PROFIS Anchor 2.4.

www.hilti.lu
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

-|-

Page:
Project:
Sub-Project I Pos. No.:
Date:

1/30/2017

Specifier's comments:

1. Input data

Anchor type and diameter:


HIT-RE 500 + Rebar, 16mm
Dynamic set or any suitable annular gap filling solution
Effective embedment depth:
h ef,act = 150 mm (hef,limit = - mm)
Material:
BSt 500 S
Evaluation Service Report:
ETA 04/0027
Issued I Valid:
6/26/2013 | 5/16/2018
Proof:
design method SOFA design method + fib (07/2011) - after ETAG BOND testing
Stand-off installation:
e b = 0 mm (no stand-off); t = 8 mm
Anchor plate:
lx x l y x t = 500 x 400 x 8 mm (Recommended plate thickness: not calculated)
Profile
no profile
Base material:
uncracked concrete , C25/30, fc = 25.00 N/mm; h = 500 mm, Temp. short/long: 40/24C
Installation:
hammer drilled hole, installation condition: dry
Reinforcement:
no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
no longitudinal edge reinforcement

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.4.6

www.hilti.lu
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

-|-

1/30/2017

Case
1

Description
Combination 1

Forces [kN] / Moments [kNm]


N = -237.560; Vx = -32.780; Vy = -45.770;
Mx = -79.000; My = 23.000; Mz = 3.000

Seismic
no

Fire
no

Max. Util. [%]


447

Combination 2

N = 105.000; Vx = 6.000; Vy = 16.000;


Mx = -4.000; My = 0.000; Mz = 0.000

no

no

232

2. Load case/Resulting anchor forces


Load case (Design loads):
Anchor reactions [kN]
Tension force: (+Tension, -Compression)

Compression

Anchor

Tension force

Shear force

Shear force x

Shear force y

16.864

28.312

-19.442

-20.581

75.339

20.806

3.052

-20.581

9.379

19.578

-19.442

-2.304

67.854

3.824

3.052

-2.304

y
1

3
x

Tension
2

max. concrete compressive strain []: 1.03


max. concrete compressive stress [N/mm]: 30.87
resulting tension force in (x/y)=(59/-55) [kN]: 169.400
resulting compression force in (x/y)=(81/171) [kN]: 407.000

3. Tension load SOFA (fib (07/2011), section 16.2.1)


Load [kN]

Capacity [kN]

Utilization bN [%]

Status

Steel Strength*

75.339

79.286

95

OK

Combined pullout-concrete cone

169.435

70.570

241

not recommended

169.435

65.819

258

not recommended

N/A

N/A

N/A

N/A

Proof

failure**
Concrete Breakout Strength**
Splitting failure**
* anchor having the highest loading

**anchor group (anchors in tension)

Steel Strength
NRk,s [kN]

g M,s

NRd,s [kN]

NSd [kN]

111.000

1.400

79.286

75.339

Combined pullout-concrete cone failure


2

Ap,N [mm ]

Ap,N [mm ]

y A,Np

t Rk,ucr,25 [N/mm ]

s cr,Np [mm]

c cr,Np [mm]

c [mm]

338736

191147

1.772

14.00

437

219

10000

yc

t Rk,ucr [N/mm ]

maxt Rk,ucr [N/mm ]

y g,Np

y g,Np

1.018

14.26

13.40

1.000

1.000

e c1,N [mm]

y ec1,Np

e c2,N [mm]

y ec2,Np

y s,Np

y re,Np

0.974

55

0.798

1.000

1.000

NRk,p [kN]

NRk,p [kN]

g M,p

NRd,p [kN]

NSd [kN]

107.503

148.197

2.100

70.570

169.435

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.4.6

www.hilti.lu
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

-|-

1/30/2017

Concrete Breakout Strength


2

Ac,N [mm ]

Ac,N [mm ]

y A,N

c cr,N [mm]

s cr,N [mm]

353800

202500

1.747

225

450

e c1,N [mm]

y ec1,N

e c2,N [mm]

y ec2,N

y s,N

y re,N

k1

0.975

55

0.803

1.000

1.000

11.000

NRk,c [kN]

g M,c

NRd,c [kN]

NSd [kN]

101.041

2.100

65.819

169.435

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.4.6

www.hilti.lu
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

-|-

1/30/2017

4. Shear load SOFA (fib (07/2011), section 16.2.2)


Proof

Utilization bV [%]

Load [kN]

Capacity [kN]

28.312

36.667

77

OK

N/A

N/A

N/A

N/A

28.312

58.845

48

OK

N/A

N/A

N/A

N/A

Steel Strength (without lever arm)*


Steel failure (with lever arm)*
Pryout Strength*
Concrete edge failure in

Status

direction**
* anchor having the highest loading

**anchor group (relevant anchors)

Steel Strength (without lever arm)


VRk,s [kN]

g M,s

V Rd,s [kN]

VSd [kN]

55.000

1.500

36.667

28.312

Pryout Strength (Concrete Breakout Strength controls)


2

Ac,N [mm ]

Ac,N [mm ]

y A,N

c cr,N [mm]

s cr,N [mm]

k4

88450

202500

0.437

225

450

2.000

e c1,V [mm]

y ec1,N

e c2,V [mm]

y ec2,N

y s,N

y re,N

k1

1.000

1.000

1.000

1.000

11.000

NRk,c [kN]

g M,c,p

VRd,c1 [kN]

VSd [kN]

101.041

1.500

58.845

28.312

5. Combined tension and shear loads SOFA (fib (07/2011), section 16.2.3)
steel
concrete
a

bN

bV

Utilization bN,V [%]

Status

0.950

0.567

2.0

122

not recommended

2.574

0.481

1.5

not recommended

bN + bV <= 1

6. Warnings
The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient sompressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means.
The compliance with current standards (e.g. EC3) is the responsibility of the user
Characteristic bond resistances depend on short- and long-term temperatures.
Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
To avoid failure of the anchor plate the required thickness can be calculated in PROFIS Anchor. Load re-distributions on the anchors due to
elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be sufficiently stiff, in order not to be deformed
when subjected to the loading!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.

Fastening does not meet the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

PROFIS Anchor 2.4.6

www.hilti.lu
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

-|-

1/30/2017

7. Installation data
Anchor plate, steel: Anchor type and diameter: HIT-RE 500 + Rebar, 16mm
Profile: no profile
Installation torque: 0.000 kNm
Hole diameter in the fixture: df = 16 mm
Hole diameter in the base material: 20 mm
Plate thickness (input): 8 mm
Hole depth in the base material: 150 mm
Recommended plate thickness: not calculated
Minimum thickness of the base material: 190 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Annular gap must be removed by e.g. filling the holes with mortar of sufficient compressive strength.

7.1. Required accessories


Drilling
Suitable Rotary Hammer
Properly sized drill bit

Cleaning
Manual blow-out pump
Proper diameter wire brush

Setting
Dispenser including cassette and mixer
For deep installations, a piston plug is
necessary
Dynamic set
Torque wrench

200.0

120.0

4
120.0

250.0

120.0

250.0

Coordinates Anchor [mm]


Anchor
x
y
1
0
80
2
0
-80
3
130
80
4
130
-80

c -x
-

c +x
-

c -y
-

250.0

c +y
-

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

200.0

PROFIS Anchor 2.4.6

www.hilti.lu
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

-|-

Page:
Project:
Sub-Project I Pos. No.:
Date:

1/30/2017

8. Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard
to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret
norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a
specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not
use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in
each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like