AOP#1
Auto Start
S. Description
No.
1. AOP-1 will auto start with SLC AOP-1 On & AOP-2 OFF & AOP-2 Status
Discrepancy (MCC Fault)
2. AOP-1 will auto start with SLC AOP-1 On & AOP-2 Trip
3. AOP-1 will auto start with SLC AOP-1 On & Discharge Header Press<4.8
Ksc **
4. AOP-1 will auto start with SGC Oil On & Turbine Speed<2850 rpm
5. Manual Command
** Discharge Header pressure is through Transmitters MAV21CP001&CP002
(1 out of 2 logic or Average of two)
Auto Stop
S. Description
No.
1. With Fire Protection-1 or 2 (UCB,TG Floor, MOT Room) Operated AOP-1 will auto
Stop
2. AOP-1 will auto Stop with SGC Oil On & Turbine Speed>2850 rpm & Discharge
Header Press>7.0 Ksc **
3. Manual Command
# Fire Protection -2 is Operated through only MMI .Other Fire Protection Point are not
Ready/Erected (MOT room,13 Mtr. Near Turbine Floor.)
Auto Start
S. Description
No.
1. SLC AOP-2 On &AOP-1 off & AOP-1 Status Discrepancy (MCC Fault)
2. SLC AOP-2 On & AOP-1 Trip
3. SLC AOP-2 On & Discharge Header Press<4.5 Ksc **
4. SGC Oil On & Turbine Speed<2850 rpm
5. Manual Command
** Discharge Header pressure is through Transmitters MAV21CP001&CP002
(1 out of 2 logic or Average of two)
Auto Stop
2. AOP-2 will auto Stop with SGC Oil On & Turbine Speed>2850 rpm & Discharge
Header Press>7.0 Ksc **
3. Manual Command
# Fire Protection -2 is Operated through only MMI .Other Fire Protection Point are not
Ready/Erected (MOT room,13 Mtr. Near Turbine Floor.)
TG-LUB OIL SYSTEM
EOP#AC
Auto Start
S. Description
No.
1. SLC EOP-AC On & Lub Oil Header Press<1.2 Ksc **
2. If EOP-DC On, Start Command will go to EOP-AC (Even without SLC EOP-AC On)
3. With Fire Protection-2 Operated Start Command will go to EOP-AC (Even without
SLC EOP-AC On)
4. Manual Command
** Lub Oil Header pressure at Bearings is through Transmitter MAV42CP002, CP003, CP004
(2/3 logic)
# Fire Protection -2 is Operated through only MMI .Other Fire Protection Point are not
Ready/Erected (MOT room,13 Mtr. Near Turbine Floor.)
Auto Stop
S. Description
No.
1. Manual Command
Auto Start
S. Description
No.
1. SLC EOP-DC On & Lub Oil Header Press<1.1 Ksc **
2. It will take start if HP Casing Top (50%) >120 oC & Lub Oil Header Press<1.1 Ksc **
(Even without SLC EOP-DC On)
3. It will take start if HP Casing Bottom (50%) >120 oC & Lub Oil Header Press<1.1 Ksc
** (Even without SLC EOP-DC On)
4. With Fire Protection-2 Operated & Lub Oil Header Press<1.1 Ksc (Even without SLC
EOP-DC On ), EOP DC will take start) * Through Memory Relay Set
5. SLC EOP-DC On & Lub Oil Header Press Switch <1.1 Ksc * Through Memory Relay
Set
6. Manual Command
*Memory relay in DC starter panel will set by SLC ON command.
** Lub Oil Header pressure at Bearings is through Transmitter MAV42CP002, CP003, CP004
(2/3 logic)
#Fire Protection -2 is Operated through only MMI .Other Fire Protection Point are not
Ready/Erected (MOT room,13 Mtr. Near Turbine Floor.)
Auto Stop
S. Description
No.
1. Manual Command
Auto Start
S. Description
No.
1. SLC JOP-AC On & Turbine Speed<510 rpm
2. SLC JOP-AC On & Jacking Oil Header Press<150 Ksc **
2. SLC JOP-AC On & JOP-DC Off & Status Discrepancy (MCC Fault)
3. Manual Command
Auto Stop
S. Description
No.
1. SLC JOP-AC On & Turbine Speed>540 rpm
2. Fire Protection-2 Operated #
3. Manual Command
Note:-JOP-AC can start only when JOP-DC is in Off condition (Release) O.K
#Fire Protection -2 is Operated through only MMI .Other Fire Protection Point are not
Ready/Erected (MOT room,13 Mtr. Near Turbine Floor.)
Auto Start
S. Description
No.
1. SLC JOP-DC On & Turbine Speed<510 rpm & Jacking Oil Header Press<150 Ksc **
with TD=5 Sec
2. SLC JOP-DC On & Turbine Speed<510 rpm & Jacking Oil Header Press<150 Ksc **
& JOP-AC Voltage failure * JOP-DC will take start in auto
3. SLC JOP-DC On & JOP-AC Off & Status Discrepancy (MCC Fault) JOPDC will take
start in auto
4. Turbine Speed>15 rpm & Turbine Speed<2850 rpm & JOP-AC Off & JOP-AC
Voltage Failure *(Even without SLC JOP-DC On) JOP-DC will take start in auto
5. When Fire Protection-2 Operated , JOP-DC will take start in auto
6. Manual Command
** Jacking Oil Header pressure is through Transmitter MAV35CP001,CP002 (1 out of 2 logic
or Average of two)
*AC Failure logic not connected
#Fire Protection -2 is Operated through only MMI .Other Fire Protection Point are not
Ready/Erected (MOT room,13 Mtr. Near Turbine Floor.)
Auto Stop
S. Description
No.
1. Manual Command
ON
S. Description
No.
1. Any JOP On & Seal Oil and H2 Diff Press (Both end)>0.9 Ksc
2. Lube oil Pressure V. Low >1.2 Ksc
Solenoid OFF Means Barring ON
TRIP
S. Description
No.
1. Any JOP On & Seal Oil and H2 Diff Press (Both end)<0.7 Ksc
2. Lube oil Pressure V. Low <0.8 Ksc
Solenoid ON Means Barring OFF(TRIP)
Auto Start
S. Description
No.
Release (Permissive): SO Vacuum Tank Level>500 MM
1. SLC SOPs On & SOP-2 Off & SOP-2 Discrepancy (MCC Fault)
2. SLC SOs On & SOP-2 Off
3. SLC SOPs On & SOP-2 On & Seal Oil Press after SOP-2 <5 Ksc with TD=02 Sec
4. Manual Command
Auto Stop
S. Description
No.
1. Manual Command
Release: 1. SOP-2 On & Seal Oil Press after SOP-2 >5 Ksc with TD=05 Sec; Or
2. SLC SOPs Off
Auto Start
S. Description
No.
Release (Permissive): SO Vacuum Tank Level>500 MM
1. SLC SOPs On & SOP-1 Off & SOP-1 Discrepancy (MCC Fault)
2. SLC SOPs On & SOP-1 On & Seal Oil Press after SOP-1 <5 Ksc with TD=02 Sec
3. Manual Command
Auto Stop
S. Description
No.
1. Manual Command
Release: 1. SOP-1 On & Seal Oil Press after SOP-1 >5 Ksc with TD=05 Sec; Or
2. SLC SOPs Off
Auto Start
S. Description
No.
Release (Permissive): Always Available
1. SLC SOP-DC On & Memory Relay Set & Seal Oil Press <4.5 Ksc
2. SLC SOP-DC On & (SOP-1 Off Or Seal Oil Press after SOP-1 <5 Ksc) & (SOP-2 Off Or
Seal Oil Press after SOP-2 <5 Ksc)
3. SLC SOP-DC On & SOP-1 Tripped & SOP-2 Tripped
4. SLC SOP-DC On & SO & H2 Diff Press at TE/EE <0.9 Ksc with TD=02 Sec
5. Manual Command
Auto Stop
S. Description
No.
1. Manual Command
Release: 1. SOP-1 On & Seal Oil Press after SOP-1 >5 Ksc with TD=05 Sec; Or
2. SOP-2 On & Seal Oil Press after SOP-2 >5 Ksc with TD=05 Sec; Or
3. SLC SOP-DC Off
2. Auto Stop
Release: 1. SOP-1 On & Seal Oil Press after SOP-1 >5 Ksc with TD=05 Sec; Or
SOP-2 On & Seal Oil Press after SOP-2 >5 Ksc with TD=05 Sec; And
2. SLC SOP-DC On; And
3. SO & H2 Diff Press at TE/EE >1.2 Ksc; And ***
4. SOP-DC On
with TD=02 Sec
***not available as per Logic
S. Description
No.
Release (Permissive) :Always Available
1. Any SOP ON & SO Vacuum Pump 1Selected
2. Any SOP ON & SO Vacuum Pump 1 Selected & Pr.in SO Vac Tank > -0.4 Ksc with
TD 2sec
3. SO Vacuum Pump 1Selected & SO Vacuum Pump 2 off & SO Vacuum Pump 2
discrepancy
4. Manual Command
Auto Stop
S. Description
No.
1. Manual Command
Release: 1. SO Vac Pump -2 On & Pressure in SO Vacuum Tank < -0.40 ksc with TD
5 OR 2. SLC Seal Oil Pumps Off
2. Pressure in SO Vacuum Tank < -0.65 ksc
Release: 1. SO Vac Pump -2 On & Pressure in SO Vacuum Tank < -0.40 ksc with TD
5 OR 2. SLC Seal Oil Pumps Off
Auto Start
S. Description
No.
Release (Permissive) :Always Available
1. Any SOP ON & SO Vacuum Pump 2 Selected
2. Any SOP ON & SO Vacuum Pump 2 Selected & Pr.in SO Vac Tank > -0.4 Ksc with TD
2sec
3. SO Vacuum Pump 2 Selected & Vacuum Pump 1 off & SO Vacuum Pump 1
discrepancy
4. Manual Command
Auto Stop
S. Description
No.
1. Manual Command
Release: 1. SO Vac Pump -1 On & Pressure in SO Vacuum Tank < -0.40 ksc with TD
5 OR P2. SLC Seal Oil Pumps Off
2. Pressure in SO Vacuum Tank < -0.65 ksc
Release: 1.SO Vac Pump -1 On & Pressure in SO Vacuum Tank < -0.40 ksc with TD
5 OR 2. SLC Seal Oil Pumps Off
Fire Protection
If MOT Level Low( < 550 mm) Fire Protection -2 will operate.
TGECW Protections
SGECW Protections.
CEP Protection
Turbine Protection:
BFP Permissive
BFP Protections
Heaters Level :
LPH-2
Sl.No: Description
1 LHP-2 Level High-High
2 If LHP-2 Level High-High and By Pass valve control V/V CD-34 not Time
closed, Then LPH-2 Isolating valve CD-32 & CD-33 will close (LPH-2 will Delay-
by Pass from condensate side)By Opening Heater By Pass Valve CD-34 10 sec
4 LPH-2 level hi-hi ,Alternate drain control V/V DR-28 opens
5 LPH-2 Normal Control V/V Close ORLPH-1 Level High, DR-28 Closes
6 EXTRACTION- EX-9 V/V( From EXT-2 to LPH-2)
7 If LPH-2 Level HighOR Turbine Tripped, Extraction steam Motorized
V/v(EX-9) Closes
8 Motorized drain line Valve EX-117 Opens
LPH-3
Sl.No. Description
1 LPH-3 Level High-High
2 If LHP-3 Level High-High and By Pass valve control V/V CD-37 not closed, Then Time
LPH-3 Isolating valve CD-35 & CD-36 will close (LPH-3 will by Pass from Delay-10
condensate side)By Opening Heater By Pass Valve CD-37 sec
3 LPH-3 level hi-hi ,Alternate drain control V/V DR-22 opens
4 LPH-3 Normal Control V/V Close ORLPH-2 Level High, DR-22 Closes
5 EXTRACTION- EX-10 V/V( From EXT-3 to LPH-3)
6 If LPH-3 Level HighOR Turbine Tripped, Extraction steam Motorized V/v(EX-10)
Closes
7 Motorized drain line Valve EX-116 Opens
HPH-5
Sl.No. Description
1 HPH-5 Level High-High
2 If HPH-5 Level High-High and By Pass valve control V/V FD-8 not Time
closed, Then HPH-5 Isolating valve FD-7 &FD-9 will close (HPH-5 will by Delay-
Pass from Feed water side)By Opening Heater By Pass Valve FD-8 30 sec
3 HPH-5 level hi-hi ,Alternate drain control V/V DR-16 opens(to HP
Drain Flash tank)
4 If D/A level High ,DR-13 Will Remain at minimum position.
5 HPH-5Level High ORExtraction to HPH-5 inlet Pressure <6.0
KscORHPH-6 normal control valve minimum, DR-2 will remain at
minimum Position
6 EXTRACTION- EX-12 V/V( From EXT-5 to HPH-5)
7 If HPH-5 Level HighOR Turbine Tripped, Extraction steam Motorized
V/v(EX-12) Closes
8 Motorized drain line Valve EX-103 on extraction line Opens
HPH-6
Sl.No. Description
HPH-6 Level High-High
1 If HPH-6 Level High-High and By Pass valve control V/V FD-11 not Time
closed, Then HPH-6 Isolating valve FD-10 &FD-12 will close (HPH-6 will Delay-
by Pass from Feed water side)By Opening Heater By Pass Valve FD-11 30 sec
2 HPH-6 level hi-hi ,Alternate drain control V/V DR-9 opens(to HP Drain
Flash tank)
CD-21 Change over from Auto to manual Hot well Level High(2/3 Logic) 2 values bad
Anti Flood tank Level not Min Auto Off 3-Way Soln.V/V
OR
SEP. Motor Over Load
SEP. Cover NOT Close
OR
Oil Temp <55 Deg
SEP. feed back OFF
Oil Flow --High
Oil Purifier ---Step-54
Oil Purifier --- Step-03 Auto ON 3-Way Soln.V/V
SEP.Motor ON Permit ON
Oil Pressure <Min for 30 sec
AND
3-Way Solenoid v/v ON PROTECTION OFF
Solenoid Valve for water
seal
If SEP. Motor ON for 180 sec AUTO ON water seal sov.
2 Lub oil Pressure <1.2 Ksc (2/3 Logic) Pulse for 02 Sec Vac. Breaker Auto Open
OR
Axial shift Tripped (2/3 Logic)
AND Vac. Breaker Protection
Gen.Breaker Open (BAC01AA001XG02) ON (through Fire Prot.)
3 Logic for Sl.No.-2 Vac. Breaker Auto OFF
AND
Cond.Pressure>0.18 Ksc(MAG10CP901)
CW Pump Protection and Permissive:
PROTECTION
CW Pump Protection:
SLC ON & CO2 Flash Evap Temp <145 Deg then Heater will be on.
CO2 Flash Evap Temp > 150 Deg OR SLC OFF then Heater will be off.
SLC to Be Switch ON only when Hydrogen Purging /CO2 Filling is required for GENERATOR
Ammonia Dozing Pump:
Stat Permissive: Pump Should be in remote& Agitator tank level not low(<20mm)
&
Start permissive: Pump Should be in remote& Agitator tank level not low(<20mm