4,0/0,16 4,0/0,16 4,0/0,16
[mm/in] DS01 BS01 DS02 BS02 DS03 BS03 DS04 BS04 [mm/in] DS01 BS01 DS02 BS02
E 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 E 33,5/1,32 33,5/1,32 33,5/1,32 33,5/1,32
A 162,0/6,38 143,0/5,63 162,0/6,38 143,0/5,12 162,0/6,38 143,0/5,63 162,0/6,38 143,0/5,63 A 154,0/6,06 154,0/6,06 154,0/6,06 154,0/6,06
F 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 F 148,5/5,85 148,5/5,85 148,5/5,85 148,5/5,85
B 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 164,5/6,48 B 162,0/6,38 162,0/6,38 162,0/6,38 162,0/6,38
G 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 G 53,5/2,11 53,5/2,11 53,5/2,11 53,5/2,11
C 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 198,5/7,81 C 193,0/7,60 193,0/7,60 193,0/7,60 193,0/7,60
H -/- -/- 43,5/1,71 43,5/1,71 43,5/1,71 43,5/1,71 43,5/1,71 43,5/1,71 H -/- 54,0/2,13 54,0/2,13 54,0/2,13
D 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 D 4,0/0,16 4,0/0,16 4,0/0,16 4,0/0,16
I 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 I 25,0/0,98 25,0/0,98 25,0/0,98 25,0/0,98
E 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 36,5/1,44 E 33,5/1,32 33,5/1,32 33,5/1,32 33,5/1,32
C

J 138,5/5,45 138,5/5,45 182,0/7,17 182,0/7,17 225,5/8,88 225,5/8,88 269,0/10,59 269,0/10,59 J 148,5/5,85 202,5/7,97 256,5/10,10 310,5/12,22
F 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 144,5/5,69 F 148,5/5,85 148,5/5,85 148,5/5,85 148,5/5,85
K 40,0/1,57 40,0/1,57 40,0/1,57 40,0/1,57 40,0/0,39 840,0/1,57 40,0/1,57 40,0/1,57 K 45,0/1,77 45,0/1,77 45,0/1,77 45,0/1,77
M00153/OS200-250_S01-04_

G 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 48,5/1,91 G 53,5/2,11 53,5/2,11 53,5/2,11 53,5/2,11
L 10,0/0,39 10,0/0,39 10,0/0,39 10,0/0,39 10,0/0,39 10,0/0,39 10,0/0,39 10,0/0,39 L 11,0/0,43 11,0/0,43 11,0/0,43 11,0/0,43
H -/- -/- 43,5/1,71 43,5/1,71 43,5/1,71 43,5/1,71 43,5/1,71 43,5/1,71 H -/- 54,0/2,13 54,0/2,13 54,0/2,13
M 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,4/0,33 8,5/0,33 8,5/0,33 8,5/0,33 M 11,5/0,45 11,5/0,45 11,5/0,45 11,5/0,45
I 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 20,0/0,79 I 25,0/0,98 25,0/0,98 25,0/0,98 25,0/0,98
N 121,5/4,78 121,5/4,78 165,0/6,50 165,0/6,50 208,5/8,21 208,5/8,21 252,0/9,92 252,0/9,92 N 131,5/5,18 186,0/7,32 240,0/9,45 294,0/11,57
C

JA1 138,5/5,45
60,5/2,38 138,5/5,45
60,5/2,38 182,0/7,17
104,0/4,09 182,0/7,17
104,0/4,09 225,5/8,88
147,5/5,81 225,5/8,88 191,0/7,52
147,5/5,81 269,0/10,59 191,0/7,52
269,0/10,59 A1 J 70,5/2,78
148,5/5,85124,5/4,90
202,5/7,97178,5/7,03
256,5/10,10 310,5/12,22
232,5/9,15
K 40,0/1,57 40,0/1,57 40,0/1,57 40,0/1,57 40,0/0,39 166,5/6,56
840,0/1,57 210,0/8,27
40,0/1,57 210,0/8,27
40,0/1,57 B1 K89,5/3,52
45,0/1,77143,5/5,65
45,0/1,77197,5/7,78
45,0/1,77 45,0/1,77
M00153/OS200-250_S01-04_

B1 79,5/3,13 79,5/3,13 123,0/4,84 123,0/4,84 166,5/6,56 251,5/9,90


LC1 10,0/0,39
96,5/3,80 10,0/0,39
96,5/3,80 10,0/0,39
140,0/5,51 10,0/0,39
140,0/5,51 10,0/0,39 183,5/7,22
183,5/7,22 10,0/0,39 227,0/8,94
10,0/0,39 227,0/8,94
10,0/0,39 C1 L106,5/4,19
11,0/0,43214,5/8,44
11,0/0,43 11,0/0,43
268,5/10,57 11,0/0,43
322,5/12,70
M 8,5/0,33 8,5/0,33 8,5/0,33 8,5/0,33 8,4/0,33 8,5/0,33 8,5/0,33 8,5/0,33 M 11,5/0,45 11,5/0,45 11,5/0,45 11,5/0,45
N 121,5/4,78 121,5/4,78 165,0/6,50 165,0/6,50 208,5/8,21 208,5/8,21 252,0/9,92 252,0/9,92 N 131,5/5,18 186,0/7,32 240,0/9,45 294,0/11,57
A1 60,5/2,38 60,5/2,38 104,0/4,09 104,0/4,09 147,5/5,81 147,5/5,81 191,0/7,52 191,0/7,52 A1 70,5/2,78 124,5/4,90 178,5/7,03 232,5/9,15
86 Dimension drawings | Switch fuses OS and OSM
B1 79,5/3,13 79,5/3,13 123,0/4,84 123,0/4,84 166,5/6,56 166,5/6,56 210,0/8,27 210,0/8,27 B1 89,5/3,52 143,5/5,65 197,5/7,78 251,5/9,90
C1 96,5/3,80 96,5/3,80 140,0/5,51 140,0/5,51 183,5/7,22 183,5/7,22 227,0/8,94 227,0/8,94 C1 106,5/4,19 214,5/8,44 268,5/10,57 322,5/12,70
Dimension drawings, IEC
Side operated switch fuses

OS315...400_S_
86 58,5 81
3,39 2,30 10,8 3,19
55,8/130,9 56,5 5
0,43 2,22
86 58,5 7,5 2,20/5,15 0,20 81
3,39 2,30 0,30 10,8 3,19
11,5 55,8/130,9 56,5 5
0,43
0,45 7,5 2,20/5,15 40 2,22 0,20
1,56
0,30 17
11,5 0,67 26
1,02 26,5
82 0,45 5 40 1,04
3,23 0,20 1,56
17
201 164 0,67 159
26
1,02 108 26,5
149 82 7,91 5
6,46 6,26 4,25 1,04
5,87 3,23 230 D
9,06 0,20
201 164 159 108
149 7,91 6,46 6,26 4,25
5,87 230 D A1 B1 C1
9,06

A1 B1 C1

75,5 64 25 46,5 95
2,97 2,52 0,98 1,83 3,74
B (OS315/400_) C
A 75,5 64
(OS315/400_K) 25 46,5 95
2,97 2,52 0,98 1,83 3,74
B (OS315/400_) C
A (OS315/400_K)

OS315, OS315_K, OS400, OS400_K OS400_, OS400_K


[mm] BS01 BS02 BS03 BS04 [mm] DS01 DS02 DS03 DS04
M00154/OS315-400_S01-04_ A

A 185,0 OS400_K
OS315, OS315_K, OS400, 249,0 313,0 377,0 A OS400_, OS400_K 185,0 249,0 313,0 377,0
B [mm] 160,0
BS01 224,0
BS02 288,0
BS03 352,0
BS04 B [mm] 160,0
DS01 224,0
DS02 288,0
DS03 352,0
DS04
M00154/OS315-400_S01-04_ A

C A 176,0
185,0 176,0
249,0 176,0
313,0 176,0
377,0 C A 193,0
185,0 193,0
249,0 193,0
313,0 193,0
377,0
D B 194,0
160,0 194,0
224,0 194,0
288,0 194,0
352,0 D B 166,0
160,0 166,0
224,0 166,0
288,0 166,0
352,0
A1 C 98,5
176,0 162,5
176,0 226,5
176,0 290,5
176,0 A1 C 98,5
193,0 162,5
193,0 226,5
193,0 290,5
193,0
B1 D 116,5
194,0 180,5
194,0 244,5
194,0 308,5
194,0 B1 D 116,5
166,0 180,5
166,0 244,5
166,0 308,5
166,0
C1 A1 134,598,5 198,5
162,5 262,5
226,5 326,5
290,5 C1 A1 134,598,5 198,5
162,5 262,5
226,5 326,5
290,5
B1 116,5 180,5 244,5 308,5 B1 116,5 180,5 244,5 308,5
C1 134,5 198,5 262,5 326,5 C1 134,5 198,5 262,5 326,5

OS630_S_ and OS800_S_


6
107,5 77,5 6 0,24
4,24 3,05 0,24 23 137/62 62 6
107,5 77,5 13,5 6 0,91 5,4/2,44 2,44 500,24
M8 4,24 3,05 0,53
13,5 0,24 23 137/62 62 1,97
5/16 0,53 0,91 5,4/2,44 2,44 50
M8 1,97 73
5/16 45 60 2,87
1,77 2,36
45 73
116 5 60 2,87
4,57 0,20 ON 1,77 2,36
116 259,5 5 306
206 4,57 0,20 230 232 223 176
10,22 12,06 O 9,06
ON

8,12
OFF OFF

9,14
OFF

O
8,79
OFF OFF
O

6,93
O O

259,5 306 230


ON ON ON

206 ON

10,22 12,06 232 223 176


8,12 9,06
OFF OFF

9,14
OFF

O
8,79
OFF OFF

O
O

6,93
O O

ON ON ON

ON

A1 B1 C1
A1 B1 C1
122,5 88 39
4,83 3,46 1,54 144
122,5 88 39 62 5,67
B (OS600/800_)
4,83 3,46 1,54 2,44 247144
B (OS600/800_)
62 9,735,67
A (OS600/800_K) 2,44 247
9,73
A (OS600/800_K)
M00146/OS600-800_S01_-04_ C

OS600/630/800_ , OS600/630/800_K
M00146/OS600-800_S01_-04_ C

[mm] DS/BS01 DS/BS02 DS/BS03 DS/BS05


OS600/630/800_ , OS600/630/800_K
A 238 326/12,84 414 502
[mm] DS/BS01 DS/BS02 DS/BS03 DS/BS05
B 213 301/11,86 389 477
A 238 326/12,84 414 502
A1 147,5 235,5/9,28 323,5 411,5
B 213 301/11,86 389 477
B1 177,5 265,5/10,46 353,5 441,5
A1 147,5 235,5/9,28 323,5 411,5
C1 203,5 291,5/11,48 379,5 467,5
B1 177,5 265,5/10,46 353,5 441,5
C1 203,5 291,5/11,48 379,5 467,5

Switch fuses OS and OSM | Dimension drawings 87


Dimension drawings, IEC
Special connected switch fuses 75
20
G OS 200:110/46 40,5
I K OS 250:116/46 3
M5
L
J
33,5 5,5 C
*) 6 A2 B2
C2
45
72 3
D
144 M B 59 108
144 138,5
Back connection types: 126
65
49 A1 B1 C1
OS200_12/22_
*) and OS250_12/22
11 (BB) 14 min
10,5 8,6
8,4 75 A
12,5
N F 189...254
E 20 G OS 200:110/46 (OXP 6X210)
40,5
G K 3
M5 H I *) OS_N3: OS 250:116/46
L
J
33,5 5,5 C
*) 6 A2 B2
C2
45
72 3
D
144 M B 59 108
144 138,5
Back connection types: 126
65
49 A1 B1 C1
10,5
*) 11 14 min
8,6
8,4 A
12,5
N F 189...254
E G (OXP 6X210)
H *) OS_N3:

OS200 OS250
[mm] D11 B11 D12 B12 D13 B13 D22 B22 [mm] D11 D12 D13 D22
A 149 130 149 130 141 130 149 130 A 154 154 154 154
B 199 199 199 199 199 199 199 199 B 193 193 193 193
C 36,5 36,5 36,3 36,5 36,5 36,5 36,5 36,5 C 33,5 33,5 33,5 33,5
D 144,5 144,5 144,5 144,5 144,5 144,5 144,5 144,5 D 148,5 148,5 148,5 148,5
E 92 92 92 92 92 92 135,5 135,5 E 112,5 112,5 112,5 161
F 43,5 43,5 43,5 43,5 43,5 43,5 43,5 43,5 F 54 54 54 54
G 20 20 20 20 20 20 20 20 G 25 25 25 25
H 132 132 175,5 175,5 219 219 219 219 H 152 206 260 260
I 40 40 40 40 40 40 40 40 I 45 45 45 45
J 10 10 10 10 10 10 10 10 J 11 11 11 11
K 8,4 8,4 8,4 8,4 8,4 8,4 8,4 8,4 K 11,5 11,5 11,5 11,5
L OS200 8,6 8,6 8,6 8,6 8,6 8,6 8,6 8,6 L OS250 4 4 4 4
M00014/OS200_250_11_22 K

M [mm] 165D11 165B11 165D12 165B12 165D13 165B13 165D22 165B22 M [mm] 162D11 162D12 162D13 162D22
N A 80149 80130 80149 OS80200: 43 80 80130 80149 75
80130 N A 90154 90154 90154 90154
130 53
OS 250: 141
A1 B 104199
20 I 104199 147,5199 147,5199 191199 191199 191199 191199 A1 B 124193 178193 232193 232193
A2 C 52 20 52 52 52 52 52 OS 200:110/46
95,5 40,5
95,5
10,5 36,5 36,5 K 36,3 36,5 36,5 OS 250:116/46
36,5 36,5 36,5 3A2 C 62
33,5 62
33,5 62
33,5 116
33,5
B1 D 123 123 166,5 166,5 210 210 210 210
144,5 B1 D 6143 197 251 251
8,4
144,5 J 144,5L 144,5 144,5 144,5 144,5 144,5 148,5 148,5 148,5 148,5
B2 61,5 92
8,6 61,5 92 61,5 92 61,5 92 61,5 92 61,5 92 105
5,5 105
135,5 B2 E 71,5 71,5 71,5 125,5161
E
33,5 135,5 D 112,5 112,5 112,5
)
C1 F 43,5*
140 140
43,5 183,5
43,5 183,5
43,5 227
43,5 227
43,5 227
43,5 227
43,5 C1 F 160 54 214 54 268 54 268 54
C2 G 70 20 70 20 70 20 70 20 70 20 70 20 113,5 20 113,5 20 C2 G 80 25 4580 80 25 8,5
134 25
25 18 26,5
72 3
H 132 132 175,5 175,5 219 219 219 219 H 152 206 260 260
126 E
I 40 40 40 40 40 40 4059 40 I 45 45 45 45
OS200_03/04_
J 10
and OS250_03/04
10 10
M
10
(BB)
Back
10connection 10
types:
C
10 10 J 11 11 11
144
11
138,5 108
K 8,4 8,4 8,4 8,4 8,4 8,4 8,4 8,4
75 K 11,5 11,565 11,5 11,5
OS 200: 43
L 8,6 8,6 8,6 OS 250:
8,6 53 8,6 8,6 8,6 8,6 L 4 4 4 4
M00014/OS200_250_11_22 K

20 I 11 49 A1 B1 C1
M 165*) 165 165 165 165 165 165
OS 200:110/46 165
40,5 M 162 162 162 162
M5
10,5 20 K OS 250:116/46 3 N14 min 90
N 80 80 80 80 80
12,5 80 80 80 90 90 90
6
A1 8,4 104 J 104L H
147,5 147,5 191 H 191 191 191 A1 B 124 178 232 232
8,6 52 F G 5,5
33,5
A2 52 52 52 52 52 95,5 95,5 D189...254
A2 62 62 62 116
*) A *) OS_N3 (OXP 6X210)
B1 123 123 166,5 166,5 210 210 210 210 B1 143
45 197 251 251
8,5
B2 18 26,5
72 61,5 61,5 61,5 61,5 61,5 61,5 3 105 105 B2 71,5 71,5 71,5 125,5
C1
126 140 140 183,5 183,5 227 227 227 227 C1 160 214 E 268 268
C2 70 70 70 M 70 70 70 C113,559 113,5 C2 80 80 80 134
144 138,5 108
Back connection types:

65

11 49 A1 B1 C1
*)
M5 14 min
12,5
H H B
F G
189...254
A *) OS_N3 (OXP 6X210)

OS200_BB_ OS250_BB_
[mm] D01 B01 D02 B02 D03 B03 D04 B04 [mm] D01/B01 D02/B02 D03/B03 D04/B04
A 89,5 89,5 133 133 176,5 176,5 220 220 A 99,5 153,5 207,5 261,5
B 149 130 149 130 149 130 149 149 B 154 154 154 154
C 198,5 198,5 198,5 198,5 198,5 198,5 198,5 198,5 C 193 193 193 193
D 36,5 36,5 36,5 36,5 36,5 36,5 36,5 36,5 D 33,5 33,5 33,5 33,5
K / M07023

E 144,5 144,5 144,5 144,5 144,5 144,5 144,5 144,5 E 148,5 148,5 148,5 148,5
F 48,5 48,5 48,5 48,5 48,5 48,5 48,5 48,5 F 53,5 53,5 53,5 53,5
G - - 43,5 43,5 43,5 43,5 43,5 43,5 G - 54 54 54
H 20 20 20 20 20 20 20 20 H 25 25 25 25
M00008/OS200_250_01_04

I 40 40 40 40 40 40 40 40 I 45 45 45 45
OS200_BB_ OS250_BB_
J 10 10 10 10 10 10 10 10 J 11 1 11 11
[mm] D01 B01 D02 B02 D03 B03 D04 B04 [mm] D01/B01 D02/B02 D03/B03 D04/B04
K 8,4 8,4 8,4 8,4 8,4 8,4 8,4 8,4 K 11,5 11,5 11,5 11,5
A 89,5 89,5 133 133 176,5 176,5 220 220 A 99,5 153,5 207,5 261,5
L 8,6 8,6 8,6 8,6 8,6 8,6 8,6 8,6 L 4 4 4 4
B 149 130 149 130 149 130 149 149 B 154 154 154 154
M 164,5 164,5 164,5 164,5 164,5 164,5 164,5 164,5 M 162 162 162 162
C 198,5 198,5 198,5 198,5 198,5 198,5 198,5 198,5 C 193 193 193 193
A1 60,5 60,5 104 104 147,5 147,5 191 191 A1 70,5 124,5 178,5 232,5
D 36,5 36,5 36,5 36,5 36,5 36,5 36,5 36,5 D 33,5 33,5 33,5 33,5
B1 79,5 79,5 123 123 166,5 166,5 210 210 B1 89,5 143,5 197,5 251,5
K / M07023

E 144,5 144,5 144,5 144,5 144,5 144,5 144,5 144,5 E 148,5 148,5 148,5 148,5
C1 96,5 96,5 140 140 183,5 183,5 227 227 C1 106,5 160,5 214,5 268,5
F 48,5 48,5 48,5 48,5 48,5 48,5 48,5 48,5 F 53,5 53,5 53,5 53,5
G - - 43,5 43,5 43,5 43,5 43,5 43,5 G - 54 54 54
H 20 20 20 20 20 20 20 20 H 25 25 25 25
88 Dimension
40 drawings
40 | Switch
40 fuses40OS and40
OSM
250_01_04

I 40 40 40 I 45 45 45 45
J 10 10 10 10 10 10 10 10 J 11 1 11 11
K 8,4 8,4 8,4 8,4 8,4 8,4 8,4 8,4 K 11,5 11,5 11,5 11,5
Dimension drawings, IEC
81
Special connected
58,5
64
2,52 switch fuses
mm
in
5
0,20 3,19
2,30 43,5 5
25 7,5 10,8 55,8/130,9 1,71 0,20
0,98 0,30 0,43 2,20/5,15 12
M5 40 45
3/16 1,57 0,47 1,77
*)
5 A2 B2 C2
0,20 B
193 94 164
7,60 159 128
230 3,70
Back connection types:
6,46 6,26 5,04
9,06 95
OS315_12/22_ and OS400_12/22 (BB)11 3,74
45 A1 B1 C1
mm *) 64 0,43
38 5 1,77
81
11,5 12,5 1,50 min 20 0,20 3,19
in 58,5 2,52
0,45 0,49 0,79
2,30 25
43,5 5 A
117 64 0,98
25 7,5 4,6110,8 2,52 55,8/130,9 1,71 0,20
0,98 2,20/5,15 230...325
0,30 C 0,43 12 45 12x250)
40
0,47 (OXP
9,06...12,80
M5 * )
OS_N3
3/16 D 1,57 1,77
*)
5 A2 B2 C2
0,20 B
193 94 164
7,60 Back connection types: 159 128
230 3,70 95
6,46 6,26 5,04
9,06 3,74
11 45 A1 B1 C1
*) 0,43
38 1,77
11,5 12,5 1,50 min 20
0,45 0,49 0,79
117 64
25
0,98 A
4,61 2,52 230...325
C 9,06...12,80 (OXP 12x250)
D * )
OS_N3

OS315-400_BB_ OS400_BB_
[mm] B11 B12 B13 B21 B22 [mm] D11 D12 D13 D21 D22
A 176 176 176 176 176 A 193 193 193 193 193
C000011/OS315-400_11_22 D / M07024

B 194 194 194 194 194 B 166 166 166 166 166
C 140 140 140 204 204 C 140 140 140 204 204
D 190 254 318 254 318 D 190 254 318 254 318
mm 5
in 81
0,20
28 58,5
OS315_BB_ OS400_BB_ 3,19
1,10 2,30 B1210,8
55,8/130,9 43,5 5
[mm] B11 B21 B22 B13 [mm] B11/D11 B12/D12 B21/D21 B22/D22 B13/D13
0,43
A1 11,5
163 227
7,5 227 291 291 A1
2,20/5,15 1,711630,20 227 227 291 291
M5A2 0,45
81,5 0,30
81,5 145,5 145,5 81,5 A2 81,5 81,5
12 45 145,5 145,5 81,5
3/16
B1 181 245 245 309 309 B1 181 40 0,47245 1,77 245 309 309
1,56
B2 )
*90,5 90,5 154,5 154,5 90,5 B2 90,5 90,5 154,5 154,5 90,5
17 26 35
82C1 199 263 263 327 327
5 C1 199 263 263
0,67
327
1,02
327
1,38
3,23
C2 99,5 99,5 163,5 163,5 99,5 0,20
C2 99,5 99,5 163,5 163,5 99,5
OS315-400_BB_ 193 OS400_BB_ C
[mm]140 B11 B12 B13 B21 7,60
B22 [mm] D11 94 164 159 128
5,51 230D123,70 D13 D21 D22
6,46 6,26 5,04
A
OS315_03/04_ and OS400_03/04 (BB)
176 176 176 176 176 A 193
9,06193 193 193 193
95
C000011/OS315-400_11_22 D / M07024

B 194 194 194 194 194 B connection166


Back types: 166 166 166 166
45 3,74
C 140
mm
140 140 204 204 C 140 140 140 204 204 A1 B1 C1
D in
190 )
*254 318 254 318 D 190 1,77 5 318
254 81254 318
11 0,20 3,19 min 20
28 58,5 0,43
10,825 38 0,79
OS315_BB_ 1,1075,5 2,3064 OS400_BB_1,50
12,5
55,8/130,9 43,5B12/D12
B5
0,43 0,49
[mm] B11 B12 11,5
2,97 2,52
B21
7,5 B22
0,98 B13 [mm] 25 B11/D11
2,20/5,15 1,71 0,20 B21/D21 B22/D22 B13/D13
A1 163 M5 227 0,45 227 0,30291 291 A1 0,98 163 230...325 (OXP 22712x250) 22745 291 291
12
A2 81,5 3/16 81,5 145,5 A 145,5 81,5 A2 81,5 40
9,06...12,80
81,5 1,77
0,47 145,5 145,5 81,5
1,56
B1 181 245
*) 245 309 ) OS_N3 B1
*309 181 245 245 309 309
B2 90,5 154,517 90,526 35
82 90,5 154,5 154,5 90,5 B2
5 90,5 90,5 154,5
0,67 1,02 1,38
C1 199 3,23 263 263 327 327 C1 0,20 199 263 263 327 327
C2 99,5 99,5 163,5 163,5 99,5 193C2 99,5 99,5 163,5 C 163,5 99,5
140 7,60 94 164 159 128
5,51 230 3,70 6,46 6,26 5,04
9,06
Back connection types:
95
45 3,74
A1 B1 C1
*) 1,77
11 min 20
0,43
38
1,50
0,79
75,5 64 25 12,5
0,49
B
2,97 2,52 0,98 25
0,98 230...325 (OXP 12x250)
A 9,06...12,80
*) OS_N3
D / M07025

OS315 - 400_BB_ OS400_BB_


[mm] B01 B02 B03 B04 [mm] D01 D02 D03 D04
A 127 191 255 319 A 127 191 255 319
C000012 /OS315_400_01_04

B 176 176 176 176 B 193 193 193 193


C 194 194 194 194 C 166 166 166 166

OS315_BB_ OS400_BB_
[mm] B01 B02 B03 B04 [mm] B01/D01 B02/D02 B03/D03 B04/D04
A1 98,5 162,5 226,5 290,5 A1 98,5 162,5 226,5 290,5
B1 116,5 180,5 244,5 308,5 B1 116,5 180,5 244,5 308,5
C1 134,5 198,5 262,5 326,5 C1 134,5 198,5 262,5 326,5
D / M07025

OS315 - 400_BB_ OS400_BB_


[mm] B01 B02 B03 B04 [mm] D01 D02 D03 D04 Switch fuses OS and OSM | Dimension drawings 89
A 127 191 255 319 A 127 191 255 319
01_04

B 176 176 176 176 B 193 193 193 193


Dimension drawings, IEC
Special connected switch fuses

OS125G...160GD12LR (LR)

162
142

32

45

97
63 69
28

185
55 90 156
M00364/OS160GD12LR_B

56
35
122 100
35
56

5,5 M6
65 44
242

OS125G...160GD21LR (LR)
162
142

97
63
28

185
90 55 156

56
35
M00365/OS160GD21LR_A

122 100
35
56

M6
5,5
242 44

90 Dimension drawings | Switch fuses OS and OSM


Dimension drawings, IEC
Special connected switch fuses

OS125G...160GD22LR (LR)

197
177

97 63 69
28

156
220 7 44
90 90

56
35
100
150
35
M00366/OS160GD22LR_A

56
35
5,5

M6
277

OS125G...160GB12LR (LR)

162
142

97
63 69
28

185
55 90 141

56
35
M00361/OS160GB12LR_A

122 118
35
56

5,5 M6
242 44

Switch fuses OS and OSM | Dimension drawings 91


Dimension drawings, IEC
Special connected switch fuses

OS125G...160GB21LR (LR)

162
142

97
63 69
28

90 55 141

56
35
M00362/OS160GB21LR_A

122 118
35
56

5,5 M6
242 44

OS125G...160GB22LR (LR)

197
177

97
63 69
28

141
220 44
90 7
90

56
35
118
150
35
M00363/OS160GB22LR_A

56
35

M6
277

92 Dimension drawings | Switch fuses OS and OSM


Dimension drawings, IEC
Special connected switch fuses

G
OS125G...160G_21LR + OSS160G 3LS
T

101

228 193 6

56

122

56

438

G
OS125G...160G_22LR + OSS160G 4LS
T

101

228 228 6

56 61

91 96

473

Switch fuses OS and OSM | Dimension drawings 93


Dimension drawings, IEC
Special connected switch fuses

0_LR, 3-pole OS200B12_ and OS250_12_ (LR)


R
R
36
R

65 45
101,5 155,5

(OXP 6X210)
Back right

218...283
184

5
Back left
108
59,5
25,5
25 12,5 50
11
45 45 54
252 306
151 206
121,5 175,5
94 148
M8 79,5 133,5
45
B / M07026

42,5 25
67,5 50
148,5
150
M00120/OS250_12BL-BR

3
67,5 11 50
42,5

OS200B...250_LR, 3-pole 21,6 34,3 11,5 4 6


85

11
OS200B12LR 3 105 25 53
OS250B12LR 69,6 45 45 54
137 191 36
OS250D12LR 108
149,5 203,5
53 45
65
101,5 155,5
(OXP 6X210)

Back right
218...283

184

5
Back left
108
59,5
25,5
OS200B21_ and OS250_21_ (LR) 25 12,5
50_LR, 3-pole
50
R 11
45 45 54
R 36
R 252 306
151 206
65 45
121,5 175,5
155,5 94
101,5 148
M8 79,5 133,5
45
(OXP 6X210)

BR
42,5
218...283

25 184
67,5 50
148,5
BL 5
150
3 108
67,5 11 59,5 50
42,5
25,5
21,6 34,3 25 11,5 12,5 50 4 6
85

11 11
3 105 25 53
69,6 54 45 45
45 45 54
108 306 137 252 191
205 149,5 151 203,5
175,5 121,5 53
148 94
M8 133,5 79,5
45
B / M07027

42,5 25
67,5
148,5
150
M00119/OS250_21BD-BR

3
67,5 11 50
42,5
21,6 34,3 11,5 6
85

OS200B...250_LR, 3-pole
4
OS200B21LR 3 105 11 25 53
69,6 54 45 45
OS250B21LR
191 137 36
OS250D21LR
108 203,5 149,5
53 65 45
155,5 101,5
(OXP 6X210)

BR
218...283

184

BL 5
108
94 Dimension drawings | Switch fuses OS and OSM 59,5
25,5
25 12,5 50
Dimension drawings, IEC
Special connected switch fuses

OS315B12_ and OS400_12_ (LR)


OS315B...400_LR
A B
OS315B12LR 201 194 36
OS400B12LR 201 194
OS400D12LR 218 166 95 45
120,5 184,5

(OXP 12X250)
BR

255...350
A

BL
5
110
61,5
28
29 20
25 12,543 11 50
12,5 58,5 58,5 64
271,5 335,5
169 233
47 140 204
112 176
M8 21 99 163 5,5
23
25
C / M07028

69 50
B 150
9
5 50
69 11
M00130/OS400_12BL-BR

23
OS315B...400_LR 40 51 7,5
A B 11,5 104 25
5 126 64 36
OS315B12LR 201 194 68,7 58,5 58,5 64
OS400B12LR 201 194 155,5 220
OS400D12LR 218 166 110 168 232 95 45
64
120,5 184,5
(OXP 12X250)

BR
255...350

A
OS315B21_ and OS400_21_ (LR) BL
S315B...400_LR
5
A B
S315B21LR 201 194 36 110
S400B21LR 201 194
61,5
28 95 45
S400D21LR 218 166
29 20
184,5 25 120,5 12,543 11 50
12,5 58,5 58,5 64
(OXP 12X250)

271,5 335,5
BR 169 233 A
255...350

47 140 204
112 176
M8 21 99 163 5,5
BL 23
25 5
69 50
110
B 150 61,5
9 28
5 29 20 50
69 11 11 50
23 25
12,5
64 58,5 58,5
40 51 335 7,5 271,5
233 11,5 104 169 25
47 204 140 64
5 68,7 126 176 112
M8 21 163 58,5
99 58,5 64
155,5 220
11023 168
64
232
69 25
C / M07029

50
B 150
9
5 69 50
M00127/OS400_21BL-BR

23 11

40 104 5,5
OS315B...400_LR
5 51 7,5
64
A B 11,5 25
68,7 126 58,5 58,5 36
OS315B21LR 201 194 64
220 155,5
OS400B21LR 201 194
110 232 168 45
OS400D21LR 218 166 64 95
184,5 120,5
(OXP 12X250)

BR A
255...350

Switch fuses OS and OSM | Dimension drawings 95


BL
5
Dimension drawings, IEC
Special connected switch fuses

OS315B22_N2 and OS400_22_N2 (LR)


15B...400_LR
A B
36
15B22LR 201 194
00B22LR 201 194
95 45
00D22LR 218 166
183,5 183,5

(OXP 12X250)
BR A

255...350
BL
5
110
61,5
28
29 20
25 11 50
12,5
64 58,5 58,5 64
334 334
233 233
203,5 203,5
5 68,7 176,5 176,5
153,5 153,5
22 30 5,5
31 33
80
C / M07030

85 72,5 50
75
B
9 50
5
M00126/OS400-22BL-BRN2

125 80
85 25
33,5 50

OS315B...400_LR 41,1 122,5 11 7,5 104


11 64
A B 2536
M8 47 11,5
OS315B22LR 201 194 116,2 64 58,5 58,5
219 219
OS400B22LR 201 194 110 231,5 231,595 45
OS400D22LR 218 166 64
183,5 183,5
(OXP 12X250)

BR A
255...350

BL
5
110
61,5
28
29 20
25 11 50
12,5
64 58,5 58,5 64
334 334
233 233
203,5 203,5
5 68,7 176,5 176,5
153,5 153,5
22 30 5,5
31 33
80
85 72,5 50
75
B
9 50
5 80
125
85 25
33,5 50

41,1 122,5 11 7,5 104


11 64
25
M8 47 11,5
116,2 64 58,5 58,5
219 219
110 231,5 231,5
64

96 Dimension drawings | Switch fuses OS and OSM


Dimension drawings, IEC
Motorized switch fuses

OSM32...63_M_

OSM32-63_M_
[mm] D3 D4 B3 B4
A

A 23,5 23,5 23,5 23,5


M00293 / OSM32-63-M

A1 122 122 122 122


A2 187,5 211 187,5 211
B 229 252,5 229 252,5 OSM32-63_M_
C 100 100 100 100 [mm] D3 D4 B3 B4
A

D 136,5 136,5 124,5 124,5 A 23,5 23,5 23,5 23,5


M00293 / OSM32-63-M

A1 122 122 122 122


A2 187,5 211 187,5 211
B 229 252,5 229 252,5
OSM100...160_M_ C 100 100 100 100
D 136,5 136,5 124,5 124,5

OSM100-160_M_
A

[mm] D/F3 D/F4 B3 B4


M00294 / OSM100-160-M

A 35 35 35
OSM100-160_M_ 35
A

A1 122 122 [mm] 122


D/F3 122
D/F4 B3 B4
M00294 / OSM100-160-M

A2 272 307 A 272 35 307 35 35 35


B 290 325 A1 290122 325 122 122 122
C 100 100 A2 118272 188 307 272 307
D 146 146 B 130,5290 130,5 325 290 325
C 100 100 118 188
D 146 146 130,5 130,5

Switch fuses OS and OSM | Dimension drawings 97


Dimension drawings, IEC
Motorized switch fuses

OSM200_M_

OSM200_M_
[mm] B3 B4 D3 D4
A 43,5 43,5 43,5 43,5
B
M001997 OSM200-M

A1 118 118 118 118


OSM200_M_
A2 301,5 345 301,5 345
[mm] B3 B4 D3 D4
B 323,5 367 323,5 367
A 43,5 43,5 43,5 43,5
B

C 144,5 144,5 144,5 144,5


M001997 OSM200-M

A1 118 118 118 118


D 132 132 151 151
A2 301,5 345 301,5 345
B 323,5 367 323,5 367
C 144,5 144,5 144,5 144,5
D 132 132 151 151

OSM250_M_

OSM250_M_
[mm] D3/B3 D4/B4
A 54 54
M00198 / OSM250-M B

A1 118 118 OSM250_M_

A2 332 386 [mm] D3/B3 D4/B4

B 354 408 A 54 54
M00198 / OSM250-M B

C 148,5 148,5 A1 118 118

D 156 156 A2 332 386


B 354 408
C 148,5 148,5
D 156 156

98 Dimension drawings | Switch fuses OS and OSM


Dimension drawings, IEC
Motorized switch fuses

OSM315...400_M_

OSM315_M_ OSM400_M_
OSM315_M_ OSM400_M_
[mm] B3 B4 [mm] B3 B4 D3 D4
C

[mm] B3 B4 [mm] B3 B4 D3 D4
C

A 64 64 A 64 64 64 64
M00199/ OSM315-400-M

A 64 64 A 64 64 64 64
M00199/ OSM315-400-M

A1 136 136 A1 136 136 136 136


A1 136 136 A1 136 136 136 136
A2 382 446 A2 382 446 382 446
A2 382 446 A2 382 446 382 446
B 404 468 B 404 468 404 468
B 404 468 B 404 468 404 468
C 194 194 C 194 194 166 166
C 194 194 C 194 194 166 166
D 178,5 178,5 D 178,5 178,5 196,5 196,5
D 178,5 178,5 D 178,5 178,5 196,5 196,5

OSM630...800_M_
M00206 / OSM639-800-M B

OSM630-800_M_
[mm] D3/B3 D4/B4
A 88 88
M00206 / OSM639-800-M B

A1 180 180
A2 465,5 553,5 OSM630-800_M_

B 486,5 574,5 [mm] D3/B3 D4/B4


A 88 88
A1 180 180
A2 465,5 553,5
B 486,5 574,5

Switch fuses OS and OSM | Dimension drawings 99


Dimension drawings, IEC
Motorized switch fuses

OSM1250_M_
M00238 / OSM1250-M C

OSM1250_M_
[mm] B3/D3 B4/D4
A 110 110
A1 230 230
A2 569,5 679,5
B 599,5 709,5
M00238 / OSM1250-M C

OSM1250_M_
[mm] B3/D3 B4/D4
A 110 110
A1 230 230
A2 569,5 679,5
B 599,5 709,5

100 Dimension drawings | Switch fuses OS and OSM


Dimension drawings
Accessories

Plastic handles
Door drilling for OH_ handles:

Handle type B shaft diameter Length L


[mm] [mm]
OH_45J6 6 45
OH_65J6 6 65
OH_95J12 12 95
OH_125J12 12 125
OH_145J12 12 145
OH_175J12 12 175
OH_275J12 12 275

Handle type Length L


[mm]
OH_274J12 274
OH_330J12 330
M07015

31 5
31 5 Handle type Length L
[mm]
OHB150J12P 300
80 80
54 54 71 71 OHB200J12P 400

69,4 69,4 45 45
53 53
53 53
L L
M00134 / 13/OH-150-200J12P A

M00134 / 13/OH-150-200J12P A

Stainless steel handles


OHM_ Door drilling for OHM_

69 37 51 31 5 Handle type B shaft diameter Lenght L


[mm] [mm]
OHM65L6 6 65
B
M00133/13OHM45-275L-A/KE00020

OHM125L12 12 125
OHM175L12 12 175
OHM275L12 12 275

45
53
L 53

Switch fuses OS and OSM | Dimension drawings 101


Dimension drawings
Accessories

Metallic handles
YASDA7, 8 (A=220) Door drilling for YASDA:

Minimum distance L between the hinge and the rotating shaft

Sizes [A] Length L Handle type


[mm]
30...250 60 OH_65J6
315...400 95 OH_95J12
630...800 150 OH_125J12, OH_145J12
630...800 175 OH_175J12
630...800 275 OH_275J12
630...800 220 YASDA7, 8
1200...1250 274 OH_274J12
hinge 1200...1250 330 OH_330J12

shaft

6 and 8-pole switch fuses


OESAZW2 OETLZW9

102 Dimension drawings | Switch fuses OS and OSM


Dimension drawings
Accessories

Mechanical interlock
S00120A

OTZW10, 24
OTZW10 OTZW24
OETLZX3, 14, 15 A 206 114
OETLZW3 OETLZW14 OETLZW15 B 190 100
A 300 250 500 C 6 5
B 31 31 36 D 30 25

Change-over and by-pass switch fuses

OETLZW11 OETLZW12, 13 OTZW 25

OETLZW12, 13
OETLZW12 OETLZW13
OETLZW11 A 210+(0...18)x20 mm 210+(0...18)x20 mm
A00213_B

OETLZW11 B 250+(0...18)x20 mm OTZW25


A 210+(0...11)x20 mm D 220 mm 320 mm A 210+(0...18)x20mm

OTZW 26

OTZW26
A 210+(0...9)x20mm
B 210+(0...9)x20mm

Switch fuses OS and OSM | Dimension drawings 103


Contact functions

Handle indications and functions


The handle indicates the position of the contacts with
complete reliability in all situations. If the contacts are
welded together, the handle doesnt reach the OFF-position
but remains between ON and OFF, maintaining the door
interlock and padlocking is not possible to do.
When operating the switch fuse to the Test-position with a
test handle the testauxiliary contacts change position. The
main contacts remain open.

ON and OFF-functions of main and auxiliary contacts

Example -45 0 30 60 90

Main contacts close


Places of auxiliary open
2 NO auxiliary contact close
contacts and Test ind. 1 open
NC auxiliary contact open
close
1
NO auxiliary contact close
2 open
NC auxiliary contact open
close

Test OFF ON
O I

OS Mini
-45 0 30 60 90

Main contacts
OA4B1C, 1 NO-NC Change over NO auxiliary contact
contacts NC auxiliary contact

OA1G10, 1NO NO auxiliary contact


OA3G01, 1NC NC auxiliary contact

Test OFF ON
O I

0 30 60 90

Main contacts O I
O I
MCB-10 + OESAZX169, 1NO NO auxiliary contact
MCB-01 + OESAZX169, 1NC
NC auxiliary contact

OFF ON
O I

OS30...63
-45 0 30 60 90

Main contacts
104 Contact functions | Switch
OA1G10,fuses
1NOOS and OSM NO auxiliary contact
OA3G01, 1NC NC auxiliary contact
Contact functions

OS/OSM32G...1250 -45 0 30 60 90
Main contacts O I
O I
OA1G10, 1NO
OA3G01, 1NC NO test contacts O I
inside the mechanism O I
OS_, OSM

OA1G10, 1NO NO early operation O I


test contacts inside O I
OA3G01, 1NC the mechanism 1)
+ OEA28 NC test contacts inside O I
OS_
the mechanism O I

OA1G10, 1NO NC early operation test O I


contacts inside the O I
OA3G01, 1NC mechanism 1)
OSM_
NO test indication O I
contacts inside the O I
mechanism

NC test indication O I
contacts inside the O I
mechanism

NO auxiliary contacts O I
in the module on the O I
side of the switch2)
NC auxiliary contacts O I
in the module on the O I
S07188A

side of the switch2)


Test OFF ON
O I

1)
OS/OSM1200...1250 only
2)
Also OSM32G...1250 mounted on the right side of the switch

Switch fuses OS and OSM | Contact functions 105


Index

Type Order number Description Page Type Order number Description Page
MCB-01 1SCA022150R5370 Auxiliary contacts 54 OHB175J12T 1SCA022708R0740 Pistol handles 47
MCB-10 1SCA022150R5110 Auxiliary contacts 54 OHB200J12P 1SCA022865R9510 Optional handles 48
OA1G10 1SCA022353R4970 Auxiliary contacts 54 OHB200J12PT 1SCA106510R1001 Optional handles 48
OA1G10 1SCA022353R4970 Auxiliary contacts 55 OHB274J12 1SCA115920R1001 Optional handles 48
OA1G10AU 1SCA022436R7910 Auxiliary contacts 54 OHB274J12T 1SCA120250R1001 Optional handles 48
OA1G10AU 1SCA022436R7910 Auxiliary contacts 55 OHB330J12 1SCA115922R1001 Optional handles 48
OA3G01 1SCA022456R7410 Auxiliary contacts 54 OHB330J12T 1SCA120252R1001 Optional handles 48
OA3G01 1SCA022456R7410 Auxiliary contacts 55 OHB4 1SCA022439R4050 Direct mount handles 50
OA3G01AU 1SCA022819R5260 Auxiliary contacts 54 OHB45J6 1SCA022380R8770 Pistol handles 47
OA3G01AU 1SCA022819R5260 Auxiliary contacts 55 OHB45J6T 1SCA109870R1001 Pistol handles 47
OA4B01 1SCA022276R9210 Auxiliary contacts 54 OHB65J6 1SCA022380R9660 Pistol handles 47
OA4B10 1SCA022276R9050 Auxiliary contacts 54 OHB65J6E00S 1SCA022382R9850 Pistol handles 49
OA4B1C 1SCA022193R0150 Auxiliary contacts 54 OHB65J6T 1SCA022399R8110 Pistol handles 47
OEA28 1SCA022714R8810 Module for auxiliary contacts 56 OHB65J6TE00S 1SCA109016R1001 Pistol handles 49
OEA30L 1SCA131816R1001 Mounting plate 57 OHB80J6 1SCA022381R0240 Pistol handles 47
OEA30R 1SCA131817R1001 Mounting plate 57 OHB80J6T 1SCA022399R8290 Pistol handles 47
OESAZW2 1SCA022078R1600 Conversion kits 65 OHB95J12 1SCA022381R0830 Pistol handles 47
OETLZK19 1SCA022093R1850 Adapters for extension socket 53 OHB95J12T 1SCA022736R1750 Pistol handles 47
OETLZW11 1SCA022078R0030 Conversion kits 65 OHG125J12 1SCA022381R1640 Pistol handles 47
OETLZW12 1SCA022078R0200 Conversion kits 65 OHG145J12 1SCA022381R2290 Pistol handles 47
OETLZW13 1SCA022078R0460 Conversion kits 65 OHG175J12 1SCA022381R2610 Pistol handles 47
OETLZW14 1SCA022077R3410 Conversion kits 65 OHG45J6 1SCA022380R8850 Pistol handles 47
OETLZW15 1SCA022081R9340 Conversion kits 65 OHG65J6 1SCA022380R9740 Pistol handles 47
OETLZW16 1SCA022095R2070 Cam attachment 69 OHG65J6E00S 1SCA022383R4510 Pistol handles 49
OETLZW3 1SCA022049R0380 Conversion kits 65 OHG65J6T 1SCA022456R9620 Pistol handles 47
OETLZW5 1SCA022052R3900 Cam attachment 69 OHG65J6TE00S 1SCA109014R1001 Pistol handles 49
OETLZW9 1SCA022061R3300 Conversion kits 65 OHG95J12 1SCA022381R0910 Pistol handles 47
OETLZX95 1SCA022083R5620 Shaft extension socket 53 OHY125J12 1SCA022381R1720 Pistol handles 47
OEZNL1 1SCA022723R7400 Solid links 59 OHY125J12T 1SCA022652R2310 Pistol handles 47
OEZNL10 1SCA116437R1001 Solid links 59 OHY145J12 1SCA022381R2370 Pistol handles 47
OEZNL8 1SCA113998R1001 Solid links 59 OHY145J12T 1SCA022652R2650 Pistol handles 47
OEZXU14/3 1SCA100361R1001 Terminal angle 61 OHY150J12P 1SCA101586R1001 Optional handles 48
OEZXU14/4 1SCA101082R1001 Terminal angle 61 OHY175J12 1SCA022381R2700 Pistol handles 47
OEZXU68/3 1SCA121380R1001 Terminal angle 61 OHY200J12P 1SCA101587R1001 Optional handles 48
OEZXU68/4 1SCA121379R1001 Terminal angle 61 OHY200J12PT 1SCA111512R1001 Optional handles 48
OFAE506 1SCA128175R1001 Fuse replacement handles 50 OHY274J12 1SCA115919R1001 Optional handles 48
OFAW00 1SCA022003R9680 Solid links 59 OHY330J12 1SCA115921R1001 Optional handles 48
OFAW1 1SCA022003R9760 Solid links 59 OHY45J6 1SCA022380R8930 Pistol handles 47
OFAW2 1SCA022003R9840 Solid links 59 OHY65J6 1SCA022380R9820 Pistol handles 47
OFAW3 1SCA022003R9920 Solid links 59 OHY65J6E00S 1SCA022382R9930 Pistol handles 49
OFD110EA 1SCA121775R1001 Electronic fuse monitor 67 OHY65J6T 1SCA022456R9540 Pistol handles 47
OFD500EA 1SCA121776R1001 Electronic fuse monitor 67 OHY65J6TE00S 1SCA022688R0140 Pistol handles 49
OFM240 1SCA022579R1340 Electronic fuse monitor 67 OHY95J12 1SCA022381R1050 Pistol handles 47
OFM260 1SCA022459R8560 Electronic fuse monitor 67 OHY95J12T 1SCA022736R1910 Pistol handles 47
OFM600 1SCA022579R1260 Electronic fuse monitor 67 OS100GB03N3P 1SCA125531R1001 Front operated switch fuse 28
OFM690 1SCA022459R8480 Electronic fuse monitor 67 OS100GB03N3P-42 1SCA129907R1001 Switch fuse, BS-type 31
OFMZX2 1SCA022475R9910 Electronic fuse monitor 67 OS100GB03P 1SCA114613R1001 Front operated switch fuse 28
OFS260 1SCA022716R0180 Electronic fuse monitor 67 OS100GB03P-42 1SCA128217R1001 Switch fuse, BS-type 31
OFS690 1SCA022715R9920 Electronic fuse monitor 67 OS100GB04N1P 1SCA114614R1001 Front operated switch fuse 28
OHB125J12 1SCA022381R1560 Pistol handles 47 OS100GB12N3P-42 1SCA129910R1001 Switch fuse, BS-type 31
OHB125J12T 1SCA022652R2220 Pistol handles 47 OS100GJ03 1SCA115436R1001 Front operated fusible disconnect 40
OHB145J12 1SCA022381R2110 Pistol handles 47 switches
OHB145J12E00S 1SCA022679R9700 Pistol handles 49 OS100GJ04F 1SCA115438R1001 Front operated fusible disconnect 40
OHB145J12T 1SCA022652R2570 Pistol handles 47 switches
OHB150J12P 1SCA022865R9430 Optional handles 48 OS100GJ12 1SCA115665R1001 Front operated fusible disconnect 40
OHB175J12 1SCA022381R2450 Pistol handles 47 switches

106 Index | Switch fuses OS and OSM


Type Order number Description Page Type Order number Description Page
OS100GJ22F 1SCA115668R1001 Front operated fusible disconnect 40 OS125GF04FP 1SCA115606R1001 Front operated switch fuses 38
switches OS125GF04N1P 1SCA115888R1001 Front operated switch fuses 38
OS100GJS30 1SCA115971R1001 Side operated fusible disconnect 42 OS125GFS30K 1SCA115944R1001 Side operated switch fuse 39
switches OS125GFS40FK 1SCA115946R1001 Side operated switch fuse 39
OS100GJS40F 1SCA115972R1001 Side operated fusible disconnect 42 OS125GFS40N1K 1SCA115945R1001 Side operated switch fuse 39
switches OS160GB03BBP 1SCA120657R1001 Special connected switch fuse 36
OS1200L02 1SCA116924R1001 Front operated fusible disconnect 41 OS160GB03K 1SCA116753R1001 Front operated switch fuse 32
switches OS160GB03N3P 1SCA122010R1001 Front operated switch fuse 28
OS1200L03 1SCA105467R1001 Front operated fusible disconnect 41 OS160GB03N3P-42 1SCA129916R1001 Switch fuse, BS-type 31
switches OS160GB03N3P-42 1SCA129916R1001 Front operated switch fuse 32
OS1200L04F 1SCA105465R1001 Front operated fusible disconnect 41 OS160GB03P 1SCA115413R1001 Front operated switch fuse 28
switches OS160GB03P-42 1SCA128213R1001 Switch fuse, BS-type 31
OS1250B02P 1SCA114070R1001 Front operated switch fuse 30 OS160GB03P-42 1SCA128213R1001 Front operated switch fuse 32
OS1250B03K 1SCA108715R1001 Front operated switch fuse 33 OS160GB04BBN1P 1SCA122598R1001 Special connected switch fuse 36
OS1250B03N3P 1SCA107936R1001 Front operated switch fuse 30 OS160GB04N1K 1SCA116754R1001 Front operated switch fuse 32
OS1250B03P 1SCA105250R1001 Front operated switch fuse 30 OS160GB04N1P 1SCA115896R1001 Front operated switch fuse 28
OS1250D02P 1SCA114051R1001 Front operated switch fuse 21 OS160GB12LRP 1SCA120271R1001 Special connected switch fuse 37
OS1250D03K 1SCA108718R1001 Front operated switch fuse 23 OS160GB12N3P-42 1SCA129919R1001 Switch fuse, BS-type 31
OS1250D03N3P 1SCA107932R1001 Front operated switch fuse 21 OS160GB21LRP 1SCA120273R1001 Special connected switch fuse 37
OS1250D03P 1SCA105475R1001 Front operated switch fuse 21 OS160GB22LRP 1SCA120277R1001 Special connected switch fuse 37
OS1250D04FP 1SCA105473R1001 Front operated switch fuse 21 OS160GBS30K 1SCA115927R1001 Side operated switch fuse 34
OS1250D04N2K 1SCA108719R1001 Front operated switch fuse 23 OS160GBS40N1K 1SCA115928R1001 Side operated switch fuse 34
OS1250D04N2P 1SCA105248R1001 Front operated switch fuse 21 OS160GD02P 1SCA116717R1001 Front operated switch fuse 19
OS1250DA02P 1SCA114059R1001 Front operated switch fuse 21 OS160GD03BBP 1SCA120655R1001 Special connected switch fuse 26
OS1250DA03K 1SCA108720R1001 Front operated switch fuse 23 OS160GD03K 1SCA116742R1001 Front operated switch fuse 22
OS1250DA03N3P 1SCA107934R1001 Front operated switch fuse 21 OS160GD03P 1SCA115399R1001 Front operated switch fuse 19
OS1250DA03P 1SCA105238R1001 Front operated switch fuse 21 OS160GD04BBN2P 1SCA120661R1001 Special connected switch fuse 26
OS1250DA04FP 1SCA105240R1001 Front operated switch fuse 21 OS160GD04FK 1SCA116880R1001 Front operated switch fuse 22
OS1250DA04N2K 1SCA108721R1001 Front operated switch fuse 23 OS160GD04FP 1SCA115402R1001 Front operated switch fuse 19
OS1250DA04N2P 1SCA105243R1001 Front operated switch fuse 21 OS160GD04N2K 1SCA116743R1001 Front operated switch fuse 22
OS125GB03BBP 1SCA120783R1001 Special connected switch fuse 36 OS160GD04N2P 1SCA115882R1001 Front operated switch fuse 19
OS125GB03N3P 1SCA122008R1001 Front operated switch fuse 28 OS160GD12LRP 1SCA120267R1001 Special connected switch fuse 27
OS125GB03N3P-42 1SCA129912R1001 Switch fuse, BS-type 31 OS160GD21LRP 1SCA120294R1001 Special connected switch fuse 27
OS125GB03N3P-42 1SCA129912R1001 Front operated switch fuse 32 OS160GD22LRP 1SCA120275R1001 Special connected switch fuse 27
OS125GB03P 1SCA115634R1001 Front operated switch fuse 28 OS160GDS30K 1SCA115935R1001 Side operated switch fuse 24
OS125GB03P-42 1SCA128215R1001 Switch fuse, BS-type 31 OS160GDS40N2K 1SCA115939R1001 Side operated switch fuse 24
OS125GB03P-42 1SCA128215R1001 Front operated switch fuse 32 OS200B02P 1SCA022769R7820 Front operated switch fuse 29
OS125GB04BBN1P 1SCA122597R1001 Special connected switch fuse 36 OS200B03BBP 1SCA102082R1001 Special connected switch fuse 36
OS125GB04N1P 1SCA115901R1001 Front operated switch fuse 28 OS200B03K 1SCA022763R6950 Front operated switch fuse 33
OS125GB12LRP 1SCA120258R1001 Special connected switch fuse 37 OS200B03N3P 1SCA022750R0620 Front operated switch fuse 29
OS125GB12N3P-42 1SCA129914R1001 Switch fuse, BS-type 31 OS200B03P 1SCA022709R9330 Front operated switch fuse 29
OS125GB21LRP 1SCA120261R1001 Special connected switch fuse 37 OS200B04BBN2P 1SCA102123R1001 Special connected switch fuse 36
OS125GB22LRP 1SCA120265R1001 Special connected switch fuse 37 OS200B12LRP 1SCA022854R2910 Special connected switch fuse 37
OS125GBS30K 1SCA116400R1001 Side operated switch fuse 34 OS200B21LRP 1SCA022854R3050 Special connected switch fuse 37
OS125GBS40N1K 1SCA115926R1001 Side operated switch fuse 34 OS200B22LRP 1SCA022854R4290 Special connected switch fuse 37
OS125GD02P 1SCA116716R1001 Front operated switch fuse 19 OS200BS30K 1SCA022870R7850 Side operated switch fuse 35
OS125GD03BBP 1SCA120802R1001 Special connected switch fuse 26 OS200BS40N2K 1SCA022870R8230 Side operated switch fuse 35
OS125GD03K 1SCA116878R1001 Front operated switch fuse 22 OS200D02P 1SCA022759R9220 Front operated switch fuse 20
OS125GD03P 1SCA115639R1001 Front operated switch fuse 19 OS200D03BBP 1SCA102150R1001 Special connected switch fuse 26
OS125GD04BBN2P 1SCA120806R1001 Special connected switch fuse 26 OS200D03K 1SCA022764R7130 Front operated switch fuse 23
OS125GD04FK 1SCA116741R1001 Front operated switch fuse 22 OS200D03N3P 1SCA022749R8710 Front operated switch fuse 20
OS125GD04FP 1SCA115686R1001 Front operated switch fuse 19 OS200D03P 1SCA022709R9500 Front operated switch fuse 20
OS125GD04N2K 1SCA116740R1001 Front operated switch fuse 22 OS200D04BBN2P 1SCA102139R1001 Special connected switch fuse 26
OS125GD04N2P 1SCA115877R1001 Front operated switch fuse 19 OS200D04FP 1SCA022725R4750 Front operated switch fuse 20
OS125GD12LRP 1SCA120062R1001 Special connected switch fuse 27 OS200D04N2K 1SCA022768R7430 Front operated switch fuse 23
OS125GD21LRP 1SCA120255R1001 Special connected switch fuse 27 OS200D04N2P 1SCA022709R9680 Front operated switch fuse 20
OS125GD22LRP 1SCA120263R1001 Special connected switch fuse 27 OS200DS30K 1SCA022871R1450 Side operated switch fuse 25
OS125GDS30K 1SCA115933R1001 Side operated switch fuse 24 OS200DS40FK 1SCA022871R1610 Side operated switch fuse 25
OS125GDS40N2K 1SCA115934R1001 Side operated switch fuse 24 OS200DZ03P 1SCA022797R3440 Front operated switch fuse 20
OS125GF02P 1SCA116727R1001 Front operated switch fuses 38 OS200DZ04N2P 1SCA022820R9230 Front operated switch fuse 20
OS125GF03P 1SCA115602R1001 Front operated switch fuses 38

Switch fuses OS and OSM | Index 107


Type Order number Description Page Type Order number Description Page
OS200J02 1SCA107591R1001 Front operated fusible disconnect 41 OS32GBS30K 1SCA115918R1001 Side operated switch fuse 34
switches OS32GBS40N1K 1SCA115923R1001 Side operated switch fuse 34
OS200J03 1SCA022733R6130 Front operated fusible disconnect 41 OS32GD02P 1SCA116714R1001 Front operated switch fuse 19
switches OS32GD03K 1SCA116733R1001 Front operated switch fuse 22
OS200J04F 1SCA022758R9340 Front operated fusible disconnect 41 OS32GD03P 1SCA115189R1001 Front operated switch fuse 19
switches OS32GD04FK 1SCA116737R1001 Front operated switch fuse 22
OS250B02P 1SCA022769R9440 Front operated switch fuse 29 OS32GD04FP 1SCA115196R1001 Front operated switch fuse 19
OS250B03BBP 1SCA102168R1001 Special connected switch fuse 36 OS32GD04N2K 1SCA116734R1001 Front operated switch fuse 22
OS250B03K 1SCA022763R6010 Front operated switch fuse 33 OS32GD04N2P 1SCA115193R1001 Front operated switch fuse 19
OS250B03N3P 1SCA022750R8010 Front operated switch fuse 29 OS32GDS30K 1SCA115929R1001 Side operated switch fuse 24
OS250B03P 1SCA022750R6660 Front operated switch fuse 29 OS32GDS40N1K 1SCA115930R1001 Side operated switch fuse 24
OS250B04BBN2P 1SCA102164R1001 Special connected switch fuse 36 OS32GDS40N2K 1SCA116402R1001 Side operated switch fuse 24
OS250B12LRP 1SCA022854R5690 Special connected switch fuse 37 OS400B02P 1SCA022813R7220 Front operated switch fuse 29
OS250B21LRP 1SCA022854R5850 Special connected switch fuse 37 OS400B03BBP 1SCA102252R1001 Special connected switch fuse 36
OS250B22LRP 1SCA022854R7210 Special connected switch fuse 37 OS400B03K 1SCA022763R6790 Front operated switch fuse 33
OS250BS30K 1SCA022870R8660 Side operated switch fuse 35 OS400B03N3P 1SCA022753R9160 Front operated switch fuse 29
OS250BS40N2K 1SCA022870R9040 Side operated switch fuse 35 OS400B03P 1SCA022719R0840 Front operated switch fuse 29
OS250D02P 1SCA022760R0170 Front operated switch fuse 20 OS400B04BBN2P 1SCA102248R1001 Special connected switch fuse 36
OS250D03BBP 1SCA102190R1001 Special connected switch fuse 26 OS400B12LRP 1SCA022855R1400 Special connected switch fuse 37
OS250D03K 1SCA022763R6360 Front operated switch fuse 23 OS400B21LRP 1SCA022855R1580 Special connected switch fuse 37
OS250D03N3P 1SCA022749R9430 Front operated switch fuse 20 OS400B22LRP 1SCA022855R2710 Special connected switch fuse 37
OS250D03P 1SCA022719R0090 Front operated switch fuse 20 OS400BS30K 1SCA022871R0210 Side operated switch fuse 35
OS250D04BBN2P 1SCA102205R1001 Special connected switch fuse 26 OS400BS40N2K 1SCA022871R0640 Side operated switch fuse 35
OS250D04FP 1SCA022726R8620 Front operated switch fuse 20 OS400D02P 1SCA022811R2740 Front operated switch fuse 20
OS250D04N2K 1SCA022763R6440 Front operated switch fuse 23 OS400D03BBP 1SCA102260R1001 Special connected switch fuse 26
OS250D04N2P 1SCA022719R2380 Front operated switch fuse 20 OS400D03K 1SCA022779R5410 Front operated switch fuse 23
OS250D12LRP 1SCA022852R8410 Special connected switch fuse 27 OS400D03N3P 1SCA022753R9320 Front operated switch fuse 20
OS250D21LRP 1SCA022852R8500 Special connected switch fuse 27 OS400D03P 1SCA022719R0250 Front operated switch fuse 20
OS250D22LRP 1SCA022853R0310 Special connected switch fuse 27 OS400D04BBN2P 1SCA102289R1001 Special connected switch fuse 26
OS250DS30K 1SCA022871R2260 Side operated switch fuse 25 OS400D04FP 1SCA022753R7110 Front operated switch fuse 20
OS250DS40FK 1SCA022871R2420 Side operated switch fuse 25 OS400D04N2K 1SCA022763R7250 Front operated switch fuse 23
OS25FFS3010 1SCA108639R1001 Side operated switch fuse 39 OS400D04N2P 1SCA022719R2460 Front operated switch fuse 20
OS25FFS3010-2 1SCA108808R1001 Side operated switch fuse 39 OS400D12LRP 1SCA022853R2280 Special connected switch fuse 27
OS30FACC12 1SCA108813R1001 Front operated fusible disconnect 40 OS400D21LRP 1SCA022853R2360 Special connected switch fuse 27
switches OS400D22LRP 1SCA022853R4140 Special connected switch fuse 27
OS30FACC22F 1SCA108819R1001 Front operated fusible disconnect 40 OS400DS30K 1SCA022871R2930 Side operated switch fuse 25
switches OS400DS40FK 1SCA022871R3150 Side operated switch fuse 25
OS30FACCS30 1SCA108822R1001 Side operated fusible disconnect 42 OS400J02 1SCA107592R1001 Front operated fusible disconnect 41
switches switches
OS30FAJ12 1SCA108824R1001 Front operated fusible disconnect 40 OS400J03 1SCA022755R0810 Front operated fusible disconnect 41
switches switches
OS30FAJ22F 1SCA108829R1001 Front operated fusible disconnect 40 OS400J04F 1SCA022755R3660 Front operated fusible disconnect 41
switches switches
OS30FAJS30 1SCA108834R1001 Side operated fusible disconnect 42 OS50GF02P 1SCA118345R1001 Front operated switch fuses 38
switches OS50GF03P 1SCA115492R1001 Front operated switch fuses 38
OS315B02P 1SCA022817R3450 Front operated switch fuse 29 OS50GF04FP 1SCA115498R1001 Front operated switch fuses 38
OS315B03BBP 1SCA102222R1001 Special connected switch fuse 36 OS50GF04N1P 1SCA115495R1001 Front operated switch fuses 38
OS315B03K 1SCA022763R6520 Front operated switch fuse 33 OS50GFS30K 1SCA116404R1001 Side operated switch fuse 39
OS315B03N3P 1SCA022753R8940 Front operated switch fuse 29 OS50GFS40FK 1SCA116425R1001 Side operated switch fuse 39
OS315B03P 1SCA022719R0680 Front operated switch fuse 29 OS50GFS40N1K 1SCA116013R1001 Side operated switch fuse 39
OS315B04BBN2P 1SCA102225R1001 Special connected switch fuse 36 OS600J02 1SCA107593R1001 Front operated fusible disconnect 41
OS315B12LRP 1SCA022854R8790 Special connected switch fuse 37 switches
OS315B21LRP 1SCA022854R8870 Special connected switch fuse 37 OS600J03 1SCA022825R8610 Front operated fusible disconnect 41
OS315B22LRP 1SCA022855R0000 Special connected switch fuse 37 switches
OS315BS30K 1SCA022870R9470 Side operated switch fuse 35 OS600J04F 1SCA022839R3900 Front operated fusible disconnect 41
OS315BS40N2K 1SCA022870R9800 Side operated switch fuse 35 switches
OS32GB02P 1SCA116721R1001 Front operated switch fuse 28 OS60GJ03 1SCA115866R1001 Front operated fusible disconnect 40
OS32GB03K 1SCA116744R1001 Front operated switch fuse 32 switches
OS32GB03P 1SCA115259R1001 Front operated switch fuse 28 OS60GJ04F 1SCA115445R1001 Front operated fusible disconnect 40
OS32GB04N1K 1SCA116856R1001 Front operated switch fuse 32 switches
OS32GB04N1P 1SCA114610R1001 Front operated switch fuse 28

108 Index | Switch fuses OS and OSM


Type Order number Description Page Type Order number Description Page
OS60GJ12 1SCA122981R1001 Front operated fusible disconnect 40 OSB160/4 1SCA131820R1001 Phase barries 59
switches OSB160/6 1SCA131821R1001 Phase barries 59
OS60GJ22F 1SCA115468R1001 Front operated fusible disconnect 40 OSB250/4 1SCA131822R1001 Phase barries 59
switches OSB250/6 1SCA131823R1001 Phase barries 59
OS60GJS30 1SCA116051R1001 Side operated fusible disconnect 42 OSD25P3 1SCA022192R9060 Blown fuse indicators (DPMM) 68
switches OSD25P4 1SCA022196R9520 Blown fuse indicators (DPMM) 68
OS60GJS40F 1SCA115970R1001 Side operated fusible disconnect 42 OSGD125P3 1SCA115690R1001 Blown fuse indicators (DPMM) 68
switches OSGD125P4 1SCA115692R1001 Blown fuse indicators (DPMM) 68
OS630B02P 1SCA113529R1001 Front operated switch fuse 30 OSGD50P3 1SCA116401R1001 Blown fuse indicators (DPMM) 68
OS630B03K 1SCA108708R1001 Front operated switch fuse 33 OSGD50P4 1SCA115689R1001 Blown fuse indicators (DPMM) 68
OS630B03N3P 1SCA100860R1001 Front operated switch fuse 30 OSGZD1 1SCA115688R1001 Mounting accessories 70
OS630B03P 1SCA022825R5850 Front operated switch fuse 30 OSM100GB3M230C 1SCA116679R1001 Motorized switch fuse 44
OS630BS30K 1SCA108148R1001 Side operated switch fuse 35 OSM100GB4N1M230C 1SCA118779R1001 Motorized switch fuse 44
OS630BS40N2K 1SCA108151R1001 Side operated switch fuse 35 OSM1250B3M230C 1SCA112552R1001 Motorized switch fuse 44
OS630D02P 1SCA107745R1001 Front operated switch fuse 21 OSM1250B3N3M230C 1SCA112550R1001 Motorized switch fuse 44
OS630D03K 1SCA108704R1001 Front operated switch fuse 23 OSM1250B4N1M230C 1SCA118795R1001 Motorized switch fuse 44
OS630D03N3P 1SCA100858R1001 Front operated switch fuse 21 OSM1250D3M230C 1SCA112549R1001 Motorized switch fuse 43
OS630D03P 1SCA022825R2830 Front operated switch fuse 21 OSM1250D3N3M230C 1SCA112547R1001 Motorized switch fuse 43
OS630D04FP 1SCA022825R4610 Front operated switch fuse 21 OSM1250D4N2M230C 1SCA118850R1001 Motorized switch fuse 43
OS630D04N2K 1SCA108705R1001 Front operated switch fuse 23 OSM1250DA3M230C 1SCA112546R1001 Motorized switch fuse 43
OS630D04N2P 1SCA022825R4290 Front operated switch fuse 21 OSM1250DA3N3M230C 1SCA112544R1001 Motorized switch fuse 43
OS630DS30K 1SCA108136R1001 Side operated switch fuse 25 OSM1250DA4N2M230C 1SCA118851R1001 Motorized switch fuse 43
OS630DS40FK 1SCA108138R1001 Side operated switch fuse 25 OSM125GB3M230C 1SCA116677R1001 Motorized switch fuse 44
OS63GB02P 1SCA116854R1001 Front operated switch fuse 28 OSM125GB4N1M230C 1SCA118780R1001 Motorized switch fuse 44
OS63GB03K 1SCA116745R1001 Front operated switch fuse 32 OSM125GD3M230C 1SCA116674R1001 Motorized switch fuse 43
OS63GB03P 1SCA115235R1001 Front operated switch fuse 28 OSM125GD4N2M230C 1SCA118828R1001 Motorized switch fuse 43
OS63GB04N1K 1SCA116746R1001 Front operated switch fuse 32 OSM160GB3M230C 1SCA116670R1001 Motorized switch fuse 44
OS63GB04N1P 1SCA115238R1001 Front operated switch fuse 28 OSM160GB4N1M230C 1SCA118781R1001 Motorized switch fuse 44
OS63GBS30K 1SCA115924R1001 Side operated switch fuse 34 OSM160GD3M230C 1SCA116673R1001 Motorized switch fuse 43
OS63GBS40N1K 1SCA115979R1001 Side operated switch fuse 34 OSM160GD4N2M230C 1SCA118831R1001 Motorized switch fuse 43
OS63GD02P 1SCA116715R1001 Front operated switch fuse 19 OSM200B3M230C 1SCA104272R1001 Motorized switch fuse 44
OS63GD03K 1SCA116738R1001 Front operated switch fuse 22 OSM200B3N3M230C 1SCA104323R1001 Motorized switch fuse 44
OS63GD03P 1SCA115207R1001 Front operated switch fuse 19 OSM200B4N1M230C 1SCA118784R1001 Motorized switch fuse 44
OS63GD04FK 1SCA116739R1001 Front operated switch fuse 22 OSM200D3M230C 1SCA104284R1001 Motorized switch fuse 43
OS63GD04FP 1SCA115228R1001 Front operated switch fuse 19 OSM200D3N3M230C 1SCA104282R1001 Motorized switch fuse 43
OS63GD04N2K 1SCA116876R1001 Front operated switch fuse 22 OSM200D4N2M230C 1SCA118836R1001 Motorized switch fuse 43
OS63GD04N2P 1SCA115209R1001 Front operated switch fuse 19 OSM250B3M230C 1SCA104287R1001 Motorized switch fuse 44
OS63GDS30K 1SCA115931R1001 Side operated switch fuse 24 OSM250B3N3M230C 1SCA104290R1001 Motorized switch fuse 44
OS63GDS40N1K 1SCA115932R1001 Side operated switch fuse 24 OSM250B4N1M230C 1SCA118785R1001 Motorized switch fuse 44
OS63GDS40N2K 1SCA116403R1001 Side operated switch fuse 24 OSM250D3M230C 1SCA104295R1001 Motorized switch fuse 43
OS800B02P 1SCA022837R6480 Front operated switch fuse 30 OSM250D3N3M230C 1SCA104297R1001 Motorized switch fuse 43
OS800B03K 1SCA108713R1001 Front operated switch fuse 33 OSM250D4N2M230C 1SCA118838R1001 Motorized switch fuse 43
OS800B03N3P 1SCA100861R1001 Front operated switch fuse 30 OSM315B3M230C 1SCA104303R1001 Motorized switch fuse 44
OS800B03P 1SCA022825R7550 Front operated switch fuse 30 OSM315B3N3M230C 1SCA104306R1001 Motorized switch fuse 44
OS800BS30K 1SCA108084R1001 Side operated switch fuse 35 OSM315B4N1M230C 1SCA118788R1001 Motorized switch fuse 44
OS800BS40N2K 1SCA108087R1001 Side operated switch fuse 35 OSM32GB3M230C 1SCA116662R1001 Motorized switch fuse 44
OS800D02P 1SCA022837R2650 Front operated switch fuse 21 OSM32GB4N1M230C 1SCA118775R1001 Motorized switch fuse 44
OS800D03K 1SCA108725R1001 Front operated switch fuse 23 OSM32GD3M230C 1SCA116664R1001 Motorized switch fuse 43
OS800D03N3P 1SCA100859R1001 Front operated switch fuse 21 OSM32GD4N2M230C 1SCA118822R1001 Motorized switch fuse 43
OS800D03P 1SCA022825R4880 Front operated switch fuse 21 OSM400B3M230C 1SCA104310R1001 Motorized switch fuse 44
OS800D04FP 1SCA022825R5000 Front operated switch fuse 21 OSM400B3N3M230C 1SCA104312R1001 Motorized switch fuse 44
OS800D04N2K 1SCA108722R1001 Front operated switch fuse 23 OSM400B4N1M230C 1SCA118789R1001 Motorized switch fuse 44
OS800D04N2P 1SCA022825R5180 Front operated switch fuse 21 OSM400D3M230C 1SCA104315R1001 Motorized switch fuse 43
OS800DS30K 1SCA108099R1001 Side operated switch fuse 25 OSM400D3N3M230C 1SCA104317R1001 Motorized switch fuse 43
OS800DS40FK 1SCA108101R1001 Side operated switch fuse 25 OSM400D4N2M230C 1SCA118842R1001 Motorized switch fuse 43
OS800L02 1SCA116920R1001 Front operated fusible disconnect 41 OSM630B3M230C 1SCA104516R1001 Motorized switch fuse 44
switches OSM630B3N3M230C 1SCA104535R1001 Motorized switch fuse 44
OS800L03 1SCA022825R9760 Front operated fusible disconnect 41 OSM630B4N1M230C 1SCA118791R1001 Motorized switch fuse 44
switches OSM630D3M230C 1SCA104518R1001 Motorized switch fuse 43
OS800L04F 1SCA022839R5350 Front operated fusible disconnect 41 OSM630D3N3M230C 1SCA104533R1001 Motorized switch fuse 43
switches OSM630D4N2M230C 1SCA118846R1001 Motorized switch fuse 43

Switch fuses OS and OSM | Index 109


Type Order number Description Page Type Order number Description Page
OSM63GB3M230C 1SCA116657R1001 Motorized switch fuse 44 OSS400G4LSL 1SCA100398R1001 Three and four pole terminal 61
OSM63GB4N1M230C 1SCA118776R1001 Motorized switch fuse 44 shroud
OSM63GD3M230C 1SCA116660R1001 Motorized switch fuse 43 OSS400G4LSR 1SCA100400R1001 Three and four pole terminal 61
OSM63GD4N2M230C 1SCA118865R1001 Motorized switch fuse 43 shroud
OSM800B3M230C 1SCA104520R1001 Motorized switch fuse 44 OSS400G4SSL 1SCA100392R1001 Three and four pole terminal 61
OSM800B3N3M230C 1SCA104536R1001 Motorized switch fuse 44 shroud
OSM800B4N1M230C 1SCA118792R1001 Motorized switch fuse 44 OSS400G4SSR 1SCA100394R1001 Three and four pole terminal 61
OSM800D3M230C 1SCA104522R1001 Motorized switch fuse 43 shroud
OSM800D3N3M230C 1SCA104534R1001 Motorized switch fuse 43 OSS800G1L/3 1SCA022776R7200 Terminal shroud 60
OSM800D4N2M230C 1SCA118847R1001 Motorized switch fuse 43 OSS800G1L/4 1SCA022776R7380 Terminal shroud 60
OSP1250B 1SCA107950R1001 Fourth poles 57 OSS800G1S/3 1SCA022776R7540 Terminal shroud 60
OSP1250D 1SCA107946R1001 Fourth poles 57 OSS800G1S/4 1SCA022776R7460 Terminal shroud 60
OSP1250DA 1SCA112402R1001 Fourth poles 57 OSV1250DK 1SCA107797R1001 Direct mount handles 50
OSP1250N 1SCA107943R1001 Fourth poles 57 OSV200BK 1SCA022779R7530 Direct mount handles 50
OSP160GB 1SCA114769R1001 Fourth poles 57 OSV250DK 1SCA022763R3510 Direct mount handles 50
OSP160GD 1SCA114768R1001 Fourth poles 57 OSV400BK 1SCA022763R3930 Direct mount handles 50
OSP160GN 1SCA114770R1001 Fourth poles 57 OSV400DK 1SCA022763R4230 Direct mount handles 50
OSP200B 1SCA022735R9180 Fourth poles 57 OSV800DK 1SCA107794R1001 Direct mount handles 50
OSP200D 1SCA022735R8960 Fourth poles 57 OSVY1250DK 1SCA108702R1001 Direct mount handles 50
OSP200N 1SCA022735R8700 Fourth poles 57 OSVY200BK 1SCA022779R7700 Direct mount handles 50
OSP250B 1SCA022770R4030 Fourth poles 57 OSVY250DK 1SCA022778R6500 Direct mount handles 50
OSP250D 1SCA022735R9340 Fourth poles 57 OSVY400BK 1SCA022779R5830 Direct mount handles 50
OSP250N 1SCA022735R9260 Fourth poles 57 OSVY400DK 1SCA022779R5590 Direct mount handles 50
OSP400B 1SCA022770R3140 Fourth poles 57 OSVY800DK 1SCA108703R1001 Direct mount handles 50
OSP400D 1SCA022770R3220 Fourth poles 57 OSZ1 1SCA022481R3710 Neutral links 58
OSP400N 1SCA022770R3490 Fourth poles 57 OSZ2 1SCA022481R3800 Neutral links 58
OSP800B 1SCA100434R1001 Fourth poles 57 OSZ4 1SCA022530R0200 Electronic fuse monitor 67
OSP800D 1SCA100433R1001 Fourth poles 57 OSZT1A 1SCA106532R1001 Mechanism interlock kits & 69
OSP800N 1SCA100432R1001 Fourth poles 57 Electrical interlocks
OSS1250G1L/3 1SCA107938R1001 Terminal shroud 60 OSZT1L 1SCA106538R1001 Mechanism interlock kits & 69
OSS1250G1L/4 1SCA107940R1001 Terminal shroud 60 Electrical interlocks
OSS1250G1S/3 1SCA107939R1001 Terminal shroud 60 OSZT2A 1SCA106534R1001 Mechanism interlock kits & 69
OSS1250G1S/4 1SCA107941R1001 Terminal shroud 60 Electrical interlocks
OSS160GG1L/3 1SCA114764R1001 Terminal shroud 60 OSZT2L 1SCA106539R1001 Mechanism interlock kits & 69
OSS160GG1L/4 1SCA114765R1001 Terminal shroud 60 Electrical interlocks
OSS160GG1S/3 1SCA114766R1001 Terminal shroud 60 OSZT3A 1SCA106535R1001 Mechanism interlock kits & 69
OSS160GG1S/4 1SCA114767R1001 Terminal shroud 60 Electrical interlocks
OSS160GG3LS 1SCA121570R1001 Three and four pole terminal 61 OSZT3L 1SCA106540R1001 Mechanism interlock kits & 69
shroud Electrical interlocks
OSS160GG4LS 1SCA121571R1001 Three and four pole terminal 61 OSZT4A 1SCA106536R1001 Mechanism interlock kits & 69
shroud Electrical interlocks
OSS200G1L/3 1SCA022731R8910 Terminal shroud 60 OSZT4L 1SCA106541R1001 Mechanism interlock kits & 69
OSS200G1L/4 1SCA022731R9040 Terminal shroud 60 Electrical interlocks
OSS200G1S/3 1SCA022732R0130 Terminal shroud 60 OSZX3 1SCA101224R1001 Blown fuse indicators (DPMM) 68
OSS200G1S/4 1SCA022732R0050 Terminal shroud 60 OSZX4 1SCA101225R1001 Blown fuse indicators (DPMM) 68
OSS250G1L 1SCA022727R5080 Terminal shroud 60 OTS1600G1L 1SCA106134R1001 Terminal shroud 60
OSS250G1L/3 1SCA022731R9390 Terminal shroud 60 OTS1600G1S 1SCA102667R1001 Terminal shroud 60
OSS250G1L/4 1SCA022731R9470 Terminal shroud 60 OTS250G1L 1SCA022715R5340 Terminal shroud 60
OSS250G1S 1SCA022727R4940 Terminal shroud 60 OTS250G1S 1SCA022715R5260 Terminal shroud 60
OSS250G1S/3 1SCA022731R9550 Terminal shroud 60 OTS800G1L 1SCA022776R7710 Terminal shroud 60
OSS250G1S/4 1SCA022731R9630 Terminal shroud 60 OTS800G1S 1SCA022776R8010 Terminal shroud 60
OSS250G1SH/1 1SCA103500R1001 Terminal shroud 60 OTVS1 1SCA111413R1001 Handle and spare fuse storage clip 59
OSS400G1L/3 1SCA022776R6650 Terminal shroud 60 OTVS2 1SCA111414R1001 Handle and spare fuse storage clip 59
OSS400G1L/4 1SCA022776R6730 Terminal shroud 60 OTZT1A 1SCA106522R1001 Mechanism interlock kits & 69
OSS400G1S/3 1SCA022776R6900 Terminal shroud 60 Electrical interlocks
OSS400G1S/4 1SCA022776R7030 Terminal shroud 60 OTZT1L 1SCA106527R1001 Mechanism interlock kits & 69
OSS400G1SH/1 1SCA103503R1001 Terminal shroud 60 Electrical interlocks
OSS400G3LS 1SCA100396R1001 Three and four pole terminal 61 OTZW10 1SCA022431R5280 Conversion kits 65
shroud OTZW25 1SCA022778R6920 Conversion kits 65
OSS400G3SS 1SCA100390R1001 Three and four pole terminal 61 OTZW26 1SCA022778R7060 Conversion kits 65
shroud OWC6DSH1 1SCA105251R1001 Conversion kits 65

110 Index | Switch fuses OS and OSM


Type Order number Description Page Type Order number Description Page
OWC6DSH2 1SCA105252R1001 Conversion kits 65 OXP6X400 1SCA108226R1001 Extended shafts 51
OWM6DS1 1SCA105253R1001 Conversion kits 65 OXP6X400-451) 1SCA108229R1001 Extended shafts 51
OWM6DS2 1SCA105254R1001 Conversion kits 65 OXP6X400-451) 1SCA108229R1001 Extended shafts 51
OWP6DS1 1SCA105255R1001 Conversion kits 65 OXP6X430 1SCA022056R6030 Extended shafts 51
OWP6DS2 1SCA105256R1001 Conversion kits 65 OXP6X430 1SCA022056R6030 Extended shafts 52
OXN1250S 1SCA104163R1001 Neutral links 58 OXP6X63 1SCA111010R1001 Extended shafts 51
OXN250 1SCA022752R9950 Neutral links 58 OXP6X63 1SCA111010R1001 Extended shafts 52
OXN250 1SCA022752R9950 Neutral links 58 OXP6X90 1SCA022064R1180 Extended shafts 51
OXN400 1SCA022770R3060 Neutral links 58 OXP6X90 1SCA022064R1180 Extended shafts 52
OXN800S 1SCA022831R4880 Neutral links 58 OZXB17 1SCA022859R3230 Terminal clamp sets 62
OXP12X2503) 1SCA022325R6980 Extended shafts 52 OZXB1L 1SCA022169R2030 Terminal clamp sets 62
OXP12X280 1SCA022137R5140 Extended shafts 52 OZXB1L 1SCA022169R2030 Terminal clamp sets 62
OXP12X2802) 1SCA022137R5140 Extended shafts 53 OZXB1L 1SCA022169R2030 Terminal clamp sets 62
OXP12X280-451) 1SCA022382R0800 Extended shafts 53 OZXB2 1SCA022119R7610 Terminal clamp sets 62
OXP12X325 1SCA022042R5810 Extended shafts 52 OZXB2K 1SCA022264R0010 Single pole terminal shroud 61
OXP12X325 1SCA022042R5810 Extended shafts 53 OZXB2K/1 1SCA022644R6700 Single pole terminal shroud 61
OXP12X325-451) 1SCA022304R4450 Extended shafts 53 OZXB2L 1SCA022158R7750 Terminal clamp sets 62
OXP12X395 1SCA022042R5990 Extended shafts 52 OZXB2L 1SCA022158R7750 Terminal clamp sets 62
OXP12X395 1SCA022042R5990 Extended shafts 53 OZXB2L 1SCA022158R7750 Terminal clamp sets 63
OXP12X3952) 1SCA022042R5990 Extended shafts 53 OZXB3 1SCA022136R8100 Terminal clamp sets 62
OXP12X465 1SCA022042R6020 Extended shafts 52 OZXB3 1SCA022136R8100 Terminal clamp sets 63
OXP12X465 1SCA022042R6020 Extended shafts 53 OZXB3 1SCA022136R8100 Terminal clamp sets 63
OXP12X465 1SCA022042R6020 Extended shafts 53 OZXB3 1SCA022136R8100 Terminal clamp sets 64
OXP12X535 1SCA022042R6110 Extended shafts 52 OZXB3K 1SCA022264R0440 Single pole terminal shroud 61
OXP12X535 1SCA022042R6110 Extended shafts 53 OZXB3K/1 1SCA022644R6880 Single pole terminal shroud 61
OXP12X535 1SCA022042R6110 Extended shafts 53 OZXB4 1SCA022137R4760 Terminal clamp sets 62
OXP6X130 1SCA022057R0570 Extended shafts 51 OZXB4 1SCA022137R4760 Terminal clamp sets 63
OXP6X130 1SCA022057R0570 Extended shafts 52 OZXB4 1SCA022137R4760 Terminal clamp sets 63
OXP6X150-451) 1SCA022294R4400 Extended shafts 51 OZXB4 1SCA022137R4760 Terminal clamp sets 64
OXP6X150-451) 1SCA022294R4400 Extended shafts 51 OZXB4K 1SCA022199R2850 Single pole terminal shroud 61
OXP6X1505) 1SCA022295R5600 Extended shafts 51 OZXB4K/1 1SCA022644R6960 Single pole terminal shroud 61
OXP6X1505) 1SCA022295R5600 Extended shafts 51 OZXB5 1SCA022137R2470 Terminal clamp sets 62
OXP6X161 1SCA022067R1760 Extended shafts 52 OZXB5 1SCA022137R2470 Terminal clamp sets 63
OXP6X161 1SCA022067R1760 Extended shafts 52 OZXB5 1SCA022137R2470 Terminal clamp sets 63
OXP6X1613) 1SCA022067R1760 Extended shafts 51 OZXB5 1SCA022137R2470 Terminal clamp sets 64
OXP6X1613) 1SCA022067R1760 Extended shafts 52 OZXB5K 1SCA022283R8040 Single pole terminal shroud 61
OXP6X170 1SCA108224R1001 Extended shafts 51 OZXB5K/1 1SCA022644R7000 Single pole terminal shroud 61
OXP6X170 1SCA108224R1001 Extended shafts 51 OZXB6 1SCA022137R4920 Terminal clamp sets 63
OXP6X170-451) 1SCA108227R1001 Extended shafts 51 OZXB6 1SCA022137R4920 Terminal clamp sets 63
OXP6X170-451) 1SCA108227R1001 Extended shafts 51 OZXB6 1SCA022137R4920 Terminal clamp sets 64
OXP6X210 1SCA022295R6080 Extended shafts 51 OZXB7 1SCA022185R0040 Terminal clamp sets 63
OXP6X210 1SCA022295R6080 Extended shafts 52 OZXB7L 1SCA022185R7130 Terminal clamp sets 62
OXP6X2103) 1SCA022295R6080 Extended shafts 52 OZXB7L 1SCA022185R7130 Terminal clamp sets 63
OXP6X2103) 1SCA022295R6080 Extended shafts 52 OZXB7L 1SCA022185R7130 Terminal clamp sets 64
OXP6X210-451) 1SCA022294R4230 Extended shafts 51 OZXB8 1SCA022744R1510 Terminal clamp sets 62
OXP6X210-451) 1SCA022294R4230 Extended shafts 52 OZXB8 1SCA022744R1510 Terminal clamp sets 62
OXP6X265 1SCA108225R1001 Extended shafts 51 OZXB8 1SCA022744R1510 Terminal clamp sets 62
OXP6X265 1SCA108225R1001 Extended shafts 51 OZXB8 1SCA022744R1510 Terminal clamp sets 63
OXP6X265-451) 1SCA108228R1001 Extended shafts 51 OZXB8 1SCA022744R1510 Terminal clamp sets 63
OXP6X265-451) 1SCA108228R1001 Extended shafts 51 OZXB8 1SCA022744R1510 Terminal clamp sets 64
OXP6X290 1SCA022042R6370 Extended shafts 51 OZXB9 1SCA022750R3210 Terminal clamp sets 62
OXP6X290 1SCA022042R6370 Extended shafts 52 OZXB9 1SCA022750R3210 Terminal clamp sets 62
OXP6X290 1SCA022042R6370 Extended shafts 52 OZXB9 1SCA022750R3210 Terminal clamp sets 63
OXP6X290 1SCA022042R6370 Extended shafts 52 OZXB9 1SCA022750R3210 Terminal clamp sets 63
OXP6X290-451) 1SCA022304R4290 Extended shafts 51 OZXB9 1SCA022750R3210 Terminal clamp sets 64
OXP6X290-451) 1SCA022304R4290 Extended shafts 52 OZXP120 1SCA115540R1001 Terminal clamp sets 64
OXP6X360 1SCA022042R6530 Extended shafts 51 OZXP150 1SCA115541R1001 Terminal clamp sets 64
OXP6X360 1SCA022042R6530 Extended shafts 52 OZXP240 1SCA115542R1001 Terminal clamp sets 64
OXP6X360-451) 1SCA022341R4640 Extended shafts 51 OZXP240 1SCA115542R1001 Terminal clamp sets 64
OXP6X360-451) 1SCA022341R4640 Extended shafts 52 OZXP240 1SCA115542R1001 Terminal clamp sets 64
OXP6X400 1SCA108226R1001 Extended shafts 51 OZXP2X240 1SCA115544R1001 Terminal clamp sets 64

Switch fuses OS and OSM | Index 111


Type Order number Description Page
OZXP2X240 1SCA115544R1001 Terminal clamp sets 64
OZXP300 1SCA115543R1001 Terminal clamp sets 64
OZXP95 1SCA115539R1001 Terminal clamp sets 64
OZXP95 1SCA115539R1001 Terminal clamp sets 64
OZXR185 1SCA115531R1001 Terminal clamp sets 64
OZXR185 1SCA115531R1001 Terminal clamp sets 64
OZXR240 1SCA115532R1001 Terminal clamp sets 64
OZXR2X185 1SCA115534R1001 Terminal clamp sets 64
OZXR2X185 1SCA115534R1001 Terminal clamp sets 64
OZXR2X185 1SCA115534R1001 Terminal clamp sets 64
OZXR2X300 1SCA115535R1001 Terminal clamp sets 64
OZXR300 1SCA115533R1001 Terminal clamp sets 64
OZXR70 1SCA115529R1001 Terminal clamp sets 64
OZXR95 1SCA115530R1001 Terminal clamp sets 64
OZXR95 1SCA115530R1001 Terminal clamp sets 64
OZXT1 1SCA022469R6310 Terminal clamp sets 62
PB200 high 1SDA054972R1 Phase barries 59
PB200 high 1SDA054973R1 Phase barries 59
PDAL2/110AC50Hz 1SCA106543R1001 Coils 70
PDAL2/110AC60Hz 1SCA107100R1001 Coils 70
PDAL2/110DC 1SCA107105R1001 Coils 70
PDAL2/120AC60Hz 1SCA111353R1001 Coils 70
PDAL2/125DC 1SCA111338R1001 Coils 70
PDAL2/208AC60Hz 1SCA107101R1001 Coils 70
PDAL2/220DC 1SCA112503R1001 Coils 70
PDAL2/230AC50Hz 1SCA107102R1001 Coils 70
PDAL2/240AC60Hz 1SCA111356R1001 Coils 70
PDAL2/24AC60Hz 1SCA111350R1001 Coils 70
PDAL2/24DC 1SCA106542R1001 Coils 70
PDAL2/48DC 1SCA107103R1001 Coils 70
PDAL2/60DC 1SCA107104R1001 Coils 70

112 Index | Switch fuses OS and OSM


For Your Notes

Switch fuses OS and OSM | Index 113


For Your Notes

114 Index | Switch fuses OS and OSM


For Your Notes

Switch fuses OS and OSM | Index 115


Contact us

Note: We reserve the right to make technical changes or


ABB Oy modify the contents of this document without prior notice.

Copyright ABB. Catalogue OS1GB 15-08, 1SCC311013C0201


With regard to purchase orders, the agreed particulars shall
Breakers and Switches prevail. ABB AG does not accept any responsibility whatsoever
for potential errors or possible lack of information in this document.
P.O. Box 622 We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
FI-65101 Vaasa, Finland to third parties or utilization of its contents in whole or in parts
Phone: +358 10 22 11 is forbidden without prior written consent of ABB AG.

Fax: +358 10 22 45708 Copyright 2014 ABB


All rights reserved
E-Mail: firstname.surname@fi.abb.com

http://new.abb.com/low-voltage/

You can find the address of your local sales organization


on the ABB homepage:

www.abb.com/contacts
> Low Voltage Products and Systems

You might also like